Bacharach FT-10 User Manual

3015-4568 Revision 0
9/11/03
Installation Guide
Bacharach HGM300 to LonWorks FT-10
Introduction
The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network. Zone PPM readings, flow status, refrigerant selections, and HGM internal health may be viewed over LonWorks. Each HGM zone supports three levels of alarming (Leak, Spill, Evacuate) and each alarm threshold can be set over LonWorks.
The LonWorks Communications Adapter can be used in conjunction with the RDM800 remote display if desired. Wiring details and operation limitations when using the RDM800 will be discussed later in this document.
Caution
The adapter is powered from the 120V Auxiliary Power connection on the HGM power supply board. When the HGM is powered up, 120V is present on the lower left corner of the adapter within the area shown on the board silkscreen. Keep fingers away from this area when the HGM is powered!!
Adapter Installation Inside HGM300
The communications adapter board will normally be installed in the HGM300 at the factory. It can, however, be field installed by following the instructions below.
The following installation materials are needed for field installation of the adapter:
(5) 6-32 x ¼” screws (standard finish) (5) 6-32 x ½” threaded standoffs (5) 6-32 x ¼” decorative black anodized screws (standard finish OK, black looks nicer)
The adapter board mounts on the rear of the HGM300 door. Position the adapter board so as not to interfere with the HGM internal components when the door is shut. Mark (Figure 1) and drill the board’s four corner holes and center hole in the door. Install the five standoffs on the rear side of the door using the five black decorative screws on the
1 of 18
front side of the door. Position the adapter board over the standoffs mounted on the HGM door. Install the five remaining 6-32 screws through the board and into the standoffs and tighten.
Connect power wiring from the HGM300’s 120V Auxiliary Power terminal block to the adapter board’s POWER terminal block. Use UL approved wire. Wire polarity does not matter.
If an RDM800 remote display is NOT used with the adapter, refer to Figure 2 for wiring details. In this case, all wiring between the HGM300 main board and adapter is contained within the HGM300 and the only external cable is the LonWorks FT-10 communications cable.
2 of 18
If an RDM800 remote display IS to be used with the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cables must be run between the HGM300 and RDM800, so plan accordingly.
In either case, be sure to set the HGM300’s internal “Terminator” slide switch next to the RS-485 terminal block to the “In” position.
3 of 18
4 of 18
Setting HGM Communication Address On Adapter
See Figure 4 for the location of adapter dipswitch ‘A’.
Switches 5-8 on the adapter’s ‘A’ dipswitch are used to match the node address set on the HGM’s address dipswitch (on HGM main board). Values from 0-15 are possible:
HGM address A5 A6 A7 A8
----------------- ---------------------------------------------­ 0 Off Off Off Off 1 Off Off Off On 2 Off Off On Off 3 Off Off On On 4 Off On Off Off 5 Off On Off On 6 Off On On Off 7 Off On On On 8 On Off Off Off 9 On Off Off On 10 On Off On Off 11 On Off On On 12 On On Off Off 13 On On Off On 14 On On On Off 15 On On On On
Since the HGM is the only node on the adapter-to-HGM interface, address 1 is normally used. Be sure to set the same address on the adapter and the HGM main board dipswitches.
5 of 18
6 of 18
Loading...
+ 12 hidden pages