Badger Meter B3000 User Manual

Compact Digital Flow Monitor
Model B3000
2
1
MODEL SERIAL
4-20mA Loop Pulse Output Reset Input RS485 Turbine Input
V Max 28 Vdc 28 Vdc 5 Vdc 10 Vdc Voc=3.5V I Max 26mA 100mA 5mA 60mA Ics=3.6mA
Ci 0.5µF 0.0µF 0.0µF 0.0µF Ca=1.5µF Li 0.0mH 0.0mH 0.0mH 0.0mH La=1.65H
Substitution of Components May Impair Intrinsic
WARNING:
Safety Use Only Blancett B300028, 3.6V Lithium
CAUTION:
Battery. La Substitution De Composants Peut
ADVERTSSEMENT:
Compromettre La Securtie Intrinseque Utiliser Suelement Que Des Batterie Blancett B300028, 3.6V Lithium
MODEL SERIAL
Pulse Output Reset Input Turbine Input
V Max 28 Vdc 5 Vdc Voc=2.5V I Max 100mA 5mA Ics=1.8mA Ci 0.0µF 0.0µF Ca=1.5µF
Li 0.0mH 0.0mH La=1.65H
WARNING:
Substitution of Components May Impair Intrinsic
Safety
ADVERTSSEMENT:
Compromettre La Securtie Intrinseque
FAITES ATTENTION:
La Substitution De Composants Peut
XXXXXXXXXX XXXXXXXXXX
!
Intrinsically Safe When Installed Per Drawing ­B300020
SÈcuritÈ intrinsËque lorsqu'il est installÈ par le dessin B300020
!
Intrinsically Safe When Installed Per Drawing -
B300020
SÈcuritÈ intrinsËque lorsqu'il est installÈ par le dessin B300020
!
Electrical and
Hazardous
Location Safety
E113407
Class I Div 1 Groups C,D Class I Zone 0, IIB, T4 Class II Div 1 Groups E,F,G Class III
-30∞C<Tamb<70∞C
Electrical and Hazardous
Location Safety
E113407
Class I Div 1 Groups C,D Class I Zone 0, IIB, T4 Class II Div 1 Groups E,F,G Class III
-30∞C <Tamb<70∞C
USC
Electrical and
Hazardous
Location Safety
E113407
Menu
S1
USC
12
S3UpS2
USC
S4
1
2
COM
1
Down
J1
S
I
F
S
I
E
A
D
L
C
DSY-PM-00022-EN-03 (March 2014)
Programming Manual
Flow Monitor, B3000 Flow Monitor For Gas or Liquid Meters
Page ii March 2014
Programming Manual
CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PART NUMBER CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connecting the B3000 to a Frequency Output Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Solar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OPERATING THE MONITOR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Programming Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Programming Using Frequency Output Turbine Flow Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
PROGRAMMING PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
GAS COMPENSATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Absolute Pressure and Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Default K Factor Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Battery Replacement (B30A/B/X/Z only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
NEMA 4X Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Explosion Proof Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
MENU MAPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
K FACTORS EXPLAINED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Calculating K factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
SYMBOL EXPLANATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ELECTRICAL SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
EXPLOSION-PROOF ENCLOSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Page iii March 2014
Flow Monitor, B3000 Flow Monitor For Gas or Liquid Meters
MODBUS INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Modbus Register / Word Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Register Mappings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
C Source Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) DIRECTIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Page iv March 2014
Programming Manual
Page v March 2014
Compact Digital Flow Monitor, Model B3000

INTRODUCTION

The B3000 flow monitor incorporates state-of-the-art, digital signal processing technology, designed to provide the user with exceptional flexibility at a very affordable price. Though designed for use with Blancett flow sensors, this monitor can be used with almost any flow sensor producing a low amplitude AC output or contact closure signal.
2
1
Menu
S1
12
S3UpS2
Enter
S4
1
2
COM
1
Down
J1
Figure 1: B3000 Flow monitor (NEMA 4X) Figure 2: B3000 Flow monitor (Ex-Proof)
This monitor is capable of accepting low-level frequency input signals typically found in turbine flow sensors. The output signal for these type of sensors is a frequency proportional to the rate of flow. The B3000 monitor uses the frequency information to calculate flow rate and total flow. Through the use of the programming buttons the user can select rate units, total units and unit time intervals among other functions. All B3000 flow monitors come pre-configured from the factory, if ordered with a Blancett flow sensor. If required, however, it can easily be re-configured in the field. Finally, the user can choose between simultaneously showing rate and total, or alternating between rate and grand total.
The monitor is available in two different levels of functionality and two packaging options. The base model provides all the functions necessary for the most common flow metering applications. The advanced version adds communications capabilities over an RS485 bus using Modbus RTU and control outputs. Completing the line is a solar powered model (NEMA 4X Only).
Packaging options include a polycarbonate, NEMA 4X version and an aluminum explosion proof enclosure.
Page 6 March 2014

SPECIFICATIONS

COM
Programming Manual
Display
Common
Simultaneously shows Rate and Total
5 x 7 Dot Matrix LCD, STN Fluid
6 Digit Rate, 0.5 inch (12.7 mm) numeric
B30A/B/L/M/S
7 Digit Total, 0.5 inch (12.7 mm) numeric
Engineering Unit Labels 0.34 inch (8.6 mm)
6 Digit Rate, 0.37 inch (9.4 mm) numeric
B30W/X/Y/Z
7 Digit Total, 0.37 inch (13 mm) numeric
Engineering Unit Labels 0.24 inch (6.1 mm)
Annunciators Alarm 1(1), Alarm 2 (2), Battery Level ( ), RS485 Communications (
Power
Auto switching between internal battery and external loop power; B30A/Z includes isolation between loop power and other I/O
B30A/B/X/Z
Battery: 3.6V DC lithium “D Cell” gives up to 6 years of service life Loop: 4-20 mA, two wire, 25 mA limit, reverse polarity protected, 7V DC loop loss
B30L/M/W/Y Loop: 4-20mA, 7V DC loop loss
B30S
Internal battery (3.6V DC Nicd) provides up to 30 days of power after 6…8 hours exposure of the integrated photovoltaic cell to direct sunlight.
Inputs
Frequency Range: 1…3500 Hz
Magnetic Pickup
Frequency Measurement Accuracy: ±0.1% Over Voltage Protection: 28V DC Trigger Sensitivity: 30 mV
(High) or 60 mV
p-p
(Low) - (selected by circuit board jumper)
p-p
)
Amplified Pulse Direct connection to amplified signal (pre-amp output from sensor)
Outputs
Analog 4-20 mA
4-20 mA, two-wire current loop
25 mA current limit One pulse for each Least Significant Digit (LSD) increment of the totalizer Pulse Type: (selected by circuit board jumper)
Opto-isolated (Iso) open collector transistor
Totalizing Pulse
Non-isolated open drain FET
Maximum Voltage: 28V DC Maximum Current Capacity: 100 mA Maximum Output Frequency: 16 Hz Pulse Width: 30 mSec fixed Type: Open collector transistor
Adjustable flow rate with programmable dead band and phase.
Status Alarms
B30A/M/Y/Z
Maximum Voltage: 28V DC Maximum Current: 100 mA Pullup Resistor: External required (2.2 k Ohm minimum, 10 k Ohm maximum)
Page 7 March 2014
Compact Digital Flow Monitor, Model B3000
Status Alarms B30B/L/S/W/X
B30A/M/Y/Z
B30B/L/S/W/X None
B30A/B/L/M/W/X/
Y/Z
Common Functions
Totalizer Reset
None
Modbus Digital Communications
Modbus RTU over RS485, 127 addressable units / 2-wire network, 9600 baud, long integer and single precision IEEE754 formats; retrieve: flow rate, job totalizer, grand totalizer, alarm status and battery level; write: reset job totalizer, reset grand totalizer.
Data Configuration and Protection
Two four-digit user selectable passwords; level one password enables job total reset only, level two password enables all configuration and totalizer reset functions
OTE:N Not applicable on solar powered units.
Totalizer Operation
Monitors contain two totalizers: Job and Grand. The user can enable or disable the grand totalizer function. If grand totalizer is enabled, it shares the seven-digit display line with the job totalizer – alternating between job and grand. Grand totalizer rollovers are displayed with a count value that increments at each rollover. Totalizers are automatically backed up into non-volatile FLASH memory every twenty minutes and prior to battery expiration; manually via keypad or when signaled via Modbus (B30A/M/Y/Z only).
B30A/B/L/M/S only: The job totalizer can be reset by momentarily contacting the total reset terminal to ground or pressing MENU and ENTER simultaneously. The grand totalizer can be reset via selection in the advanced menu or modbus.
OTE:N Modbus not applicable on solar powered units.
B30W/X/Y/Z: *The job totalizer can be reset via the “through the glass” touch sensor, by
momentarily contacting the total reset terminal to ground or pressing MENU and ENTER simultaneously. The grand totalizer can be reset via selection in the advanced menu or Modbus command.
Totalizer Preset User can preset job total values.
B30A/B/L/M/S: Class I Division 1, Groups C, D; Class II, Division 1 Groups E, F, G; Class III for US and
Canada. Complies with UL 913 and CSA C22.2 No. 153
Safety
B30W/X/Y/Z: Class I Division 1 Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III for US and
Canada Complies with UL 1203 and CSA C22.2 No. 30
ATEX II 2 G Ex d IIC T4 Gb and ATEX II D Ex tb IIIC T125 °C Db
Complies with Directive 94/9/EC.
B30A/B/L/M only 4-20 mA Loop: Vmax = 28V DC Imax = 26 mA Ci = 0.5 F Li = 0 mH B30A/B/L/M/S only Pulse Output: Vmax = 28V DC Imax = 100 mA Ci = 0 F Li = 0 mH
Entity Parameters
B30A/B/L/M/S only Reset Input: Vmax = 5V DC Imax = 5 mA Ci = 0 F Li = 0 mH B30A/M only RS485: Vmax = 10V DC Imax = 60 mA Ci = 0 F Li = 0 mH B30A/B/L/M/S only Turbine Input: Voc = 2.5V Isc = 1.8 mA Ca = 1.5 F La = 1.65 H
EMC 2004/108/EC
Measurement Accuracy
Common Accuracy 0.05%
Certifications
Page 8 March 2014
Programming Manual
Response Time (Damping)
Common Response
Time
Common Limits –22…158° F (–30…70° C); 0…90% humidity, non-condensing;
B30A/B/L/M/S Polycarbonate, stainless steel, polyurethane, thermoplastic elastomer, acrylic; NEMA 4X/IP 66
B30W/X/Y/Z Copper free, epoxy-coated, aluminum, buna seal, NEMA 4X/IP66
Liquid
Gas
Rate Time Seconds, minutes, hours, days
Totalizer Exponents 0.00, 0.0, X1, x10, x100, x1000
K factor Units Pulses/Gallon, Pulse/cubic meter, pulses/liter, pulses/cubic foot
1…100 seconds response to a step change input, user adjustable
Environmental Limits
Materials and Enclosure Ratings
Engineering Units
Gallons, Liters, Oil Barrels (42 gallon), Liquid Barrels (31.5 gallon), Cubic Meters, Million Gallons, Cubic Feet, Million Liters, Acre Feet
Cubic Feet, Thousand Cubic Feet, Million Cubic Feet, Standard Cubic Feet, Actual Cubic Feet, Normal Cubic Meters, Actual Cubic Meters, Liters

PART NUMBER CONSTRUCTION

Blancett B3000 Display -
Model
Blancett B3000 Display B30
Model
Base B Advanced A Solar S Base – Loop Powered Only L Base – Explosion Proof*– Loop Power Only W Base – Explosion Proof* – Battery & Loop Power X
Advanced – Loop Powered Only M Advanced – Explosion Proof* – Loop Power Only Y Advanced – Explosion Proof* – Battery & Loop Power Z
Mounting
Meter M Remote R Swivel S
Units of Measure
Customer Selectable CS
*For hazardous locations the monitor must be installed on an Explosion-Proof rated meter. To maintain compliance, optional kit P/N B280-737 for meter mounting is required.
Page 9 March 2014
Compact Digital Flow Monitor, Model B3000

