Badger Meter B132-050, B131-038, B131-075, B131-050, B131-100 Standard User Manual

...
Turbine Flow Meter
QuikSert® Standard
TRB-UM-00372-EN-06 (October 2018)
User Manual
Turbine Flow Meter, QuikSert® Standard
CONTENTS
Scope of This Manual � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �3
Unpacking and Inspection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �3
Safety � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �3
Terminology and Symbols � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Introduction � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �4
Operating Principle � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �4
Installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �5
Operational Startup � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �7
Calibration � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �7
Troubleshooting Guide � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �8
Part Number Information � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �9
Flow Range Chart � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
Strainer Recommendations � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
Repair Kit Information� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
Pressure Rating � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 11
Page ii October 2018TRB-UM-00372-EN-06

Scope of This Manual

SCOPE OF THIS MANUAL
This manual is intended to help you install and operate the QuikSert turbine flow meter�
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.

UNPACKING AND INSPECTION

Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment�
OTE:N If damage is found, request an inspection by the carrier’s agent within 48 hours of
delivery and file a claim with the carrier� A claim for equipment damage in transit is the sole responsibility of the purchaser�

SAFETY

Terminology and Symbols

Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing death or serious personal injury� Indicates a hazardous situation, which, if not avoided, could result in severe personal injury or death� Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing minor or moderate personal injury or damage to property�
MPORTANTI
Not following instructions properly may impair safety of equipment and/or personnel.
Page 3 October 2018 TRB-UM-00372-EN-06

Introduction

INTRODUCTION
The QuikSert Standard turbine flow meter was developed for liquid applications where accuracy and dependability are of concern to the operator� The stainless steel body incorporates a helical turbine with tungsten carbide shaft and bearings� It provides an efficient, long service life and a cost-effective solution for your measurement requirements�
Simple in design and construction, QuikSert uses modified upstream and downstream flow straighteners for a high degree of flow accuracy� Its between­the-flange design eliminates the need for mating flanges, requiring less space in the flow line, lowering costs and providing easy, one-person installation�
The meter produces a sine wave signal proportional to its volumetric flow rate� With optional Blancett electronics, QuikSert provides local flow rate and volume totalization and can interface with most instruments, PLCs and computers�

OPERATING PRINCIPLE

Fluid entering the meter passes through the inlet flow straightener which reduces its turbulent flow pattern and improves the fluid’s velocity profile� Fluid then passes through the turbine, causing it to rotate at a speed proportional to the fluid velocity� As each turbine blade passes through the magnetic field, the blade generates an AC voltage pulse in the pickup coil at the base of the magnetic pickup (see Figure 1)� These pulses produce an output frequency proportional to the volumetric flow through the meter� The output frequency represents flow rate and/or totalization of fluid passing through the turbine flow meter�
Figure 1: Electric signal generated by rotor movement
Page 4 October 2018TRB-UM-00372-EN-06

