Badger Meter 3000-00, 3020-00, 3000-10, 3020-10, 3000-01 User Manual

...
Industrial Flow Monitor
Series 3000
DSY-UM-01667-EN-05 (April 2017)
User Manual
Industrial Flow Monitor, Series 3000
CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Unpacking & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Programming the Series 3000 Flow monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Output Option Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Display and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Selection Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Option List Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Data Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Programming Flowchart—Software Version 1.2.29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Flow Inputs Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Flow Inputs Flowchart (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Relays & Pulse Outputs Flowchart (Manual, Set-Point Rate and Pulse/Volume). . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Analog Output Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
RS485 Communication Port Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RS485 COM Port Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
BACnet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
USB Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
USB Command List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Input Channel Conguration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Ordering Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Page ii April 2017DSY-UM-01667-EN-05
Introduction
INTRODUCTION
The Badger Meter® Data Industrial® Series 3000 flow monitor is an economical, full featured, digital flow monitor. The two-line × 16-character alphanumeric display can be configured by the user to display flow rate and flow total. The panel
meter has a NEMA 4X rated front panel and conforms to DIN Standard dimensions, 96 mm × 96 mm, for meter sizes and panel cutouts. An optional NEMA 4 wall mount is also available.
The Series 3000 flow monitor accepts pulse, sine wave or linear analog input signals. Like all Data Industrial flow monitors, the Series 3000 flow monitor may be field calibrated by the user. For Data Industrial sensors “K” and “offset” numbers are entered, while other pulse or frequency output sensors may use a K-factor only. Analog inputs are fully programmable for slope and intercept.
SAFETY INFORMATION
The installation of the flow monitor must comply with all applicable federal, state, and local rules, regulations, and codes. Failure to read and follow these instructions can lead to misapplication or misuse of the flow monitor, resulting in personal
injury and damage to equipment.
UNPACKING & INSPECTION
Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:N If damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
PROGRAMMING THE SERIES 3000 FLOW MONITOR
Programming is menu driven. All data is entered using the LCD/keypad interface. A password gate is included to prevent unauthorized access to programming parameters. Programming flexibility is extended to units of measure. In addition to several factory units of measure, the Series 3000 flow monitor software permits the custom units for rate and total to be created by the installer.
The Series 3000 flow monitor provides one Form C solid-state relay, and one solid-state switch output. Both are fully programmable as either pulse/volume, or setpoint control. For pulse output, the installer can program both the resolution and the pulse width. Setpoint control is extremely versatile with fully independent set and release points, each with its own time delay.
Options
• Analog output
• Analog input
• Single flow channel input
• One control relay output
• One programmable pulse output
• Low voltage AC/DC supply
• USB
• RS485 w\BACnet™ or Modbus® protocols
• Wall mounting
Page 3 April 2017 DSY-UM-01667-EN-05
Installation
INSTALLATION
Mechanical
The Series 3000 flow monitor can be either panel mounted or wall mounted.
Location
In any mounting arrangement the primary concern is easy viewing and convenient operation of the keypad. The unit generates very little heat, so no consideration need be given to cooling or ventilation. However, prolonged direct sunlight can damage the front panel so some level of shading is recommended, especially if installed in a tropical climate.
Panel Mount Installation
The Series 3000 panel mount flow monitor is designed for through-panel mounting, which allows access to the back of the unit. The flow monitor is secured to the panel by two draw brackets shown in Figure 1. See Figure 2 for flow monitor and panel cutout dimensions.
3.78 in.
(96 mm)
3.49 in.
(88.7 mm)
TOP
Figure 1: Panel mounting
3.23 in.
(82 mm)
3.78 in.
(96 mm)
2.21 in.
(56 mm)
Figure 2: Physical dimensions and panel cutout
SIDE
3.57…3.60 in.
(90.6…91.4 mm)
PANEL
CUTOUT
3.49 in.
(88.7 mm)
3.57…3.60 in.