INSTALLATION

Connecting the B3000 to a Frequency Output Device

Most turbine flow sensors produce a frequency output that is directly proportional to the volumetric flow through the sensor. There are, however, different output waveforms that can be presented to the display device depending on the transducer that converts the mechanical motion of the turbine into an electrical signal.
The B3000 monitor has two jumpers that are used to set the type of signal and the minimum amplitude of the signal that it accepts. The first thing to established is the type of output provided by the flow sensor. The outputs almost always fall into one of two types.
Type 1 – This is the unaltered frequency signal coming from an un-amplified magnetic pickup. This signal is normally a sine wave in appearance and the amplitude of the waveform varies with the flow. Small turbines have comparatively small rotating masses so they produce a smaller amplitude waveform and higher frequencies than larger turbine sensors.
Type 2 – The frequency signal from the transducer is amplified, wave shaped or both to produce a waveform of a specified type and amplitude. Most amplified transducers output a square wave shape at one of many standard amplitudes. For example a popular amplified output is a 10V DC square wave.
If the flow sensors output signal is type 1, the minimum amplitude of the frequency output must also be determined. The B3000 has a high or low signal sensitivity setting. High signal sensitivity (30 mV) is used with low amplitude (usually small) turbine flow sensors. The low signal sensitivity setting (60 mV) is typically used for larger turbines and amplified transducers (see Figure 3 and Figure 4).
OTE:N The high signal sensitivity setting is used where the minimum signal amplitude is below 60 mV. Setting the sensitivity
lower than necessary opens the instrument up to a greater possibility of noise interference.
Input Signal Level Selection
Input Waveform Selection
JP1
Pulse
TB1
Figure 3: Input jumper settings (NEMA 4X) Figure 4: Input jumper settings (Ex-Proof)
Input Total Pulse Signal
Mag
JP2
OC
Iso
JP3
High
Low
(Magnetic Pickup Selection Shown)
Input Signal Level Selection
(Low Signal Sensitivity (60 mV) Selection Shown)
TB1
P1
P1
(Low Signal Sensitivity (60 mV) Selection Shown)
JP2
LowHigh
Signal
Gnd
Input Waveform Selection
(Magnetic Pickup Selection Shown)
Input
JP1
MagPulse
TB2
+
Freq. In
Once the type of waveform and input signal level (amplitude) are determined the jumpers on the B3000 circuit board are set.
For typical variable reluctance magnetic pickups the waveform selection jumper should be set for Mag. The setting for the input level must be determined from looking at the magnetic pickup specifications. If the minimum amplitude at the minimum rated flow is greater than 60 mV use the low signal sensitivity jumper position (see Figure 3 and Figure 4).
If the minimum signal level is below 60 mV use the high signal sensitivity jumper position.
Again all B3000 flow monitors come pre-configured from the factory, if ordered with a Blancett flow sensor.
Page 10 March 2014
Iso Total Pluse
OC Total Pluse
Programming Manual
TR_B
P1
TR_A
RS485 Gnd
Setpoint 1
Setpoint 2
Gnd
+
Freq. In
JP1
Input Total Pulse Signal
Pulse
Mag
+
4-20mA
JP2
OC
+
Iso
JP3
High
Total Reset
Low
Signal Gnd
TB1
Pulse
Mag
JP1
Input
Input
JP1
MagPulse
JP2
LowHigh
Signal
Input
JP1
Total Pulse
Iso Total Pluse
OC Total Pluse
Freq. In
4-20mA
Total Reset
Signal Gnd
ISO OC
MagPulse
TB2
+
+
+
JP3
P1
P1
TB1
Gnd
Setpoint 2
Setpoint 1
RS485 Gnd
TR_A
TR_B
+ –
P2
3.6Vdc Battery
Figure 5: Typical magnetic pickup connection (NEMA 4X) Figure 6: Typical magnetic pickup connection (Ex-Proof)
For amplified input signals the input jumper should be set to Pulse and the signal jumper set to Low (see Figure 7 and Figure 8).
OTE:N Amplified magnetic pickups require an external power source. The B3000 does not supply power to an
amplified pickup.
Input
JP1
MagPulse
POWER SUPPLY
POWER
SUPPLY
Iso Total Pluse
OC Total Pluse
TR_B
P1
TR_A
RS485 Gnd
Setpoint 1
Setpoint 2
Gnd
+
Freq. In
JP1
Input Total Pulse Signal
Pulse
Mag
+
4-20mA
JP2
OC
+
Iso
JP3
High
Total Reset
Low
Signal Gnd
TB1
Pulse
Mag
JP1
Input
P1
P1
TB1
Gnd
Setpoint 2
Setpoint 1
RS485 Gnd
TR_A
TR_B
P2
3.6Vdc Battery
JP2
LowHigh
Signal
Input
JP1
MagPulse
TB2
+
Freq. In
+
4-20mA
+
Iso Total Pluse
Total Pulse
Total Reset
OC Total Pluse
Signal Gnd
ISO OC
JP3
+ –
Figure 7: Typical amplified pickup connection (NEMA 4X) Figure 8: Typical amplified pickup connection (Ex-Proof)
Page 11 March 2014
Compact Digital Flow Monitor, Model B3000

POWER CONNECTIONS

Standard

The power supply used in the B30A/B/X/Z is an internal lithium 3.6V DC “D” cell that will power the monitor for about six years when no outputs are used. The monitor can also get power from a 4-20 mA current loop (see Figure 9 and Figure 10). If the current loop is used a sensing circuit within the monitor detects the presence of the current loop and disconnects the battery from the circuit. The B30L/M/W/ versions use loop power only and the B30S uses solar power only.
JP2
LowHigh
10…28V DC
4-20 mA
Current Loop
(10…28V DC)
Load
RS485 Gnd
Setpoint 1
Setpoint 2
Freq. In
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
Signal
TR_B
TR_A
Gnd
+
+
+
P1
JP1
Input Total Pulse Signal
Pulse
Mag
JP2
OC
Iso
JP3
High
Low
TB1
P2
P1
P1
TB1
Gnd
Setpoint 2
Setpoint 1
RS485 Gnd
TR_A
TR_B
3.6Vdc Battery
+ –
Iso Total Pluse
Total Pulse
Input
JP1
Freq. In
4-20mA
Total Reset
OC Total Pluse
Signal Gnd
ISO OC
JP3
MagPulse
TB2
+
10…28 VDC
+
4-20 mA Current Loop (10…28V DC)
+
Load
Figure 9: Loop power connections (NEMA 4X) Figure 10: Loop power connections (Ex-Proof)
CAUTION
GROUNDING FOR THE EXPLOSION PROOF ENCLOSURE IS NECESSARY. THE EXPLOSION PROOF ENCLOSURE IS PROVIDED WITH A GROUNDING SCREW ON THE INSIDE OF THE ENCLOSURE. THE CONDUCTOR USED FOR GROUNDING MUST BE OF A WIRE GAGE EQUAL TO OR GREATER THAN THE SIGNAL WIRES BEING USED. SEE FIGURE 11.
The explosion proof enclosure is provided with a grounding screw on the inside of the enclosure. The conductor used for grounding must be of a wire gage equal to or greater than the signal wires being used.
To Earth Ground
Figure 11: Required grounding for Ex-proof enclosure
Page 12 March 2014
Programming Manual

Solar

A solar cell mounted on the top of the monitor in the B30S charges an internal 3.6V DC nickel-cadmium battery that powers the monitor. A fully charged battery powers the monitor for approximately 30 days. The solar powered B3000 has a single totalizing pulse output and cannot be powered by a 4-20 mA loop.
Solar Cell
2
1
Figure 12: Solar powered B3000
Page 13 March 2014
Compact Digital Flow Monitor, Model B3000

OPERATING THE MONITOR

The monitor has three modes of operation referred to as the Run, Programming, and Extended Programming modes.
Communications
Indicator
Rate
Alarm
Activation
2
1
Battery
Indicator
Rate
Units
Totalizer
Multiplier
Total
Totalizer
Units
Figure 13: Display annunciators
To access the program mode, momentarily press and then release MENU until the first programming screen is displayed. The extended programming mode is entered by pressing and holding MENU until the first programming option appears. After programming the display with the necessary information, a lock out feature is available to prevent unauthorized access or changing of the meter’s setup parameters.

Programming Mode

COM
1
2
Figure 14: Keypad detail
Menu
Up
Enter
S1
12
S3
S4
1 2
COM
1
Down
S2
J1
Page 14 March 2014
Programming Manual
Buttons
MENU – Switches between normal running and programming modes. UP Arrow () – In programming mode scrolls forward through the parameter choices and increments
numeric variables. RIGHT Arrow () – In programming mode scrolls backward through the parameter choices and moves the active
digit to the right. ENTER – Used to save programming information, advance to the next programming parameter, and in the
reset process. TOTAL FLOW RESET – This touch sensor button allows the total to be reset without opening up the case. This button
pertains to the explosion proof version only.
OTE:N The “through the glass” touch sensor button is currently under development in the explosion proof version
of the B3000.
Special Functions
MENU + ENTER – Simultaneously press and hold to reset the current totalizer. MENU - Press and hold menu for three seconds to enter extended programming mode. UP Arrow () + Right Arrow () – Simultaneously press and hold to show the firmware version number, then the
grand total.
UP Arrow () – In run mode increases display contrast. RIGHT Arrow () – In run mode decreases display contrast.
Modes
RUN – Normal operating mode. PROGRAM – Used to program variables into the display. EXTENDED PROGRAM – Used to program advanced variables into the display. TEST – Used as a diagnostic tool to show input frequency and totalizer counts.
If your monitor was ordered with a Blancett flow meter, the two components ship from the factory configured as a set. If the monitor is a replacement, the turbine’s K factor changed, or the monitor is used with some other pulse generating device; programming is necessary.
Page 15 March 2014
Compact Digital Flow Monitor, Model B3000

Programming Using Frequency Output Turbine Flow Meters

Each Blancett turbine flow meter is shipped with either a K factor value or frequency data. If frequency data is provided, the data must be converted to a K factor before programming the monitor. K factor information, when supplied, can usually be found on the neck of the flow meter or stamped on the flow meter body. The K factor represents the number of pulses per unit of volume (see K FACTORS EXPLAINED on page 38). The K factor is required to program the monitor.
Essentials
The B3000 monitor is engineered to provide several levels of programming tailored to the needs of the user. The first or standard level provides access to the most commonly used setup parameters bypassing the more advanced settings. The first level programming is entered by pressing and holding MENU for about one second.
The second level or extended settings are accessed by pressing and holding MENU until the extended programming menu starts.
With the standard and solar liquid monitors there is a third level. For the most basic unit setup choices the B3000 monitor employes a simple and advanced setup option accessed through the Rate SU parameter. If Simple is selected the rate and total choices are reduced to the five most common combinations avoiding the need to make unit and interval choices.
Liquid Meters Standard Solar Advanced I/O Basic Functions Press MENU for about one second and then release.
Extended Functions Press and hold MENU until the extended programming menu starts. Simple Setup Select Rate SU in the extended functions and choose Simple. Advanced Setup Select Rate SU in the extended functions and choose Advanced.
Table 1: Display mode selection information
Not Applicable
Enter Programming Mode
The programming modes are accessed by pressing MENU for basic functions. Extended functions are accessed by pressing and holding MENU until the first programming parameter appears.
Battery
Indicator
Units
Indicator
Totalizer
Multiplier
Numeric
Values
Function
Figure 15: Programming mode display
2
1
Totalizer
Units
Page 16 March 2014
Programming Manual

