Badger Meter 3000 Specifications

Industrial Flow Monitor
Series 3000
DESCRIPTION
The Badger Meter® Series 3000 flow monitor is an economical, full-featured, compact unit designed for flow measurement applications and general hydronic thermal transfer systems.
A two line by 16-character 3/8 in. (9.5 mm) high backlit LCD display is configured by the user to display flow rate, flow total. In addition to many pre-programmed units of measure, many custom units can be created during field setup.
The flow sensor input features flexible scaling options and signal type selections that permit the use of most Badger Meter sensors, or other frequency sine/pulse or linear analog devices.
DIMENSIONS
3.78 in.
(96 mm)
3.23 in.
(82 mm)
OPTIONS
NEMA 4X panel mount conforms to DIN standard 96 mm x 96 mm for meter size and cutouts. NEMA 4X wall mount is available as an option.
FEATURES
Infinite Impulse Response Filter (IIRF) smooths the flow rate calculations. This proprietary smoothing software provides accurate calculations by compensating for a wide variety of flow signal variables.
Password-restricted access to programming, reset total, or both.
Non-volatile memory of totals and field configuration, without need for battery backup.
Efficient switching power supply permits 12…24V AC/DC operations.
PROGRAMMING
Programming is very easy and can be done using the five front panel push buttons, or optionally by using Windows®-based software via a USB port.
PART NUMBER CONFIGURATION
Series
Flow Monitor 3000
Option - Analog Output, RS485 (BACnet / Modbus), and USB
No Option 0 Analog Output, RS485 with BACnet and Modbus, and USB 1
Option - Mounting
Panel Mount 0 Wall Mount 1
Example: 3000 - x x
3.49 in.
(88.7 mm)
TOP
3.54 in.
(90 mm)
MOUNTING TEMPLATE
(122 mm)
3.78 in.
(96 mm)
3.57…3.60 in.
(90.6…91.4 mm)
2.21 in.
(56 mm)
Figure 1: Panel mount template
4.33 in.
(110 mm)
1/8 in.
(3.2 mm)
WALL
4.80 in.
4.72 in.
(120 mm)
SIDE
PANEL
CUTOUT
3.49 in.
(88.7 mm)
(90.6…91.4 mm)
3.62 in.
(92 mm)
SIDE
3.57…3.60 in.
DSY-DS-01685-EN-04 (February 2017)
Figure 2: Wall mount template
Product Data Sheet
Industrial Flow Monitor, Series 3000
FLOW SENSOR INPUTS
Type Threshold Signal Input Frequency Pull-up Impedance Aux. Power Calibration
Pulse-DI 2.5V DC 30V DC 0.4 Hz…10 kHz 1K…12V DC 12V DC @30 mA K + Offset
Pulse K-factor 2.5V DC 30V DC 0.4 Hz…10 kHz 12V DC @30 mA Pulse/Gal
Pull-up K-factor 2.5V DC 30V DC 0.4 Hz…10 kHz 1K…12V DC 12V DC @30 mA Pulse/Gal Analog 4…20 mA 50 mA Fused 100 Ω 12V DC @30 mA Linear Analog 0…20 mA 50 mA Fused 100 Ω 12V DC @30 mA Linear Analog 0…1V DC 30V DC 100 Ω 12V DC @30 mA Linear Analog 0…5V DC 30V DC 100 Ω 12V DC @30 mA Linear
Analog 0…10V DC 30V DC 100 Ω 12V DC @30 mA Linear
SPECIFICATIONS
Voltage 12…24V DC/AC (limit: 8…35V DC); (limit: 8…28V AC)
Operating Temperature –4…158° F (–20…70° C)
Storage Temperature –22…176° F (–30…80° C) Weight Panel Mount: 12 oz Pulse and Relays Both pulse and relay are fully functional as either totalizing or setpoint outputs Pulse Electrical 1 Amp at 35V DC/30V AC Closed: 0.5 Ω at 1 Amp; Open: >10
Relay Electrical
Pulse/Unit Volume (Totalizer)
Setpoint (Alarm)
Resistive Load:
5A @ 120V AC/30V DC
Driving Source: flow total, Rate: 1 pulse per 1.0000000…99999999 units Contact Time: 1…9999 mS
Driving Source: flow rate Units: Any predefined or custom unit Setpoint: 1.0000000…999999999 Delay to Set: 1…9999 sec Release Point: 1.0000000…999999999 Delay to Release: 1…9999 sec
Optional Analog Output Driving Source: flow rate
Inductive Load:
1A @ 120V AC/30V DC
Range: 4…20 mA; 0…20 mA (isolated current sinking or sourcing)
8
USB Communication Provides complete access to all programming and operation features
RS-485 Communication Supports Modbus and BACnet/MSTP Accessories Programming kit; wall mount kit
US gpm; US gal/sec; US gal/hr; US mgal/day; lps; lpm; lph; ft3/Sec; ft3/min; ft3/hr; m3/sec; m3/min;
Rate
Units of Measure
Total
m3/hr; acre-ft/sec; acre-ft/min; acre-ft/hr; bbl/sec; bbl/min; bbl/hr; and field programmed custom units 0.00…999999999
US gallon; US mgal; liters; ft3; m3; acre-ft; bbl; and field programmed custom units
0.00…999999999
DC current draw (~ 280 mA) AC power rating (~5 VA)
Sinking: 30V DC @ 0 mA max; 3V @ 20 mA min.
Sourcing: 600 Ω max load Requirements: USB 2.0 A to Mini-B, five-pin
cable
Control. Manage. Optimize.
Data Industrial is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2017 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 54 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: DTB-078-02