Product Leadership • Training • Service • Reliability
INSPECTION EQUIPMENT
MEASURING EQUIPMENT
61KN
Notice:
Product improvements and enhancements are continuous; therefore the specifications and information
contained in this document may change without notice.
Bacharach, Inc. shall not be liable for errors contained herein or for incidental or consequential damages in
connection with the furnishing, performance, or use of this material.
No part of this document may be photocopied, reproduced, or translated to another language without the prior
written consent of Bacharach, Inc.
WARNING STATEMENTS ........................................................................................ERROR!BOOKMARK NOT DEFINED.
CAUTION STATEMENTS .........................................................................................ERROR!BOOKMARK NOT DEFINED.
HAZARD SYMBOLS ON MONITOR ..........................................................................ERROR!BOOKMARK NOT DEFINED.
FUNCTIONAL OVERVIEW .............................................................................................................................................. V
AGM300-CONNECTING AIR LINES..............................................................................................................................4
GENERAL OPERATION .................................................................................................................................................44
WORKING WITH ALARMS ............................................................................................................................................50
WORKING WITH THE TREND SCREEN........................................................................................................................... 53
WORKING WITH SYSTEM FAULTS ................................................................................................................................54
WORKING WITH THE CALIBRATION SCREEN................................................................................................................57
WORKING WITH THE DIAGNOSTIC SCREEN..................................................................................................................59
SERVICE MODE ...........................................................................................................................................................61
WARRANTY AND SERVICE .................................................................................................................................... 81
Thank you for investing in a BACHARACH Ammonia Gas Monitoring System.
This manual provides important information on how to install, operate, and service the AGM300 Ammonia Gas
Monitor and ADM800 Ammonia Display Module.
Please Read this Manual Carefully Before Use
If you have a working knowledge of gas monitors, you will find this manual useful as a reference tool. If you are
new to the use of gas monitors, you can educate yourself about the principles of gas detection and the proper
operation of this device by reading this manual thoroughly.
iiInstruction 3015-4275
Safety Precautions
AC Power Supply
Ensure the source voltage matches the voltage of the product before energizing the equipment. It is highly
suggested that the AGM300 be placed on a separate circuit (with UPS or surge protection).
• A switch or circuit-breaker shall be included in the building installation
• It shall be in close proximity to the equipment and within easy reach of the operator
• It shall be marked as the disconnecting device for the equipment
Protective Grounding
Under no circumstances should this equipment be operated without connection to a protective ground. Doing
so poses a potential shock hazard and is also a violation of electrical safety standards applicable to this type
of equipment.
Explosive Atmosphere
Do not operate this equipment in the presence of flammable liquids, vapors or aerosols. Operation of any
electrical instrument in such an environment constitutes a safety hazard.
Proper Exhaust Venting
It is imperative that the exhaust port on this instrument be properly vented as described in this manual. Failure
to do so constitutes a safety hazard.
Working Inside the Instrument
Extreme care should be exercised when accessing the interior of this instrument. Only qualified electrical
maintenance personnel should perform connections and adjustments. Always de-energize the power supply
before working inside the instrument.
Modifications to the Instrument
Under no circumstances should this instrument be modified without written consent from Bacharach, Inc.
Changes or modifications to this instrument, not expressly approved, will void the warranty.
In Case of Malfunction
Do not continue to use this equipment if there are any symptoms of malfunction or failure. In the case of such
occurrence, de-energize the power supply and contact a qualified repair technician or the nearest Bacharach
Service Center. ONLY provided knockouts are to be used for electrical and communication wiring. Drilling into
the box will void the warranty.
Fusing
AGM300, 120 VAC Input, Power Supply P/N 3015-3167
F1: 0.5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2538
F2: 250 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2537
F3: 5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2539
F4: 63 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2535
AGM300, 230 VAC Input, Power Supply P/N 3015-3161
F1: 250 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2537
F2: 125 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2536
F3: 5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2539
F4: 32 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2534
ADM800
F1 & F2: 1 A, 250VAC, Fast Acting, 5mm x 20mm, P/N 3015-4011
Instruction 3015-4275 iii
Safety Precautions (Cont.)
Installation Category
Installation Category II, Pollution Degree II, as defined by UL.
Altitude Limit
2,000 meters
Cleaning
USE a dry cloth to clean the outside of the case. DO NOT use soap and water.
Warning Statements
The use of the word WARNING in this manual denotes a potential hazard associated with the use of this
equipment. It calls attention to a procedure, practice, or condition, or the like, which if not correctly performed or
adhered to, could result in personal injury or death.
Caution Statements
The use of the word CAUTION in this manual denotes a potential hazard associated with the use of this
equipment. It calls attention to a procedure, practice, condition, or the like, which if not correctly performed or
adhered to, could result in damage to the equipment.
Hazard Symbols on Monitor
This symbol indicates the need to consult this operating instruction
manual when opening the enclosure.
WARNING: A potential risk exists if the operating instructions are not
followed.
This symbol indicates the presence of electric shock hazards when
the enclosure is opened.
WARNING: To avoid risk of injury from electric shock, do not open
the enclosure when power is applied.
ivInstruction 3015-4275
Functional Overview
General Description
The AGM300 is designed to support compliance to federal, state and local safety codes governing ammonia
gas emissions. Avoiding significant ammonia gas loss reduces equipment replacement costs, maintains
equipment efficiency, promotes safety, and protects the environment.
The AGM300 provides for the continuous monitoring of ammonia gas levels in up to 16 separate test zones.
Each zone can be independently programmed to identify leak (small), spill (medium), or evacuation (large)
levels of gas. The instrument also retains a log of previous readings that can be easily accessed for analysis.
