Badger Meter 3100-10, 3100-00 User Manual

Industrial Flow Monitor
Series 3100
CTL-UM-01026-EN-05 (October 2017)
User Manual
Industrial Flow Monitor, Series 3100
Page ii October 2017CTL-UM-01026-EN-05
User Manual
CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Unpacking & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Panel Mount Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wall Mount Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Low Voltage 12…24V AC/DC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
High Voltage Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pulse Inputs (Solid-State Switch or Sine Wave). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mechanical Form C Relays (COM, N.O. and N.C.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Normally Open Solid-State Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
RS485 Communication Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
USB Communications Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Keypad/Display Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Selection Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Option List Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Data Entry Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Programming Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Flow Inputs Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Relays and Pulse Outputs Flowchart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Analog Outputs Flowchart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Page iii October 2017 CTL-UM-01026-EN-05
Industrial Flow Monitor, Series 3100
RS485 Communication Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Solid-State Switch and Form C Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Totalizer Pulse Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
RS485 COM Port Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
BACnet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
USB Command List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Trouble Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Ordering Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Page iv October 2017CTL-UM-01026-EN-05

Introduction

INTRODUCTION
The Badger Meter® Data Industrial® Series 3100 flow monitor is an economical, dual channel, full featured, digital rate and totalizing monitor, compete with setpoint control, scaled pulse output, analog outputs, analog PID controller, USB, and RS485 Modbus and BACnet communication.
Panel mount is Type NEMA 4X, and conforms to DIN standard dimensions (96 mm × 96 mm) for meter size and panel cutout. An optional Type NEMA 4 wall mount will be available in the future.
The back-lit, two-line by 16-character alphanumeric display can be configured by the user with factory preset or with user-defined units of measure. Any combination of two rates or totals from either input channel can be displayed at any one time, with the special feature of channel addition or subtraction. LEDs report relay status and digital communication.
Inputs are from any combination of two pulse, sine wave or linear analog input devices. Configuration is menu driven using the LCD/keypad interface, or USB computer connection, with multiple password gates to
prevent unauthorized access, while allowing access to select features such as total and relay reset functions. Outputs include four Form C mechanical relays, one solid-state switch, two Analog Outputs, one USB, and one RS485 with
BACnet and Modbus protocols.

Advanced Standard Features

• Easy to switch power supplies from 12…24V AC/DC to the optional 120/240V AC
• Nonvolatile memory; no battery backup is required
• Two independent pulse and analog input channels can be used separately or combined in addition or subtraction modes, for all display output functions
• Field-definable custom units of measure labeling and conversion factors
• Two line by 16-character 3/8 in. (7.95 mm) high back-lit display
• Front panel LEDs indicate status of each relay, pulse output, and Rx/Tx activity
• Simple front panel configuration with the option to use the USB port
• USB communication is a very powerful diagnostic and OEM tool
• Two-level password protection; one to restrict setup access and one to protect totals
• Field-definable custom units of measure labeling and conversion factors
• A total of seven independent relay, pulse and analog outputs
• Powerful setpoint control, with independent set and release point values, set and release delays, and latching functions
• Scaled pulse output with pulse width control
• Dual channel analog outputs are either current sinking or sourcing 4…20 mA or 0…20 mA. Current sourcing 0…20 mA permits external conversion to 0…5V DC or 0…10V DC
• PID process control using analog outputs
• RS485 with Modbus and BACnet/MSTP protocols
• IIRF (Infinite impulse response filter). Proprietary input signal smoothing

SAFETY INFORMATION

The installation of the flow monitor must comply with all applicable federal, state, and local rules, regulations, and codes. Failure to read and follow these instructions can lead to misapplication or misuse of the flow monitor, resulting in personal
injury and damage to equipment.
Page 5 October 2017 CTL-UM-01026-EN-05

Unpacking & Inspection

UNPACKING & INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:N If damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.

INSTALLATION

Mechanical

The Series 3100 flow monitor can be either panel mounted or wall mounted.

Location

In any mounting arrangement, the primary concern is easy viewing and convenient keypad operation. The flow monitor generates very little heat, so no consideration need be given to cooling or ventilation. However, prolonged direct sunlight can damage the front panel so some level of shading is recommended, especially if installed in a tropical climate.

Panel Mount Installation

The Series 3100 panel mount monitor is designed for through-panel mounting, which allows access to the back of the unit. The monitor is secured to the panel by two draw brackets.
Figure 1: Panel mounting
3.49 in.
Relay 1
(88.7 mm)
3.78 in.
(96 mm)
Data Industrial
A BadgerMeter, Inc. Company
Relay 2
Menu
R
Series 3100
Relay 4Relay 3
Enter
TX RX
Pulse Out
4.31 in.
(109 mm)
3.78 in.
(96 mm)
3.57 in. to 3.60 in.
(90.6 mm to 91.4 mm)
Panel Cutout
4.79 in.
(122 mm)
Figure 2: Physical dimensions and panel cutout
Page 6 October 2017CTL-UM-01026-EN-05
3.57 in. to 3.60 in.
(90.6 mm to 91.4 mm)
3.49 in.
(88.7 mm)
Installation

Wall Mount Installation

Badger Meter does not currently offer a wall mount enclosure for this product. However, Series 3100 flow monitors can be wall mounted in the field into any appropriate customer-supplied enclosure.

Electrical Power

MPORTANTI
Before applying power to this unit, check the Model # label: The Series 3100 flow monitor can be ordered as low voltage 12…24V AC/ DC (3100-0x) or as high voltage 120/240V AC (3100-1x).