PROGRAMMING PARAMETERS

Conventions

The individual programming parameters are arranged as follows.
Top Line – Indicates what the parameter is and if it is a selection or an entry. Bottom Line – Indicates what menu level the parameter resides in.
Select Fluid Type Fluid
Basic Function
At the Fluid prompt use or to select either Liquid or Gas.
OTE:N The fluid selection choice will affect what menu choices are available to the user. Consult the full MENU MAPS on page
32 in the for further details.
OTE:N The following programming assumes the meter is set for liquid. Parameters for gaseous fluids can be found later in
the manual.
Select Meter Size Meter
Basic Function
At the Meter prompt press ENTER to show the current meter size. Use or to select the correct meter size and press ENTER again to advance to the next parameter.
OTE:N The meter size selection refers to the bore of the meter and not the connections size. For a listing of the Blancett
turbine bore sizes see the default K factor table in the Default K Factor Values on page 29.
Select Display Function Display
Extended Function
The B3000 monitor has three display selections.
Flow Flow
The Flow setting is used for normal operation of the monitor. In this mode the display shows both the instantaneous flow rate and current total simultaneously. See Figure 16.
2
1
Instantaneous
Flow Rate
Current
Total
Current Total Units
Figure 16: Instantaneous flow rate and current total
Flow Rate
Units
Totalizer
Multiplier
Grand Total G-Total
The Flow-GT choice forces the meter to alternate between the instantaneous flow and the grand total with roll-over counts. See Figure 17.
The grand total is the accumulation of all the fluid that has gone through the meter sense the last time the grand total was cleared. This totalizer is in addition to the current total totalizer on the display and is always enabled.
In addition the grand total screen also displays the number of times the grand total has reached its maximum count (9,999,999) and rolled over to zero.
Page 17 March 2014
Compact Digital Flow Monitor, Model B3000
2
1
Roll-Overs
Total
Totalizer
Mode
Figure 17: Grand total
Roll-Over Indicator
Test Test
The Test setting places the monitor into a special diagnostic mode that shows the current input frequency and the accumulated input counts. Figure 18 shows the layout for test mode values. The diagnostic mode makes it possible for the user to see precisely the frequency input the monitor is seeing and is very useful in troubleshooting and noise detection.
2
1
Input
Frequency
Totalizer
Counts
Figure 18: Test mode screen
If the current setting requires a change, press to advance to the alternate choice. Once the correct choice is displayed, press
ENTER to save the new selection and advance to the next parameter.
Select Meters K Factor Unit KFacUnt
Basic Function
At the KFacUnt prompt, press ENTER. The display now shows the current K factor unit. If the current selection is correct, press ENTER to advance to the next parameter. For meters calibrated in gallons, use Pul/Gal; for meters calibrated in cubic meters,
use Pul/m3; and so on.
Enters Meters K Factor KFactor
Basic Function
OTE:N The K factor supplied with your meter or calculated from calibration data will be needed to complete this step.
At the KFactor prompt, press ENTER. The most significant digit in the K factor will begin to flash. Using increment the display digit until it matches the meter’s first K factor digit. If the current selection is correct, press to advance to the next digit. Repeat this process until all K factor digits have been entered. Press ENTER to save the K factor.
OTE:N The number of digits available before and after the decimal point is determined by the bore size of the flow sensor
being used. The largest K factors will be associated with the smallest bore sizes. The maximum allowable K factor is 99999.9. The minimum must be at least 1.000. If an out of range number is entered the display flashes Limit and refuses to allow the entry.
Page 18 March 2014
Programming Manual
Select Rate Units Setup Rate SU
Extended Function
The Rate SU is only available on the standard and solar liquid monitors. For the most basic unit setup choices the B3000 monitor has a simple and advanced setup option accessed through the rate setup parameter. If Simple is selected the rate and total choices are reduced to the five most common combinations avoiding the need to make unit and interval choices. When Advanced is selected the monitor allows access to all rate, total, and interval parameters.
Select Flow Rate Units Flo Unit
Basic Function (Simple Setting)
The monitor allows the choice of many common rate units. Consult the MENU MAPS on page 32 or the SPECIFICATIONS on
page 7 for all the unit choices. At the Flo Unit prompt, press ENTER. The monitor now shows the current rate and totalizer
units choice flashing on and off. If the current selection is correct, press ENTER to advance to the next parameter. To change to an alternate unit, use or to scroll to the required rate unit and press ENTER to save the choice.
Select Rate (Time) Interval RateInt
Basic Function (Advanced Setting)
The term rate implies that something is occurring over a period of time. Most people are familiar with the speed of a car reported in miles per hour (mph). The same concept holds true for a flow meters based on sensing velocity. The time choices are Sec (seconds), Min (minutes), Hour (hours), and Day (days). At the Rate Int prompt, press ENTER. The monitor now shows the current time interval choice flashing on and off. If the current selection is correct, press ENTER to advance to the next parameter. To change to an alternate time interval, use the use or to scroll to the required time interval and press ENTER to save the choice.
Select Flow Rate Units RateUnt
Basic Function (Advanced Setting)
The monitor allows the choice of many common rate units. Consult the MENU MAPS on page 32 or the SPECIFICATIONS on
page 7 for all the unit choices At the RateUnt prompt, press ENTER. The monitor now shows the current rate unit choice
flashing on and off. If the current selection is correct, press ENTER to advance to the next parameter. To change to an alternate unit, use or to scroll to the required rate unit and press ENTER to save the choice.
Select Total Units of Measure TotlUnt
Basic Function (Advanced Setting)
If a flow total is required, the units for the total must first be selected. The monitor allows the choice of many common totalization units. Consult the MENU MAPS on page 32 or the SPECIFICATIONS on page 7 for all the unit choices. At the TotlUnt prompt, press ENTER. The monitor shows the current total units. If the current selection is correct, press ENTER to advance to the next parameter. To change to an alternate unit, use ▲ or to scroll to the required totalization unit and press
ENTER to save the choice.
Select Total Multiplier TotlMul
Basic Function (Advanced Setting)
The monitor has a very versatile display that has the ability to accumulate the flow total in multiples of ten. For example, if the most desirable totalization unit is 1000 gallons, the monitor can easily be set up for this requirement. Once the unit is back in run mode, every time the total display increments by one digit the actual total would be an additional 1000 gallons. At 1000 gallons the total display would read 1, at 3000 gallons the total display would read 3, and so on. This feature eliminates having to look at a total, count the digits, and mentally insert commas for each 1000 multiple.
At the TotlMul prompt, press ENTER . The monitor now shows the current total multiplier. If the selection is correct, press ENTER to advance to the next parameter. To change to an alternate multiplier, use or to scroll to the required multiplier unit and press ENTER to save the choice. The multiplier choices: 0.01 (÷ 100), 0.1 (÷ 10), 1, x10, x100, x1000 units
Page 19 March 2014
Compact Digital Flow Monitor, Model B3000
ENTER SPECIFIC GRAVITY VALUE (SPEC GR)
Basic Function (activated when mass units are selected)
The B3000 has two mass flow unit and two mass total unit choices (pounds and kilograms). When either pounds or kilograms are chosen in either the RateUnt or TotlUnt parameters the Spec Gr entry parameter is activated.
Mass readings in the B3000 are not temperature or pressure compensated so it is best to enter the specific gravity of the fluid as close to the system running temperature as possible. As liquids are essentially incompressible pressure compensation is not necessary for liquids.
Enter a Scale Factor Scale F
Extended Function
The scale factor is used to force a global span change. For example, under operating conditions the display is reading a consistent three percent below the expected values at all flow rates. Rather than changing the K factor and linearization parameters individually, the scale factor can be used to compensate for the three percent offset. The scale factor would be set to 1.03 to correct the readings. The range of scale factors is from 0.10…5.00. The default scale factor is 1.00.
At the Scale F prompt, press ENTER. The first digit of the existing scale factor, if any, will begin to flash. If the current selection is correct, press ENTER to advance to the next parameter.
If the current selection requires a change, use to increment the display digit until it matches the first digit of the new scale factor. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the new scale factor. Repeat this step for the third digit. Press ENTER to save the new scale factor.
OTE:N If an out of range number is entered the display will flash Limit and refuse to allow the entry.
Preset Total SetTotl
Extended Function
It is sometimes helpful to be able to set the totalizer to a predetermined number before starting a process. The B3000 allows this through the use of the set total menu entry. The preset is capable of seven digits or up to 8,888,888.
At the SetTotl prompt, press ENTER twice. The first digit of the current preset total will begin to flash. If the current selection is correct, press ENTER to advance to the next parameter.
If the current selection requires a change, use to increment the display digit until it matches the first digit of the required preset. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the preset. Repeat this step until the preset is complete. Press ENTER to save the new preset.
OTE:N If an out of range number is entered the display will flash Limit and refuse to allow the entry.
Low Flow Cutoff Cutoff
Extended Function
A low flow cutoff entry is provided to allow low flow rates (that can be present when pumps are off and valves are closed) to be displayed as zero flow. A typical value would be about five percent of the flow sensors maximum flow. This setting is a good compromise between suppression of noise and utilizing the full span of the flow sensor.
The low flow cutoff is entered as an actual flow value. For example if the maximum flow rate for the flow sensor was 100 gpm the low flow cutoff values should be set for five percent of 100 gpm. The entry would then be 5.0.
At the Cutoff prompt, press ENTER. The first digit of the current low flow cutoff will begin to flash. If the current selection is correct, press ENTER to advance to the next parameter.
If the current selection requires a change, use to increment the display digit until it matches the first digit of the required low flow cutoff value. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the preset. Repeat this step until the low flow cutoff is entered. Press ENTER to save the new low flow cutoff.
OTE:N If an out of range number is entered the display will flash Limit and refuse to allow the entry.
Page 20 March 2014
Programming Manual
T
T
22

GAS COMPENSATION

Gas Turbines Only
Fluid measured by the gas turbine meter is compressible, and is also affected by temperature changes and pressure changes as illustrated by the ideal gas law equation.
PV
11
PV
=
1

