Badger Meter 380DS User Manual

3/4" - 2" Badger Meter 380 Btu Meter Pressure Loss
Flow Rate
(GPM)
Flow Vel. Sch.
40 Pipe (Ft/Sec)
Pressure
Loss (PSI)
Flow Rate
(GPM)
Flow Vel. Sch.
40 Pipe (Ft/Sec)
Pressure
Loss (PSI)
Flow Rate
(GPM)
Flow Vel. Sch.
40 Pipe (Ft/Sec)
Pressure
Loss (PSI)
Flow Rate
(GPM)
Flow Vel. Sch.
40 Pipe (Ft/Sec)
Pressure
Loss (PSI)
Flow Rate
(GPM)
Flow Vel. Sch.
40 Pipe (Ft/Sec)
Pressure
Loss (PSI)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
5.1
3.0
0.2 13.1
4.8
0.4 20.1
4.3
0.3 30.1
4.7
0.3 50.1
4.8
0.2
9.9
6.0
1.0 19.9
7.4
1.2 30.1
6.5
0.7 48.4
7.6
1.1 79.7
7.6
0.7
15.8
9.5
2.6 27.0
10.0
2.3 43.2
9.3
1.8 65.1
10.3
1.9 102.4
9.8
1.3
20.0
12.1
4.2 29.8
11.1
2.9 54.6
11.7
3.0 78.9
12.4
2.9 127.0
12.1
2.0
25.0
15.0
6.5 39.7
14.8
5.2 70.7
15.2
4.9 94.0
14.8
4.1 154.8
14.8
3.0
3/4"
1"
1-1/4"
1-1/2"
2"
y = 0.0298x2 - 0.0135x
y = 0.0265x2- 0.0365x
y = 0.0228x2- 0.019x
y = 0.0203x2- 0.0218x
y = 0.0157x2- 0.0308x
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Pressure Loss (PSI)
Flow Rate Ft/sec
380 Btu - Pressure Loss vs. Flow Velocity
3/4" 1" 1-1/4" 1-1/2" 2" Poly. (3/4") Poly. (1") Poly. (1-1/4") Log. (1-1/2") Poly. (1-1/2") Poly. (2")
Loading...