Low Voltage 12…24V AC/DC Wiring

The Series 3100 flow monitor has a green, three-terminal connector with screw heads, and requires 12…24V AC/DC to operate. See "Specifications" on page 30 for the current DC draw and AC Volt-Amp requirements. Always use a fused circuit.
Connect the positive end of the power supply to the Series 3100 flow monitor terminal marked LV AC/DC (+), and connect the negative end of the power supply to the Series 3100 flow monitor terminal marked LV AC/DC (–). Earth ground can be connected to the terminal marked EARTH.
Ground should be heavy gauge wire and as short as possible. If panel mounting in a metal enclosure, Ground to door and bond the door to the enclosure across the hinges with a brad just long enough to allow the door to open freely.
Orange Label
AC AC 12 . . . 24V AC Power Supply
(+) (-) 12 . . . 24V DC Power Supply
Either AC or DC power can be used. AC is not polarity sensitive.
Earth Ground LV AC/DC (+) LV AC/DC (-)
3 2 1
Figure 3: Series 3100-0x low voltage power supply wiring

High Voltage Power Supply Wiring

The Series 3100-1x is designed to accept a standard EL-712 (NEMA 5-15R) plug similar to those used on many laptop computers. Power can be 120…240V AC 50…60 Hz. When the High Voltage option is ordered (3100-1x), a power cord is supplied with the unit.
See "Specifications" on page 30 for volt/amp ratings for inverter or other non-conventional source.
Page 7 October 2017 CTL-UM-01026-EN-05
Installation

Input Sensor Wiring

The Series 3100 flow monitor is a Dual Channel unit. Either a single input, or any combination of two pulse or analog inputs can be used. The pulse inputs are extremely versatile, designed to accept either two-wire (Data Industrial 200 Series), three­wire pulse inputs (4000 Series) or zero-crossing sine wave inputs (turbines with a magnetic coil pickup).
The analog inputs can accept 0…20 mA, 4…20 mA, 0…1V DC, 0…5V DC or 0…10V DC. Both the top and bottom ends of the analog range can be configured in the field so that most inputs can be accepted if the hardware limitations are not exceeded. Contact the factory for assistance with custom inputs. Although different rear panel terminals are used, all parameters are set with the LCD/keypad interface. No internal or external jumpers, switches or potentiometers require movement or adjustment.

Pulse Inputs (Solid-State Switch or Sine Wave)

The Series 3100 flow monitor accommodates four types of pulse inputs:
• Pulse-DI: Used for all Data Industrial Flow Sensors. Provides an internal pullup resistor and uses “K” and “Offset” values for calibration.
• Pulse –K Factor: Accepts non Zero Crossing inputs but provides no internal pullup, classical “K” (pulses/gal) values for calibration.
• Pullup K Factor: Provides an internal pullup resistor and uses classical “K” ( pulses/gal) values for calibration.
• Sine-K Factor: Accepts zero crossing low voltage sourcing devices, with classical “K” ( pulses/gal) calibration.
Analog 1 IN (+) 1 Analog 1 IN (-) 2 Shield 3 Analog 2 IN (+) 4
Channel #1 Two Wire Flow Sensor Sensor (+) Sensor (-) Shield
Shield Sensor (+) Sensor (-)
Channel #2 Two Wire Flow Sensor
Analog 2 IN (-) 5 Shield 6 Pulse 1 IN (+) 7 Pulse1 IN (-) 8 Shield 9 Pulse 2 IN (+) 10 Pulse 2 IN (-) 11 Sensor Power 12
Sensor Input Card Green Label 12 Pin Connector
200 Series Flow Sensors
Red = Sensor (+) Black = Sensor (-)
SDI Series Sensors
Varies with Model Refer to SDI User Manual
Other Sensors
Contact Technical Support as needed
Figure 4: Wiring a two-wire pulse flow sensor
Channel #1 Three Wire Flow Sensor Sensor Power Sensor (+) Sensor (-) Shield
Shield
Sensor (+)
Sensor (-)
Sensor Power
Channel #2 Three Wire Flow Sensor
4000 Series Flow Sensors
Red = Sensor Power White = Sensor (+) Black = Sensor (-)
SDI Series Sensors
Varies with Model Refer to SDI User Manual
Other Sensors
Contact Technical Support as needed
Figure 5: Wiring a three-wire pulse sensor
Page 8 October 2017CTL-UM-01026-EN-05
Analog 1 IN (+) 1 Analog 1 IN (-) 2 Shield 3 Analog 2 IN (+) 4 Analog 2 IN (-) 5 Shield 6 Pulse 1 IN (+) 7 Pulse1 IN (-) 8 Shield 9 Pulse 2 IN (+) 10 Pulse 2 IN (-) 11 Sensor Power 12
Sensor Input Card Green Label 12 Pin Connector
Installation

Analog Input

As an alternative to the pulse inputs, the Badger Meter Series 3100 also accepts up to two analog inputs. The input is non-isolated, but can accept 0…1V DC, 0…5V DC, 0…10V DC, 0…20 mA and 4…20 mA with both factory-defined and custom units of measure. Low impedance 100 Ohm input for current inputs optimizes performance and flexibility for loop power supplies. Both the low and high end scaling are independent and field-configured by the installer.
Channel #1 Loop Powered Sensor
Loop (-)
Loop (+)
Shield
Voltage or Current Sourcing Device
with internal Power Supply
NOTES:
1. Analog Inputs share an isolated ground from power supply and earth grounds; however, Channel #1 and #2 share a single ground plane.
2. Input ranges of 0 . . . 1V DC, 0 . . . 5V DC, 0 . . . 10V DC, 1 . . . 20 mA, or 4 . . . 20 mA can be selected from front panel or via USB communication port.
3. Voltage inputs are high impedance 100 K +. Current inputs are 100 Ohm. As a result, a 4 . . . 40 mA input will appear as 0.2V DC to 2.0V DC across the Analong Input Terminals. This information can be helpful in troubleshooting.
External
24V DC
Power
Supply
(+)
(-)
Voltage/Current (+)
Voltage/Current Com
Shield
Analog 1 IN (+) 1 Analog 1 IN (-) 2 Shield 3 Analog 2 IN (+) 4 Analog 2 IN (-) 5 Shield 6 Pulse 1 IN (+) 7 Pulse1 IN (-) 8 Shield 9 Pulse 2 IN (+) 10 Pulse 2 IN (-) 11 Sensor Power 12
Sensor Input Card Green Label 12 Pin Connector
Figure 6: Wiring current and voltage sourcing inputs

Output Wiring

The Series 3100 flow monitor has four mechanical Form C relays, one solid-state, normally open (N.O.) switch closure, two analog outputs, RS485 for Modbus and BACnet communications and a USB connector for configuration and other purposes.
See "Specifications" on page 30 for maximum voltage and current ratings for each output type.