An audible alarm and large LED indicators are provided to signal alarm conditions, and relay contacts are
provided for the connection of external alarm devices. The system also includes two 4–20 mA current loop
interfaces (optional) for connection to external devices.
The AGM300 requires only minor periodic maintenance such as the occasional replacement of filters. The
instrument incorporates active diagnostics that continuously monitor the system for proper operation. An LED
indicator is provided to indicate system malfunctions, and fault codes are displayed that enable the operator to
identify the source of the fault.
Communication Options
The AGM300 features full two-way communications via an RS-485 interface. MODBUS RTU is the
communication protocol standard. The instrument can be connected directly to a Building Management System
or it may be operated as a stand-alone system using the ADM800 Ammonia Display Module.
An RS-232C port is also provided for connection to a PC. This enables the AGM300 to be setup from a
personal computer.
Please refer to the Appendix for a more complete discussion of communication protocols.
Suggested Location of Sampling Points
At the point of an ammonia gas leak the gas is nearly pure. As the gas is dispersed into the air, the gas
molecules diffuse causing a dilution of the original concentration. The AGM300 measures the ammonia gas
concentration at the precise point the sample is collected. Therefore, if the termination of the collection line is
not at the exact point of the gas leak, then the unit will read a diluted mixture of the gas and air.
It should also be noted that when ammonia gas is cold it is heaver than air and settles below the leak point, but
as the gas warms to room temperature it becomes lighter than air and tends to collect above the point of a leak.
Consequently, sampling points should ideally be located as close as possible to the source of potential leaks. If
this is impractical, then the alarm set points should be adjusted for that zone to compensate for the dilution of
the gas. DO NOT plug any of the zones. Plugging a zone will give the monitor a false indication during
start up.
The AGM300 should be centrally located in the mechanical room and be readily accessible for easy visual
monitoring and servicing. Air sample tubing may be run in lengths up to 500 feet. The fresh air purge line
should draw from an area that does not contain any ammonia gas and cannot exceed 300 feet in length. The
exhaust line should run to an out side location if possible. The length of the exhaust line cannot exceed
300 feet.
Ideally, two to three pick up points spaced around each chiller will provide sufficient coverage. It may be
necessary to perform a “smoke” test of the mechanical room to determine the best locations. The smoke test
would provide the pattern of air currents present in the mechanical room.
Instruction 3015-4275 v
AGM300 / ADM800 Refrigerant Gas Leak Monitor Mechanical Room Placement
Exhaust Fan
Outside Hallway
Aux. Horn/Strobe
Remote Alarm
Fresh air purge
from area away
from ammonia
gas
Sample Inlet
Pickup Point
Machine Room
ADM800
Ammonia Display
Module outside of
mechanical room
Chiller
AGM300
Ammonia
Gas
Monitor
Sample Inlet Pickup Points
The ADM800 should be mounted outside of the mechanical room or at least just inside of a door to the room.
This is the “split architecture design” for safety of the operator. The ADM800 can be located up to 4500 feet
from the AGM300. The ADM800 is the main interface by which you program the AGM300, acknowledge
alarms, and observe conditions inside of the mechanical room. Note that there are two additional alarm relay
contacts in the ADM800 that can be programmed to alarm with “leak, spill, evacuate, fault or monitor on”.
viInstruction 3015-4275
acket
AGM300 Installation
Upper Mounting
Bracket
LED
Indicators
STANDARD ACCESSORIES FOR A 4 POINT SYSTEM
5 Line-End Filters (P/N 3015-3420)
AGM300/ADM800 Instruction Manual (P/N 3015-4275)
Lower Mounting
Br
Water Trap
Instruction 3015-4275 1
AGM300 - Installation Considerations
Locating the Monitor
The AGM300 should be centrally located in the facility and should be easily accessible for visual monitoring and
servicing. Intake sample lines can be up to 500 feet in length, but it is important to remember that sampling
cycle time is proportional to the total number and length of individual sample lines.
Dirt, grease, and oils can adversely affect the operation of the AGM300. The monitor should be installed out of
direct sunlight in a clean, dry area that is not subject to temperature or humidity extremes. Installation of the
monitor in a mechanical room is acceptable provided reasonable environmental conditions exist. If there is a
question, consider installing the unit outside of the mechanical room in a cleaner area of the facility.
Warnings and Cautions
WARNING – Drilling holes in the AGM300 and
ADM800 enclosure will void the warranty. Please
use knockouts provided for electrical connections.
WARNING - Do not operate this equipment in the
presence of flammable liquids, vapors or aerosols.
Operation of any electrical instrument in such an
environment constitutes a safety hazard.
WARNING - Always de-energize the power supply
before working inside the instrument.
CAUTION - The AGM300 contains sensitive
electronic components that can be easily damaged.
Be careful not to touch or disturb any of these
components.
Inspection
The AGM300 has been thoroughly inspected and tested prior to shipment from the factory. Nevertheless, it is
recommended that the monitor be re-checked prior to installation. Inspect the outside of the enclosure to make
sure there are no obvious signs of shipping damage. Open the door latches and inspect the interior of the
instrument for loose components that may have become dislodged during shipment. If damage is discovered,
please contact the nearest Bacharach Service Center for assistance.
2Instruction 3015-4275
AGM300 - Mounting Instructions
Screw Locations
The AGM300 should be installed plumb and level and securely fastened to a rigid mounting surface. The
enclosure utilizes keyhole mounting brackets designed for #12 pan head fasteners. Locate the four screws as
shown in the diagram and leave the screw heads protruding approximately 3/16".
