Badger Meter 380DS Operating Manual

Series 380 BTU System
380DS Meter
IND-UM-02074-EN-01 (July 2016)
User Manual
Series 380 BTU System , 380DS Meter

Introduction

CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ordering System Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mechanical Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INTRODUCTION
The Series 380 BTU System from Badger Meter® provides a low cost solution for metering cold or hot systems. The 380DS can accurately measure flow and temperature differential to compute energy. Using BACnet™ or Modbus® RS-485 communications protocols or a scaled pulse output, the BTU System can interface with many existing control systems.
The rugged design incorporates an impeller flow sensor and two temperature probes. One temperature probe is conveniently mounted directly in the flow sensor tee. The second temperature probe is placed on either the supply or the return line depending on installation requirements. These minimal connections help simplify installation and save time.
The main advantage of the Series 380 BTU System is the cost savings over other systems offered on the market today. The integration of flow and temperature sensors, along with metering components provide a single solution for metering. With this system, it will be possible to meter energy where metering had not cost effective.

Ordering System Matrix

Commissioning of this meter can be completed in the field via a computer connection. Setup includes energy measurement units, measurement method, communications protocol, pulse output option, fluid density and specific heat parameters.

Series 380

The 380 combines an electronics package with a PEEK sensor probe inserted in a 3/4", 1", 1-1/4", 1-1/2" and 2" proprietary cast bronze pipe tee with threaded NPT connections.
Series 380 Btu System Ordering Matrix
380 DS Meter
TYPE
DS - Dual Service 2
SIZE
0.75" 07 1" 10
1.25" 12
1.5" 15 2" 20
ELECTRONIC HOUSING
Polycarbonate 0
OUTPUT
Scaled Pulse and RS-485 (Modbus and BACnet) 0
DISPLAY
N/A 0
O-RING
EPDM 1
SHAFT
Tungsten Carbide (STANDARD) 2
IMPELLER
Stainless Steel 0
BEARING
Ketron® 2
Example: 380 2 07 0 0 0 - 1 2 0 2
Figure 1: Ordering system matrix
Page 3 July 2016 IND-UM-02074-EN-01Page ii July 2016IND-UM-02074-EN-01

Mechanical Installation

Commissioning

MECHANICAL INSTALLATION

General

The accuracy of flow measurement for all flow measuring devices is highly dependent on proper location of the sensor in the piping system. Irregular flow velocity profiles caused by valves, fittings, pipe bends, etc. can lead to inaccurate overall flow rate indications, even though local flow velocity measurement may be accurate. A sensor located in the pipe can be affected by air bubbles, floating debris, or sediment may not achieve full accuracy and could be damaged. Badger Meter flow sensors are designed to operate reliably under adverse conditions, but the following recommendations should be followed to ensure maximum system accuracy.
1. Choose a location along the pipe where 10 pipe diameters upstream and 5 pipe diameters downstream of the sensor provide no ow disturbances. Pipe bends, valves, other ttings, pipe enlargements and reductions should not be present in this length of pipe.
2. The recommended location for the sensor around the circumference of a horizontal pipe is on top of the pipe. The sensor should never be located at the bottom of the pipe, as sediment may collect there. Locations away from the top-center on a pipe cause the impeller friction to increase, which may aect performance at low ow rates. Any circumferential location is correct for installation in vertical pipes. Rising ow is preferred to reduce eects of any trapped air.

Installing the Sensor Tee

1. Position the tee for unrestricted pipe ow for at least 10 pipe diameters upstream and 5 pipe diameters downstream of the tee.
2. Apply pipe compound over the rst 3 or 4 threads of the mating pipe.
3. Thread the pipe into the sensor tee until hand tight.
4. Tighten the pipe an additional 1-1/2 turns, using a wrench.