Mechanical Form C Relays (COM, N.O. and N.C.)

The four Form C mechanical relays are labeled N.O., N.C. (normally closed) and COM (common). When a relay is de-energized, the corresponding LED is unlit, and continuity exists between N.C. and COM; and N.O. to COM
is open. When a relay is energized, the corresponding LED lights yellow and there is continuity between N.O. and COM and N.C. to
COM is open.
Page 9 October 2017 CTL-UM-01026-EN-05
Installation
Sensor Input Card Red Label 14 Pin Connector
Indicator Light
Signaling Device
Indicator Light
or other
Signaling Device
or other
(Appropriate for Master Valve)
(COM) (Line)
Normally Closed
Irrigation Controller
(COM) (Master Valve Out)
Normally Open
Master Valve
Power Supply
Typically 24V DC
Figure 7: High flow shutdown and normally open master valve
Master Valve
Relay 1 NO Relay 1 NC Relay 1 COM Relay 2 NO Relay 2 NC Relay 2 COM Relay 3 NO Relay 3 NC Relay 3 COM Relay 4 NO Relay 4 NC Relay 4 COM
Pulse 1 OUT Pulse 1 OUT
Sensor Input Card Red Label 14 Pin Connector
Relay 1 NO Relay 1 NC Relay 1 COM Relay 2 NO Relay 2 NC Relay 2 COM Relay 3 NO Relay 3 NC Relay 3 COM Relay 4 NO Relay 4 NC Relay 4 COM
Pulse 1 OUT Pulse 1 OUT
1 2 3 4 5 6 7 8
9 10 11 12 13 14
1 2 3 4 5 6 7 8
9 10 11 12 13 14
NOTE: Relay pregrammed for the desired Set Point and Set Delay, and LATCHED.
Under normal conditions, the relay simply passes the commands of the irrigation controller through the Normally Open contact.
However, once tripped, the Irrigation Controller signal is simply passed to the signalling device to warn the operators.
Figure 8: High flow shutdown with irrigation clock and normally closed master valve
Page 10 October 2017CTL-UM-01026-EN-05

Normally Open Solid-State Switch

Installation
Sensor Input Card Red Label 14 Pin Connector
Relay 1 NO Relay 1 NC Relay 1 COM Relay 2 NO
Mechanical
Counter
Power Supply
(Appropriate Mechanical Counter)
Typically 12V DC
(-) (+)
NOTE:
Although the example shown here is showing the Pulse Output as a Pulse/Unit Volume, this output is a fully functional relay, with all the programming feature of the four mechanical relays. However, instead of a Form C mechanical, it is a Form A Solid-State Switch (NO).
Relay 2 NC Relay 2 COM Relay 3 NO Relay 3 NC Relay 3 COM Relay 4 NO Relay 4 NC Relay 4 COM
Pulse 1 OUT Pulse 1 OUT
1 2 3 4 5 6 7 8
9 10 11 12 13 14
Figure 9: External mechanical counter and power supply
The pulse output is a completely programmable, isolated N.O. solid-state switch. It is a non-polarized device that can handle either DC or AC loads. See "Specifications" on page 30 for voltage and
load limitations.

Analog Outputs

The Series 3100 flow monitor has two analog outputs. Each is isolated and independent and can be configured for 0…20 mA or 4…20 mA. This unique design permits external conversion to 0…5V DC or 1…5V DC with a 250 Ohm resistor or 0…10V DC or 2…10V DC with a 500 Ohm resistor.
A 15V DC power supply to permits current sinking or sourcing. If additional source voltage is required, an external source of up to 30V DC can be used.
NOTES:
4 . . . 20 mA input devices only require that
1. the 4 . . . 20 mA range be selected.
0 . . . 1V DC requires 0 . . . 20 mA range and external 50 Ohm resistor.
0 . . . 5V DC requires 0 . . . 20 mA range and external 250 Ohm resistor.
2 . . . 10V DC requires 0 . . . 20 mA range and external 500 Ohm resistor.
2. Loop (+) is +15V DC power our. Loop (-) is a current sink to CHx GND. CHx GND is the +15V reference.
3. Analog Out #1 and Analog #2 are totally independent but are programmed and wired identically, and can be used interchangeably. For example, one can be 0 . . . 20 mA and the other 4 . . . 20 mA; or one could be wired current sinking while the other is wired current sourcing.
The Output Channels are assigned to an Input Channel by the installer. Both Output Channels can be assigned to the same Input Channel.
Analog Input Device 12V max. @20 mA
NOTE:
Resistor only required for voltage input devices 0 . . . 1V DC, 0 . . . 5V DC, 1 . . . 5V DC, 2 . . . 10V DC, etc.
0 . . . 20 mA and 4 . . . 20 mA devices do not use an external resistor.
Analog Input Device with External or Integral Power Supply
Power Supply COM
Analog (+)
Analog (-)
24V DC (+)
Analog IN (+)
Analog IN (-)
R e s
i
s
t
o
r
Figure 10: Current sourcing analog output to voltage input device
Analog Output Card Yellow Label 9 Pin Connector
RS485 B (+) RS385 A (-) RS485 Iso. GND (REF) CH2 Loop (+) CH2 Loop (-) CH2 GND CH1 Loop (+) CH1 Loop (-) CH1 GND
1 2 3 4 5 6 7 8 9
Page 11 October 2017 CTL-UM-01026-EN-05
Installation