(90.6…91.4 mm)
Page 4 April 2017DSY-UM-01667-EN-05
Installation
Wall Mount Installation
The Series 3000 wall mount flow monitor is designed to mount onto a wall with four bolts or screws. The mounting hole pattern and box dimensions for the Series 3000 NEMA4 wall mount are shown in Figure 3.
4.33 in.
(110 mm)
1/8 in.
3.54 in.
(3.2 mm)
(90 mm)
WALL
MOUNTING TEMPLATE
4.80 in.
(122 mm)
Figure 3: Wall mount and dimensions
4.72 in.
(120 mm)
3.62 in.
(92 mm)
SIDE
Page 5 April 2017 DSY-UM-01667-EN-05
Installation
Electrical Installation
Power Supply Wiring
The Series 3000 flow monitor requires 12…24V DC/AC to operate. See "Specifications" on page 24 for DC current draw and AC Volt-Amp requirements.
Always use a fused circuit. Connect the positive of the power supply to the flow monitor terminal marked (ACL/DC+), and connect the negative of the power supply to the flow monitor terminal marked (ACC/DC-).
If a Badger Meter Data Industrial plugin power supply (Model A-1028) is being used, connect the black-white wire to the terminal marked (ACL/DC+) and the black wire to the terminal marked (ACC/DC-).
Ground wire should be heavy gauge and as short as possible.
(+) (-)
12 . . . 24V DC
Power
Supply
Figure 4: Power supply wiring
or
(Line) (Com)
12 . . . 24V AC
Power
Supply
Earth
or
Panel
Ground
POWER
Earth LV AC/DC (-) LV AC/DC (+)
3 2 1
Flow Sensor Wiring
The Series 3000 flow sensor inputs are extremely versatile, designed to accept either two-wire or three-wire pulse inputs (Data Industrial 200 Series, 4000 Series) or Analog inputs. Although different rear panel terminals are used, all parameters are set with the LCD/keypad interface. There are no internal or external jumpers, switches or potentiometers to move or adjust.
The following pulse input types are accommodated:
• Pulse DI: Used for all Badger Meter Data Industrial Flow Sensors. Provides an internal pullup resistor and uses and Offset values for calibration.
• Pulse K-Factor: Accepts non zero-crossing inputs but provides no internal pullup, classical K ( pulses/gallon) values for calibration.
• Pullup K-Factor: Provides an internal pullup resistor and uses classical K (pulses/gallon) values for calibration.
OTE:N All the above pulse input types wire the same as shown in Figure 5 on page 7. See "Programming Flowchart—
Software Version 1.2.29" on page 13 for required input configuration.
Page 6 April 2017DSY-UM-01667-EN-05
Installation
1 ANALOG IN+ 2 ANALOG IN­3 SHIELD 4 SENSOR IN 5 GND 6 SHIELD 7 SENSOR PWR
Figure 5: Data industrial flow sensor wiring examples (two- and three-wire pulse types)
Analog Input
As an alternative to the pulse inputs, the Series 3000 flow monitor can accept an Analog input. The input is non-isolated, but can accept 0…1V DC, 0…5V DC, 0…10V DC, 0…20 mA and 4…20 mA with both factory-defined and custom units of measure.
Low impedance 100 Ohm input for current inputs optimizes performance and flexibility or loop power supplies. Both the low-end and high-end scaling are independent and field configured by the installer.
OTE:N See "Programming Flowchart—Software Version 1.2.29" on page 13 for required input configuration.
1 ANALOG IN+ 2 ANALOG IN­3 SHIELD 4 SENSOR IN 5 GND 6 SHIELD 7 SENSOR PWR
Figure 6: 4…20 mA analog loop powered wiring
1 ANALOG IN+ 2 ANALOG IN­3 SHIELD 4 SENSOR IN 5 GND 6 SHIELD 7 SENSOR PWR
Figure 7: Voltage or current sourcing analog inputs
Page 7 April 2017 DSY-UM-01667-EN-05
Installation
Solid-State Switch and Form C Output Wiring
The Series 3000 flow monitor has one Normally Open (N.O.) solid-state switch, and one solid-state form “C” relay. See
"Specifications" on page 24 for maximum voltage and current ratings for each type output.