Absolute Pressure and Temperature

The ideal gas law equation shows that the volume of gas is determined by pressure and temperature applied to the gas under running conditions. In this equation, the pressure, P, is absolute pressure the observed gauge pressure plus the atmospheric pressure. The commonly used domestic unit of measure for absolute pressure is pounds per square inch absolute (psia). Atmospheric pressure is considered to be 14.73 psi. Therefore, absolute pressure (psia) is the sum of the gage pressure plus 14.73.
The absolute temperature in the equation above is expressed in degrees Rankine, which is calculated by adding 459.67 to the temperature in ° F.
Because pressure and temperature have a large impact on the mass of gas moving through the flow meter both values must be entered into the B3000 for accurate gas readings to occur.
OTE:N The B3000 calculates the correct pressure and temperature values without having to convert to absolute pressure or
degrees Rankine. The compensation values should be entered in psig and ° F.
Operating Pressure Op Pres
Basic Function (Gas Only) At the Op Pres prompt, press ENTER. The first digit of the current pressure setting begins to flash. If the current selection requires a change, use to increment the display digit until it matches the first digit of the required
pressure value. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the operating pressure. When the correct pressure setting has been entered, press ENTER to save the new pressure value.
2
Operating Temperature Op Temp
Basic Function (Gas Only) At the Op Temp prompt, press ENTER. The first digit of the current temperature setting begins to flash. If the current selection requires a change, use to increment the display digit until it matches the first digit of the required
temperature value. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the operating temperature. When the correct pressure setting has been entered, press ENTER to save the new temperature value.
Damping Factor Damping
Extended Function
The damping factor is increased to enhance the stability of the flow readings. Damping values are decreased to allow the monitor to react faster to changing values of flow. This parameter can take on any value between 0…99 % with 0 being the default.
At the Damping prompt, press ENTER. The current damping setting will begin to flash. If the current selection is correct, press ENTER to advance to the next parameter.
If the current selection requires a change, use to increment the display digit until it matches the first digit of the required damping value. Next press the arrow key to advance to the next digit and using to increment the second display digit until it matches the second digit of the damping value. Press ENTER to save the new damping value.
Page 21 March 2014
Compact Digital Flow Monitor, Model B3000
Internal
JP1
JP2
JP3
Input Total Pulse Signal
P1
JP1
JP2
JP3
Input Total Pulse Signal
P1
Freq. In
4-20mA
Iso Total Pluse
TR_B
TR_A
RS485 Gnd
Setpoint 1
Setpoint 2
Gnd
+
+
+
Total Reset
OC Total Pluse
Signal Gnd
TB1
Mag
Pulse
Iso
OC
Low
High
Isolated Output
Total Pulse
Internal
–V
2.2…10k Pullup
Resistor
V
CC
100 mA
Maximum
Totalizer Pulse Output PulsOut
Basic Function
The PulsOut parameter can be either enabled or disabled. When enabled, this output generates a fixed width 30 mS duration, pulse every time the least significant digit of the totalizer increments. The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 28V DC.
The B3000 provides two types of totalizer pulses. The basic open drain FET output, Figure 19 and Figure 20, provides a ground referenced output pulse that swings between about 0.7V DC and VCC.
Input
JP1
Total Pulse
Freq. In
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
ISO OC
MagPulse
TB2
+
+
+
JP3
Internal
2.2 …10k Pullup
Resistor
Open Drain FET
Total Pulse Output
V
CC
100 mA
Maximum
RS485 Gnd
Setpoint 1
Setpoint 2
Freq. In
4-20mA
Iso Total Pluse
Total Reset
Total Pluse
Signal Gnd
TR_B
P1
TR_A
V
Gnd
+
JP1
+
JP2
+
JP3
Pulse
Mag
High
Input Total Pulse Signal
OC
Iso
2.2…10k Pullup
Resistor
Open Drain FET
Total Pulse Output
CC
100 mA
Maximum
Low
TB1
Figure 19: Open drain connections (NEMA 4X) Figure 20: Open drain connections (Ex-Proof)
The isolated pulse output (ISO), Figure 21 and Figure 22, are again an open collector output with the emitter of the transistor connected to the negative output terminal and is not referenced to ground. This output is optically isolated from the input signal for systems that require a totally isolated output pulse.
Input
JP1
Total Pulse
Freq. In
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
ISO OC
MagPulse
TB2
+
+
+
Internal
JP3
V
CC
2.2…10k
Pullup
Resistor
Isolated Output
Total Pulse
100 mA
Maximum
–V
Figure 21: Opto-isolated open collector connections (NEMA 4X) Figure 22: Opto-isolated open collector connections (Ex-Proof)
Both outputs have a maximum current capacity of 100 mA and require a pullup resistor. The value of the pullup resistor is dependent on the supply voltage and the maximum current required by the load device.
Page 22 March 2014
Programming Manual
P1
Freq. In
4-20mA
Iso Total Pluse
TR_B
TR_A
RS485 Gnd
Setpoint 1
Setpoint 2
Gnd
+
Total Reset
OC Total Pluse
Signal Gnd
TB1
Mag
Pulse
Iso
OC
Low
High
+
+
Input Total Pulse Signal
JP1
JP2
JP3
4-20 mA
Current Loop
(11 to 30 VDC)
POWER
SUPPLY
10A MAX
FUSED
400mA FUSED
CAT III 1000V
HOLD MIN MAX REL
Hz % ms RANGE
AutoHOLD FAST MIN MX LOGGING YES
CANCEL SAVE NO
SETUP
µA
mA
A
W
V
TEMPERATURE
COM
OFF
nS
W
VIEW MEM
CLEAR MEM
V
dB
mV
dB
ac+dc
V
ac+dc
A
mA
mV
ac+dc
mA
A
µA
ac+dc
µA
°C
°F
MEM
HM MS
51000
AUTO
MANUAL
%
FAST MAX MIN AVG
0 0
LOG
HOLD
Flow at 20 mA Fl=20mA
Basic Function
When the display is operated using loop power, the flow rate that corresponds to 20 mA must be set. This setting normally represents the maximum rate of the flow sensor connected to the display but other entries are possible.
At the Fl=20mA prompt, press ENTER. The current setting will begin to flash. If the current setting is correct, press ENTER to advance to the next parameter. If the current setting requires a change, use to increment the display digit until it matches the first digit of the required maximum flow value. Next press to advance to the next digit and using to increment the second display digit until it matches the second digit of the required value. Repeat this step until the maximum flow at 20 mA is entered. Press ENTER to save the new flow value.
4-20 mA Calibration 4-20Cal
Extended Function This menu item allows the fine adjustment of the Digital to
Analog Converter (DAC) that controls 4-20 mA output. The 4-20 mA output is calibrated at the factory and under most circumstances does not need to be adjusted. If the output needs to be adjusted for any reason the 4-20 mA calibration procedure is used.
The DAC used in the B3000 is an twelve bit device so the valid entries range from 0…4095.
4 mA Adjustment 4mA Out
To set the 4 mA value, connect an ammeter in series with the loop power supply as shown in Figure 23. At the 4-20Cal prompt, press ENTER. The display will now show a steady NO indication. Press to change to a YES display and press ENTER. The 4 mA DAC setting is typically between 35…50. Using and ► while monitoring the ammeter, adjust the 4 mA value to obtain a 4 mA reading on the ammeter. The ▲ increases the DAC value and ► decreases the DAC value. When a steady 4 mA reading is obtained on the ammeter, press ENTER to lock in this value and move to the 20 mA adjustment.
Figure 23: 4-20 mA calibration setup
20 mA Adjustment 20mAOut
The 20 mA adjustment is performed using the same procedure as the 4 mA adjustment. While monitoring the ammeter, adjust the 20 mA DAC value to obtain a 20 mA reading. The ▲ increases the DAC value and ► decreases the DAC value. When a steady 20 mA reading is obtained on the ammeter, press ENTER to lock in this value and move to the next parameter.
4-20 mA Test 4-20Tst
The B3000 monitor contains a diagnostic routine that allows the simulation of mA output values between 4…20 to check output tracking. At the 4-20 TEST prompt the current is shown as a flashing number. Use to increase the simulated mA output in increments of 1 mA. The ► decreases the mA output. The ammeter should track the simulated mA output. If a 4-20 mA test is not necessary, press ENTER to move to the next parameter.
OTE:N Pressing ENTER when the monitor is in test mode will exit the test mode and move on to the next
programming parameter.
Page 23 March 2014
Compact Digital Flow Monitor, Model B3000
Linearization Linear
Extended Function
Enhanced accuracy can be obtained by linearization of the display. The linearization function accepts a maximum of ten points. Linearization requires additional calibration data from the meter to be used with the monitor. Typically, calibration information can be obtained in three, five, and ten points from the flow meter’s manufacturer. If linearization is not needed, press to advance to the next parameter. The maximum number of linearization points is ten.
Number of Points
At the Linear prompt, press ENTER. The Lin Pts value will be displayed. If the number of points is set to 0, linearization is disabled. Press ENTER and the most significant digit of the number of points entry begins to flash. The first number can either be a 1 or a 0 only. Use to change the first digit. Press to move to the least significant digit.
OTE:N If a number other than 0 or 1 is entered in this field the display will flash Limit indicating that an over range is entered
when ENTER is pressed.
Again, increments the value. When the number of points is input, press ENTER to move to the first linear points frequency entry.
Data Entry
OTE:N If the number of linear points is set to 1 the B3000 assumes the user is entering the maximum frequency and
coefficient. Further, the meter assumes that the implied first point is at a frequency of 0 Hz and a coefficient of 0.
Frequency
Press ENTER and the first linear point’s frequency input Freq#1 begins to flash. Enter the frequency for the first linear point using to increment the numerical values and ► to change the position of the number being entered. When the frequency value input is complete, press ENTER to change to the coefficient value Coef#1 for the first linear point.
Coefficient
The coefficient is the value applied to the nominal K factor to correct it to the exact K factor for that point. The coefficient is calculated by dividing the actual K factor for that point by the Average (nominal) K factor for the flow meter.
Linear Coecient =
Actual K Factor
Nominal K Factor
At the Coef#1 prompt, enter the coefficient that corresponds to the frequency value previously entered. Press ENTER to move to the scaling point.
Continue entering pairs of frequency and coefficient points until all data has been entered. Press ENTER to move to the next parameter.
OTE:N The frequency values must be entered in ascending order. If a lower frequency value is entered after a higher value
the B3000 flash Limit followed by the minimum frequency value acceptable to the display.
Example:
The following is actual data taken from a one inch turbine flow sensor calibrated with water.
Page 24 March 2014
Programming Manual
Unit Under Test (UUT) Calibration Data Table In GPM
Actual
GPM
UUT
Frequency
Hz Counts/Gallon GPM % Rate
UUT Actual
K factor
(Hz x 60)
Nominal K
Linear
Coefficient
Raw Error
50.02 755.900 906.72 49.72 1.0060 0.59
28.12 426.000 908.96 28.02 1.0035 0.35
15.80 240.500 913.29 15.82 0.9987 -0.13
8.88 135.800 917.57 8.93 0.9941 -0.59
4.95 75.100 910.30 4.94 1.0020 0.20
Nominal K (NK) 912.144
Table 2: Sample linearization data
In this example the linear coefficient has already been calculated by the calibration program so all that is required is to enter 5 into the number of linear points Lin Pts parameter and then enter, in order, the five frequency, linear coefficient data pairs.
Modbus Modbus
Extended Function
The Modbus output parameter can be either enabled or disabled. When enabled, this output allows communications with the B3000 using the Modbus RTU protocol. For additional information see MODBUS INTERFACE on page 45.
At the Modbus prompt, press ENTER. The current state of the Modbus output is shown. If the current state is correct, press ENTER to advance to the next parameter.
If the current state requires a change, use either ▲ or to toggle between state. When the proper state has been selected press ENTER.
Bus Address BusAddr
If the Modbus output is enabled a valid Modbus address must also be chosen. Every device communicating over the RS485 communications bus using the Modbus protocol must have a unique bus address. Address values range from 0…127 with 0 being the default.
At the BusAddr prompt, press ENTER. The current setting begins to flash. If the current setting is correct, press ENTER to advance to the next parameter.
If the current setting requires a change, use to increment the display digit until it matches the first digit of the required bus address. Next press to advance to the next digit and using to increment the second digit until it matches the second digit of the required address. Repeat this step for the third digit of the address and then press ENTER to save the new address and advance to the next parameter.

Set Points

Set points allow the meter to signal when a specific flow condition has been achieved. They are commonly used to indicate high or low flow conditions that need to be attended to. The B3000 has two open collector outputs controlled by the set point function.
The set point transistors have the same current limitations and setup requirements as the totalizing pulse output transistors described previously (see Figure 23 and Figure 24).
Both set point one and set point two are configured using the same procedures but the hysteresis and tripping conditions are independently set for each set point output.
OTE:N In most instances the current capacity of an open collector transistor is not sufficient to operate old style counters
that relied on relay contact closures. When used with basic counting circuits a solid state relay is likely to be needed.
Page 25 March 2014
Compact Digital Flow Monitor, Model B3000
Set Point 1 SetPt 1
Extended Function
The set point is the flow value at which the output transistor changes state. It is set using the same units as the rate units are entered.
V
1 and 2
CC
100 mA
Maximum
RS485 Gnd
Setpoint 1
Setpoint 2
Freq. In
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
TR_B
TR_A
Gnd
+
+
+
P1
JP1
Input Total Pulse Signal
Pulse
Mag
OC
Iso
High
Low
TB1
Internal
JP2
JP3
Internal
P2
P1
P1
TB1
Gnd
Setpoint 2
Setpoint 1
RS485 Gnd
TR_A
TR_B
3.6Vdc Battery
V
CC
2.2…10K
100 mA
Maximum
+ –
Open Collector
Control Output
1 and 2
Pull-up
Resistor
2.2…10K Pull-up
Resistor
Open Collector Control Output
Figure 24: Set point output (NEMA 4X) Figure 25: Set point output (Ex-Proof))
At the SetPt 1 prompt, press ENTER. The most significant digit of the current setting begins to flash. If the current setting is correct, press ENTER to advance to the next parameter.
If the current setting requires a change, press to advance to the first digit of the required set point value. Once the correct place is reached use to increment the digit until it matches the first number of the required set point. Use to advance to the next digit of the required set point value then use to increment the display digit until it matches the next digit of the required set point. Repeat this step for the all the digits of the set point and then press ENTER to save the new set point and advance to the next parameter.
Hysteresis 1 HystSP1
Extended Function
Hysteresis is used to modify how the output transistor reacts around a set point by taking recent history into account. Hysteresis prevents an output from turning on and off rapidly when the programed flow rate is at or very near the set point.
For example, a low flow alarm is set to activate when the flow falls below a pre programed point. When the flow is reduced to the set point, even minute changes of flow above the set point turns the output off disabling the alarm. Without hysteresis, if the flow rate fluctuates slightly above and below the set point the output rapidly cycle between on and off states.
Another example is a thermostat controlling a heater. The thermostat turns the heater on when the temperature drops below “A” degrees, but won’t turn it off until the temperature rises above “B” degrees. The temperature between “A” and “B” is know as the hysteresis. Thus the on/off output of the thermostat to the heater when the temperature is between “A” and “B” depends on the “history” of the temperature. This prevents rapid switching on and off as the temperature drifts around the set point.
Refer to the graphical representation of the hysteresis setting as shown in Figure 26. The hysteresis value is set using the same units as the rate units are entered.
At the HystSP1 prompt, press ENTER. The most significant digit of the current setting begins to flash. If the current setting is correct, press ENTER to advance to the next parameter.
If the current setting requires a change, press to advance to the first digit of the required hysteresis value. Once the correct place is reached use to increment the digit until it matches the first number of the required hysteresis. Use to advance to the next digit of the required hysteresis value then use to increment the display digit until it matches the next digit of the required hysteresis. Repeat this step for the all the digits of the hysteresis and then press ENTER to save the new hysteresis and advance to the next parameter.
Page 26 March 2014
Programming Manual
Minimum
Flow
OFF Setpoint
ON Setpoint
Output ON
Maximum
Flow
Output OFF
Hysteresis
Figure 26: Set point actions
OTE:N Neither the set point nor the hysteresis values are checked against the meter size to see if they are appropriate. Care
should be used when entering these values, especially in critical applications, as it is possible to enter inappropriate values preventing the outputs from working as expected.
Trip SP 1 TripSP1
Extended Function
The trip parameter can be set for either High or Lo. When set to high the open collector transistor stops conducting and sends the output high when the set point is reached. The output will not go low again until the flow rate falls below the set point minus the hysteresis value. Similarly when set to low the, open collector transistor starts conducting sending the output low when the set point is reached. The output will not go high again until the flow rate exceeds the set point plus the hysteresis value.
For example if the set point is set to ten gpm, the hysteresis is set to two gpm and the trip set point is set to high (see Figure
27). When the flow goes above ten gpm the OC transistor stops conducting and the output goes high. The output stays high
until the flow rate drops below eight gpm which is the set point (ten gpm) minus the hysteresis (two gpm).
Minimum
Flow
OFF (8 gpm)
Setpoint (10 gpm)
Output ON
Maximum
Flow
Output OFF
Hysteresis
(2 gpm)
Figure 27: Set point example
At the TripSP1 prompt, press ENTER. The tripping condition setting is displayed. If the current setting is correct, press ENTER to advance to the next parameter.
If the current setting requires a change, press to advance to the alternate choice. Once the correct choice is displayed, press ENTER to save the new trip condition and advance to the next parameter.
Page 27 March 2014
Compact Digital Flow Monitor, Model B3000
Clear Grand Total CLR G-T
Basic Function At the Clr G-T prompt, press ENTER. The display will now say no on the screen. To clear the grand total press either or the
to change from no to yes. Press ENTER to select yes and advance to the next parameter.
The totalizer can also be reset using a hardware reset as shown in the following diagrams.
Input
Iso Total Pluse
Total Pulse
JP1
Freq. In
4-20mA
Total Reset
OC Total Pluse
Signal Gnd
ISO OC
JP3
MagPulse
TB2
+
+
+
Normally Open
Pushbutton
Switch
Normally Open
Pushbutton
Switch
P1
RS485 Gnd
Setpoint 1
Setpoint 2
Freq. In
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
TR_B
TR_A
Gnd
+
JP1
Input Total Pulse Signal
Pulse
Mag
+
JP2
+
JP3
OC
Iso
High
Low
TB1
Figure 28: NEMA 4X hardware reset Figure 29: Ex-proof hardware reset
Password Passwd
Basic Function
Password protection prevents unauthorized users from changing programming information. Initially, the password is set to all zeros. If the current setting requires a change, press ENTER at the Passwd prompt. The first digit of the password begins to flash. Use to increment the digit until it matches the first number of the required password. Use to advance to the next digit of the required password value then use to increment the display digit until it matches the next digit of the required password. Repeat this step for the all the digits of the password and then press ENTER to save the new password and advance to the next parameter.
Reset Password RstPswd
Basic Function
Reset password parameter prevents unauthorized users from manually resetting the flow monitor’s main totalizer. Initially, the password is set to all zeros. To change the reset password, press ENTER at the RstPswd prompt. The first digit of the password begins to flash. Use to increment the digit until it matches the first number of the required password. Use to advance to the next digit of the required password value then use to increment the display digit until it matches the next digit of the required password. Repeat this step for the all the digits of the password and then press ENTER to save the new password and advance to the next parameter.
OTE:N Entering a password in the Passwd screen and leaving the password blank in the RstPswd screen allows for total resets
(not requiring a password), but restricts programming modification.
Page 28 March 2014

