Flow Sensors
Series 228PV PVC Tee Type Flow Sensors 1-1/2…4 inch
DESCRIPTION
Used in conjunction with any Badger Meter® flow monitor or
transmitter, Badger Meter non-magnetic flow sensors provide an
accurate reading of the rate of liquid flow and total accumulated
flow. The available sensor models cover applications for a wide
range of pipe sizes and pressure/temperature specifications.
The flow sensors generate a frequency proportional to flow rate.
An internal preamplifier allows the pulse signal to travel up to 2000
feet (610 meters) without further amplification. Power to operate
the sensor is provided by the flow monitor. The impeller bearing
assembly, shaft and O-rings are replaceable in the field.
Badger Meter flow sensors feature a closed, six-bladed impeller
design, using a proprietary, non-magnetic sensing technology.
The forward-swept impeller shape provides higher, more constant
torque than four-bladed impeller designs, and is less prone to
fouling by water-borne debris. The forward-curved shape, coupled
with the absence of magnetic drag, provides improved operation
and repeatability, even at lower flow rates. As the liquid flow
turns the impeller, a low impedance signal is transmitted with a
frequency proportional to the flow rate.
Sensors of similar type are interchangeable, so there is no need for
recalibration after servicing or replacement.
Series 228PV
These models feature a modified PVC tee with solvent weld socket
end connections, and a removable PPS or PVDF sensor insert. Sizes
include 1-1/2, 2, 3, and 4 inch.
ELECTRONIC TYPES
Badger Meter provides several basic sensor configurations,
using the same impeller element, allowing for a wide range of
applications and pipe sizes. Sensors are normally supplied with
20 feet (6 meters) of 2-conductor 20 AWG shielded UL type PTLC
221° F (105° C) cable. All Series 200 sensor electrical components
are self-contained. Pressure/temperature ratings for the models
are contained in the specifications section of this document. These
models are further described as follows.
Standard Sensor
These sensors are designed for indoor or protected area
applications such as HVAC, pump control, and industrial process
monitoring where flow rates are between 0.5…30 feet/second
and temperatures are below 140° F (60° C). Standard sensors are
supplied with 20 feet (6 meters) of 2-conductor 20 AWG shielded
UL type PTLC 221° F (105° C) cable.
IR Sensor
These sensors are designed for below grade applications such
as irrigation, municipal, and groundwater monitoring where the
flow rates are between 0.5…30 feet/second and temperatures
are below 140° F (60° C). IR sensors are supplied with two single
conductor, 18 AWG solid copper wire leads, 48 inches (122 cm) in
length, with UL Style 116666 direct burial insulation.
SEN-DS-01682-EN-08 (February 2018)
Product Data Sheet
Specications
SPECIFICATIONS
Wetted Materials (except tees) See Ordering Matrix
Tee for 228PV
Pressure/Temperature Ratings
(DO NOT EXCEED)
Rated Temperature
(DO NOT EXCEED)
Recommended Design Flow Range 0.5…30 ft/sec
Accuracy ± 1.0% of full scale over recommended design flow range
Repeatability ± 0.3% of full scale over recommended design flow range
Linearity ± 0.2% of full scale over recommended design flow range
Transducer Excitation
Output Frequency 3.2…200 Hz
Output Pulse Width 5 msec ±25%
Environmental
Electrical Cable for Standard Sensor
Electronics
Electrical Cable for IR Sensor Electronics
Schedule 80 PVC per ASTM D-2462 and D-2467, Virgin, unplasticized PVC resin, Type 1 cell classification
12454-B. Fittings and solvent carry approval for potable water by NSF and IAMPO.
Depends on hardware configurations.
80
60
40
20
0
02
Temperature (°C)
Operating: 35…110° F (2…43° C)
Storage 14…110° F (–10…43° C)
Supply voltage = 8V DC min. 35V DC max.
Quiescent current = 600 uA (typical)
OFF State (V
ON State (V
) = Supply voltage – (600 µ * Supply impedance)
High
) = 1.2V DC @ 40 mA (15 Ω + 0.7V DC)
Low
• IP 68 / NEMA 4X
• Suitable for pollution degree 4 environments
• Suitable for outdoor use above grade, IR version below grade
• Suitable for use in 100% humidity
20 feet (6 meters) of 2-conductor AWG 20 with AWG 22 drain wire shielded UL type PTLC wire provided for
connection to display or transmitter unit. Rated to 221° F (105° C). May be extended to a maximum of 2000
feet (610 meters) with similar cable and insulation appropriate for application.
48 inches (122 cm) of UL Style 116666 copper solid AWG 18 wire w/direct burial insulation. Rated to
221° F (105° C).
Page 2 February 2018SEN-DS-01682-EN-08