These outputs are completely independent, electrically isolated, and can be programmed as either Pulse or Set Point outputs. When the “Totalizer” function is selected, the unit of measure and resolution are independent from the displayed units and
can be programmed where one pulse occurs once every 0000000.1 to 999999999. of units selected, with any pulse width from 0001 to 9999 mS.
When the “Alarm” is selected as the unit of measure and the resolution is independent from the displayed units, it allows the unit to be programmed as either a high or low rate Set Point. Since the Set Point, Release Point and their associated time delays are fully independent, this output can be either a classical high rate or low rate alarm, depending on the settings selected. When design planning, keep in mind that although both of these outputs can be programmed as alarm points only, the relay provides both N.O. and N.C. contacts. The switch is a simple N.O. contact.
Examples:
High Flow Set Point
The Set Point must be a value greater than the Release Point. The relay output will have continuity between its N.C. terminal and “COM” until the flow has exceeded the Set Point (“SETPT”)
for a continuous period of time exceeding the Set Point Delay (“SDLY”), at which time the N.C. connection will open and the N.O. contact will have continuity to the “COM” terminal. When the flow has dropped below the Release Point (“RELP") for a continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satised.
Low Flow Set Point
The Set Point must be a value less than the Release Point. The relay output will have continuity between its N.C. terminal and “COM” until the flow has dropped below the Set Point
(“SETPT”) for a continuous period of time exceeding the Set Point Delay(“SDLY”), at which time the N.C. connection will open and the N.O. contact will have continuity to the “COM” terminal. When the flow has again risen above the Release Point (“RELP”) for a continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satised.
Figure 8: Relay and switch wiring examples
Page 8 April 2017DSY-UM-01667-EN-05
1 RELAY 1 NO 2 RELAY 1 NC 3 RELAY 1 COM 4 PULSE 1 OUT 5 PULSE 2 OUT
1 RELAY 1 NO 2 RELAY 1 NC 3 RELAY 1 COM 4 PULSE 1 OUT 5 PULSE 2 OUT
Figure 9: Relay and switch wiring examples (continued)
High Flow Shutdown and Normally Open Master Valve with Indication
1 RELAY 1 NO 2 RELAY 1 NC 3 RELAY 1 COM 4 PULSE 1 OUT 5 PULSE 2 OUT
Installation
High Flow Shutdown and Irrigation Clock Normally Closed Master Valve with Indication Program as High Flow with Latch
Figure 10: Relay and switch wiring examples (continued)
Page 9 April 2017 DSY-UM-01667-EN-05
Output Option Card
OUTPUT OPTION CARD
If the Series 3000 flow monitor was ordered with the Output Option card, it will have these additional outputs:
• Analog Output (0…20 mA; or 4…20 mA), which can be converted externally to 0…5V DC, 1…5V DC with a 250 Ohm resistor, or 0…10V DC or 2…10V DC with a 500 Ohm resistor. A 15V DC power supply is provided to permit current sinking or sourcing. The Series 3000 flow monitor has special software that permits the analog output.
• USB for direct access to a computer using a standard mini-USB cable.
• RS485 for fully addressable Modbus or BACnet communication.
+
1 RS485 B 2 RS485 A 3 RS485 GND 4 LOOP + 5 LOOP ­6 GND
-
Figure 11: Current sourcing analog output
1 RS485 B 2 RS485 A 3 RS485 GND 4 LOOP + 5 LOOP ­6 GND
Figure 12: Current sinking analog output
1 RS485 B 2 RS485 A 3 RS485 GND 4 LOOP + 5 LOOP ­6 GND
USB Port
To communicate using the USB port requires Windows® HyperTerminal or other similar communications software. This port is part of the Analog Output Option card. See "Communication" on page 19 for instructions on how to use this port.