AGM300 Mounting Specs
Installation
Hold the monitor flat against the mounting surface and allow it to slide down engaging the screw heads in the
keyhole slots of the mounting brackets. Adjust the screws as necessary to hold the monitor securely against the
mounting surface.
Instruction 3015-4275 3
AGM300 - Connecting Air Lines
Overview
Individual sample lines are run from the AGM300 to each area of the facility to be monitored. Additionally, a
purge line is installed to provide clean air for resetting the infrared zero baseline. An exhaust line is installed to
vent residual gas away from the monitor. All sample line connections are made on the left side of the enclosure
as indicated in the photograph below.
AGM300 Side View
Intake Ports
Exhaust Port
Purge Port
RS-232 Connector
Inlet/Purge Ports
(see below)
Exhaust Port
RS-232
Inlet / Purge Ports
4Instruction 3015-4275
Tubing Considerations
Use ¼" outside diameter (0.040" wall) flex tubing is used for all air lines (P/N 304-2742). The tubing should be
clean and free of residual moisture or other contaminants. The tubing should be cut cleanly with a sharp knife
and care should be taken not to distort the tubing end.
IMPORTANT: Due to the reactive nature of ammonia gas, it is important to use materials that will not absorb
ammonia gas as it passes though the sampling system. The use of unauthorized tubing or any other materials
in the gas sampling stream may lead to erroneously low readings.
To connect the air lines to the monitor simply push the tubing firmly onto the connector. All tubing bends should
have a radius of no less than 5" to assure proper airflow. If kinks or obstructions occur in any of the air lines the
instrument may not function properly.
Connecting Purge Line
A purge line is required to draw fresh air into the instrument and should not exceed 300 feet in length. It is
advisable to terminate the line outdoors, provided the input is not exposed to rain, snow, ice, exhaust fumes, or
other airborne contaminates. If an outdoor installation is impractical, the line should be run to an area inside the
facility that you are certain is not contaminated with ambient ammonia gas. A line-end filter (P/N 3015-3420)
should be attached to the end of the purge line.
Connecting Exhaust Line
An exhaust line is required to vent gas samples away from the instrument and should not exceed 300 feet in
length. The exhaust line should terminate in a location that is completely isolated from the purge line
termination point and other areas of the facility that will be monitored. Ideally this line should terminate outdoors
in a location that is not exposed to the elements. This line does not require a line-end filter. If the exhaust line
terminates outside the building, position the tubing so that no water or moisture can enter it.
Connecting Sample Intake Lines
The AGM300 is designed to accommodate up to 16 separate sample intake lines. The standard configuration of
the unit includes one manifold of 4 intake connectors and 1 purge connector. Additional manifolds can be
easily installed to increase monitoring capacity (field installation kit part P/N 3015-3419, and 4 zone line end
filter kit P/N 3015-3411).
Sample intake lines can be up to 500 feet in length. All line terminations should be positioned to reduce the
possibility of mists, aerosols, oil, water, dust, or other contaminates being drawn into the instrument. A line-end
filter (P/N 3015-3420) should be attached to the end of each sample intake line.
IMPORTANT: DO NOT plug any of the zones. Plugging a zone will give the monitor a false indication during
start up.
Please refer to the earlier Section Suggested Location of Sampling Points to learn more about where to place
the ends of the sample intake lines.
Water Trap
A water trap has been installed as a standard feature. The water trap prevents condensation or moisture from
entering the infrared device and causing serious damage. To empty the water trap, loosen the wing nut and
allow water to drain – be sure to retighten the wing nut.
CAUTION - The introduction of contaminants through the
air intake lines can result in serious and permanent
damage to the monitor.
Instruction 3015-4275 5
AGM300 - Interior Schematic
)
Primary Filter
Intake Manifold Solenoids
Intake Solenoid Connectors
Power Supply Board
Main Board
Microcontroller Board
Infrared Optical Bench
Gas Sample Pump
Primary Filter (P/N 3015-3071
Connectors
Gas Sample
Intake
Manifold
Solenoids
Intake
Manifold
Solenoid
Pump
Power Supply
Board
120 or 230 VAC
Determined by
Sales Order
Main Board
Microcontroller
Board
Infrared
Optical Bench
6Instruction 3015-4275
4–20 mAdc
Interface Board
(Optional)
AC Power / RS-485 / Relay Connector / 4-20 mAdc Current Loop
AC Power
ON/OFF
Switch
Dual 4-20 mAdc
Outputs
(Signal Out Only)
DO NOT APPLY
POWER!
RS-485
Connector
Relay Connector
Alarm 1, 2, 3, Fault
Factory
Default
Terminator
IN / OUT
Ground Stud
CPU
Reset
(Used to Supply AC power to Alarm Devices)
Switches / Fuses
Node Address
Switches
AC IN
Connector
T1
Location of
AC Input
Line Filter
(230 VAC
Units Only)
Auxiliary AC Out Connector T2
(Overload Protected by Fuse F3)
F4
F2
F1
Connects to Aux. AC Out
Connector T2
5 Amp 250VAC
(P/N 604-2539)
AC Power
ON/OFF
Switch
AGM300
Fuses
(Refer to
Maintenance
Section for
values Page 64)
F3
Instruction 3015-4275 7
AGM300 - Electrical Wiring
It is highly recommended that the AGM300 be connected directly to the AC power source, preferably on its own
circuit. The connection should be completed with a UL rated multi-conductor wire (14-18 AWG).
Locate service knockouts on exterior of enclosure and install electrical conduit in the typical manner.