ELECTRICAL INSTALLATION

1. The Series 380 requires an isolated 12…24 V AC/DC power supply. To avoid ground fault conditions, the 380 power should not be shared with other devices. This is especially true when the RS-485 network connections are being utilized, where damage to the product or system could result. The power connections are labeled 1 and 2 and are not polarity sensitive.
2. The RS-485 requires three connections: RS-485+, RS-485­and REF. The connections are labeled 1 (+), 2 (-) and 3 (GND). RS­485 is a high-speed connection and should be wired to meet TIA-EIA-485-A standards. This is especially true if a long cable run is involved or multiple devices are to be networked.
3. The pulse output is a simple solid state switch. The connections are labeled "PULSE OUTPUT 1" and "PULSE OUTPUT 2". The switch is not polarity sensitive, however, be careful that the maximum voltage and current ratings are not exceeded. See "Specifications" on
page 7 for details.
OTE:N The pulse and RS-485 may be used simultaneously.
COMMISSIONING
All setup and commissioning of the Series 380 is done using a USB to Mini USB cable and the Badger Meter Series 380 commissioning software.
Figure 2 shows the main setup screen. Flow and Energy rates and totals can be selected or a custom unit can be put in with the correct conversion factor.
For the temperature sensors the user can select the units along with the calculation mode, i.e., T1>T2, Absolute, or T1<T2. The Diff Zero parameter is the difference between T1 and T2 that will still read 0 energy rate.
If the Scaled Pulse Output is going to be used, the user can select what the pulse is representing (Energy or Flow), along with Units/Pulse and the pulse width. If the Scaled Pulse Output is not going to be used, this output can be set to OFF.
Figure 3 shows the communication parameters tab. The user can select BACnet or Modbus along with the network address. If using BACnet, the Device Name, Device ID BACnet BitRate and the Max Master number should be entered for the appropriate network for which the 380 is being connected.
Figure 2: Main setup screen
RS-485 Network Congurations
The RS-485 Section can be configured in two ways:
• Modbus
• BACnet The following sections explain each in detail.
RS-485 Network Configurations—Modbus
Figure 4: Comm parameters—modbus
Select Modbus, to access the Modbus pull-down menus.
Select the Address, Bit Rate (Baud Rate) and Mode (RTU or ASCII).
The Series 380 uses IEEE 754 Float Data Located in “Read Holding Registers.”
The Series 380 Data Format is “Float 32” where the Data is stored across two “Read Holding Registers”.
In the case of sensor mounted in the 380 body, the upper byte is stored in register 40001 and the lower byte is stored in the register 40002.
For example, a temperature of 53.36° F when converted to IEEE 754 is “425570A4.” In the case of the Series 380, Register # 40001 = 70A4 Hex and Register # 40002 = 4255 Hex. See
Table 1 on page 6 for additional information.
Page 4 July 2016 Page 5 July 2016 IND-UM-02074-EN-01IND-UM-02074-EN-01
Figure 3: Communication parameters
Commissioning
Specications
Modbus Register Map
Series 380 Register Map
Register
Name
Sensor
Temperature
Remote
Sensor Flow Rate 40005 + 40006 IEEE 754 Float Read Only Flow Total 40009 + 40010 IEEE 754 Float Read Only
Energy Rate 40007 + 40008 IEEE 754 Float Read Only Energy Total 40011 + 40012 IEEE 754 Float Read Only Energy Calc
Mode
Flow Filter 40015 + 40016 IEEE 754 Float Read Only
Temp Coef 40017 + 40018 IEEE 754 Float Read Only Specific Heat 40019 + 40020 IEEE 754 Float Read Only Fluid Density 40021 + 40022 IEEE 754 Float Read Only
Address Data Type Read/Write
40001 + 40002 IEEE 754 Float Read Only
40003 + 40004 IEEE 754 Float Read Only
40013 + 40014 IEEE 754 Float Read Only
Table 1: 380 register map
RS-485 Network Configuration—BACnet
Figure 5: Comm parameters—BACnet
Select BACnet to access the BACnet pull-down menus.
Select the Bit Rate (BAUD rate) to match other devices on the network.
BACnet Device Name can be set to help identify this device and location.
BACnet Device ID (Incidence #) is a unique number that identifies this device on the network. Typically, the first part of the number is the same as the network #, and the last two characters are the same as the address.
OTE:N The numbering sequence is not a requirement, but
can help in system planning.
BACnet Protocol Implementation Conformance Statement
BACnet Standardized Device Profile
BACnet Smart Actuator (B-SA)
Supported BIBBs
Supported BIBBs BIBB Name Tested
DS-RP-B ReadProperty - B
DS-WP-B WriteProperty - B
DM-DDB-B
Standard Object Types Supported
Analog Input No No
Analog Value No No
Device No No
Data Link Layer Options
MS/TP Slave
Segmentation Capability
Able to transmit segmented messages No N/A
Device Address Binding
Static Binding Supported Tested
No N/A
Character Sets
Character Sets supported Tested
ANSI X3.4
Dynamic Device Binding - B (Who-Is, I-Am)
Object Type Creatable Deletable Tested
Data Link Options Tested
Segmentation Type Supported
Device Profile Tested
baud rates: 9600, 19200, 38400, 76800 bps
Window Size
(MS/TP product limited to 1)
Figure 6: BACnet Device Profile
� � �
� � �
Tested

