Badger Meter 340 Specifications

Transmitters
Series 340 BN/MB Btu Energy Transmitter
DESCRIPTION
The 340 BN/MB Btu Energy Transmitter from Badger Meter® is an economical, compact device for sub-metering applications using the BACnet or Modbus® communications protocol.
The on-board microcontroller and circuitry make precise measurements and produce accurate, drift-free outputs. The 340 BN/MB Btu Energy Transmitter is programmed using Badger Meter Windows®-based software. Calibration information for the flow sensor type and pipe size may be preselected or entered by the user in the field. While the unit is connected to a PC or laptop computer, real-time flow rate, flow total, temperatures, energy rate and energy total are available.
340 BN/MB Ordering Matrix
EXAMPLE: 340 BN/MB xx
SERIES
Btu Energy Transmitter w/
340 BN/MB
output
OPTIONS
Transmitter Only 00
With Metal Enclosure 02
With Plastic Enclosure 03
With DIN Rail Mounting Clips 04
The 340 BN/MB Btu Energy Transmitter features three indicator LEDs to verify the sensor input signal, network link and pulse output.
The 340 BN/MB Btu Energy Transmitter communicates via RS485.
The compact cast body measures 3.65 × 2.95 inches (93 × 75 mm) and can be easily mounted on panels, DIN rails or enclosures.
1.60 in.
(40.6 mm)
2.95 in.
(74.9 mm)
3.65 in.
(92.7 mm)
Output
Pulse Out -
AC L /DC
AC C /DC
Power Out Signal + Signal Shield
1
Temp 2
2
3
3
Temp 1
2
1
+
-
Sensor Input
-
Input LED
Power In
Btu ENERGY METER
Model: 340 BN/MB S/N 340-
Comm LED
Pulse Out +
Output LED
Data Industrial
005100
D.I.C.
Comm
Port
+
Figure 1: Overall dimensions
0.88 in.
(22 mm)
Factory Port
0.60 in.
(15 mm)
NT PDPU
REF
_
0.20 in. (5 mm)
XMT-DS-01661-EN-05 (March 2018)
Product Data Sheet
Transmitters, Series 340 BN/MB Btu Energy Transmitter
Side
5.125 in.
(130 mm)
3.25 in.
(82 mm)
4.60 in.
(117 mm)
4.60 in. (117 mm)
Top
Side
2.25 in.
(57 mm)
)
SPECIFICATIONS
Power
Power supply
Current draw: 115 mA max. at 12V DC
Flow Sensor Input Pulse Type Sensors:
Signal amplitude 2.5V DC threshold
Signal limits Vin < 12V (DC or AC peak)
Frequency range 4…1000 Hz
Sine Wave Sensors:
Signal amplitude 30 mV p-p threshold
Signal limits Vin < 12V (DC or AC peak)
Frequency 4…1000 Hz
Power Out Terminal 15V DC ± 1V DC @ 500 Ω source Impedance Temperature Sensor (2 of same type required) Input
• 10k Ω thermistor, 2 wire, type II, 10k Ω @ 25° C (77° F)
• 100 Ω platinum RTD, DIN calibration curve, conforms to IEC-751 Standard
• 1000 Ω platinum RTD, DIN calibration curve, conforms to IEC-751 Standard Calibration range of measurement 0…150° C (32…302° F)
Communication Port
Pulse Output
• Isolated solid-state switch in any standard or custom total units
• Adjustable 50 ms to 1.0 second pulse output width in 50 ms increments
Maximum sinking current: 100 mA @ 36V DC
Temperature
Operating 0…70° C (32…158° F)
Weight 4.8 oz with connector headers installed Sensor Calibration
Badger Meter Use K and offset values provided in sensor manual
Other Sensors
Units of Measure Flow Measurement:
Energy Measurement:
Temperature Measurement Fahrenheit, Centigrade Programming
• Requires PC or laptop running Windows 2000, XP, Vista or Windows 7
• Data Industrial 340BN/MB Programming Kit A-301-20 containing software and
Data Industrial Series programming cable is required for programming and setup
12…24V AC 12…35V DC
Pull-up: 15V DC @ 2k Ω source Impedance
RS-485 with termination, pull-up and pull-down jumpers
Storage – 40…85° C (– 40…185° F)
Check with respected manufacturer of flow sensor and with factory
gpm, gph, l/sec, l/min, l/hr, ft3/sec, ft3/min, ft3/hr, m3/
Rate
sec, m3/min, m3/hr Gallons, Gallons X 100, Gallons X 1000, Liters, Cubic
Total
Feet, Cubic Meters
Rate kBtu/min, kBtu/hr, kW, MW, hp, tons
Total Btu, kBtu, MBtu, kWh, MWh, kJ, MJ
Figure 2: Plastic enclosure dimensions
Top
4.50 in. (114 mm)
Side
Figure 3: Metal enclosure dimensions
4.50 in.
(114 mm
2.00 in.
(50 mm)
Control. Manage. Optimize.
Data Industrial is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2018 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Eastern Europe Branch Oce (for Poland, Latvia, Lithuania, Estonia, Ukraine, Belarus) | Badger Meter Europe | ul. Korfantego 6 | 44-193 Knurów | Poland | +48-32-236-8787 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: DTB-102
Loading...