Badger Meter AS - Steam User Manual

Ellipse® Pitot Tube Meter
AS Annular Threaded Steam Meter
PTT-UM-00515-EN-02 (April 2014)
User Manual
Ellipse® Pitot Tube Meter, AS Annular Threaded Steam Meter
CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pipe Orientation and Sensor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation Instructions, Single Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Instructions, Double Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Installation with Dierential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Location Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Flow Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Page ii April 2014
The Preso patented elliptical design outperforms and provides greater accuracy than traditional differential pressure flow measurement devices. This differential pressure flow meter is designed with a series of ports facing the upstream velocity pressures, as well as flow sensing ports strategically located ahead of the trailing edge flow separation.
The multi-ported, self-averaging flow element consists of an elliptical shape with two independent flow sensing chambers. The impact velocity sensing holes (high pressure) are located along the leading edge and the true static sensing holes (low pressure) are on the exterior probe side. Model AS comes with instrument shutoff valves with provisions to accept a transmitter or direct indicating meter.
User Manual
True static sensing holes
Impact velocity sensing holes
Figure 1: AS pressure sensing holes

SPECIFICATIONS

Applications Steam
Pipe Sizes
Pressure
Temperature
Accuracy
Turndown Ratio
Standard Components
Reynolds Number
Resonance
2…48 inches (50…1220 mm)
600 psi (4100 kPa) maximum
480° F (250° C) maximum
±0.75% of reading
17:1 with no vacuum effect
T-type head, 316 SS 1/2" FNPT connection CS compression fitting with SS ferrule CS 3000 lb weld fitting, ASTM A105 316/316L SS Ellipse sensor 316 SS ID tag with wire
Greater than 75,000 maintains most accurate flow measurements Less than 75,000 consult factory for estimated results
If greater than 0.8, use double support.
Table 1: Specifications
Page 3 April 2014
W
Ellipse® Pitot Tube Meter, AS Annular Threaded Steam Meter

PIPE ORIENTATION AND SENSOR MOUNTING

FLOW
Field Weld
Preferred installation
Figure 2: Horizontal pipe installation
F L
OR
O
OTE:N For general steam applications, instrument valves should be mounted at the same elevation to maintain equal
condensation levels.
F L
O
W
Field Weld
OTE:N Preferred flow direction for steam is upward.
Illustration represents installation for upward flow.
Figure 3: Vertical pipe installation
Allowable plane of installation
O
F L
OR
W
O
F L
W
Page 4 April 2014
User Manual

INSTALLATION INSTRUCTIONS, SINGLE SUPPORT

1. Choose the proper location to install the AS Ellipse using AGA/ASME standards (or equivalent). See "Location Instructions"
on page 7.
2. Grind the surface of the pipe where the AS Ellipse is to be inserted to provide a clean area for welding.
3. Weld the supplied weld-o-let to the pipe using standard codes for your application (1/16" weld gap recommended). Take care to protect the threads during the welding process.
4. Drill a hole through the pipe wall according to Table 2.
5. Deburr the hole just drilled, especially on the inside of the pipe.
Model / Sensor Weld Connector Drill Bit
AS (7/8") 1" 1-1/8"
AS1 (1-1/4") 1-1/4" 1-3/8"
Table 2: Single support drill bit size
6. Assemble the supplied compression tting as diagrammed in Figure 3. Thread the assembled compression tting into the weld-o-let manually. With a wrench, tighten the body of the tting another 1-1/4 turns, taking care not to tighten the compression nut.
7. Install the instrument valves (optional) at the AS Ellipse head connections. Make sure the valves are FULLY CLOSED to prevent them from leaking during startup. Install the two forged crosses to the valves.
8. Insert the AS Ellipse through the compression tting. Carefully push the sensor by hand further into the pipe until it reaches the opposite wall.
9. While holding the AS Ellipse in its fully inserted position, align the arrow on the sensor head with the direction of ow. See
Figure 4.
Compression
Fitting Nut
Insert
Body
Figure 4: Compression fitting Figure 5: Sensor alignment
Tighten Nut, as Shown, onto Body of the Compression Fitting
Install Insert as Shown
Install Threaded Portion into Weld Fitting on Pipe
FLOW
Field Weld
10. To prevent leakage, manually tighten the compression nut, the use a wrench to tighten it another 1-1/4 turns.
11. Connect the 1/2" tubing to the connections on the forged cross components. Connect these lines to a three-valve manifold transmitter.
12. Verify that the instrument valves are FULLY CLOSED. Remove the 1/2" plugs from the top and side ports of the two forged cross tees.
13. Slowly pour water into the top ports of each forged cross tee until the system is full. Water will flow out of the side ports of both crosses.
14. Reinstall the 1/2" plugs into the top and side ports. Ensure that they are secure. Then fully open the two gate valves.
15. Allow condensation levels to stabilize for 30 minutes before taking instrument reading.
Page 5 April 2014
Ellipse® Pitot Tube Meter, AS Annular Threaded Steam Meter