Installation

INSTALLATION
1� Check the ow meter internally for foreign material and make sure the turbine rotor
spins freely prior to installation�
2� Check uid lines and clear any debris�
3� Install the ow meter with the ow arrow, etched on the exterior of the meter body,
pointing in the direction of uid ow�
4� Install the meter horizontally with the pickup facing upward, where possible� The liquid
being measured should be free of any large particles that may obstruct rotation of the rotor�
5� Install a mesh strainer upstream before operation of the ow meter if particles are
present� See“Repair Kit Information” on page 10
6� Install a bypass line (Figure 2) for meter inspection and repair without interrupting ow�
Install all control valves downstream of the ow meter, if a bypass line cannot be used (Figure 3 on page 6)�
PRESSURE IN EXCESS OF ALLOWABLE RATING MAY CAUSE THE HOUSING TO BURST AND CAUSE SERIOUS PERSONAL INJURY.
DAMAGE CAN BE CAUSED BY STRIKING AN EMPTY METER WITH A HIGH VELOCITY FLOW STREAM.
Display
21
Isolation
Valve
5 Pipe Diameters
Minimum
Bypass Line
Isolation
Valve
Flow Straightner
(Optional)
QuikSert Turbine
Flow Meter
10 Pipe Diameters
Minimum
Figure 2: Meter installation using a bypass line
Page 5 October 2018 TRB-UM-00372-EN-06
Installation
Flow Straightner
(Optional)
Figure 3: Meter installation without using a bypass line
QuikSert Turbine
Flow Meter
10 Pipe Diameters
Minimum
Display
21
Isolation
Valve
5 Pipe Diameters
Minimum
7� Install all restrictions in the ow line that may cause the liquid to ash, downstream of
the meter� If necessary, install air eliminators so the meter is not incorrectly measuring entrained air or gas�
8� Install a minimum length of ten pipe diameters of straight pipe on the upstream side
of the meter and ve diameters on the downstream side of the ow meter or meter accuracy may be aected� Piping should be the same size as the meter bore or threaded port size�
Do not install the flow meter or connection cable close to electric motors, transformers, sparking devices, high voltage lines, or place connecting cable in conduit with wires furnishing power for such devices� These devices can induce false signals in the flow meter coil or cable, causing the meter to read inaccurately�
Consult the "Troubleshooting Guide" on page 8 � If the internal components of the turbine flow meter are damaged beyond repair, order a turbine meter repair kit� Information pertaining to the turbine meter repair kits is referenced in "Repair Kit
Information" on page 10
Page 6 October 2018TRB-UM-00372-EN-06

Operational Startup

OPERATIONAL STARTUP
Follow these steps when installing and starting the meter�
MAKE SURE THAT FLUID FLOW HAS BEEN SHUT OFF AND PRESSURE IN THE LINE RELEASED BEFORE ATTEMPTING TO INSTALL THE METER IN AN EXISTING SYSTEM.
1� Close the isolation valves and open the bypass valve after installing the meter�
2� Flow liquid through the bypass valve for sucient time to eliminate any air or gas in the
ow line�
HIGH VELOCITY AIR OR GAS MAY DAMAGE THE INTERNAL COMPONENTS OF THE METER.
3� Open the upstream isolating valve slowly to eliminate hydraulic shock while charging
the meter with the liquid�
4� Open the valve to full open�
5� Open the downstream isolating valve to permit meter to operate�
6� Close the bypass valve to a full closed position�
7� Adjust the downstream valve to provide the required ow rate through the meter�
OTE:N The downstream valve may be used as a control valve�

CALIBRATION

The meter and all attached electronics are calibrated on water at the factory and tagged with a K-factor (pulses per US Gallon)� For maximum accuracy, calibrate the meter with the actual fluid being measured� The QuikSert meter can be recalibrated by any conventional meter-proving processes used to calibrate standard meters�
Page 7 October 2018 TRB-UM-00372-EN-06

Troubleshooting Guide

TROUBLESHOOTING GUIDE
Trouble Possible Cause Remedy
Meter indicates higher than actual flow rate
Meter indicates lower than actual flow rate
Erratic system indication, meter alone works well (remote monitor application only)
Indicator shows flow when shut off Mechanical vibration
No flow indication
Full or partial open position
Erratic indication at low flow, good indication at high flow
No flow indication Faulty pickup Replace pickup System works perfect, except
indicates lower flow over entire range Meter indicating high flow, upstream
piping at meter smaller than meter bore
Opposite effects of above Viscosity lower
Cavitation
Debris on rotor support
Build up of foreign material on meter bore
Gas in liquid
Debris on rotor
Worn bearing
Viscosity higher than calibrated
Ground loop in shielding Ground shield in one place
causes rotor to oscillate without turning
Fluid shock, full flow into dry meter or impact caused bearing separation or broken rotor shaft
Rotor has foreign material wrapped around it
Bypass flow, leak Repair or replace bypass valves,
Fluid jet impingement on rotor
than calibrated
Increase back pressure
Clean meter
Clean meter
Install gas eliminator ahead of meter
Clean meter and add filter
Clean meter and add filter
Recalibrate monitor
only, look for internal electronic instrument ground� Reroute cables away from electrical noise
Isolate meter
Rebuild meter with repair kit and recalibrate monitor� Move to location where meter is full on startup or add downstream flow control valve
Clean meter and add filter
or faulty solenoid valves Change piping
Change temperature, change fluid or recalibrate meter
Page 8 October 2018TRB-UM-00372-EN-06