RS485 Communication Wiring

Analog Output Card Yellow Label 9 Pin Connector
RS485 (+)
RS485 (-)
Series 3700 or other
Modbus or BACnet
Master Device
Shield
RS485 B (+) RS385 A (-) RS485 Iso. GND (REF) CH2 Loop (+) CH2 Loop (-) CH2 GND CH1 Loop (+) CH1 Loop (-) CH1 GND
Figure 11: RS485 communication wiring (Modbus + BACnet)

USB Communications Port

Using the USB Port requires Windows® HyperTerminal or other similar communications software.
Use Standard Cable USB Type A Male to Type Mini B 5-Pin Male
Connect to Computer USB COM Port
1 2 3 4 5 6 7 8 9
Figure 12: USB port
Page 12 October 2017CTL-UM-01026-EN-05
Installation

Keypad/Display Menu Navigation

The Series 3100 flow monitor has a two line by 16-character display with two modes of operation and 5 keys on the front panel for programming. Two of the keys (Menu and Enter) serve a single function while the three remaining keys () serve dual purposes.
When the flow monitor is first powered up, it performs internal testing while displaying “Badger Meter DIC Initializing.” At the end of the internal testing cycle, the main display appears.
In the normal mode, using the factory defaults, the flow rate displays on the top line and the flow total displays on the bottom. Both lines can be custom defined in the field. In the normal mode, ENTER has no function.
1 123.00 GPM 1 123456.7 gal
Flow Channel 1 Flow Rate and Flow Total
2 10.01 PSI 1 23.09 Feet
Channel 2: Pressure and Channel 1: Level
SETUP PWORD DSPY FLOW1
On every screen there are three choices and three
corresponding buttons. However, on this Setup menu there
are more options than t on the screen. The arrow ()
indicates additional options. To access these remaining
options, press ENTER.
1 123.00 GPM 2 123456.70 GPM
Flow Channel 1 Flow Rate and Flow Channel 2 Rate
RESET SETUP DIAG
Main Setup screen accessed by pressing MENU.
On each screen there are three options:
selects RESET selects SETUP and selects DIAG
SETUP
FLOW1 RLY1 RLY2
Press ENTER again to bring up the next set of choices.
Press MENU to exit an option, or return to the previous
screen, or—in some cases—to return to the main
display screen.
Page 13 October 2017 CTL-UM-01026-EN-05
Menu Enter
Menu Enter
Flow 1 units
GPM
Menu Enter
t
0

Programming

PROGRAMMING

Selection Screens

Press MENU while the normal display is shown to access the programming mode. In this mode, press one of the three arrow keys () to select the option displayed above that key. On option list screens, use the arrows to scroll through a list of choices, like a pull-down menu. Note that most screens presenting choices show three choices, one for each arrow button. When the number of choices exceeds three, a small arrow () appears in the upper right side of the display to indicate more choices on that level. Press ENTER to toggle to the next set of choices. Once a selection has been made, press ENTER to complete the selection. Press MENU to return to the Normal screen. For example: Press MENU from the Normal screen to display the “RESET SETUP DIAG” screen. Press to display the Reset screens, to display the Setup screens and to display the Diagnostic screens. If is pressed, the following screen appears:
SETUP PWORD DSPY FLOW1
Menu Enter
Figure 13: Selection screen

Option List Screens

Units of measure is an example of an options list. Press to scroll up the list, and to scroll down through the list. In this case, starting with GPM; gal/s; gal/hr; LPM; ending in
a selection of custom units. Press ENTER to complete the selection. Press MENU to leave the selection unchanged. The key has no function on this type of screen.

Data Entry Screens

Some screens are data entry screens, such as setpoints or custom units. When a data screen is initially displayed, the current value will be displayed. The cursor will be flashing the left-most digit. Press to increase a value, and to reduce a value.
If the cursor is flashing on the decimal point, press to move the decimal point to the right, press to move the decimal to the left.
Flow 1 units
GPM
Menu Enter
Figure 14: Options list screen
Set poin
1.0000000
Menu Enter
Figure 15: Data entry screen
Page 14 October 2017CTL-UM-01026-EN-05
INTENTIONAL BLANK PAGE
User Manual
Page 15 October 2017 CTL-UM-01026-EN-05
Programming

Programming Flowchart

RESET SETUP DIAG
Require setup PW YES [NO]
RESET
FLOW1 FLOW2
Reset ow x? OK CANCEL
Enter password 0000
Reset ow x? RESET
Password setup
ENAB SETUP RESET
Enter password
0000
Setup Password is enabled.
SETUP
PWORD DSPY FLOW1
Reset password 0000
Continued at A
on next page.
Appears only if
Continued at B
on next page.
Set Up password 0000
Page 16 October 2017CTL-UM-01026-EN-05
Batch password 0000
LINE1 Flow 1 Rate Flow 1 Total Flow 2 Rate Flow 2 Total Flow 1 +2 Rate Flow 1 +2 Total Flow 1 -2 Rate Flow 1 -2 Total Flow 2 -1 Rate Flow 2 -1 Total
Display LINE1 LINE2 RATE
LINE1 Flow 1 Rate Flow 1 Total Flow 2 Rate Flow 2 Total Flow 1 +2 Rate Flow 1 +2 Total Flow 1 -2 Rate Flow 1 -2 Total Flow 2 -1 Rate Flow 2 -1 Total
Update rate
+0.00000000 sec
. . .
+9.99999999 sec
Programming Flowchart (continued)
Programming
RESET SETUP DIAG
SETUP
PWORD DSPY FLOW1
Continued from B on previous page.
Continued from A
on previous page.
DIAG
MODL# SER# REV#
Model # 3100XX
Serial # XXXXXX
SETUP
FLOW2 RLY1 RLY2
Firmware rev:
v1.2.29
DIAG ERROR
Error codes:
000 000 000 000
SETUP
RLY3 RLY4 Pulse
SETUP
AOUT1 AOUT2 COMM
Go to
Analog
Outputs
Go to
Flow
Inputs
Go to
Relays & Pulse
Outputs
Go to RS485
MODBUS/BACnet
Page 17 October 2017 CTL-UM-01026-EN-05
Programming