INSTALLATION INSTRUCTIONS, DOUBLE SUPPORT

1. Follow steps 1 through 7 in “Installation Instructions, Single Support” on page 5. At 180° from and on the same plane as the previously drilled hole, grind the surface of the pipe to provide a clean area for welding. Drill a hole and deburr, especially on the inside of the pipe. Size the hole used for the double support according to Table 3.
2. Weld the double support weld-o-let, making sure that it is centered with the drilled hole (1/16" weld gap recommended).
Model / Sensor Weld Connector Drill Bit
AS (7/8") 1/2" 1/2"
AS1 (1-1/4") 1" 7/8"
Table 3: Double support drill bit size
3. Install the AS Ellipse sensor through the two holes. Make sure that the double support pin passes through the guide ring. See Figure 5.
Ellipse Sensor
Double Support Pin
Guide Ring
Figure 6: Double support pin
4. While holding the AS Ellipse in its fully inserted position, align the sensor head with the direction of ow as in step 9,
“Installation Instructions, Single Support” on page 5.
5. Check that the AS Ellipse is in the correct orientation and spans the inside of the pipe. Tighten the compression nut manually, then use a wrench to tighten it another 1-1/4 turns.
6. Install the plug into the end of the double support weld-o-let. Tighten the plug to prevent leakage. Ensure that there is no leakage in the system.
7. Follow steps 11 through 15 in “Installation Instructions, Single Support” on page 5.

TYPICAL INSTALLATION WITH DIFFERENTIAL PRESSURE TRANSMITTER

Vertical Pipes
Pipe
Fill here with water
1/2" Tubing
3- or 5-Valve Manifold
DP Transmitter
Ellipse Sensor
Cross Tees
Horizontal Pipes
Figure 7: Installation with differential pressure transmitter
Page 6 April 2014
User Manual

LOCATION INSTRUCTIONS

Straight pipe requirements: Accuracy is affected by the piping configurations due to the disturbances of the flow profile. A fully developed symmetrical flow profile is achieved with the minimum upstream and downstream recommended lengths.
TYPICAL INSTALLATION ORIENTATION
DISTANCES ARE EXPRESSED IN
NUMBER OF NOMINAL PIPE DIAMETERS
THROTTLED VALVE OR REGULATOR TWO ELBOWS IN DIFFERENT PLANES
CHANGE IN PIPE SIZE TWO ELBOWS IN THE SAME PLANE
DIRECT MOUNT TO A SINGLE ELBOW* A SINGLE ELBOW
Figure 8: Location instructions
Page 7 April 2014

FLOW CURVE

ANNULAR ELLIPS
1
.9
.6
.5
.4
.3
12" 16" 20"
2 3 4 5 6 7 8 9 1
0
0
0
0
WATER 60° F
2 3 4 5 6 7 8 9 1
0
0
0
0
0
E
2" 2.5" 3.5"3" 4" 5" 6" 8" 10" 14" 18" 24" 30"
100
90
80
70
60
50
40
30
20
O
2
10
9
8
7
6
5
4
3
2
Figure 9: Flow curve
2 3 4 5 6 7 8 9 1
0
0
0
USGPM
2 3 4 5 6 7 8 9 1
0
0
0
P – INCHES OF H
.8
.7
.2
2 3 4 5 6 7 8 9 1
NOTE:
2" THRU 10" CURVES ARE FOR SCH. 40 PIPE
12" AND ABOVE ARE FOR SCH. STD. PIPE
1
Control. Manage. Optimize.
PRESO is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2014 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Legacy Document Number: 10-PTT-UM-00306
Loading...