Part Number Information

PART NUMBER INFORMATION
Part
Number*
B131-038 3/8 × 1 B131-050 1/2 × 1 60 13,000 6�5 B131-075 3/4 × 1 60 3300 18 B131-088 7/8 × 1 60 3100 20 B131-100 1 × 1 60 870 20 B132-050 1/2 × 2 60 13,000 12 B132-075 3/4 × 2 60 3300 18 B132-088 7/8 × 2 60 3100 20 B132-100 1 × 2 40 870 20 B132-150 1-1/2 × 2 20 330 16 B132-200 2 × 2 20 52 9 B132-250 2 × 3 10 52 10 B133-300 3 × 3 10 57 10 B134-400 4 × 4 10 29 10 B136-600 6 × 6 4 7 10 B138-800 8 × 8 4 3 10 B139-900 10 × 10 4 1�6 10
Meter Bore
Size × Line
Size (in.)
End
Connection
Flow
Range
See “Flow
Range
Chart”
Strainer
Approx. K-Factor
Mesh
pulses/US gal
60 18,000 3�75
Weight

Flow Range Chart

Max. Pres-
sure Drop
(psi)
Part Number
B131-038 0�60…3�00 (2�27…11�36) 20…100 3�3…16 B131-050 0�75…7�50 (2�84…28�39) 25…250 4�1…41 B131-075 2�00…15�00 (7�57…56�78) 68…515 10�9…81�75 B131-088 3�00…30�00 (11�36…113�56) 100…1000 16…160 B131-100 5�00…50�00 (18�93…189�27) 170…1700 27�25…272�5 B132-050 0�75…7�50 (2�84…28�39) 25…250 4�1…41 B132-075 2�00…15�00 (7�57…56�78) 68…515 10�9…81�75 B132-088 3�00…30�00 (11�36…113�56) 100…1000 16…160 B132-100 5�00…50�00 (18�93…189�27) 170…1700 27�25…272�5 B132-150 15�00…180�00 (56�78…681�37) 515…6000 82…981 B132-200 40�00…400�00 (151�42…1514�16) 1300…13,000 218…2180 B132-250 40�00…400�00 (151�42…1514�16) 1300…13,000 218…2180 B133-300 60�00…600�00 (227�12…2271�25) 2100…21,000 327…3270 B134-400 100�00…1200�00 (378�54…4542�49) 3400…41,000 545…6540 B136-600 200�00…2500�00 (757�08…9463�53) 6800…86,000 1,090…13,626 B138-800 350�00…3500�00 (1324�89…13248�94) 12,000…120,000 1,363…19,076 B139-900 500�00…5000�00 (1892�71…18927�06) 17,000…171,000 2,725…27,252
gpm (lpm) bpd m3/d
Flow Ranges
Page 9 October 2018 TRB-UM-00372-EN-06
Part Number Information

Strainer Recommendations

Part Number Strainer Mesh Clearance (in.) Filter Size
B131-038 60 0�0092 260 Micron B131-050 60 0�0092 260 Micron B131-075 60 0�0092 260 Micron B131-088 60 0�0092 260 Micron B131-100 60 0�0092 260 Micron B132-050 60 0�0092 260 Micron B132-075 60 0�0092 260 Micron B132-088 60 0�0092 260 Micron B132-100 40 0�0150 400 Micron B132-150 20 0�0340 0�86 B132-200 20 0�0650 0�86 B132-250 10 0�0900 1�6 B133-300 10 0�0900 1�6 B134-400 10 0�0650 1�6
B136-600 4 0�1875 4�8
B138-800 4 0�0900 4�8
B139-900 4 0�0900 4�8