Flow Inputs Flowchart

Flow 1 setup
RATE TOTAL SENSR
Flow X rate
UNITS #.DIG CUST
Flow 1 # digits
0 1 2
Flow x units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Custom units
LABEL CONV
1 UNIT =
-0.00000000 GPM . . . +999999999. GPM
Flow X total
UNITS #.DIG CUST
Flow total units
gal Mgal L ft3 m3 acre-ft bbl Custom units
Flow 1 # digits
0 1 2
Enable password?
YES [NO]
Enable password? [YES] NO
Custom units
LABEL CONV
1 UNIT =
-0.00000000 GPM . . . +999999999. GPM
Flow X total
RESET
Reset BTU total
PASSWD RESET
Reset total NOW?
OK CANCEL
Continued at A on next page.
Unit label
? > = < ; : 9999999999 8888888888 . . . 1 0000000000 / .
­, + * ) ( ' & % $ " !
{ z y x . . .
c b a ` _ ^ ] ¥ [ ZZZZZZZ Y X . . . J BBBBBBB AAAAAA
Page 18 October 2017CTL-UM-01026-EN-05
Flow Inputs Flowchart (continued)
Continued from
A
previous page.
Programming
Sensor 1 type
Pulse DI
Pulse K-Factor
Pullup K-Factor
Sine K-Factor
Analog
Flow 1 sensor
TYPE xxxx xxxx
Flow 1 sensor
TYPE AVG DICAL
Flow 1 sensor
TYPE AVG KFACT
Flow 1 sensor
TYPE ANALOG
Analog ow 1
UNITS RANGE HIGH
Flow 1 timeconst
-0.00000000 sec . . .
+100.000000 sec
Flow 1 timeconst
-0.00000000 sec
. . . +100.000000 sec
Analog ow 1
LOW CAL
DI Sensor Cal.
KNUM OFFSET
DI sensor K num
-0.00000000 . . .
+999999999.
K-Factor
-0.00000000 . . .
+999999999.
0V (1V scale) XXX Factory (Next)
DI Sensor Oset
-999999999. . . .
-0.00000001
+0.00000001
. .
+999999999.
Flow x units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Analog x range
0 to 1V 0 to 5V 0 to 10V 0 to 20 mA 4 to 20 mA
Max reading = ?
-0.00000001
+999999999.
Min reading = ?
-0.00000001 . . .
+999999999.
Sampling XXXXXXXXXXXX
0V (10V scale) XXX Factory (Next)
0mA (20mA scale) XXX Factory (Next)
2V (2V scale) XXX Factory (Next)
. .
10V (10V scale)
.
XXX Factory (Next)
20mA (20mA scale) XXX Factory (Next)
Page 19 October 2017 CTL-UM-01026-EN-05
SETUP
FLOW2 RLY1 RLY2 RLY3 RLY4 Pulse
Programming

Relays and Pulse Outputs Flowchart

Relay 1 (or Pulse) FUNC xxxxx xxxxx
Manual Control
Totalizer
Alarm
Relay 1 (or Pulse) FUNC INPUT UNITS
Relay 1 (or Pulse) input
Flow 1 Total Flow 2 Total Flow Sum Total Flow 1-2 Total Flow 2-1 Total
Relay 1 (or Pulse) FUNC INPUT UNITS
Totalizer input
Flow 1 Total Flow 2 Total Flow Sum Total Flow 1-2 Total Flow 2-1 Total
Set point units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Pulse rate units
gal Mgal L ft3 m3 acre-ft bbl Custom units
Relay 1 (or Pulse) LATCH SETPT RELP
Relay 1 Latch?
ON [OFF]
Set point
-0.00000001
+999999999.
1 pulse = ?
0.00000001 . . .
999999999.
Release point
. . .
Relay 1 (or Pulse) RATE CTIME
-0.00000001
+999999999.
Time closed
0001 ms
9999 ms
. . .
Relay 1 (or Pulse) FUNC MANUAL
. . .
Relay 1 (or Pulse) SDLY RDLY
Trigger delay
0000000 s
10000000 s
Relay 1 (or Pulse) ON [OFF]
Relay 1 (or Pulse) [ON] OFF
Release delay
0000000 s . . .
10000000 s
. . .
Page 20 October 2017CTL-UM-01026-EN-05

Analog Outputs Flowchart

SETUP
AOUT1 COMM
Analog output 1
FUNC RANGE SCR
Analog function
Flow Rate
Analog output 1
FUNC RANGE SCR
Analog output 1
UNITS LOW HIGH
Programming
Analog output 1
CAL
PID
Analog output 1
FUNC RANGE SCR
Analog output range
0 to 20 mA 4 to 20 mA
Drive source
Flow 1 Rate
Analog output range
0-20 mA 4-20 mA
Analog output 1
UNITS SETPT P
Flow x units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Drive source
Flow 1 Rate
PID Set point
-0.00000000
+999.99999
PID P const
+000.000
+999.000
. . .
Analog 1 units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
PID I const
+000.0000 . . .
+999.9999
0 mA = ?
0.0000000
Analog output 1
I D LOW
PID D const
+000.000 . . .
. . .
+999.000
20 mA = ?
0.0000000
4 mA = ?
+000.0000
+999.9999
Adjust 4 mA
12107 FACTRY
Analog output 1
HIGH
20 mA = ?
+000.0000 . . .
+999.9999
Adjust 4 mA
12107 FACTRY
. . .
Adjust 20 mA
60748 FACTRY
Analog output 1
CAL
Adjust 20 mA
60748 FACTRY
Page 21 October 2017 CTL-UM-01026-EN-05
Programming

RS485 Communication Flowchart

Comm NET BAUD ADDR
Network
Disable
MODBUS
BACnet/MSTP
Comm
NET
Comm
NET BAUD ADDR
Network
MODBUS
Comm
NET BAUD ADDR MAX DEVID
Baud Rate
300 1200 2400 9600
19200 38400 76800
MODBUS Address
001
. . .
247
Network
BACnet/MSTP
Page 22 October 2017CTL-UM-01026-EN-05
Baud Rate
Auto
9600 19200 38400 76800
MSTP Address
001
127
MSTP Max master
. . .
001
127
Device Instance
. . .
00000000
. . .
99999999
Programming

Solid-State Switch and Form C Outputs

The four Form C mechanical relays, and one NO solid-state switch pulse output are completely independent, electrically isolated and can be programmed as either pulse or setpoint outputs.