APPENDIX

TROUBLESHOOTING GUIDE

Trouble Remedy
Battery – B30A/B/X/Z only Check battery voltage. Should be 3.6V DC. Replace if low or bad.
No LCD Display
No Rate or Total Displayed
Flow Rate Display Interprets Reading Constantly
Flow Rate Indicator Bounces
Loop Power
OTE:N Not available on B30S
Solar Place meter with solar cell exposed to a strong light source for 24 hours.
Programming Manual
Check 4-20 mA input. Voltage must be within the minimum and maximum supply voltage and capable of supplying enough current to run the display. The input voltage is checked “across” or in parallel with the 4-20 mA terminals. and current is checked with the ammeter in series with the 4-20 mA output.
Check connection from meter pick-up to display input terminals.
Check turbine meter rotor for debris. Rotor should spin freely.
Check programming of flow monitor.
This is usually an indication of external noise. Keep all AC wires separate from DC wires.
Check for large motors close to the meter pick-up.
Check for radio antenna in close proximity.
Try disconnecting the pick-up from the monitor pig tail. This should stop the noise.
This usually indicates a weak signal. Replace pick-up and/or check all connections.
Examine K factor.
Table 3: Troubleshooting guide

Default K Factor Values

Meter Bore Size Default K factor Lower Limit Upper Limit
0.375 20,000 16,000 24,000
0.500 13,000 10,400 15,600
0.750 2750 2200 3300
0.875 2686 2148 3223
1.000 870.0 696.0 1044
1.500 330.0 264.0 396.0
2.000 52.0 41.6 62.0
3.000 57.0 45.6 68.0
4.000 29.0 23.2 35.0
6.000 7.0 5.6 8.0
8.000 3.0 2.4 4.0
10.000 1.6 1.3 2.0
Meter Range Default K factor
Medium 125
Liquids
Table 4: Liquid K factors
Gas
Low 325
High 80
Table 5: Gas K factors
Page 29 March 2014
Compact Digital Flow Monitor, Model B3000

Battery Replacement (B30A/B/X/Z only)

Battery powered monitors use a single 3.6V DC “D” size, lithium battery. When replacement is necessary, use a clean fresh battery to ensure continued trouble-free operation.
Replacement Batteries
Manufacturer Part Number
Blancett B300028
Xeno S11-0205-10-03
Tadiran TL-5930/F
Table 6: Replacement batteries

NEMA 4X Enclosure

Unscrew the four captive screws on the front panel to gain access to the battery. Press the tab on the battery connector to release it from the circuit board. Remove the old battery and replace it with new one and then re-fasten the front panel.
OTE:N The battery is held in place with a wire-tie that will need to be cut and replaced (see Figure 30). The approval on the
product requires the wire tie.
J1
Unscrew
Captive Screws
KB/Display
2
1
P2
+ –
RS485 Gnd
Setpoint 1
Setpoint 2
4-20mA
Iso Total Pluse
Total Reset
OC Total Pluse
Signal Gnd
TR_B
TR_A
Freq. In
P1
Gnd
+
JP1
+
+
Input Total Pulse Signal
Pulse
Mag
JP2
OC
Iso
JP3
High
Low
TB1
Figure 30: NEMA 4X battery replacement
The solar powered variation uses a single nickle-cadmium battery and is not field replaceable.

Explosion Proof Enclosure

DANGER
REMOVE DEENERGIZE ANY EXTERNAL POWER FROM THE UNIT BEFORE REMOVING THE SCREW COVER FROM THE ENCLOSURE. FAILURE TO DO SO CAN BE DANGEROUS. SEE FIGURE 30 AND FIGURE 31
1. Remove the screw cover from the enclosure body.
2. Remove the two thumb screws and carefully remove the circuit board assembly far enough to access the battery connector.
3. Press the tab on the battery connector plug to release it from the battery connector socket.
4. Remove the four screws holding the battery mounting plate to the enclosure base and then remove the battery mounting plate.
Page 30 March 2014
Programming Manual
5. Cut the tie wrap holding the battery to the mounting plate and remove the worn-out battery.
6. Install a new tie wrap and battery securing the battery to the mounting plate with the tie wrap.
7. Re-install the battery mounting plate.
8. Plug the battery into the circuit board and re-install the circuit assembly into the explosion proof housing using the thumb screws.
9. Re-install the enclosure screw cover.
Thumb Screws
Menu
S1
TADRAN LITHIUM INORGANIC BATTORY
12
S4
1
S3UpS2
Enter
3.6 VOLTS
COM
Down
Tie Wrap
Battery Bracket
3.6 VOLTS
1
2
+
TADRAN LITHIUM
+
INORGANIC BATTORY
J1
Battery Connector
Release Tab
Figure 31: Ex-proof battery replacement
Page 31 March 2014
Compact Digital Flow Monitor, Model B3000
Liquid
Fluid Type
Meter Size
Numeric Entry
KFactor
K-Factor Value
Pulses/Gallon
Pulses/Liter
Pulses/Ft³
KFacUnt
K-Factor Unit
Flow-GT
Display
Display Options
START