The AGM300 is available in either a 120 or 230 VAC configuration. The unit’s AC voltage rating is marked on
the outside of the enclosure. Do one of the following to connect the AC power leads and ground:
• 120 VAC Installation
Locate the AC IN connector T1 and the Ground Stud on the inside of the enclosure (Page
Remove the AC IN connector from the Power Supply board, and then secure the incoming AC power line
(black) and neutral (white) wires to this connector as shown in the following illustration. Carefully plug the
connector back onto the circuit board.
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along
with the ground wire connected to the enclosure’s lid to the monitor’s Ground Stud.
• 230 VAC Installation
Locate the AC Input Line Filter’s black and white wires, and the Ground Stud on the inside of the enclosure
7).
(Page
Using wire nuts, secure the incoming AC power Line 1 (black) and Line 2 (white) wires to the AC Input Line
Filter as shown in the following illustration.
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along
with the ground wire connected to the enclosure’s lid to the monitor’s Ground Stud.
7).
WARNING – Drilling holes in the AGM300 enclosure will
void the warranty. Please use knockouts provided for
electrical connections.
WARNING - Electrical installation should be performed
by a certified electrician and should comply with all
applicable local, state, and federal electrical safety
codes.
WARNING - Under no circumstances should this
instrument be operated without connection to a
protective ground. Doing so poses a potential shock
hazard and is also a violation of electrical safety
standards applicable to this type of equipment.
• A switch or circuit-breaker shall be included in the building installation
• It shall be in close proximity to the equipment and within easy reach of the operator
• It shall be marked as the disconnecting device for the equipment
8Instruction 3015-4275
AGM300 AC Input Power and Ground Connections
Instruction 3015-4275 9
AGM300 - Connecting Communication Devices
Ammonia Display Module (ADM800) Connection
The AGM300 is connected to the ADM800 using a shielded twisted pair instrument cable. The maximum
distance between the farthest away AGM300 and ADM800 is 4500 feet.
Use any of the remaining service knockouts to gain access to the interior of the monitor. The RS-485
communication wiring between the AGM300 and ADM800 must be connected in the following manner:
Locate the RS-485 connector in the AGM300 (Page
“B” connection point (the far left point), note the wire color. Connect the second wire to the “A” connection
point (the middle), note the wire color. Connect the ground to the “GND” connection point
Locate the RS-485 connector marked “TO MONITORS” in the ADM800 (Page
located on the far-left bottom of the ADM800 PC board. Make the wire run to the ADM800 and connect the
twisted shielded pair to the RS-485 TO MONITORS connector using the same color code as used on the
AGM300.
7). Connect one lead of a twisted shielded pair to the
23). This connector is
Integrating with Building Management Systems
The AGM300 may be connected directly to a Building Management System using a shielded twisted pair cable.
The cable from the Building Management System is connected to the RS-485 connector inside the AGM300.
MODBUS RTU is the standard communication protocol.
Use any of the remaining service knockouts to gain access to the interior of the monitor. Locate the RS-485
connector and remove it from the circuit board. Secure the wire leads to the connector orienting them as shown
in the diagram below. Check to make sure that the polarity matches the wiring to the Building Management
System. When you are through securing the connections, carefully plug the connector back onto the circuit
board.
Larger Integrated Systems
You may also connect the AGM300 to a Building Management System through an ADM800. In this case, first
connect the AGM300 to the ADM800 as described above. Then, follow the instructions under the heading
ADM800 – Communications Connections on Page
Building Management System.
26 for information on how to connect the ADM800 to a
RS-485 Connector
10Instruction 3015-4275
Changing Terminator Settings
The terminator switch is shipped from the factory in the terminated or “IN” position. This is the correct setting if
the AGM300 is connected as a single device, or it is the last device on the network chain. If the AGM300 is
being installed in the middle of a network, the terminator must be moved to the “OUT” position.
Locate the switch and determine its position. If it needs to be moved, slide the switch to the appropriate
position.
Network Node
Address
Switch
Terminator
Switch
IN OUT
Node Address DIP Switch Settings
(Refer to Multiple AGM's and Connecting to a Building Management System)
Each AGM300 on the network must have a distinct node address. The node address may be set from 1 to 15.
Four dip switches numbered 1, 2, 4, 8 on the main circuit board are used to define this value by setting the
correct combination of dip switches to their ON positions. The node address is the sum of the switch numbers
that are ON.
Example: - For node address “5” switches 1 and 4 are ON.
- For node address “13” switches 1, 4, & 8 are ON.
Power must be cycled to elect this change.
Personal Computer
(Refer to AGM300 PC Software Section)
The AGM300 may be connected to a personal computer using the RS-232 interface on the left side of the
enclosure.
Software will be provided upon request or as a download from:
http://www.bacharach-inc.com/downloads.htm.
Instruction 3015-4275 11
Multiple AGM’s
TERMINATOR
“IN”
AMD800
MULTIPLE AGM300’S WITH ADM800
NOTE 1: The last AGM300 or ADM800 on either end of the network must have its terminator
in the “IN” position, and all other units must have their terminators in the “OUT” position.
NOTE 2: The total length of the RS-485 cable cannot exceed 4500 feet. (Use instrument
cable 20 gage multi-strand shielded and twisted pair – similar or equal to Belden
cable #8762.)
RS-485 CONNECTIONS BETWEEN AGM300’s
RS-485
AGM300
UNIT 1
NODE 1
TERMINATOR TERMINATOR TERMINATOR TERMINATOR
“OUT” “OUT” “OUT” “IN”
NOTE: The terminators in the ADM800 and AGM300 Unit 4 must be in the “IN” position. The
terminators in AGM300 Units 1, 2 & 3 must be in the “OUT” position.