Page 10 April 2017DSY-UM-01667-EN-05
Figure 13: Analog output wiring
Display and Keypad
DISPLAY AND KEYPAD
The Series 3000 flow monitor has a two line by 16-character display with two modes of operation and 5 keys on the front panel for programming.
Menu
Enter
1-Switch to main menu 2-Backward/Previous menu 1-Save value
2-Forward/Next menu
Up Arrow
Down Arrow
Right Arrow
1-Select Menu option 2-Increase numerical value
1-Select Menu option 2-Decrease numerical value
1-Select Menu option 2-Move cursor to the right
When the Series 3000 flow monitor is first powered up, it runs through internal self checks while displaying “Badger Meter DIC Initializing." At the end of this cycle its normal mode display will appear.
In the normal mode, if still using the factory defaults, flow rate will be displayed on the top line, and flow total displayed on the bottom. Both lines can be custom-defined in the field as desired. In the normal mode the Enter key has no function.
0.0 GPM
0.0 gal
Menu Enter
Figure 14: Normal mode display
The other mode is the program mode, used to configure the unit. Press Menu to enter and exit this mode. See "Programming
Flowchart—Software Version 1.2.29" on page 13.
RESET SETUP DIAG
Menu Enter
Figure 15: Program mode display
Page 11 April 2017 DSY-UM-01667-EN-05
FLOW1
Flow 1 units
Programming
PROGRAMMING
With the normal mode display showing, press Menu to enter the programming mode. In this mode, the three arrow keys () are used on the selection screens to select the option displayed above the key, and on the option list screens to scroll up or down a list of choices, like a pull-down menu. Most screens presenting choices show three choices, one for each arrow key. When the number of choices exceeds three, a small arrow () appears on the upper right side of the display indicating there are more choices on that level. Press Enter to toggle to the next set of choices. Once the selection has been made, press
Enter to complete the selection. Press Menu again to return to the normal mode display.
Selection Screens
Most selection screens show three choices, one for each arrow () key. When the number of choices exceeds three, a small arrow ( ) appears on the upper right side of the display indicating there are more choices on that level. Press Enter to view the next set of choices.
For example, pressing Menu from the normal mode screen shows the RESET SETUP DIAG screen. Pressing the key brings up the reset screens. The key brings up the setup screens and the key brings up the diagnostic screens. If thekey is pressed, the screen would appear as follows.
SETUP PWORD DSPY
Menu Enter
Figure 16: Selection screen
Option List Screens
Units of measure is an example of an options list screen. Pressing the key scrolls up the list while the key scrolls down through the list. In this case starting with GPM; gal/s; gal/
hr;…LPM;….ending in a selection of custom units. Pressing Enter completes the selection. Pressing Menu leaves the selection unchanged. The key has no function on this
type of screen.
GPM
Menu Enter
Figure 17: Option list screen
Data Screens
Some screens are data entry screens. For example, Set Points or Custom Units screens. When a data entry screen is first displayed, the current value will be displayed. The cursor will be flashing the most left hand
digit. Pressing the key will increase the value. The key will reduce it. If the cursor is flashing the decimal point, pressing thekey will move the decimal point to the right, pressing the key will move the decimal to the left.
Page 12 April 2017DSY-UM-01667-EN-05
Setpoint
1.00000000
Menu Enter
Figure 18: Data screen
Programming Flowchart—Software Version 1.2.29
ommunications
RESET SETUP DIAG
Programming
Require setup PW YES [NO]
RESET FLOW1
Reset ow 1? OK CANCEL
Reset ow 1? Reset
Password setup ENAB SETUP RESET
Set Up password 0000
Enter password 0000
SETUP
PWORD DSPY FLOW1
Reset password 0000
Go to
Flow
Inputs
DIAG MODL# SER# REV#
Model #: 300010
Relays & Pulse
Serial #: 004620
SETUP RLY1 PULSE
Go to
Outputs
DIAG ERROR
Firmware rev: v1.2.29
Error codes 000 000 000 000
SETUP AOUT1 COMM
Go to
Analog
Out
LINE1 Flow 1 Rate Flow 1 Total
Display LINE1 LINE2 RATE
LINE2 Flow 1 Rate Flow 1 Total
Go to RS485
C
Port
Update rate +0.50000000 sec
Page 13 April 2017 DSY-UM-01667-EN-05
Programming
Flow Inputs Flowchart
Flow 1 setup
RATE TOTAL SENSR
Flow X rate
UNITS #.DIG CUST
Flow 1 # digits
0 1 2
Flow X units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Custom units
LABEL CONV
1 unit =
+0.00000001 gpm . . .