Repair Kit Information

Repair Kit Fits Meter Part
Number
B131-038 B253-102
B131-050 B253-105
B131-075 B253-108
B131-088 B253-109
B131-100 B253-112
B132-050 B253-205
B132-075 B253-208
B132-088 B253-209
B132-100 B253-212
B132-150 B253-216
B132-200 B253-220
B132-250 B253-220
B133-300 B253-330
B134-400 B253-440
B136-600 B253-660
B138-800 B253-880
B139-900 B253-990
All Meter Sizes B111109 Standard Magnetic Pickup
Repair Kit Part
Number
Max. Pressure Drop
3�75 psi 2 × 4 (50�4 × 101�6)
6�5 psi 2 × 4 (50�4 × 101�6) 18 psi 2 × 4 (50�4 × 101�6) 20 psi 2 × 4 (50�4 × 101�6) 20 psi 2 × 4 (50�4 × 101�6) 12 psi 3�62 × 2�5 (91�9 × 63�5) 18 psi 3�62 × 2�5 (91�9 × 63�5) 20 psi 3�62 × 2�5 (91�9 × 63�5) 20 psi 3�62 × 2�5 (91�9 × 63�5) 16 psi 3�62 × 2�5 (91�9 × 63�5)
9 psi 3�62 × 2�5 (91�9 × 63�5) 10 psi 3�62 in × 4�25 (91�9 × 108) 10 psi 5 × 4�25 (127 × 108) 10 psi 6�18 × 5 (157 × 127) 10 psi 8�5 × 5�75 (215�9 × 146�1) 10 psi 10�62 × 6�25 (269�7 × 158�8) 10 psi 12�75 × 6�75 (323�8 × 171�4)
Dimensions
Diameter × Length
in. (mm)
Page 10 October 2018TRB-UM-00372-EN-06
Specications

SPECIFICATIONS

Body 316 stainless steel
Materials of Construction
Operating Temperature

Pressure Rating

End Connections Wafer-Style ASME/ANSI B16�5-1996 Turndown Ratio Accuracy ± 1�0% of reading Repeatability ± 0�1% Calibration Water; NIST Traceable Calibration, Certificate available, consult factory for details
Pickup B111109, B220111, B220210, B220243, B111126
Certifications
Pulsation and Vibration
Rotor CD4MCU stainless steel Bearings Tungsten carbide Rotor Shaft Tungsten carbide Rotor Support
–150…350° F (–101…177° C) standard Temperatures to 450° F (232° C) with high-temp pickup, consult factory for details The standard meter should not be subjected to temperatures above 350° F (177° C), or below –150° F (–101° C) or the freezing point of the metered liquid�
See “Troubleshooting Guide” on page 8
Severe pulsation and mechanical vibration will affect accuracy and shorten the life of the meter
Pressure Rating
The pressure rating of the meter is dependent upon the class of ANSI flanges between which the meter is to be mounted� The pressure rating chart below is based on Carbon Steel at 100° F (37�8° C)�
Flange Class (ANSI) 150# 300# 600# 900# 1500# Working Pressure (psi) 285 740 1480 2220 3705 Working Pressure (MPa) 1�97 5�10 10�20 15�31 25�55 * Test Pressure (psi)
* Test Pressure (MPa)
* Test pressure based on 1�5 safety factor
427�5
2�95
1110 2220 3330
7�65 15�31 22�98
5557�5
38�32
Page 11 October 2018 TRB-UM-00372-EN-06
Turbine Flow Meter, QuikSert® Standard
Figure 4: Typical cross-section of models B131-038…B131-100
Figure 5: Typical cross-section of models B132-050…B139-900
Control. Manage. Optimize.
BLANCETT and QuikSert are registered trademarks of Badger Meter, In� Other trademarks appearing in this document are the property of their respective entities� Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists� © 2018 Badger Meter, Inc� All rights reserved�
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq� Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Eastern Europe Branch Oce (for Poland, Latvia, Lithuania, Estonia, Ukraine, Belarus) | Badger Meter Europe | ul� Korfantego 6 | 44-193 Knurów | Poland | +48-32-236-8787 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 02-TUR-UM-00455