AGM300
UNIT 2
NODE 2
AGM300
UNIT 3
NODE 3
AGM300
UNIT 4
NODE 4
Connecting to a Building Management System
The AGM300 may be connected to a Building Management System via the RS-485 connector. The node
address switch on each AGM300 may be set from “1” to “15” in order to identify itself to the Building
Management System. Note that Building Management Systems set to a “0” or “1” address both respond to
messages from the ADM800 as address “1” therefore you should not have a unit set to “0” and another set to
“1” on the same network.
If the AGM300 network is connected directly to a Building Management System it may not
ADM800. However, the ADM800 has two communication ports, an “upstream” port (labeled TO HOST) and a
“downstream port (labeled TO MONITORS). A BMS node may be connected to the up stream ADM800 port
while the downstream ADM800 port talks to the AGM300’s. In this case, the BMS is talking “through” the
ADM800 to the AGM300’s, but not physically on the AGM300/ADM800 network.
NOTE: If the AGM300 is not at the end of the line in a series connection, then the terminator on the AGM must
be set to “OUT.” Also, each end of the series must have the terminator set to “IN”.
MULTIPLE AGM300'S CONNECTED TO A BUILDING MANAGEMENT SYSTEM
TERMINATOR
“OUT”
TERMINATOR TERMINATOR TERMINATOR TERMINATOR
“IN” “OUT” “OUT” “IN”
AGM300
NODE 1
AGM300
NODE 2
BMS
AGM300
NODE 3
be connected to the
AGM300
NODE 4
12Instruction 3015-4275
MULTIPLE AGM300’s CONNECTED TO A BUILDING MANAGEMENT SYSTEM
DAISY CHAIN FASHION
RS-485
TERMINATOR
“IN”
AGM300
UNIT 1
NODE 1
TERMINATOR TERMINATOR TERMINATOR TERMINATOR
“OUT” “OUT” “OUT” “IN”
AGM300
UNIT 2
NODE 2
BUILDING
MANAGEMENT
SYSTEM
AGM300
UNIT 3
NODE 3
AGM300
UNIT 4
NODE 4
AGM300 - PC Software
Programming the AGM300 Using PC Software
NOTE 1: There are two versions of PC software. Use Version 1.0 with AGM300 units with v1.0 Unit Firmware,
which were built June 2001 or before (as indicated by a serial number that starts with AF01 or lower). Use
Version 1.52 or higher with v1.21 Unit Firmware or above, which were built August 2001 or later (as indicated
by a serial number that starts with AH01 or above). The Firmware version is indicated on the label on the ROM
module inside the AGM300.
NOTE 2: The PC software uses COM1 by default. Therefore, the interface cable should be connected to the
port configured as COM1 on the PC. Also, no other software drivers or devices in the PC may control COM1
when the AGM300 software is in use.
The connection is made through a standard “straight through” serial port connection. A three-wire connection is
used (RXD, TXD, and GND). No hardware flow control is used. The AGM300 software automatically
configures COM1 to match the AGM300 RS-232 communications parameters.
NOTE 3: Occasionally the laptop connection will not connect properly and only two beeps are heard and the
program times out. The cure for this is to disconnect the RS-232 cable and cycle power on both the AGM300
and the laptop. After both the AGM300 and the laptop are up and running connect the RS-232 cable and start
the software program.
1. Turn on power to AGM300 and allow it to warm up.
2. Connect RS-232 interface cable to PC and RS-232 port on the AGM300.
3. Insert software disk into PC.
4. Open the AGM300 software using Windows Explorer.
5. Upon start up, the program will immediately attempt to download data from the AGM300. Several beeps
can be heard as the program communicates with the AGM300.
NOTE: To move through the screen use the ARROW keys to move up, down, left and right.
6. Use the ENTER key to select options and the ESC key to back out of a selection.
Instruction 3015-4275 13
7. Using the arrow keys go to EDIT; press ENTER – the EDIT Menu DROPS DOWN; select SYSTEM and
then press ENTER – the AGM LOCATION becomes highlighted. Press ENTER to move to the AGM
TAG area; use the BACKSPACE key to remove the existing tag; then enter in a new tag. Press
ENTER to return to LOCATION. Use the ARROW key to select the next item to be addressed. Note
that you cannot change the “SN” or “FIRMWARE” items. Press the ESC key to return to the menu bar.
8. Go to EDIT; press ENTER; select ZONES; and then press ENTER. You may now select a specific
zone to identify and set parameters. When REFRIGERANT is selected use the ARROW keys to move
up and down through the gas library to locate the gas type for that zone. Highlight the gas type and
press ENTER.
9. To set the ALARMS first select EVAC LEVEL; press ENTER; use the BACKSPACE key to clear
previous setting; and type in the new PPM level. Use the same method to set the SPILL LEVEL and
LEAK LEVEL.
10. To close or bypass a zone, set the DISTANCE to 0 feet.
IMPORTANT: Any time you modify a parameter (zone, system or calibration) and send it to the
AGM300, please wait for the PC software to indicate that the download is complete before continuing
with any edits.
Saving the AGM300 Program to a Disk or Drive
Go to FILE, PATH, and change the drive letter to the drive where the program is to be saved. Give the program
a name, such as A:\AGM300 or C:\MY DOCUMENTS\AGM300; press ENTER; go to SAVE SETUP and press
ENTER again. Type in the file name, such as “CHRM1” (eight characters maximum without a filename
extension) and then press ENTER. The program will automatically add “.cfg” to the filename that you typed.
To Open a Saved Program
Open software; go to FILE, PATH, and clear the old path and type in the proper drive for the saved program
(A: or C: etc.). Press ENTER; select the proper program; press ENTER again. The saved program will be
downloaded into the software.
