Recordall® Compound Series Meters
Door Seal Replacement
DESCRIPTION
The door seal in the valve assembly for the 2" and 3" Compound Series meters is replaceable, should it become necessary,
with the use of the Door Seal Replacement Tool Kit (64201-001.) This instruction sheet provides step-by-step instructions for
using this kit. The 4" and 6" valve assemblies do not permit door seal replacement. If service or replacement is required, a new
complete valve assembly must be installed.
DOOR SEAL REPLACEMENT PROCEDURE
Disassembling the Unit
1. Remove the bolts from the cover assembly and lift the cover
o the housing. Removing the cover assembly exposes the
valve assembly for service.
2. Remove the lock pawl.
3. Turn the valve assembly counter-clockwise to unscrew it from
the housing, then lift it out of the housing.
4. Remove the door seal bolt, nut and washers from the
valve assembly.
5. Place one of the spacer bolts through the spacer and into the
threaded hole on the back of the valve assembly.
6. Use a wrench to turn the bolt head clockwise to open the
door about 1/2", exposing the door seal.
The kit is made up of a spacer and 2 bolts—
one with a washer for a 2" meter, and a larger
bolt with no washer for a 3" meter.
Cover
Assembly
Lock Pawl
Nut
Valve
Assembly
Bolt
Replacing the Door Seal
7. Replace the old seal with the new seal.
8. Turn the spacer bolt counter-clockwise until the door closes while maintaining alignment between the seal and the door.
9. Completely remove the bolt/washer and spacer.
Threaded
Hole
RCS-UM-00075-EN-02 (September 2013)
Small Hole Up
Spacer Bolt
Through Spacer
Door Open
Seal Exposed
Seal
Replaced
User Manual
Reassembling the Unit
1. Replace the door seal bolt, nut and washers that you removed in Step 4 of Disassembling the Unit.
2. Reinstall the valve assembly into the meter housing.
3. Place the lock pawl in position.
4. Make sure the O-ring seal is installed properly in the O-ring counter bore.
5. Position the cover assembly back in place and reinstall the bolts.
Badger Meter recommends that a new O-ring be used after each teardown and reassembly of the cover assembly. To assure
a tight seal, make sure O-ring is positioned correctly on the housing. Make sure the housing and cover assembly are clean
and free of dirt or residual traces of old O-ring material. If necessary, use silicone grease to help retain O-ring and to serve as a
lubricant in reassembly it to the housing.
Recordall is a registered trademark of Badger Meter Inc. Other trademarks appearing in this document are the property of their respective entities.
Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the
extent an outstanding contractual obligation exists. © 2013 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400
México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882
Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0
Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411
Slovakia | Badger Meter Slovakia s.r.o. | Raciansk a 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01
Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836
China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Legacy Document Number: RCS-I-01