SPECIFICATIONS

Electrical Input
Electrical Output Scaled Pulse Open drain, 0.01…100 Hz max.
Materials
Sensor Body Sizes
Environmental
Accuracy
Flow Range
Power 12…35V DC, 12…28V AC Communication Modbus RTU, BACnet MSTP
Housing Polycarbonate Flow Sensor PEEK Potting Material Polyurethane Tee Material Brass
Tee Sizes
Fluid Temperature 20…260° F (–6.7…126.7° C)
Ambient Temperature
± 2% of flow rate within flow range ± 0.5% repeatability RTD meets IEC751 Class B 1…15 ft/sec
Diameter
0.75 in. (19 mm)
1 in. (25 mm)
1.25 in. (32 mm)
1.5 in. (38 mm)
2 in. (50 mm)
This chart is based on ASME/ANSI B336.10 Welded and Seamless Wrought Steel Pipe and ASME/ANSI B3619 Stainless Steel Pipe.
3/4 in., 1 in., 1-1/4 in., 1-1/2 and 2 in.
–4…149° F (–20…65° C)
380 BTU Meter Flow Range
1.65…24.69 gpm (6…93 lpm)
2.70…40.48 gpm (10…153 lpm)
4.66…69.93 gpm (17…265 lpm)
6.35…95.18 gpm (24…360 lpm)
10.49…157.34 gpm (40…595 lpm)
Weight
6.5 lbs (2.9 kg)
7.5 lbs (3.4 kg)
9.5 lbs (4.3 kg)
11 lbs (4.9 kg)
13 lbs (5.9 kg)
Series 380 BACnet Object Map
Description ID Name Units
Analog Input AN1 TempIn ºC, ºF Analog Input AN2 TempOut ºC, ºF Analog Value AV1 VolFlow gpm, gph, lpm, lps, lph, ft3/s, ft3/m, ft3/h, m3/s, m3/min, m3/h, custom Analog Value AV2 EnergyFlow kBtu/min, kBtu/h, kW, MW, HP, Tons, custom Analog Value AV3 TotalVol gallons, galx100, galx1000, liters, ft3, m3, custom Analog Value AV4 TotEnergy Btu, kBtu, MBtu, kWh, MWh, kJ, MJ, custom Analog Value AV5 TempMode dimensionless Analog Value AV6 FFilterCoef dimensionless Analog Value AV7 TFiltCoef dimensionless Analog Value AV8 SpHtCapac Btu/lb-F Analog Value AV9 Density lb/gallon Analog Value AV10 SerialNum dimensionless
Table 2: 380 BACnet object map
Page 6 July 2016 Page 7 July 2016 IND-UM-02074-EN-01IND-UM-02074-EN-01
Series 380 BTU System , 380DS Meter
Control. Manage. Optimize.
Data Industrial is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2016 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 880102-0001
Loading...