MENU MAPS

to127)
MODBus Address
BusAddr
MODBus Address
(1
START
Passwd
Password
RstPswd
Reset Password
Numeric Entry
Numeric Entry
Modbus
Modbus
Disabled
Enabled
4mA Out
4 mA Output
Numeric Entry
4-20Cal
Calibrate 4-20
No
Ye s
x1000
x100
x10
ADVANCED I/O LIQUID
TotlMul
Totalizer Multiplier
X 1,000
X 100
X 10
X 1
X 0.1
X 0.01
20mAOut
SetPT1
20 mA Output
Setpoint 1
Numeric Entry
HystSP1
Hysteresis 1
Numeric Entry
4-20Tst
4-20 mA Test Output
TripSP1
Trip On 1
Numeric Entry
High
Numeric Entry
Linear
Linearization
Linear Points
to10)
(2
SetPT2
Setpoint 2
Lo
Freq#1
Frequency 1
HystSP2
Hysteresis 2
Numeric Entry
Coef#1
Coecient 1
Numeric Entry
TripSP2
Trip On 2
Numeric Entry
(x)
Freq#(x)
Frequency (2-10)
Numeric Entry
Numeric Entry
High
Lo
(x)
Coef#(x)
Coecient (2-10)
Clr G-T
Clear Grand Total
No
Ye s
Numeric Entry
for Extended settings
Press and hold MENU button
Extended
Scale Factor
Spec Gr
Specic Gravity
(T)
(T)
Scale F
Numeric Entry
(T)
(T)
(T)
(T)
(T)
Set Total Value
SetTotl
Numeric Entry
Low Flow Cuto
Cuto
Numeric Entry
Display Damping
Damping
Numeric Entry
PulsOut
Pulse Output
Numeric Entry
Disabled
Enabled
Flow at 20 mA
Fl=20mA
Numeric Entry
Sub Menu
(T)
(T)
(T)
(T)
Basic
RateInt
Fluid
Mass
RateUnt
Rate Interval
Day
Hour
Minute
Gas
Second
Rate Unit / Time
Gallons
Million Gallons
Ft³
Meters³
Liters
Million Liters
Acre Feet
Oil Barrel
Liquor Barrel
Meter
0375
0500
0750
0875
1.0
1.5
2.0
3.0
4.0
6.0
8.0
10.0
Pounds
Kilograms
1225
1250
1275
TotlUnt
Totalizing Unit
Gallons
Million Gallons
Flow
Ft³
Meters³
Test
Liters
Million Liters
Acre Feet
Oil Barrel
Mass
Liquor Barrel
Pulses/M³
Pounds
Kilograms
Menu item only
units are selected.
appears when Mass
Page 32 March 2014
Programming Manual
Flow-GT
Display
Display Options
Liquid
Fluid Type
Numeric Entry
KFactor
K-Factor Value
Pulses/Gallon
Pulses/Liter
Pulses/Ft³
KFacUnt
K-Factor Unit
START
Passwd
Clr G-T
Clear Grand Total
No
Password
Ye s
RstPswd
Reset Password
Numeric Entry
Numeric Entry
LIQUID
4-20Cal
Calibrate 4-20
TotlMul
Totalizer Multiplier
No
Ye s
x1000
x100
X 1,000
X 100
x10
X 10
X 1
4mA Out
X 0.1
4 mA Output
Numeric Entry
X 0.01
(x)
to10)
(2
Cuto
Freq#1
Frequency 1
Low Flow Cuto
Numeric Entry
20mAOut
20 mA Output
Specic Gravity
Spec Gr
4-20Tst
4-20 mA Test Output
Numeric Entry
Numeric Entry
Scale F
Scale Factor
Numeric Entry
Linearization
Linear
Linear Points
Set Total Value
SetTotl
Numeric Entry
Numeric Entry
Numeric Entry
Damping
Coef#1
Display Damping
Numeric Entry
Coecient 1
Freq#(x)
Frequency (2-10)
Numeric Entry
PulsOut
Pulse Output
Disabled
Enabled
(x)
Coef#(x)
Coecient (2-10)
Numeric Entry
Flow at 20 mA
Fl=20mA
Numeric Entry
Numeric Entry
for Extended settings
Press and hold MENU button
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
Extended
Rate SU
Rate Unit Setup
START
Advanced
Fluid
RateInt
Simple
Mass
RateUnt
Rate Interval
Day
Hour
Minute
Second
Rate Unit / Time
Gallons
Million Gallons
Ft³
Meters³
Liters
Million Liters
Acre Feet
Oil Barrel
Liquor Barrel
Pounds
Kilograms
TotlUnt
Totalizing Unit
Gallons
Million Gallons
Ft³
Meters³
Liters
Million Liters
Acre Feet
Mass
Menu item only
units are selected.
Oil Barrel
Liquor Barrel
Pounds
Kilograms
appears when Mass
Sub Menu
Basic
Flo Unit
Rate/Total Units
Gallons/Min
Gallons
Oil Barrel/Day
Barrels
Meters³/Day
Meters ³
Meters³/Hour
Meters³
Liters/Min
Liters
Meter
Meter Size
Gas
0375
0500
0750
0875
1.0
1.5
2.0
3.0
4.0
6.0
8.0
10.0
1225
1250
1275
Flow
Test
Pulses/M³
Page 33 March 2014
Compact Digital Flow Monitor, Model B3000
Liquid
Fluid Type
Numeric Entry
KFactor
K-Factor Value
Pulses/Gallon
Pulses/Liter
Pulses/Ft³
KFacUnt
K-Factor Unit
Flow-GT
Display
Display Options
Passwd
Clr G-T
Clear Grand Total
No
Password
Ye s
Numeric Entry
START
RstPswd
Reset Password
Numeric Entry
LIQUID (Solar Powered)
PulsOut
Pulse Output
TotlMul
Totalizer Multiplier
Disabled
Enabled
x1000
x100
X 1,000
X 100
x10
X 10
Linear
X 1
Linearization
X 0.1
Linear Points
X 0.01
to10)
(2
(x)
Freq#1
Frequency 1
Specic Gravity
Spec Gr
Numeric Entry
Coef#1
Coecient 1
Numeric Entry
Scale F
Freq#(x)
Frequency (2-10)
Numeric Entry
Scale Factor
SetTotl
Numeric Entry
Set Total Value
(x)
Coef#(x)
Coecient (2-10)
Numeric Entry
Numeric Entry
Cuto
Numeric Entry
Menu item only
units are selected.
Low Flow Cuto
Damping
Display Damping
Numeric Entry
Numeric Entry
appears when Mass
for Extended settings
Press and hold MENU button
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
(T)
Extended
Mass
Mass
RateUnt
Rate Interval
RateInt
Day
Hour
Minute
Second
Rate Unit / Time
Gallons
Million Gallons
Ft³
Meters³
Liters
Million Liters
Acre Feet
Oil Barrel
Liquor Barrel
Pounds
Kilograms
TotlUnt
Totalizing Unit
Gallons
Million Gallons
Ft³
Meters³
Liters
Million Liters
Acre Feet
Oil Barrel
Liquor Barrel
Pounds
Kilograms
Sub Menu
Basic
Flo Unit
Rate/Total Units
Gallons/Min
Gallons
Oil Barrel/Day
Barrels
Meters³/Day
Meters ³
Meters³/Hour
Meters³
Liters/Min
Rate SU
Rate Unit Setup
Advanced
Simple
Liters
START
Fluid
Page 34 March 2014
Meter
Meter Size
Gas
0375
0500
0750
0875
1.0
1.5
2.0
3.0
4.0
6.0
8.0
10.0
1225
1250
1275
Flow
Test
Pulses/M³
Programming Manual
START
Passwd
Clr G-T
Clear Grand Total
No
Password
Ye s
RstPswd
Reset Password
Numeric Entry
Numeric Entry
GAS
4-20Cal
Calibrate 4-20
Scale F
Scale Factor
No
Numeric Entry
(x)
4mA Out
4 mA Output
Ye s
20mAOut
20 mA Output
Numeric Entry
4-20Tst
4-20 mA Test Output
Numeric Entry
Numeric Entry
Linear
Linearization
Freq#1
Frequency 1
to10)
Linear Points
(2
Coef#1
Coecient 1
Numeric Entry
Freq#(x)
Frequency (2-10)
Numeric Entry
(x)
Coef#(x)
Coecient (2-10)
Numeric Entry
Numeric Entry
for Extended settings
Press and hold MENU button
Operating Temperature in °F
SetTotl
Set Total Value
Cuto
Low Flow Cuto
Numeric Entry
(T)
(T)
Operating Pressure in PSI
Op Pres
Numeric Entry
(T)
(T)
(T)
(T)
Op Temp
Numeric Entry
Damping
Display Damping
Numeric Entry
(T)
PulsOut
Pulse Output
Numeric Entry
Disabled
Enabled
Flow at 20 mA
Fl=20mA
Numeric Entry
Extended
x1000
x100
x10
Sub Menu
Basic
START
RateInt
Fluid
Rate Interval
Fluid Type
Day
Hour
Liquid
Gas
RateUnt
Second
Rate Unit / Time
Standard Ft³
Actual Ft³
Normal M³
Actual M³
Liters
Display
Meter
Meter Size/Capacity
2” Low
2” Medium
2” High
Display Options
Flow
Minute
Million Ft³
Thousand Ft³
Flow-GT
Test
TotlUnt
Totalizing Unit
K-Factor Unit
KFacUnt
Standard Ft³
Actual Ft³
Pulses/M³
Normal M³
Actual M³
Pulses/Liter
Pulses/Ft³
Liters
Million Ft³
KFactor
TotlMul
Thousand Ft³
K-Factor Value
Numeric Entry
Totalizer Multiplier
X 1,000
X 100
X 10
X 1
X 0.1
X 0.01
Page 35 March 2014
Compact Digital Flow Monitor, Model B3000
to127)
MODBus Address
BusAddr
MODBus Address
(1
START
Passwd
Password
RstPswd
Reset Password
Numeric Entry
Numeric Entry
Modbus
Modbus
Disabled
Enabled
4mA Out
4 mA Output
4-20Cal
Calibrate 4-20
No
Ye s
ADVANCED I/O GAS
Scale F
Scale Factor
SetTotl
Set Total Value
Numeric Entry
Numeric Entry
SetPT1
Setpoint 1
20mAOut
20 mA Output
Numeric Entry
HystSP1
Hysteresis 1
Numeric Entry
4-20Tst
4-20 mA Test Output
Numeric Entry
TripSP1
Trip On 1
Numeric Entry
Numeric Entry
Linear
Linearization
Linear Points
High
to10)
(2
SetPT2
Setpoint 2
Lo
Freq#1
Frequency 1
HystSP2
Hysteresis 2
Numeric Entry
Coef#1
Coecient 1
Numeric Entry
TripSP2
Trip On 2
Numeric Entry
High
(x)
Freq#(x)
Frequency (2-10)
Numeric Entry
Numeric Entry
Lo
(x)
Coef#(x)
Coecient (2-10)
Clr G-T
Clear Grand Total
No
Ye s
Numeric Entry
for Extended settings
Press and hold MENU button
Extended
Operating Temperature in °F
Cuto
Low Flow Cuto
(T)
(T)
Operating Pressure in PSI
Op Pres
Numeric Entry
(T)
(T)
(T)
(T)
Op Temp
Numeric Entry
Display Damping
Damping
Numeric Entry
(T)
PulsOut
Pulse Output
Numeric Entry
Disabled
Enabled
Flow at 20 mA
Fl=20mA
Numeric Entry
Sub Menu
x1000
x100
x10
Basic
RateUnt
Rate Interval
RateInt
Day
Hour
Minute
Second
Rate Unit / Time
Standard Ft³
Actual Ft³
Normal M³
Actual M³
Liters
Million Ft³
TotlUnt
Totalizing Unit
Thousand Ft³
Standard Ft³
Actual Ft³
Normal M³
Actual M³
Liters
Million Ft³
Thousand Ft³
TotlMul
Totalizer Multiplier
X 1,000
X 100
X 10
X 1
X 0.1
X 0.01
START
Fluid Type
Fluid
Liquid
Meter
Meter Size/Capacity
Gas
2” Low
2” Medium
Page 36 March 2014
2” High
Display
Display Options
Pulses/Liter
Pulses/Ft³
KFactor
Numeric Entry
K-Factor Unit
KFacUnt
Flow
Flow-GT
Test
Pulses/M³
K-Factor Value
Programming Manual
START
Passwd
Clr G-T
Clear Grand Total
No
Password
Ye s
RstPswd
Reset Password
Numeric Entry
Numeric Entry
GAS (Solar Powered)
Linear
Scale F
Scale Factor
(x)
Freq#1
Frequency 1
to10)
Linearization
Linear Points
(2
Coef#1
Coecient 1
Numeric Entry
Freq#(x)
Frequency (2-10)
Numeric Entry
(x)
Coef#(x)
Coecient (2-10)
Numeric Entry
Numeric Entry
for Extended settings
Press and hold MENU button
Operating Temperature in °F
SetTotl
Set Total Value
Numeric Entry
Cuto
Low Flow Cuto
Numeric Entry
(T)
(T)
Operating Pressure in PSI
Op Pres
Numeric Entry
(T)
(T)
(T)
(T)
Op Temp
Numeric Entry
Damping
Display Damping
Numeric Entry
(T)
PulsOut
Pulse Output
Disabled
Numeric Entry
Enabled
Extended
x1000
x100
x10
Sub Menu
START
RateInt
Fluid
Rate Interval
Fluid Type
Day
Hour
Liquid
Gas
Basic
RateUnt
Second
Rate Unit / Time
Standard Ft³
Actual Ft³
Normal M³
Actual M³
Liters
Million Ft³
Display
Meter
Meter Size/Capacity
2” Low
2” Medium
2” High
Display Options
Flow
Minute
TotlUnt
Thousand Ft³
Flow-GT
Test
Totalizing Unit
Standard Ft³
K-Factor Unit
KFacUnt
Pulses/M³
Actual Ft³
Normal M³
Pulses/Liter
Pulses/Ft³
Actual M³
Liters
Million Ft³
Thousand Ft³
K-Factor Value
KFactor
Numeric Entry
TotlMul
Totalizer Multiplier
X 1,000
X 100
X 10
X 1
X 0.1
X 0.01
Page 37 March 2014
Compact Digital Flow Monitor, Model B3000

K FACTORS EXPLAINED

The K factor (with regards to flow) is the number of pulses that must be accumulated to equal a particular volume of fluid. You can think of each pulse as representing a small fraction of the totalizing unit.
An example might be a K factor of 1000 (pulses per gallon). This means that if you were counting pulses, when the count total reached 1000, you would have accumulated one gallon of liquid. Using the same reasoning, each individual pulse represents an accumulation of 1/1000 of a gallon. This relationship is independent of the time it takes to accumulate the counts.
The frequency aspect of K factors is a little more confusing because it also involves the flow rate. The same K factor number, with a time frame added, can be converted into a flow rate. If you accumulated 1000 counts (one gallon) in one minute, then your flow rate would be one gpm. The output frequency, in Hz, is found simply by dividing the number of counts (1000) by the number of seconds in a minute (60) to get the output frequency.
1000 ÷ 60 = 16.6666 Hz. If you were looking at the pulse output on a frequency counter, an output frequency of 16.666 Hz would be equal to one gpm. If the frequency counter registered 33.333 Hz (2 × 16.666 Hz), then the flow rate would be two gpm.
Finally, if the flow rate is two gpm, then the accumulation of 1000 counts would take place in 30 seconds because the flow rate, and hence the speed that the 1000 counts is accumulated, is twice as great.