999999999.
Flow X total
UNITS #.DIG CUST
Total X units
gal Mgal L ft3 m3 acre-ft bbl Custom units
Total 1 # digits
Custom units
LABEL CONV
0 1 2
Enable password? YES [NO]
Enable password? [YES] NO
1 UNIT =
+0.00000001 gal . . .
999999999.
Flow X total
RESET
Reset BTU total
PASSWD RESET
Reset total NOW? OK CANCEL
Unit label
? > = < ; : 9999999999 8888888888 . . . 1 0000000000 / .
­, + * ) ( ' & % $ " !
Continued at A on next page.
{ z y x . . .
c b a ` _ ^ ] ¥ [ ZZZZZZZZZZ Y X . . . J BBBBBBBBBB AAAAAAAAA
Page 14 April 2017DSY-UM-01667-EN-05
Flow Inputs Flowchart (continued)
Continued
A
from previous page.
Sensor 1 type
Flow 1 sensor
TYPE xxxxxxxx
Flow 1 sensor
Pulse DI
TYPE AVG DICAL
Programming
DI Sensor Cal. KNUM OFFSET
Pulse K-Factor
Pullup K-Factor
Sine K-Factor
Analog
Flow x units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Flow 1 sensor
TYPE AVG KFACT
Flow 1 sensor
TYPE ANALOG
Analog ow 1
UNITS RANGE HIGH
Analog x range
0 to 1V 0 to 5V 0 to 10V 0 to 20 mA 4 to 20 mA
Max reading = ?
0.00000001
999999999.
Flow 1 timeconst +0.00000001 sec . . .
100.000000
Flow 1 timeconst +0.00000001 sec . . .
100.000000
Analog ow 1
LOW CAL
Min reading = ?
0.00000001 . . .
999999999.
Sampling XXXXXXXXXXXX
DI sensor K num
1.00000000 . . .
999999999.
K-Factor
1.00000000 . . .
999999999.
0V = xxxx Read Factory
1V = xxxx Read Factory
5V = xxxx Read Factory
10V = xxxx Read Factory
. .
4 mA = xxxx
.
Read Factory
20 mA = xxxx Read Factory
DI Sensor Ost
-999999999. . . .
-0.00000001
+0.00000001
. .
+999999999.
Page 15 April 2017 DSY-UM-01667-EN-05
Programming
Relays & Pulse Outputs Flowchart (Manual, Set-Point Rate and Pulse/Volume)
SETUP
RLY1 Pulse
Relay 1 (or Pulse) FUNC xxxxx xxxxx
Manual Control
Relay 1 (or Pulse) FUNC MANUAL
Totalizer
Alarm
Relay 1 (or Pulse) FUNC INPUT UNITS
Relay 1 input (or Pulse)
Flow 1 Rate
Set point units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Relay 1 (or Pulse) LATCH SETPT RELP
Relay 1 Latch?
ON [OFF]
Relay 1 (or Pulse) FUNC INPUT UNITS
Totalizer input
Flow 1 Total
Set point
-0.00000001
+999999999.
Release point
. . .
Pulse rate units
gal Mgal L ft3 m3 acre-ft bbl Custom units
-0.00000001
+999999999.
. . .
Relay 1 (or Pulse) Rate CTIME
1 pulse = ?
0.00000001 . . .
999999999.