To Send a Saved Program to an AGM300
Open the AGM300 PC software; open the proper saved program; connect the PC to the AGM300; and then go
to AGM, SEND SETUP and press ENTER. The saved program will be sent to the AGM300.
Trend Data
Creating a trend data file must be done while connected to the AGM300.
Go to FILE, PATH, clear the old path and type in the proper drive where the trend data will be saved. Press
ESC; go to AGM; select GET TREND DATA; select the zone that you want to trend and press ENTER. The
trend data will appear in a list format. Press ENTER again – a file name screen will appear. Type in the file
name for that zone (trend1 etc.). Press ENTER and the file is saved as a text file. The text file can be converted
to a Microsoft Excel file or printed as is.
NOTE: The TREND file must be saved ZONE by ZONE, with a filename per zone. The file will be saved in
a notepad format, which can be converted to a delimited Excel file.
To Convert the TREND Text File to a Microsoft Excel File
Open Microsoft Excel; open the desired file using All files (*.*); select DELIMITED format and SPACE as the
delimiter. Select GENERAL as the column data format. The text file now appears as an Excel file. To save the
file, go to FILE, SAVE AS; select the proper drive; then change the file name extension to “.XLS” and save it.
Comments or notes may be added to this file as needed and saved.
To Save and Print the AGM300 Software Screen, Alarm Log,
Fault Log, or Diagnostic Screen
Open the software while connected to the AGM300. After the software gets the program, open the desired
screen. With that screen as the active screen, press the ALT and PRINT SCREEN keys on the PC keyboard.
Open Microsoft Word; go to FILE, NEW; go to EDIT; then PASTE. The active screen is then brought into Word.
To save the file, select SAVE AS; select the proper drive and file name; and then press SAVE.
14Instruction 3015-4275
USB Type Laptops
Some of the newer laptops have USB ports and no RS-232 9-pin ports. You will be required to purchase a
PCMCIA card that provides an RS-232 output. We recommend the PCMCIA card manufactured by:
SEALEVEL SYSTEMS, INC.
155 TECHNOLOGY PLACE
P. O. BOX 830
LIBERTY, SC 29657
PHONE – 864-843-4343
www.sealevel.com
Part number: PC- SIO-232 PCMCIA CARD
A “ straight through” RS-232 cable and a DB25 to DB9 adapter will be required to connect the laptop to the
AGM300.
Instruction 3015-4275 15
AGM300 - Current Loop Interfaces
Optional 4–20 mAdc Outputs
Upon installation of the optional 4–20 mAdc Interface Board (Page 7) (P/N 3015-3133), the AGM300 has the
capability of providing dual 4-20 mAdc scrolling current loop outputs for connection to external monitoring
devices.
The interfaces are set up as follows:
Loop 1 indicates zone area
Loop 2 indicates PPM
Connection
The external devices are connected to the AGM300 using a shielded dual twisted pair cable. Use any of the
remaining service knockouts to gain access to the interior of the monitor. Locate the Dual 4–20 mAdc Output
connector (Page
as shown in the diagram below. Check to make sure the polarity matches the wiring at the external device.
When you are through securing the connections, carefully plug the connector back onto the circuit board.
NOTE: When one or both current loop outputs are not used, install a jumper wire between the ground the
unused loop terminal(s) to prevent the system from generating a current loop fault.
7) and remove it from the circuit board. Secure the wire leads to the connector orienting them
CAUTION - The loop outputs have isolated grounds.
Therefore, the cable shield should be terminated at the
receiver and not at the AGM300. The signal for both
current loops must be returned to the AGM300.
Current Loop Connector
NOTE:
SIGNAL OUT
ONLY DO NOT
APPLY POWER
LOOP 1 = ZONE
5 mAdc = Zone 1 Default
6 mAdc – Zone 2 0.016 mAdc = 1 PPM
--- Scalable via Software
--- 4 mAdc = 0 PPM
20 mAdc = Zone 16 20 mAdc = 1000 PPM
LOOP 1
ZONE
LOOP 2
PPM
NOTE: The ground connections are common.
LOOP 2 = PPM
GROUND
16Instruction 3015-4275
AGM300 - Connecting External Alarms
Overview
The AGM300 includes 4 Form C SPDT alarm contacts for the connection of external alarm devices. The relays
are factory assigned to the following conditions:
Relay #1 Leak
Relay #2 Spill
Relay #3 Evacuate
Relay #4 Fault
Connection
Use the AC conduit or any of the remaining service knockouts to gain cable access to the interior of the
monitor. Locate the relay connector (Page
connector orienting them as shown in the diagram below. When you are through securing the connections,
carefully plug the connector back onto the circuit board.
7) and remove it from the circuit board. Secure the leads to the
AGM300 Relay Connector
NOTE: Each relay may be connected as normally open (NO), or normally closed (NC).
Latching / Non-Latching – refer to Page
Alarm power source – power for the alarm devices connected to the relay contacts may be supplied from the
Auxiliary AC Power Out Connector, 5 amp. max. (Page
38 to select Alarm Ack Mode.
7).
Instruction 3015-4275 17
Typical AGM300 Relay 1 and Relay 2 Wiring
LEAK SPILL EVACUATE FAULT
Jumper the ‘Neutral’ of the auxiliary power connector to the ‘Common’ on the relay block.
Connect one end of strobe or horn to the ‘NO’ of whichever level of alarm is appropriate for application.
The other end of strobe or horn is connected to the ‘Line’ of the auxiliary power connector (5 A max.).
