Badger Meter B28SBM-AB, B28SLM-AB, B28SBR-AB, B28SLR-AB, B28SBS-AB Standard User Manual

...
Flow Monitor
B2800 Standard
DSY-PM-00276-EN-04 (March 2017)
User Manual
CONTENTS
Scope of This Manual � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Unpacking and Inspection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Safety � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Introduction� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4
Operating the Monitor � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
Programming� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
Additional Scaling Parameters � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
Additional Input Options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 11
Default K-factor Values � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
Battery Replacement � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
Installation Drawing� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
Battery Powered � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13 Loop Powered � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
Troubleshooting Guide� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
Part Numbering Information � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
Specications � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 16
Replacement Parts� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 17
Mounting Options and Dimensions� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
Meter Mount � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Remote Mount � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18 Swivel Mount� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 19
Flow Monitor, B2800 Standard
Page ii March 2017DSY-PM-00276-EN-04
Scope of This Manual
SCOPE OF THIS MANUAL
This manual is intended to help you get the B2800 flow monitor up and running quickly�
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
UNPACKING AND INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment�
OTE:N If damage is found, request an inspection by the carrier’s agent within 48
hours of delivery and file a claim with the carrierA claim for equipment damage in transit is the sole responsibility of the purchaser
SAFETY
Terminology and Symbols
Indicates a hazardous situation, which, if not avoided, could result in severe personal injury or death�
Considerations
The installation of the B2800 monitor must comply with all applicable federal, state, and local rules, regulations, and codes�
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
AVERTISSMENT
RISQUE D’EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CEMATÉRIEL INACCCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO BE NON-HAZARDOUS.
AVERTISSMENT
RISQUE D’EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUSTENSION, À MOINS QU’LL NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.
MPORTANTI
Not following instructions properly may impair safety of equipment and/or personnel.
Page 3 March 2017 DSY-PM-00276-EN-04
Introduction
INTRODUCTION
The B2800 flow monitor is a state-of-the-art digital signal processing flow monitor, designed to provide exceptional flexibility at a very affordable price� Though designed for use with Blancett flow meters, this display can be used with almost any flow meter producing a low amplitude AC output or contact closure signals�
This flow monitor is capable of accepting a low level frequency input for calculating flow rate and total� The calculations can then be displayed in the desired units of measurement� The monitor’s large 8-digit by 0�75 in� (19�05 mm) numeric liquid crystal display makes extended range viewing practical� The second 8-digit by 0�38 in� (9�65 mm) alphanumeric display provides for selectable units viewing in run mode and prompts for variables in program mode� Finally, you can choose to display rate or total, or alternate between both rate and total�
Page 4 March 2017DSY-PM-00276-EN-04
Operating the Monitor
OPERATING THE MONITOR
Programming
Keys
Mode
Indicator
Units Display
And
Programming Choices
Rate / Total Display
And
Programming Choices
RUN PROGRAM
RELAY1 RELAY2
Figure 1: B2800 flow monitor
Buttons
MENU Switches to PROGRAM mode
UP
Scrolls forward through the parameter options and increments numeric variables
RIGHT
Scrolls backward through the parameter options and moves the active digit to the right
ENTER
Saves programming information, advances to the next programming parameter, and used in the reset process
Modes
RUN
Normal operating mode
PROGRAM
Used to program parameters in the display
Page 5 March 2017 DSY-PM-00276-EN-04
Programming
PROGRAMMING