Totalizer Pulse Output

When the Totalizer function is selected, the unit of measure and resolution are independent of the displayed units, and can be programmed where 1 pulse occurs once every 0000000.1… 999999999 of units selected, with any pulse width from 0001…9999 mS.

Setpoints

The setpoint programming is extremely powerful and flexible, with unit of measure and resolution independent of the displayed units. Since the setpoint, release point and their associated time delays are fully independent, the alarm can be either a high rate or low rate, depending on whether the setpoint is selected greater than the release point, or the release point is greater than the setpoint. For applications where the relay must remained energized, once set, a latching feature is provided. When latched, the relay remains energized until reset from the front panel. While design planning, note that both the relays and the pulse outputs can be programmed as alarm points and only the relays provide both normally open and normally closed contacts. The switch is a simple NO contact.
Terminology
Display Definition Function
SETPT Setpoint If the setpoint value is a greater than the release point value, when the
displayed flow rate exceeds the setpoint, the Set Point Delay timer starts. If the setpoint is less than the release point when the flow drops below the setpoint, the timer starts.
SDLY Setpoint time delay If the setpoint remains crossed for a continuous period of time exceeding the
setpoint delay setting, the relay energizes. If the flow rate briefly re-crosses the setpoint before the timer reaches its setting, the timer resets and waits for another setpoint crossing before restarting the count from zero.
LATCH Locks relay in energized state If Latch is chosen, once energized by the setpoint time delay, the relay remains
energized until a reset is selected from the front panel. Otherwise, the relay de-energizes when the Release Point Delay Timer times out.
RELP Release point If the relay is already energized, is not latched and the flow input crosses the
release point, the Release Point Delay timer starts.
RDLY Release point time delay If the release point remains crossed for a continuous period of time and
exceeds the release point delay setting, the relay de-energizes. If the flow rate briefly re-crosses the release point before the timer reaches its setting, the timer resets and waits for another release point, crossing before restarting the count from zero.
High Flow Set Point
The SETPT must be a value greater than the RELP. The relay output will have continuity between its N.C. terminal and COM until the flow has exceeded the SETPT for a continuous period of time exceeding the SDLY. At this time, the N.C. connection opens and the N.O. contact will have continuity to the COM terminal. When the flow has dropped below the RELP for a continuous period of time exceeding the RDLY, the relay states return to the original states. If the latch has been set to ON once the setpoint and set delay have been satisfied, the relay will not release until manually reset.
Low Flow Set Point
The SETPT must be a value less than the RELP. The relay output will have continuity between its N.C. terminal and COM until the flow drops below the SETPT for a continuous period of time exceeding the SDLY. At this time, the N.C. connection will open and the N.O. contact will have continuity to the COM terminal. When the flow again has risen above the RELP for a continuous period of time, exceeding the RDLY, the relay states return to the original states. If the latch has been set to ON when the setpoint and set delay have been satisfied, the relay will not release until manually reset.
Page 23 October 2017 CTL-UM-01026-EN-05
Programming

Communication

RS485 COM Port Configuration

The RS485 is very simple to configure.
1. Select the communications type: Modbus or BACnet.
1. Choose the BAUD Rate: Auto, 300, 1200, 2400, 9600, 19200, 38400, or 76800 to match the rest of the devices on the network. The factory default of 9600 is recommended for most systems. The lower the baud rates have greater stability, and greater tolerance of wiring and other hardware issues.
Configuring the Modbus or BACnet are described in the following sections.

Modbus

• Network: RS485
• Baud Rate: Selectable
• Protocol: RTU or ASCII
• Addresses: 001 to 247
• Slave only
• Read Input Registers: 30001…39999 (Function “04”)
• Data Type: IEEE 754 Float (ABCD – CDAB)
Each variable is stored in two Modbus registers; lowest byte in the first and highest in the second. Only the variable value is transmitted. The associated units of measure must be manually configured in the receiving Modbus device.
1 Flow 1 Rate (Input Register 30002 + 30003) 2 Flow 2 Rate (Input Register 30004 + 30005) 3 Flow 1 Total (Input Register 30006 + 30007) 4 Flow 2 Total (Input Register 30008 + 30009)
Modbus uses the following:
Data Bits = 8 Stop Bits = 1 Parity = None
Page 24 October 2017CTL-UM-01026-EN-05
name and ICON.
HyperTerminal display screen.
Programming