RS-485
Line Neutral
Aux. Power
Line Neutral
Main AC Input
Horn
18Instruction 3015-4275
ADM800 Installation
ADM800 Oblique Photo
Upper & Lower Mounting Brackets
Upper
Mounting
Bracket
Lower
Mounting
Bracket
Instruction 3015-4275 19
ADM800 - Installation Considerations
Overview
Up to four AGM300 monitors may be connected to a single ADM800 display module. The ADM800 can be
located anywhere up to 4500 feet from the furthest AGM300. The display module should be installed out of
direct sunlight in a clean area that is not subject to temperature or humidity extremes.
Warnings and Cautions
WARNING - Drilling holes in the AGM300 and
ADM800 enclosure will void the warranty. Please
use knockouts provided for electrical connections.
WARNING - Do not operate this equipment in the
presence of flammable liquids, vapors or aerosols.
Operation of any electrical instrument in such an
environment constitutes a safety hazard.
WARNING - Electrical installation should be
performed by a certified electrician and should comply
with all applicable local, state, and federal electrical
safety codes.
WARNING - Always de-energize the power supply
before working on the interior of the instrument.
CAUTION - The ADM800 contains sensitive
electronic components that can be easily damaged.
Be careful not to touch or disturb any of these
components.
Inspection
The ADM800 has been thoroughly inspected and tested prior to shipment from the factory. Nevertheless, it is
recommended that the instrument be re-checked prior to installation. Inspect the outside of the enclosure to
make sure there are no obvious signs of shipping damage. Loosen the four screws on the sides of the
enclosure and remove the front panel. Visually inspect the interior of the display for loose components that may
have become dislodged during shipment. If damage is discovered, please contact the nearest Bacharach
Service Center for assistance.
20Instruction 3015-4275
ADM800 - Mounting Instructions
Screw Locations
The ADM800 should be installed plumb and level and securely fastened to a rigid mounting surface. The
enclosure utilizes keyhole mounting brackets designed for #12 pan head fasteners. Locate the four screws as
shown in the diagram and leave the screw heads protruding approximately 3/16".
ADM800 Mounting Specs
Installation
Hold the display module flat against the mounting surface and allow it to slide down engaging the screw heads
in the keyhole slots of the mounting brackets. Adjust the screws as necessary to hold the unit securely against
the mounting surface.
Instruction 3015-4275 21
oard
Switc
Microcontroller
Supply Board
Connector T3
B
CPU Reset
h
Power
120–230
VAC Input
Main Board
AC IN
ADM800 - Interior Schematic
Microcontroller Board
CPU Reset Switch
Main Board
Ground Stud
AC Power
Front Panel Chassis
22Instruction 3015-4275
Terminator
Switches
TO MONITORS
RS-485 to
HGM300
Monitors
AC Power
RS-485 Connectors
Terminator Switches
Relay Connector
Fuses
TO HOST
RS-485 to
Building
Management
System
Relay
Connector
1 Amp
250 VAC
P/N
3015-4011
F2
F1
AC IN
Connector T3
Instruction 3015-4275 23
ADM800 - Electrical Wiring
It is highly recommended that the ADM800 be connected directly to the AC power source, preferably on its own
circuit. The connection should be completed with a UL rated multi-conductor wire (14-18 AWG).
Locate service knockouts on exterior of enclosure and install electrical conduit in the typical manner.
The ADM800 is available in either a 120 or 230 VAC configuration. The unit’s AC voltage rating is marked on
the outside of the enclosure. Do one of the following to connect the AC power leads and ground:
• 120 VAC Installation
Locate AC IN connector T3 and the Ground Stud on the inside of the enclosure (Page
Remove the AC IN connector from the circuit board, and then secure the incoming AC power line (black) and
neutral (white) wires to this connector as shown in the following illustration. Carefully plug the connector back
onto the circuit board.
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along
with the ground wire connected to the front panel to the unit’s Ground Stud.
• 230 VAC Installation
Locate the AC Input Line Filter’s black and white wires, and the Ground Stud on the inside of the chassis
22).
(Page
Using wire nuts, secure the incoming AC power Line 1 (black) and Line 2 (white) wires to the AC Input Line
Filter as shown in the following illustration.
Using the supplied crimp-on ring terminal, washers, and nuts, connect the AC input ground wire (green) along
with the ground wire connected to the front panel to the unit’s Ground Stud.
22).
WARNING - Electrical installation should be performed
by a certified electrician and should comply with all
applicable local, state, and federal electrical safety
codes.
WARNING - Under no circumstances should this
instrument be operated without connection to a
protective ground. Doing so poses a potential shock
hazard and is also a violation of electrical safety
standards applicable to this type of equipment.
• A switch or circuit-breaker shall be included in the building installation
• It shall be in close proximity to the equipment and within easy reach of the operator
• It shall be marked as the disconnecting device for the equipment
24Instruction 3015-4275
ADM800 AC Input Power and Ground Connections
Instruction 3015-4275 25
ADM800 - Communication Connections
AGM300 Network
The ADM800 Ammonia Display Module is connected to the AGM300 network using a shielded twisted pair
cable. The maximum distance between the ADM800 and the farthest AGM300 is 4500 feet.
Use any of the remaining service knockouts to gain access to the interior of the ADM800. The RS-485
communication wiring between the ADM800 and AGM300 must be connected in the following manner:
Locate the RS-485 connector marked “TO MONITORS” in the ADM800 (Page
located on the far-left bottom of the ADM800 circuit board. Connect one lead of a twisted shielded pair to
the “B” connection point (the far left point), note the wire color. Connect the second wire to the “A”
connection point (the middle), note the wire color. Connect the ground to the “GND” connection point.
Make the wire run to the AGM300 and connect the twisted shielded pair to the AGM300 RS-485 connector
7) using the same color code as used on the ADM800.