Relay 1 (or Pulse) SDLY RDLY
Trigger delay
0000000 S
10000000 S
Time closed
Release delay
. . .
10000000 S
0001 mS
9999 mS
0000000 S
Relay 1 (or Pulse) ON [OFF]
Relay 1 (or Pulse) [ON] OFF
. . .
. . .
Page 16 April 2017DSY-UM-01667-EN-05
Analog Output Flowchart
SETUP
AOUT1 COMM
Analog output 1
FUNC RANGE SCR
Analog function
Flow Rate
Analog output 1
FUNC RANGE SCR
Analog output 1
UNITS LOW HIGH
Programming
Analog output 1
CAL
PID
Analog output 1
FUNC RANGE SCR
Analog output range
0 to 20 mA 4 to 20 mA
Drive source
Flow 1 Rate
Analog output range
0-20 mA 4-20 mA
Analog output 1
UNITS SETPT P
Flow x units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
Drive source
Flow 1 Rate
PID Set point
-0.00000000
+999.99999
Analog 1 units
GPM gal/s gal/hr Mgal/day L/s LPM L/hr ft3/s ft3/min ft3/hr m3/s m3/min m3/hr acre-ft/s acre-ft/min acre-ft/hr bbl/s bbl/min bbl/hr Custom units
PID P const
+000.000
+999.000
. . .
PID I const
+000.0000 . . .
+999.9999
0 mA = ?
0.0000000
Analog output 1
I D LOW
PID D const
+000.000 . . .
. . .
+999.000
20 mA = ?
0.0000000
4 mA = ?
+000.0000
+999.9999
Adjust 4 mA
12107 FACTRY
Analog output 1
HIGH
20 mA = ?
+000.0000 . . .
+999.9999
Adjust 4 mA
12107 FACTRY
. . .
Adjust 20 mA
60748 FACTRY
Analog output 1
CAL
Adjust 20 mA
60748 FACTRY
Page 17 April 2017 DSY-UM-01667-EN-05
Programming
RS485 Communication Port Flowchart
Comm NET BAUD ADDR
Network
Disable
MODBUS
BACnet/MSTP
Comm
NET
Comm
NET BAUD ADDR
Network
MODBUS
Comm
NET BAUD ADDR MAX DEVID
Baud Rate
300 1200 2400 9600
19200 38400 76800
MODBUS Address
001
. . .
255
Network
BACnet/MSTP
Page 18 April 2017DSY-UM-01667-EN-05
Baud Rate
Auto
9600 19200 38400 76800
MSTP Address
001
127
MSTP Max master
. . .
001
127
Device Instance
. . .
00000000
. . .
99999999
Programming
Communication
RS485 COM Port Configuration
The RS485 is very simple to configure.
1. Select the communications type: Modbus or BACnet.
2. Choose the BAUD Rate: Auto, 300, 1200, 2400, 9600, 19200, 38400, or 76800 to match the rest of the devices on the network. The factory default of 9600 is recommended for most systems. The lower the baud rates have greater stability, and greater tolerance of wiring and other hardware issues.
3. Congure the Modbus or BACnet are described in there respective sections.
Modbus
Network: RS485 Baud Rate: Selectable Protocol: RTU or ASCII Addresses: 001 to 248 Slave only Read Input Registers 30001- 39999 (Function “04”) Data Type: IEEE 754 Float (ABCD – CDAB) Each variable is stored in two Modbus registers; lowest byte in the first and highest in the second. Only the variable value is transmitted. The associated units of measure must be manually configured in the receiving Modbus device. Flow 1 Rate (Input Register 30002 + 30003)
Flow 1 Total (Input Register 30006 + 30007)
Modbus uses the following:
Data Bits = 8 Stop Bits = 1 Parity = None
BACnet
The Series 3000 can be configured to communicate on a BACnet RS485 MSTP (Master Slave Token Passing) system. Configuration is via the front panel keypad.
The following settings are required
• Baud Rate: [9600; 19200; 38400; or 76800]. The recommended factory default is 9600.