BACnet

The Series 3100 flow monitor can be configured to communicate on a BACnet RS485 MSTP (Master Slave Token Passing) system. Configuration is via the front panel keypad.
The following settings are required:
• Baud Rate: [9600, 19200, 38400 or 76800]. The recommended factory default is 9600.
• MSTP Address: [0…127]. Each device must have a unique address.
• MSTP MAX master: [0…127]. This range must be greater than the highest address on the network.
• Device Instance: [00000000…99999999]. This is a unique identifier for each device in the system.
Object Name I/O (Write/Read) Object Type Object ID Units
BACnet Address I/O Analog Value AV1
BACnet BaudRate I/O Multi-State MSV1 See Note 1
Flow 1 Rate O Analog Input AI1 Same as Displayed Flow 2 Rate O Analog Input AI2 Same as Displayed Flow 1 Total O Analog Input AI3 Same as Displayed Flow 2 Total O Analog Input AI4 Same as Displayed
Note 1: 0 = Auto, 1 = 9600, 2 = 19200, 3 = 38400, 4 = 76800 Note 2: The installer selects the units of measure from a list of pre-programmed units or creates custom units. BACnet
transmits in the same units as displayed on the front panel.
USB Communication
The Series 3100 flow monitor is ordered with an analog output option card. A five-pin USB connector is also included. As much as possible, the commands mimic the use of the front panel controls.
To use this feature, the following are required:
• PC with USB ports and Windows HyperTerminal or other communications software
• FTDI Virtual COM port drivers http://www.ftdichip.com/FTDrivers.htm
• USB 2.0 A to Mini-B 5-pin cable To communicate using HyperTerminal:
1. Make sure that the monitor has a Mini-B ve-pin connector on the back panel. The Series 3100 must have an analog output option card installed and be marked Series # 3100-1x.
2. Verify that the appropriate FTDI Virtual COM port drivers are installed on your computer.
3. Plug the USB 2.0 A end of the cable into a USB port on your computer. Plug the Mini-B ve-pin end into the back of the monitor.
Figure 2: Hyper terminal connection screens
Page 25 October 2017 CTL-UM-01026-EN-05
Programming
Figure 3: COM4 properties screen
4. Press ENTER. Both the Rx and Tx LEDs on the front of the Series 3100 ash once and the “Badger Meter DIC…Software Version…” text message appears.
5. The Series 3100 ow monitor is now communicating and ready to take commands from the list below.

USB Command List

In the list below, brackets indicate an argument, specifying its type and value range. For instance [0-18] stands for any number between 0 and 18 (inclusive).
Example
“display line1 = 1” sets Line 1 of the display to display #1, which is the totalizer for flow channel 1.
Diagnostics
id -- show model number & software version echo [on/off] -- turn on/off interactive command line: with echo off, this interface is more amenable to scripting; it still accepts the same commands. Any command entered without an “ = " sign and variable will display the current setting. Example: Typing “display line 1” returns “0” which is the variable for flow rate read flow [1-2] -- read the current flow on channel 1 or 2 in GPM read flow [1-2] total -- read the current total flow on channel 1 or 2 in gallons
comm mstpaddr = [0-127] -- BACnet/MSTP address comm maxmaster = [0-127] -- BACnet/MSTP max master address comm devinst = [x] -- BACnet device instance ID
comm mbslaveaddr = [0-255] -- Modbus slave address
Display Configuration
display line 1 = [0-1] -- set line 1 of the display display line 2 = [0-1] -- set line 2 of the display 0: flow 1 rate 1: flow 1 total 3: flow 2 total 4: flow 1+2 rate 5: flow 1+2 total 6: flow 1-2 rate 7: flow 1-2 total 8: flow 2-1 rate 9: flow 2-1 total
display urate = [0.1-10] -- set the update rate of the display, in seconds
Page 26 October 2017CTL-UM-01026-EN-05
Input Channel Configuration
flow [1-2] sensor type = [0-4] -- flow sensor type: 0: PulseDI, 1: PulseKFactor 2: PullupKFactor* 3: SineKFactor* 4: Analog* flow [1-2] sensor dical k = [x] -- DI-type flow sensor k flow [1-2] sensor dical off = [x] -- DI-type flow sensor offset flow [1-2] sensor kfact = [x] -- K factor for non-DI sensors flow [1-2] sensor analog units = [0-19] -- flow units for analog input flow [1-2] sensor analog range = [0-4] -- current range for analog input flow [1-2] sensor analog high = [x] -- flow rate @max current flow [1-2] sensor analog low = [x] -- flow rate @min current flow [1-2] sensor avg = [0-100] -- averaging "time constant", in seconds: flow [1-2] rate units = [0-19] -- flow (channel) rate units to display. 0: GPM 1: gal/s 2: gal/hr 3: Mgal/day 4: L/s 5: LPM 6: L/hr 7: ft3/s 8: ft3/min 9: ft3/hr 10:m3/s 11:m3/min 12:m3/hr 13:acreft/s 14:acreft/min 15:acreft/hr 16:bbl/s 17:bbl/min 18:bbl/hr 19:Custom flow [1-2] rate ndigits = [2-10] -- number of decimal places to show for flow rate flow [1-2] rate custom label = [string] -- set the label for custom units flow [1-2] rate custom conv = [0-100] -- conversion factor for custom units flow [1-2] total units = [0-7] -- set the totalizer units to display. 0: gal 1: Mgal 2: L 3: ft3 4: m3 5: acreft 6: bbl 7: Custom
Programming
Page 27 October 2017 CTL-UM-01026-EN-05
Programming
Relay Output Configuration
relay [1-5] func = [0-9] -- relay function; relay 5 is the pulse output 0: Totalizer 1: Alarm 2: Manual Control relay [1-5] input = [0-8] -- relay input; depends on source for totalizer: 0: Flow 1 Total 1: Flow 2 Rate 2: Flow Sum Rate 3: Flow 1-2 Rate Flow 2-1 Rate for alarms: 0: Flow 1 Rate 1: Flow 2 Rate 2: Flow Sum Rate 3: Flow 1-2 Rate 4: Flow 2-1 Rate relay [1-5] units = [0-19] -- units on setpoints/rates; depends on src/input flow units: same as 'flow [1-2] rate units' above volume units: same as 'flow [1-2] total units' relay [1-5] manual = [on/off] -- manually set relay on or off, if in manual mode relay [1-5] rate = [x] -- totalizer rate relay [1-5] ctime = [0-10000] -- pulse width in milliseconds relay [1-4] latch = [on/off] -- turn on/off relay latching relay [1-4] setpoint = [x] relay [1-4] setpoint = [x] relay [1-4] relpoint = [x] relay [1-4] setdelay = [x]
relay [1-4] reldelay = [x]
Analog Output Configuration
analogout [1-2] func = [0-3] 0: Flow rate 3: PID control analogout [1-2] src = [0-4] for flow rate: 0: Flow 1 rate 1: Flow 2 Rate 2: Flow sum 3: Flow 1-2 4: Flow 2-1 for PID control: 0: Flow 1 rate 1: Flow 2 rate analogout [1-2] range = [0-1] 0: 0-20mA 1: 4-20mA analogout [1-2] low = [x] -- value corresponding to 0 (or 4) mA analogout [1-2] high = [x] -- value corresponding to 20mA analogout [1-2] setpoint = [x] -- PID setpoint analogout [1-2] P = [x] -- PID constants analogout [1-2] I = [x] -- PID constants analogout [1-2] D = [x] -- PID constants
Page 28 October 2017CTL-UM-01026-EN-05