Calculating K factors

Many styles of flow meters are capable of measuring flow in a wide range of pipe sizes. Because the pipe size and volumetric units the meter will be used on vary, it may not possible to provide a discrete K factor. In the event that a discrete K factor is not supplied then the velocity range of the meter is usually provided along with a maximum frequency output.
The most basic K factor calculation requires that an accurate flow rate and the output frequency associated with that flow rate be known.
Example 1
Known values are:
Frequency = 700 Hz
Flow Rate = 48 gpm
700 Hz × 60 sec = 42,000 pulses per min
K factor
Example 2
Known values are:
Full Scale Flow Rate = 85 gpm
Full Scale Output Frequency = 650 Hz
650 Hz × 60 sec = 39,000 pulses per min
K factor
The calculation is a little more complex if velocity is used because you first must convert the velocity into a volumetric flow rate to be able to compute a K factor.
To convert a velocity into a volumetric flow, the velocity measurement and an accurate measurement of the inside diameter of the pipe must be known. Also needed is the fact that one US gallon of liquid is equal to 231 cubic inches.
42,000 pulses per min
48 gpm
39,000 pulses per min
85 gpm
875 pulses per gallon= =
458.82 pulses per gallon= =
Page 38 March 2014
Example 3
99.1 gpm
Known values are:
Velocity = 4.3 ft/sec
Inside Diameter of Pipe = 3.068 in.
Find the area of the pipe cross section.
2
πr
Area =
2
3.068
Area
= π = π x
 
2
2.35 = 7.39 in
2
Find the volume in one foot of travel.
Programming Manual
2
7.39 in2 x 12 in. (1 ft)ft=
88.71in
What portion of a gallon does one foot of travel represent?
231 in
3
= 0.384 gallons
3
88.71 in
So for every foot of fluid travel 0.384 gallons will pass.
What is the flow rate in gpm at 4.3 ft/sec?
0.384 gallons × 4.3 FPS × 60 sec (1 min) = 99.1 gpm
Now that the volumetric flow rate is known, all that is needed is an output frequency to determine the K factor.
Known values are:
Frequency = 700 Hz (By measurement)
Flow Rate = 99.1 gpm (By calculation)
700 Hz × 60 sec = 42,000 pulses per gallon
K factor
42,000 pulses per min
423.9 pulses per gallon= =
Page 39 March 2014
Compact Digital Flow Monitor, Model B3000
®
Badger Meter
We: Badger Meter, Inc. of: 4545 W. Brown Deer Road Milwaukee, WI 53224 USA
EU Representative: Badger Meter, Europa of: Nürtingerstr. 76 72639 Neuffen Germany
In accordance with Directives: 94/9/EC ATEX 2004/108/EC EMC
Declares that the Products: Blancett Turbine Meter Monitors B30X and B30Z
Conform to the following Standards:
Declaration of Conformity
IEC 61000-3-2 A14 (EN 61000-3-2) 2009-02 (2006-05) IEC 61000-3-3 (EN 61000-3-3) 2008-06 (2008 -12)
Emissions: CISPR 11 (EN 55011; A1 and A2) 2009-05 (2007-05)
Immunity: IEC 61000-4-2 (EN 61000-4-2) 2008-12 (2009-03)
IEC 61000-4-3 (EN 61000-4-3) 2008-04 (2008-05) IEC 61000-4-4 (EN 61000-4-4) 2004-07 (2004) IEC 61000-4-5 (EN 61000-4-5) 2005-11 (2006-12) IEC 61000-4-6 (EN 61000-4-6) 2008-10 (2007-08) IEC 61000-4-8 (EN 61000-4-8) 2001-03 (2001) IEC 61000-4-11 (EN 61000-4-11) 2004-03 (2004-10) Safety: EN 60079-0:2009, EN60079-1:2007 and EN60079-31:2009
Blancett B30X and B30Z Flow Monitor products meet the requirements as described within the specifications of EN61000-6-4 for a Class B product for emissions, EN 61000-6-2 for immunity tests of an ISM product and Council Directive ATEX, 94/9/EC to ATEX II 2G Ex d IIC T4 Gb and ATEX II 2D Ex tb IIIC 135°C Db (Ta -30°C to 70°C) for safety.
Reference Documents:
ENGINEERING TEST REPORT # 309378/C-771 conducted 30-November 2009 by LS Research, LLC
EC Type Examination Certification No.: TRAC12ATEX0017X issued by TRaC Global, Ltd. (Notified body No. 0891) Unit 1, Pendle Place, Skelmersdale, West Lancashire, WN8 9PN UK
09.07.2013
Unterschift Unterschift
Geschãftsführer / Managing Director QMB / Quality Control Horst Gras Ute Kneule
QM_Racine-ZF_CE_e_B30X-Z-540.doc 07/13
Badger Meter Europa GmbH - Nürtinger Strasse 76-72639 Neuffen (Germany)
Tel. +49-7025-9208-0 Fax +49-7025-9208-15 www.badgermeter.de E-mail:badger@badgermeter.de
Page 40 March 2014
Programming Manual

SYMBOL EXPLANATIONS

CAUTION
REFER TO ACCOMPANYING DOCUMENTS.
WARNING
EXPLOSION HAZARD  SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
AVERTISSMENT
RISQUE D’EXPLOSION  LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CEMATÉRIEL INACCCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
WARNING
DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO BE NONHAZARDOUS.
AVERTISSMENT
RISQUE D’EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUSTENSION, À MOINS QU’LL NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.
MPORTANTI Not following instructions properly may impair safety of equipment and/or personnel.

ELECTRICAL SYMBOLS

Function
Symbol
Direct
Current
Alternating
Current
Earth
(Ground)
Protective
Ground
Chassis Ground
Page 41 March 2014
Compact Digital Flow Monitor, Model B3000
EXPLOSIONPROOF ENCLOSURE
The ExDirect instrument enclosure is designed to house instrumentation and control equipment as well as act as a conduit.

Installation

1. ExDirect instrument enclosures are furnished with three 3/4 in. NPT oset through-feed cast hubs for conduit entries.
2. Secure the enclosure to the conduit system. If the enclosure has mounting feet, select a mounting location that will provide sucient strength and rigidity to support the enclosure as well as the enclosed device and wiring.
WARNING
ELECTRICAL POWER MUST BE “OFF” BEFORE AND DURING INSTALLATION AND MAINTENANCE.
CAUTION
SELECT A MOUNTING LOCATION SO THAT THE ENCLOSURE WILL NOT BE SUBJECTED TO IMPACT BY HEAVY OBJECTS. IMPACTS CAN DAMAGE ENCLOSED DEVICES OR GLASS LENS.
3. Install sealing ttings as required by Section 501-5 and/or 502-5 of the National Electrical Code® and Section 18 of the Canadian Electrical Code or any other applicable IEC 60079-14 codes and when enclosure is installed in Class I Group B
hazardous locations. (For CSA Group C applications, unsealed conduit lengths must not exceed 5 ft. or 152 cm.)
5.25 [133.4]
5.65 [143.5]
0.33 [8.4]
2.25 [57.1]
3.35 [85.1]
Figure 32: Ex-proof enclosure dimensions
4. Loosen set screw on instrument cover with a 2 mm Allen wrench.
5. Un-thread instrument cover and carefully set aside to prevent damage to the cover threads and glass lens.
6. Pull wires into enclosure making certain they are long enough to make the required connections and to remove the instrument or power supply if servicing is required. Install instrument and power supply, if applicable, and make all electrical connections.
7. Test wiring for correctness by checking continuity and also check for unwanted grounds with insulator resistance tester. Make sure test equipment being used will not damage instrument to be housed in the ExDirect instrument enclosure.
8. Carefully re-thread cover to enclosure housing. Tighten cover until cover ange contacts body face.
Page 42 March 2014
Programming Manual
WARNING
THE HAZARDOUS LOCATION INFORMATION SPECIFYING CLASS AND GROUP LISTING OF EACH INSTRUMENT ENCLOSURE IS MARKED ON THE NAMEPLATE OF EACH ENCLOSURE.
CAUTION
ALL UNUSED CONDUIT OPENINGS MUST BE PLUGGED. PLUG UNUSED CONDUIT OPENINGS WITH APPROVED EXPLOSION PROOF PLUGS. PLUGS MUST BE A MINIMUM OF 1/8"THICK AND ENGAGE A MINIMUM OF 5 FULL THREADS.
OTE:N When installing device, be sure to check instrument dimensions to avoid interference with clamping ring on glass
lens and the cover on standard units.
CAUTION
USE CARE TO PREVENT DIRT, GRIT OR OTHER FOREIGN MATERIAL FROM LODGING ON THREADS. IF SUCH MATERIAL SETTLES ON THREADS, CLEAN WITH KEROSENE OR STODDARD SOLVENT*, THEN RELUBRICATE WITH AN APPROVED THREAD LUBRICANT.
9. Tighten cover set screws with the 2 mm Allen wrench to prevent cover from loosening under vibration.
WARNING
TO MAINTAIN THE EXPLOSIONPROOF INTEGRITY OF THE ENCLOSURE WITH A SCREW IN A TAPPED MOUNTING PAD HOLE, THERE MUST BE A MINIMUM OF 1/16 IN. OF MATERIAL BETWEEN THE DRILL POINT AND THE BACK WALL. IF FOR ANY REASON A SCREW WILL NOT BE THREADED INTO THE DRILLED HOLE, A MINIMUM OF 1/8 IN. OF MATERIAL MUST REMAIN BETWEEN THE DRILL POINT AND THE BACK WALL.
WARNING
TO AVOID THE POSSIBILITY OF AN EXPLOSION, OXIDATION AND CORROSION, DO NOT USE GASOLINE OR SIMILAR SOLVENT.
Page 43 March 2014
Compact Digital Flow Monitor, Model B3000
THIS DRAWING IS PROPRIETARY TO BADGER METER INC. RECEIPT OR POSSESSION CONFERS NO RIGHT TO USE
THE SUBJECT MATTER OF THIS DRAWING OR TECHNICAL INFORMATION SHOWN; NOR THE RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART EXCEPT FOR THOSE SUPPLIERS OF BADGER METER INC. WHO RECEIVE A WRITTEN
REQUEST FOR MANUFACTURE OR SIMILAR USE.
NOTES: UNLESS OTHERWISE SPECIFIED
3. RADII TO BE .005/.010
2. FINISH TO BE 63
1. REMOVE ALL BURRS AND BREAK SHARP EDGES .005/.010
PART 1, SEC. 18 AND APPENDIX F, ARTICLE 500 OF THE NEC, OR
MANUFACTURER'S CONTROL DRAWING, CANADIAN ELECTRICAL CODE
4. BARRIERS MUST BE INSTALLED IN ACCORDANCE WITH BARRIER
2. INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE, PLUS
THE CAPACITANCE AND INDUCTANCE OF THE INTRINSICALLY SAFE
EQUIPMENT, MUST BE LESS THAN OR EQUAL TO THE CAPACITANCE
(Ca) AND INDUCTANCE(La) ENTITY PARAMETERS MARKED ON THE BARRIER.
A
PART NUMBER:
RACINE, WISCONSIN U.S.A.
TEL: 262-639-6770 FAX: 262-639-9857
BADGER METER
12/2/09
T. PAUL
< La
CHECKED BY:
DRAWN BY:
Li + Lc
DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED
ENGINEER:
ANGLES ±1/2°
.00 ±.010, .000 ±.005
TOLERANCE ON DECIMALS
INSTALLATION DRAWING FOR
NAME:
T. PAUL 3/19/12
REVISED BY:
MATERIAL:
B3000 MONITOR
CODE I.D. NO.SIZE: PART NUMBER:
SUPERSEDES:
DATE:
1 OF 1
B300020
59380
D
SCALE: SHEET:CURRENT REV:NONE A
WILL BE IGNORED UNLESS AUTHORIZED.
THIS DRAWING WAS DONE ON AUTOCAD AND
CAN ONLY BE REVISED ON AUTOCAD SYSTEM.
ANY MANUAL CHANGES DONE TO THIS DRAWING
1
2
- 3/19/12
H
G
F
E
D
C
B
B300020
REVISIONS
2 1345610 9 8 712 11
1.) WAS Voc=2.5V
2.) WAS Isc=1.8mA
H10 A
H10
ZONE REV DESCRIPTION E.C.N. DAT E APPROVAL
WIRE HARNESS
P0ART #B300070
METER MOUNT OPTION
TABLE 1:
Voc
BARRIER
>
Vmax
IS EQUIPMENT
Ca
Isc
<
>
Imax
Ci + Cc
4 3
WIRE HARNESS
PART #B300071
5
1
21
Turbine Input
Pulse Output Reset Input RS485
4-20mA Loop
TABLE 2
H
Voc = 3.5V
Isc = 3.6mA
60mA
10 Vdc
5mA
5 Vdc
100mA
28 Vdc
26mA
28 Vdc
I Max
V Max
Ca = 15µF
La = 1.65H
0.0µF
0.0mH
0.0µF
0.0mH
0.0µF
0.0mH
0.5µF
0.0mH
Li
Ci
SWIVEL MOUNT OPTION
REMOTE CABLE WITH STRAIGHT AMPHENOL
OPTIONAL CABLE ASSEMBLY
CONNECTOR (PART #B220221)
AMPHENOL CONNECTOR (PART #B220220)
REMOTE CABLE WITH 90° AMPHENOL
6
7
THROUGH SUITABLY SIZED UL & CSA CERTIFIED LIQUID TIGHT
THAN OR EQUAL TO THE CAPACITANCE(Ca) AND THE INDUCTANCE(La) "TURBINE
INPUT" ENTITY PARAMETERS MARKED ON THE B3000 MONITOR AND TABLE 2.
STRAIGHT THRU FITTINGS
1. ALL CABLE ENTRIES INTO THE ENCLOSURE MUST BE BROUGHT
NOTES ON CABLE ENTRY
NOTES ON CONTROL EQUIPMENT
WITH RESPECT TO EARTH.
1. CONTROL EQUIPMENT MUST NOT USE OR GENERATE MORE THAN 250 V,
CAPACITANCE AND INDUCTANCE OF THE MAGNETIC PICKUP, MUST BE LESS
NOTES ON FLOW SENSOR
1. INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE, PLUS THE
STRAIGHT. TO TURBINE
CONNECTOR 90° OR
REMOTE MOUNT OPTION
1
10 FT. TO MAX. 100 FT.
OPTIONAL AMPHENOL
HAZARDOUS LOCATION
OTHER LOCAL CODES.
5. WHEN SELECTING CABLE FOR CONNECTION TO
TURBINE METER, USE CABLE WITH THE FOLLOWING
10 9 8
PARAMETERS: 0.2 uh/ft. AND 60 pF/ft.
SET POINT &
(CLASSIFIED)
GROUP C & D
CLASS I, DIV 1
CLASS II, DIV 1
GROUP E, F & G
CLASS I, ZONE 0, IIB
HAZARDOUS LOCATION
TOTAL PULSE 1/F
4-20mA 1/F
R5485 1/4
CAPACITIANCE VALUE SHALL BE AS SHOWN IN TABLE 1.
NOT EXCEEDING Vmax AND Isc NOT EXCEEDING Imax
INTRINSICALLY SAFE FOR THE APPLICATION AND HAVE Voc
1. SELECTED BARRIERS MUST BE CERTIFIED AS
NOTES ON BARRIERS:
3. MAY BE IN DIVISION 2 LOCATION IF SO APPROVED
11
MODEL 7787+
MTL SAFETY BARRIER
1 3
NON-HAZARDOUS LOCATION
G
F
2 4
RTU/PLC
PULSE INPUT
26 Vdc MAX.+
E
MODEL 7706+
* 0.1 mA @ .7 VOLT DROP
1 3
20-35 VDC
2 4
R LOAD
4-20mA
-
GND.
D
MODEL 7766 Pac
HOST
1 3
2 4
R5485
C
12
B
A
Page 44 March 2014
Programming Manual