Each turbine flow meter is shipped with either a K-factor value or frequency data� If frequency data is provided, the data must be converted to a K-factor before programming the monitor� K-factor information, when supplied, can usually be found on the neck of the flow meter or stamped on the flow meter body� The K-factor represents the number of pulses per unit of volume� The K-factor is needed to program the monitor readout�
Programming Mode
K Factor Units
Units
Pulse Output
IO/SETUP
METER
PUL/GAL PUL/FT3PUL/LTRPUL/M3
K FACTOR
GPM/GAL
LPM/LIT M3PH/M3
M3PD/M3
BPD/BBL
DSP
BOTH TO TAL R ATE TEST
PULS ON PULS OFF
PASSWORD
RST PSWD
Enter Program Mode
Press MENU to enter the programming mode� The mode indicator changes from RUN to PROGRAM
Select Meter Size
At the METER prompt, press UP or RIGHT to scroll to the bore size of your meter� Press ENTER to save and advance to the K-factor Units parameter�
OTE:N The meter connection size and the bore size are different� For example,
many of the one inch NPT turbines have bore sizes that range from 3/8…1 in� Be sure to use the correct bore size or the meter will report incorrect flows and totals�
Enter The K-Factor Unit
Press UP or RIGHT to scroll to the K-factor unit of the meter� Enter the unit that the meter was calibrated in�
Page 6 March 2017DSY-PM-00276-EN-04
Programming
Example
If the meter was calibrated in US gallons, use PUL/GAL
Press ENTER to save the K-factor unit and advance to the K FACTOR parameter�
OTE:N Unless otherwise specified, Blancett turbine flow meters are supplied
with K-factors measured in pulses per gallon (PUL/GAL) which will automatically convert to your desired units of measure�
Enter The Meter's K-Factor
OTE:N The K-factor supplied with the meter or calculated from calibration data is
needed to set this parameter�
To change the K-factor value, press RIGHT to select the digit that you wish to change� Press UP to increment the digit until it matches the meter’s K-factor� Repeat this process until all K-factor digits have been entered� Press ENTER to save the K-factor and advance to RATE/ TOTAL
Select the Units of Measure
The monitor is programmed with five common rate/total unit options� The monitor shows the rate/total unit that the display is currently set for� If the current selection is correct, press ENTER once to advance to the DISPLAY FUNCTION parameter� To change the unit, press UP or RIGHT to scroll to the correct rate unit� Press ENTER to save and advance to the DISPLAY FUNCTION parameter�
Selection Rate Total
GPM/GAL Gallons per minute Gallons
LPM/LIT Liters per minute Liters M3PH/M3 Cubic meters per hour Cubic meters M3PD/M3 Cubic meters per day Cubic meters
BPD/BBL Oil barrels per day Oil barrels
Select the Display Function
The monitor displays RATE, TOTAL, alternates between BOTH rate and total or TEST� If the current selection is correct, press ENTER to advance to the next parameter� To change to an alternate display mode, press UP or RIGHT to scroll to the correct display mode and press ENTER to save and advance to the TOTALIZER PULSE OUTPUT parameter�
The TEST function acts like a frequency counter and displays the raw input frequency being supplied to the frequency input terminals� This is very useful when troubleshooting flow problems�
Page 7 March 2017 DSY-PM-00276-EN-04
Programming
Totalizer Pulse Output
The pulse output parameter can be enabled or disabled� When enabled this output generates 20 mS duration pulse for every time the least significant digit of the totalizer increments� The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 30V DC� Press UP or RIGHT to scroll to ON or OFF� Press ENTER to save and advance to the PASSWORD parameter�
Password
The PASSWORD setting restricts access to PROGRAM mode� Initially, the password is set to all zeros and any user can modify the parameter settings in PROGRAM mode� To change the password, enter any four digit code� Press UP to increment the digit, and RIGHT to advance to the next digit� Press ENTER to store the password and advance to RST PSWD� The new password is now required to enter PROGRAM mode� With this password set, any user is able to reset the stored totals on the monitor�
Reset Password
The RST PSWD restricts resetting the totals on the monitor� The PASSWORD must also be set to restrict the total reset� Initially, the password is set to all zeros and any user can reset the stored totals on the monitor� To change the password, enter any four digit code� Press UP to increment the digit, and RIGHT to advance to the next digit� After entering all digits, press ENTER to store the password and return to RUN mode� The reset password is now required to reset the totals on the monitor�
Run Mode
Reset Total
To reset the monitor total display, in RUN mode press MENU and ENTER simultaneously� If the RST PSWD has been set to something other than the default, you must enter the new password before the monitor will reset� The monitor flashes TOTAL RST and returns to RUN mode at the conclusion of the reset procedure�
Store Total
The current total can be manually stored in the monitor’s flash memory� Use this feature prior to replacing the battery� Press and hold ENTER for 2 seconds� The display responds with a flashing TOTALSVD and then returns to RUN mode�
Automatic Store Total
The monitor is equipped with a store total feature that works automatically, saving the current total to flash memory� The frequency of saves depends on the power supply option chosen�
Battery Powered: Once per hour and just before a low battery condition turns the unit off�
Loop Powered: Once every ten minutes�
Page 8 March 2017DSY-PM-00276-EN-04
Additional Scaling Parameters
ADDITIONAL SCALING PARAMETERS
OTE:N The programming instructions below are only available for loop powered
units� Battery powered units do not include these programming parameters�
Flow 4 mA Setting
Zero is the default flow rate at the 4 mA setting� If the current selection is correct, press ENTER to advance to the Flow 20 mA parameter� To change the setting, press UP to increment the flashing digit and press RIGHT to move to the next digit� Press ENTER to save and advance to the Flow 20 mA parameter�
Flow 20 mA Setting
The turbine meter’s maximum flow rate is the default value for the 20 mA setting� If the current selection is correct, press ENTER to advance to the 4…20 mA Calibration parameter� To change the setting, press UP to increment the flashing digit and press RIGHT to move to the next digit� Press ENTER to save and advance to the 4…20 mA Calibration parameter�
4…20 mA Calibration
The 4…20 mA Calibration parameter is the fine adjustment of the 4…20 mA output� The 4 mA setting is typically between 35…50� To set the 4 mA value, connect an ammeter in series with the loop power supply� At the 4MA OUT prompt, press UP to increment and RIGHT to decrement the 4 mA value to until a steady 4 mA reading is reached on the ammeter� Press ENTER to lock in this value and advance to 20MA OUT� The 20 mA adjustment is performed using the same procedure as the 4 mA adjustment�
Page 9 March 2017 DSY-PM-00276-EN-04
Additional Scaling Parameters
4…20 mA Test
The monitor contains a diagnostic routine that allows the simulation of mA values between 4…20 to check output tracking� At the 4-20TEST prompt press UP to increment the simulated mA output or RIGHT to decrement the value in increments of 1 mA� The ammeter should track the simulated mA output� If a 4…20 mA test in not necessary, press ENTER once to escape the testing at any time�
Pulse Out Freq. In4-20 mA
10…30V DC
1…5V DC
1 2 3 4 5 6
+
-
+ -+
-
JP2
Mag
Input
TB1
1 2 3 4 5
J2
Keypad
Connector
DC
Pulse Input
PULSE OUTPUT
IO/SETUP
DSP
Flow 4MA
Flow 20MA
4MA OUT
20MA OUT
4-20 TEST
PASSWORD
Figure 2: Typical ammeter connection Figure 3: 4…20 mA
programming menu
Page 10 March 2017DSY-PM-00276-EN-04
Additional Input Options
ADDITIONAL INPUT OPTIONS
The B2800 flow monitor is capable of receiving magnetic pickup input (small signal sine wave) or a contact closure input (pulse)� Since most Blancett turbine flow meters use a magnetic pickup, the B2800 flow monitor is shipped configured for magnetic pickup input� To change to a contact closure input, remove JP2 from the top two pins and jumper them to the bottom two pins� See Figure 5
+ Pulse In
Magnetic Pickup
10K
30V DC (Max)
20 mS Pulse
R
MAX
=
(Loop Supply Voltage - 5)
0.02
1 2 3 4 5 6
+ -+ -+
-
- Pulse In
10…30V DC
- Common
Pulse Input Card
Analog Input Card - 4-20 mA
Figure 4: Wiring diagram
Pulse Out Freq. In4-20 mA
Magnetic Pickup
10K
30V DC (Max)
10…30V DC
1…5V DC
20 mS Pulse
250 Typ R
MAX
=
(Loop Supply Voltage - 5)
0.02
1 2 3 4 5 6
+
-
+ -+
-
JP2
Mag
Input
Pulse
Inuput
TB1
1 2 3 4 5
J2
Keypad
Connector
Loop Powered
Pulse Out Freq. In4-20 mA
Magnetic Pickup
10K
30V DC (Max)
20 mS Pulse
1 2 3 4 5 6
+
-
+ -+
-
JP2
Mag
Input
Pulse
Inuput
TB1
1 2 3 4 5
J2
Keypad
Connector
N/C N/C
Battery Powered
Figure 5: Circuit board layouts
Page 11 March 2017 DSY-PM-00276-EN-04
Default K-factor Values
DEFAULT KFACTOR VALUES
Meter Size Default K-factor Lower Limit Upper Limit
3⁄8 in� (9�53 mm) 20,000 16,000 24,000
1/2 in� (12�7 mm) 13,000 10,400 15,600
3/4 in� (19�05 mm) 2750 2200 3300
7/8 in� (22�23 mm) 2686 2148 3223
1 in� (25�4 mm) 870�0 696�0 1044
1-1/2 in� (38�1 mm) 330�0 264�0 396�0
2 in� (50�8 mm) 52�0 41�6 62�0