TROUBLESHOOTING

Trouble Codes

1 Relay 1 totalizer rate exceeded 2 Relay 2 rate exceeded 3 Relay 3 rate exceeded 4 Relay 4 rate exceeded 5 Pulse out rate exceeded 20 Error reading EEPROM on faceplate 21 Error writing EEPROM 22 Analog Input card missing 24 Temperature Input card missing 25 Invalid flow units configured 26 Invalid volume units configured 27 Bad input frequency 29 Internal error calculating flow rate 31 Error reading from analog input AD converter channel 1 32 Error reading from analog input AD converter channel 2 36 Error writing to analog input AD converter channel 1 37 Error writing to analog input AD converter channel 2 50 Error reading I2C address 0 (relays, buttons, and LEDs) 51 Error writing to I2C address 0 52 Error reading I2C address 1 (analog input card control lines) 53 Error writing I2C address 1 54 Error reading I2C address 2 (temperature input card control lines) 55 Error writing I2C address 2 71 Watchdog timer reset occurred 82 Fatal error initializing EEPROM
Troubleshooting
Page 29 October 2017 CTL-UM-01026-EN-05
Specications

SPECIFICATIONS

Voltage 12…24V DC/AC (limit: 8…35V DC); (limit: 8…28V AC)
Display 16 character by two line alphanumeric Dot Matrix 3/8 in. (7.95 mm) high backlit LCD Operating Temperature –4…158° F (–20…70° C) Storage Temperature –22…176° F (–30…80° C) Dimensions Panel Mount: 3.78 in. W × 3.78 in. H × 4.79 in. D (96 mm × 96 mm × 122 mm) Weight Panel Mount: 12 oz. Pulse and Relays Both pulse and relay are fully functional as either totalizing or setpoint outputs Pulse Electrical 1 Amp at 35V DC/30V AC Closed: 0.5 Ω at 1 amp; Open: >108 Ω
Relay Electrical
Pulse/Unit Volume (Totalizer)
Set-Point (Alarm)
Analog Output Driving Source: flow rate
USB Communication
RS485 Communication Supports Modbus and BACnet/MSTP Accessories Programming kit
Resistive Load:
5A @ 120V AC/30V DC
Driving Source: flow total
Driving Source: flow rate,
Btu rate, temperature 1, temperature 2, delta T
Delay to Set: 1 to 9999 sec
Provides complete access to all programming and operation features
Inductive Load: 1A @ 120V AC/30V DC
Rate: 1 pulse per 1.0000000 to 99999999 units
Units: Any predefined or custom unit
Release Point: 1.0000000 to 999999999
Range: 4…20 mA; 0…20 mA (isolated current sinking or sourcing)
DC current draw (~ 280 mA) AC Power rating (~5 VA)
Contact Time: 1 to 9999 mS
Set-Point: 1.0000000 to 999999999
Delay to Release: 1 to 9999 sec
Sinking: 30V DS @ 0 mA max;
3 V @ 20 mA min
Sourcing: 600 Ω max load Requirements: USB 2.0 A to Mini-B,
five-pin cable
Flow Sensor Inputs
Type Threshold Signal Limit Frequency Pullup Impedance Aux. Power Calibration
Pulse-Di 2.5V DC 30V DC 0.4 Hz to 10 kHz 1K to 12V DC 12V DC@30 mA K + Offset
Pulse-K Factor 2.5V DC 30V DC 0.4 Hz to 10 kHz 12V DC@30 mA Pulse/Gal
Pullup K Factor 2.5V DC 30V DC 0.4 Hz to 10 kHz 1K to 12V DC 12V DC@30 mA Pulse/Gal
Sine-K Factor 30V DC 0.4 Hz to 10 kHz 10K Ω 12V DC@30 mA Pulse/Gal
Analog - 4…20 mA 50 mA Fused 100 Ω 12V DC@30 mA Linear
Analog - 0…20 mA 50 mA Fused 100 Ω 12V DC@30 mA Linear
Analog - 0…1V DC 30V DC 100K Ω 12V DC@30 mA Linear
Analog - 0…5V DC 30V DC 100K Ω 12V DC@30 mA Linear
Analog - 0…10V DC 30V DC 100K Ω 12V DC@30 mA Linear
Rate Units of Measure: GPM; gal/sec; gal/hr; Mgal/day; LPS; LPM; LPH; ft3/Sec; ft3/min; ft3/hr;m3/sec;
m3/min; m3/hr; acre-ft/sec; acre-ft/min; acre-ft/hr; bbl/sec; bbl/min; bbl/hr; and field programmed custom units 0.00 to 999999999
Total Units: gallons; Mgal; liters; ft3; m3; acre-ft; bbl; and field programmed custom units 0.00 to 999999999
Page 30 October 2017CTL-UM-01026-EN-05

ORDERING MATRIX

Series 3100 Flow Monitor Ordering Matrix
Example: 3100 1 0
Series Flow Monitor 3100
Power Supply
Mounting Panel Mount 0
Low Voltage 0
12…24V AC/VDC
High Voltage 1
120/240V AC
Figure 4: Ordering matrix
Ordering Matrix
Page 31 October 2017 CTL-UM-01026-EN-05
Industrial Flow Monitor, Series 3100
Control. Manage. Optimize.
DATA INDUSTRIAL is a regisitered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2017 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Eastern Europe Branch Oce (for Poland, Latvia, Lithuania, Estonia, Ukraine, Belarus) | Badger Meter Europe | ul. Korfantego 6 | 44-193 Knurów | Poland | +48-32-236-8787 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 941700-0031-EN
Loading...