MODBUS INTERFACE

A subset of the standard Modbus commands is implemented to provide access into the data and status of the B3000 Monitor. This feature is available on the B3000 Advanced models only. The following Modbus commands are implemented:
Command Description
01 Read Coils
03 Read Holding Registers
05 Force Single Coil
Table 7: Modbus commands
Type Bits Bytes Modbus Registers
Long Integer 32 4 2
Single Precision IEEE754 32 4 2
Table 8: Available data formats

Modbus Register / Word Ordering

Each Modbus Holding Register represents a 16-bit integer value (2 bytes). The official Modbus standard defines Modbus as a ‘big-endian’ protocol where the most significant byte of a 16-bit value is sent before the least significant byte. For example, the 16-bit hex value of ‘1234’ is transferred as ‘12’ ‘34’.
Beyond 16-bit values, the protocol itself does not specify how 32-bit (or larger) numbers that span over multiple registers should be handled. It is very common to transfer 32-bit values as pairs of two consecutive 16-bit registers in little-endian word order. For example, the 32-bit hex value of ‘12345678’ is transferred as ‘56’ ‘78’ ‘12’ ‘34’. Notice the Register Bytes are still sent in big-endian order per the Modbus protocol, but the Registers are sent in little-endian order.
Other manufactures, store and transfer the Modbus Registers in big-endian word order. For example, the 32-bit hex value of ‘12345678’ is transferred as ‘12’ ‘34’ ‘56’ ‘78’. It doesn’t matter which order the words are sent, as long as the receiving device knows which way to expect it. Since it’s a common problem between devices regarding word order, many Modbus master devices have a configuration setting for interpreting data (over multiple registers) as ‘little-endian’ or ‘big-endian’ word order. This is also referred to as swapped or word swapped values and allows the master device to work with slave devices from different manufactures.
If, however, the endianness is not a configurable option within the Modbus master device, it’s important to make sure it matches the slave endianess for proper data interpretation. The B3000 actually provides two Modbus Register maps to accommodate both formats. This is useful in applications where the Modbus Master cannot be configured for endianness.
Page 45 March 2014
Compact Digital Flow Monitor, Model B3000

Register Mappings

MODBUS Registers
Data Component Name
Long Integer Format
Single Precision
Floating Point Format
Spare 40100…40101 40200…40201
Available Units
Flow Rate 40102…40103 40202…40203
Gallons, Liters, MGallons,
Cubic Feet, Cubic Meters,
Spare 40104…40105 40204…40205
Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg,
Positive Totalizer 40106…40107 40206…40207
BTU, MBTU, MMBTU, TON
Per
Grand Total Totalizer 40108…40109 40208…40209
Second, Minute, Hour, Day
Battery Voltage 40110…40111 40210…40211 x.xx
Spare 40112…40113 40212…40213
Table 9: Modbus register map for ‘Little-Endian’ word order master devices
For reference: If the B3000 Totalizer = 12345678 hex
Register 40106 would contain 5678 hex (Word Low)
Register 40107 would contain 1234 hex (Word High)
MODBUS Registers
Data Component Name
Long Integer Format
Single Precision
Floating Point Format
Available Units
Spare 40600…40601 40700…40701
Flow Rate 40602…40603 40702…40703
Gallons, Liters, MGallons,
Cubic Feet, Cubic Meters,
Spare 40604…40605 40704…40705
Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg,
Positive Totalizer 40606…40607 40706…40707
BTU, MBTU, MMBTU, TON
Per
Grand Total Totalizer 40608…40609 40708…40709
Second, Minute, Hour, Day
Battery Voltage 40610…40611 40710…40711 x.xx
Spare 40612…40613 40712…40713
Table 10: Modbus register map for ‘Big-Endian’ word order master devices
For reference: If the B3000 Totalizer = 12345678 hex
Register 40606 would contain 1234 hex (Word High)
Register 40607 would contain 5678 hex (Word Low)
Page 46 March 2014
Modbus Coil Description Modbus Coil Notes
Reset Running Totalizer 1
Forcing this coil ON will reset the running totalizer. After reset, the coil automatically returns to the OFF state.
Forcing this coil ON will reset both the running totalizer and the
Reset Grand Totalizer 2
grand totalizer. After reset, the coil automatically returns to the OFF state.
3…8 Spares
Alarm Set point 1 9 0 = Set point OFF, 1 = Set point ON Alarm Set point 2 10 0 = Set point OFF, 1 = Set point ON
11…16 Spares
Table 11: Modbus coil map
Opcode 01 – Read Coil Status
This opcode returns the state of the alarm coils. The following Coils are defined:
Coil # Description
9 Alarm Set point 1
10 Alarm Set point 2
11 and up Spare
Table 12: Read coil status
Programming Manual
Command: <addr><01><00><08><00><02><crc-16> Reply: <addr><01><01><0x><crc-16>
Opcode 03 – Read Holding Registers
This opcode returns the input holding registers, such as flow rate or totalizer.
OTE:N Each value must be requested individually. Return of a block of registers is not implemented at this time.
Example requesting flow rate in floating point format.
Command: <addr><03><00><C9><00><02><crc-16> Reply: <addr><03><02><data><data><crc-16>
Opcode 05 – Force Single Coil
This opcode sets the state of a single coil (digital output). The following Coil Registers are defined:
Coil # Description
1 Reset Totalizer
2 Grand Totals
3 and up Spares
Table 13: Force single coil
The transition of coil from 0 to 1 will initiate function. This bit is auto reset to 0, so there is no need to set it to 0 after a totalizer reset command.
Command: <addr><05><00><00><FF><00><crc-16> Reply: <addr><05><00><00><FF><00><crc-16>
Page 47 March 2014
Compact Digital Flow Monitor, Model B3000

C Source Code

A.1.1 CRC-16 Calculations
unsigned short crc_table[256] = {
0x0000, 0xC0C1, 0xC181, 0x0140, 0xC301, 0x03C0, 0x0280, 0xC241,
0xC601, 0x06C0, 0x0780, 0xC741, 0x0500, 0xC5C1, 0xC481, 0x0440,
0xCC01, 0x0CC0, 0x0D80, 0xCD41, 0x0F00, 0xCFC1, 0xCE81, 0x0E40,
0x0A00, 0xCAC1, 0xCB81, 0x0B40, 0xC901, 0x09C0, 0x0880, 0xC841,
0xD801, 0x18C0, 0x1980, 0xD941, 0x1B00, 0xDBC1, 0xDA81, 0x1A40,
0x1E00, 0xDEC1, 0xDF81, 0x1F40, 0xDD01, 0x1DC0, 0x1C80, 0xDC41,
0x1400, 0xD4C1, 0xD581, 0x1540, 0xD701, 0x17C0, 0x1680, 0xD641,
0xD201, 0x12C0, 0x1380, 0xD341, 0x1100, 0xD1C1, 0xD081, 0x1040,
0xF001, 0x30C0, 0x3180, 0xF141, 0x3300, 0xF3C1, 0xF281, 0x3240,
0x3600, 0xF6C1, 0xF781, 0x3740, 0xF501, 0x35C0, 0x3480, 0xF441,
0x3C00, 0xFCC1, 0xFD81, 0x3D40, 0xFF01, 0x3FC0, 0x3E80, 0xFE41,
0xFA01, 0x3AC0, 0x3B80, 0xFB41, 0x3900, 0xF9C1, 0xF881, 0x3840,
0x2800, 0xE8C1, 0xE981, 0x2940, 0xEB01, 0x2BC0, 0x2A80, 0xEA41,
0xEE01, 0x2EC0, 0x2F80, 0xEF41, 0x2D00, 0xEDC1, 0xEC81, 0x2C40,
0xE401, 0x24C0, 0x2580, 0xE541, 0x2700, 0xE7C1, 0xE681, 0x2640,
0x2200, 0xE2C1, 0xE381, 0x2340, 0xE101, 0x21C0, 0x2080, 0xE041,
0xA001, 0x60C0, 0x6180, 0xA141, 0x6300, 0xA3C1, 0xA281, 0x6240,
0x6600, 0xA6C1, 0xA781, 0x6740, 0xA501, 0x65C0, 0x6480, 0xA441,
0x6C00, 0xACC1, 0xAD81, 0x6D40, 0xAF01, 0x6FC0, 0x6E80, 0xAE41,
0xAA01, 0x6AC0, 0x6B80, 0xAB41, 0x6900, 0xA9C1, 0xA881, 0x6840,
0x7800, 0xB8C1, 0xB981, 0x7940, 0xBB01, 0x7BC0, 0x7A80, 0xBA41,
0xBE01, 0x7EC0, 0x7F80, 0xBF41, 0x7D00, 0xBDC1, 0xBC81, 0x7C40,
0xB401, 0x74C0, 0x7580, 0xB541, 0x7700, 0xB7C1, 0xB681, 0x7640,
0x7200, 0xB2C1, 0xB381, 0x7340, 0xB101, 0x71C0, 0x7080, 0xB041,
0x5000, 0x90C1, 0x9181, 0x5140, 0x9301, 0x53C0, 0x5280, 0x9241,
0x9601, 0x56C0, 0x5780, 0x9741, 0x5500, 0x95C1, 0x9481, 0x5440,
0x9C01, 0x5CC0, 0x5D80, 0x9D41, 0x5F00, 0x9FC1, 0x9E81, 0x5E40,
0x5A00, 0x9AC1, 0x9B81, 0x5B40, 0x9901, 0x59C0, 0x5880, 0x9841,
0x8801, 0x48C0, 0x4980, 0x8941, 0x4B00, 0x8BC1, 0x8A81, 0x4A40,
0x4E00, 0x8EC1, 0x8F81, 0x4F40, 0x8D01, 0x4DC0, 0x4C80, 0x8C41,
0x4400, 0x84C1, 0x8581, 0x4540, 0x8701, 0x47C0, 0x4680, 0x8641,
0x8201, 0x42C0, 0x4380, 0x8341, 0x4100, 0x81C1, 0x8081, 0x4040,
};
unsigned short calculate_crc(const unsigned char *pv, int size)
{
unsigned short crc = 0xFFFF;
for ( ;size-- ; pv++)
{
crc = (crc >> 8) ^ crc_table[(crc ^ *pv) & 0xFF];
}
return crc;
Page 48 March 2014
Programming Manual
WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT WEEE DIRECTIVE
In the European Union, this label indicates that t his product should not be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.
For information on how to recycle this product responsibly in your country, please visit:
www.badgermeter.com
Page 49 March 2014
Compact Digital Flow Monitor, Model B3000
INTENTIONAL BLANK PAGE
Page 50 March 2014
INTENTIONAL BLANK PAGE
Programming Manual
Page 51 March 2014
Control. Manage. Optimize.
Blancett is a registered trademarks of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2014 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | R acianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Legacy Document Number: 02-DSY-PM-00003-EN
Loading...