3 in� (76�2 mm) 57�0 45�6 68�0
4 in� (101�6 mm) 29�0 23�2 35�0
6 in� (152�4 mm) 7�0 5�6 8�0
8 in� (203�2 mm) 3�0 2�4 4�0
10 in� (254 mm) 1�6 1�3 2�0
BATTERY REPLACEMENT
Battery powered monitors use a single 1�5V, D size alkaline battery� When replacement is necessary, use a clean fresh battery� Save the total to memory before the battery is removed�
Unscrew the two captive screws on the front panel to access the battery� Replace the battery, being sure to observe the proper polarity, and then refasten the front panel�
Page 12 March 2017DSY-PM-00276-EN-04
Installation Drawing
INSTALLATION DRAWING
Battery Powered
Page 13 March 2017 DSY-PM-00276-EN-04
Installation Drawing
Loop Powered
Page 14 March 2017DSY-PM-00276-EN-04
Troubleshooting Guide
TROUBLESHOOTING GUIDE
Issue Remedy
No LCD display
Check battery voltage� Should be 1�5V DC� Replace if low or bad�
No rate or total displayed
Check connection from meter pickup to display input terminals�
Check turbine meter rotor for debris� Rotor should spin freely�
Check programming of flow monitor�
Flow rate display interprets reading constantly
This is usually an indication of external noise� Keep all AC wires separate from DC wires�
Check for large motors close to the meter pickup�
Check for radio antenna in close proximity�
Try disconnecting the pickup from the monitor pig tail� This should stop the noise�
Flow rate indicator bounces
This usually indicates a weak signal� Replace pickup and/or check all connections�
Check K-factor�
PART NUMBERING INFORMATION
B 28 S X X - X X
Power Option
B - Battery L - Loop
Program Level
S -
Mounting Style
M - Meter Mount R - Remote Mount S - Swivel Mount H - Hand-Held
Units of Measure AB - Gallons ED - Barrels HB - Liters ID - Cubic Meters
Page 15 March 2017 DSY-PM-00276-EN-04
Specications
SPECIFICATIONS
Power Supply Options
Battery Powered One D size, 1�5V alkaline battery Loop Powered Optional 4…20 mA loop power
Alphanumeric Rate and Total Display
Eight digit, 0�75 inch high numeric display Eight character, 0�38 inch high alphanumeric display
Fixed or toggle modes of operation for flow rate and totalizer display
Accuracy ±0�1% Temperature Drift 50 ppm /° C (maximum) Mounting Classification
Meter Mount Type 4X enclosure Remote Mount Type 4X enclosure Swivel Mount Type 4X enclosure
Environmental
Operating Temperature –22…158° F (–30…70° C) Humidity 0…90% non-condensing
Inputs
Magnetic Pickup Input
Frequency Range: 0…3500 Hz
Trigger Sensitivity: 30 mV p-p
Over Voltage Protected: ±30V DC
Outputs
Type Opto-isolated open collector transistor
Maximum Voltage 30V DC Pulse Width 20 mS/maximum rate 20 Hz Current (ON state) 0�9V drop @ 5�0 mA or 0�7V drop @ 0�1 mA Optional 4…20 mA output
Certifications
CSA
Class I, Div 1 Groups C, D; Class II, Div 1 Groups E, F, G; CSA C22�2 No� 157-92, UL 913
CE IEC 61326-1
Page 16 March 2017DSY-PM-00276-EN-04
Replacement Parts
REPLACEMENT PARTS
Component Part Number
Keypad B260713 Battery B280601
Battery Tie Wrap B228036
Pickup Cable B222-121
Desiccant Bag B260630
PVC Union B220016
PVC Reducer Bushing B220056
Rubber Washer B228207
Steel Lock Washer B220018
PCB Shield (battery units) B280603
Desiccant Shield B280680
Cord Grip B220103
Page 17 March 2017 DSY-PM-00276-EN-04
Mounting Options and Dimensions
MOUNTING OPTIONS AND DIMENSIONS
Meter Mount
C
B
A
D
E
F
G
dia
A B C D E F G dia
9�25 in�
(235�0 mm)
7�00 in�
(177�8 mm)
5�75 in�
(146�0 mm)
4�00 in�
(101�6 mm)
3�45 in�
(87�6 mm)
1�50 in�
(38�1 mm)
0�875 in�
(22�2 mm)
Remote Mount
E
D
A
B
C
.25 in. dia
(6.4 mm)
(4 HOLES)
F
G
H
I
dia
A B C D E F G H I dia
7�00 in�
(177�8 mm)
2�40 in�
(61�0 mm)
2�25 in�
(57�2 mm)
7�00 in�
(177�8 mm)
5�75 in�
(146�0 mm)
4�38 in�
(111�2 mm)
3�45 in�
(87�6 mm)
1�50 in�
(38�1 mm)
0�875 in�
(22�2 mm)
Page 18 March 2017DSY-PM-00276-EN-04
Mounting Options and Dimensions
Swivel Mount
D
C
B
A
E
F
G
dia
A B C D E F G dia
12�25 in�
(311�2 mm)
7�00 in�
(177�8 mm)
5�75 in�
(146�0 mm)
4�00 in�
(101�6 mm)
3�45 in�
(87�6 mm)
1�50 in�
(38�1 mm)
0�875 in�
(22�2 mm)
Page 19 March 2017 DSY-PM-00276-EN-04
Flow Monitor, B2800 Standard
www.badgermeter.com
Blancett is a registered trademark of Badger Meter� All other trademarks appearing in this document are the property of their respective entities� Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists� © 2017 Badger Meter, Inc� All rights reserved�
Control. Manage. Optimize.
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Eastern Europe Branch Oce (for Poland, Latvia, Lithuania, Estonia, Ukraine, Belarus) | Badger Meter Europe | ul. Korfantego 6 | 44-193 Knurów | Poland | +48-32-236-8787 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 02-DSY-PM-00111
Loading...