• MSTP Address: [0…127]. Each device must have a unique address.
• MSTP MAX master: [0…127]. This range must be greater than the highest address on the network.
• Device Instance: [00000000…99999999]. This is a unique identifier for each device in the system.
Object Name I/O (Write/Read) Object Type Object ID Units
BACnet Address I/O Analog Value AV1
BACnet BaudRate I/O Multi-State MSV1 See Note 1
Flow 1 Rate O Analog Input AI1 Same as Displayed
Flow 1 Total O Analog Input AI3 Same as Displayed
Note 1: 0 = Auto, 1 = 9600, 2 = 19200, 3 = 38400, 4 = 76800 Note 2: Units of measure are selected by installer from a list of pre-programmed units, or as custom units created by the
installer. BACnet will transmit in the same units as displayed on the flow meter's front panel LCD.
Page 19 April 2017 DSY-UM-01667-EN-05
Programming
USB Communication
If the Series 3000 flow monitor is ordered with an analog output option card, a five-pin USB connector is also included. As much as possible the commands mimic the use of the front panel controls.
To use this feature the following are required.
• PC with USB ports and Windows HyperTerminal or other communications software
• FTDI Virtual COM port drivers http://www.ftdichip.com/FTDrivers.htm
• USB 2.0 A to Mini-B 5-pin cable To communicate using HyperTerminal, use the following procedure.
1. Make sure that the Series 3000 ow monitor has a Mini-B ve-pin connector on the back panel. (The Series 3000 flow monitor must have an analog output option card installed and will be marked Series # 3000-1x.)
2. Be sure the appropriate FTDI Virtual COM port drivers are installed on you computer.
3. Plug the USB 2.0 A end of the cable into an available USB port on your computer. Plug the Mini-B five-pin end into the back of the Series 3000 flow monitor.
4. Run HyperTerminal (from the Windows Start Menu) and create a new connection, with a name and icon.
Page 20 April 2017DSY-UM-01667-EN-05
Programming
5. Congure this port with 38400 baud, 8 data bits, 1 stop bit, no parity and no ow control.
6. When connected, a ">" symbol will appear in the upper left corner of the main HyperTerminal display screen. Press Enter. Both the Rx and Tx LEDs on the front of the Series 3000 ow monitor ash once, and the “Badger Meter DIC … Software Version…” text message appears.
The Series 3000 flow monitor is now communicating, ready to take commands from the list below.
Page 21 April 2017 DSY-UM-01667-EN-05
Programming
USB Command List
In the list below, brackets indicate an argument, specifying its type and value range. For instance, [0-18] stands for any number between 0 and 18 (inclusive).
Example: “display line1 = 1” sets Line 1 of the display to display #1, which happens to be the totalizer for flow channel 1.
Diagnostics
id – show model number & software version echo [on/off] – turn on/off interactive command line: with echo off, this interface is more amenable to scripting; it still accepts the same commands. Any command entered without an “ = “ sign and variable will display the current setting. Example: Typing “display line1” returns “0” which is the variable for Flow Rate.
read flow [1-2] – read the current flow on channel 1 or 2 in GPM. read flow [1-2] total – read the current total flow on channel 1 or 2 in gallons.
Display Configuration
display line1 = [0-1] – set line 1 of the display display line2 = [0-1] – set line 2 of the display 0: flow 1 rate 1: flow 1 total display urate = [0.1-10] – set the update rate of the
display, in seconds
Input Channel Configuration
flow [1-2] sensor type = [0-4] – flow sensor type: 0: PulseDI, 1: PulseKFactor, 2: PullupKFactor 3: Analog flow [1-2] sensor dical k = [x] – DI-type flow sensor k flow [1-2] sensor dical off = [x] – DI-type flow sensor offset flow [1-2] sensor kfact = [x] – K factor for non-DI sensors flow [1-2] sensor analog units = [0-19] – flow units for analog input flow [1-2] sensor analog range = [0-4] – current range for analog input flow [1-2] sensor analog high = [x] – flow rate @max current flow [1-2] sensor analog low = [x] – flow rate @min current flow [1-2] sensor avg = [0-100] – averaging "time constant," in seconds: flow [1-2] rate units = [0-19] – flow (channel) rate units to display. 0: GPM 1: gal/s 2: gal/hr 3: Mgal/day 4: L/s 5: LPM 6: L/hr 7: ft3/s
Page 22 April 2017DSY-UM-01667-EN-05
8: ft3/min 9: ft3/hr 10: m3/s 11: m3/min 12: m3/hr 13: acreft/s 14: acreft/min 15: acreft/hr 16: bbl/s 17: bbl/min 18: bbl/hr 19: Custom flow [1-2] rate ndigits = [2-10] – number of decimal places to show for flow rate flow [1-2] rate custom label = [string] – set the label for custom units flow [1-2] rate custom conv = [0-100] – conversion factor for custom units flow [1-2] total units = [0-7] – set the totalizer units to display 0: gal 1: Mgal 2: L 3: ft3 4: m3 5: acreft 6: bbl 7: Custom
Programming
Page 23 April 2017 DSY-UM-01667-EN-05
Wall Mount 1
Industrial Flow Monitor, Series 3000
SPECIFICATIONS
Voltage 12…24V DC / AC (Limit: 8…35V DC) (Limit: 8…28V AC)
DC current draw (~280 mA) AC power rating (~5V A)
Display 16 character by two line alphanumeric dot matrix 7.95 mm high backlit LCD
Operating Temperature –20…70° C
Storage Temperature –30…80° C
Dimensions
Panel mount:
3.78 in. W × 3.78 in. H × 3.23 in. D (96 mm × 96 mm × 63 mm)
Wall mount:
4.80 in. W × 4.72 in. H × 3.63 in. D (120 mm × 120 mm × 92 mm)
Weight Panel mount: 12 oz
Pulse and Relays Both pulse and relay are fully functional as either totalizing or setpoint outputs
Pulse Electrical Solid-state Form A
Relay Electrical Mechanical Form C
Pulse/Unit Volume (Totalizer)
Driving source:
Flow total; Btu total
Driving source:
flow rate; Btu rate; temperature 1;
Setpoint (Alarm)
temperature 2, delta T
Delay to set: 1…9999 Seconds
Optional Analog Output
USB Communication
Driving source:
Flow rate; PID control
Provides complete access to all programming and operation features Requirements: USB 2.0 A to Mini-B 5-Pin Cable (Example: SYSONIC model UAM56 GWT/B)
1 Amp @ 35V DC/ 30V AC
Closed: 0.5 Ω @ 1 AMP Open: >108 Ω
Resistive load: 5Amp
@ 120V AC/30V DC
Units: Any predefined or custom unit
Units: Any predefined or custom unit
Release point:
1.0000000…999999999
Range:
4…20 mA; 0…20 mA (isolated current sinking or sourcing)
Inductive load: 1Amp @ 120V AC/30V DC
Rate:
Pulse per
1.0000000…99999999 units
Setpoint: Pulse per 1.0000000…99999999 units
Delay to release: 1…9999 seconds
Sinking: 30V DC @ 0 mA maximum; 3V @ 20 mA minimum
Sourcing: 600 W maximum load
RS-485 Communication Supports Modbus and BACnet/MSTP
Accessories Wall mount kit
Contact time:
1…9999 mS
Max Pulse Rate: 1 Pulse/2 Sec
ORDERING MATRIX
Series
Option - Analog Output, RS485 (BACnet / Modbus), and USB
Option - Mounting
Control. Manage. Optimize.
DATA INDUSTRIAL is a regisitered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2017 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, C zech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 941700-0022
Flow Monitor 3000 Portable Battery Operated Kit 3020
No Option 0 Analog Output, RS485 with BACnet and Modbus, and USB 1
Panel Mount 0
Example: 3000 - x x
Loading...