(Page
23). This connector is
Integration with Building Management System
A second RS-485 connector inside the ADM800 allows a Building Management System to “talk” to the AGM300
network through the ADM800. The connection is established using a shielded twisted pair cable.
Use any of the remaining service knockouts to gain access to the interior of the ADM800. Locate the RS-485
connector marked “TO HOST” (Page
connector orienting them as shown in the diagram below. Check to make sure that the polarity matches the
wiring to the Building Management System. When you are through securing the connections, carefully plug the
connector back onto the circuit board.
23) and remove it from the circuit board. Secure the wire leads to the
RS-485 Connector
26Instruction 3015-4275
Changing Terminator Switch Settings
The terminator switch for the RS-485 “TO MONITORS” connector is shipped from the factory in the terminated
or “IN” position. This is the correct setting if the ADM800 is connected to only one AGM300, or if it is the last
device on a network chain. If the ADM800 is being installed in the middle of a network, the terminator must be
moved to the “OUT” position. Refer to Multiple AGM's on Page
The terminator switch for the RS-485 “TO HOST” connector is shipped from the factory in the terminated or “IN”
position. This is the correct setting if the ADM800 is the last device on the network chain. If other devices are
daisy chained through the ADM800, the terminator must be moved to the “OUT” position. Refer to Connecting to a Building Management System on Page
12.
Locate each terminator switch and determine its position. If it needs to be moved, carefully slide the switch to
the proper position.
12.
Terminator for RS-485
TO MONITOR
Connector
RS-485
TO MONITOR
Connector
OUT
IN
RS-485
TO HOST
Connector
Terminator for RS-485
TO HOST
Connector
OUT
IN
Instruction 3015-4275 27
ADM800 - Connecting External Alarms
Overview
Two SPDT alarm contacts are available for the connection of external alarm devices. These alarms are useful
for alerting the user to global conditions anywhere on the network. Each relay can be programmed to respond
to alarm, fault, or monitor ON conditions (refer to Setting Relay Parameters on Page
Connection
Use the AC conduit or any of the remaining service knockouts to gain access to the interior of the ADM800.
Locate the relay connector (Page
connector orienting them as shown in the diagram below. When you are through securing the connections,
carefully plug the connector back onto the circuit board.
23) and remove it from the circuit board. Secure the wire leads to the
ADM800 Relay Connector
36).
NOTE: Each relay can be connected as normally open (NO), or normally closed (NC).
Power for the external alarms can be tapped off the AC IN connector.
28Instruction 3015-4275
ADM800 Operation
dicators
Scree
ADM800 Exterior Schematic
Display Screen
Navigation Buttons
Cursor Pad
LED Indicators
Navigation
Buttons
LED
In
Display
n
Cursor
Pad
Instruction 3015-4275 29
ADM800 - Overview
The ADM800 displays comprehensive information about the AGM300 network status and enables complete
programming control of all system operations. The prominent features of the display module are discussed
below.
Display Screen
The display screen is a back-lit LCD.
Control Keys
The 4 keys on each side of the display window are used to navigate between screen displays. A graphic box
that is open to the edge of the window indicates that the adjacent control key is active. The 3 keys along the
bottom of the window are also used to navigate between screens. A text block directly above the key indicates
that the key is active. An active key can be used to navigate to another screen. A graphic box, that is not open
to the edge, displays information only and the adjacent control key is inactive.
Cursor Key-Pad
The cursor key-pad is used to move about screens, enter setup information and choose between setup
parameters. When entering information the LEFT/RIGHT keys move the cursor across an entry field, while the
UP/DOWN keys scroll data entry options. The ENTER key is used to accept data entries.
LED Indicators
The three LED indicators provide an overview of network status.
GREEN Glows when the system is operational.
RED Glows when the ADM800 detects a leak, spill, or evacuate alarm
condition anywhere on the network.
YELLOW Glows when the ADM800 detects a system fault anywhere on the network.
Internal Audible Alarm
An internal audible alarm is provided that can be programmed to sound when there is an occurrence of the
selected condition (refer to
Audible Alarm on Page 35).
External Alarms
Additionally, 2 SPDT alarm contacts are provided for the connection of external alarm devices. These alarms
are useful for alerting the user to global conditions anywhere on the network. Each relay can be programmed to
respond to alarm, fault, or monitor ON conditions (refer to
Setting Relay Parameters on Page 36).
30Instruction 3015-4275
ADM800 - Screen Displays
When first powered up a splash screen appears indicating the serial number and firmware revision number.
After a brief moment the System Screen is displayed. Please refer to the Appendix for a logic diagram of all
the screen displays.
There is a 15-minute warm-up period after power is first applied. Under “AGMS”, "WARM UP" is displayed.
The green indicator on the AGM will blink during the warm-up period.
IMPORTANT: DO NOT plug the gas-sample hose or inlet port of any zone. The monitor will perform a vacuum
test during start up and a plugged zone will give a false indication.
System Screen
Display
showing
“WARM UP”
Instruction 3015-4275 31
ADM800 - System Programming
Setup Parameters
Before working with the AGM300 network, several global parameters must be defined. Most of these are
entered in the ADM Setup Screens or via the PC software. Parameters must also be defined for each
AGM300 monitor connected to the network. These settings serve to identify each monitor and define how they
operate. These are entered in the AGM Setup Screens. Finally, parameters must be defined for each
individual monitoring zone. These are entered in the Zone Setup Screens.
Password Protection
The ADM800 can be password protected to prevent the unauthorized editing of setup parameters. When
password protection is enabled, an operator may still navigate between screens to observe settings or monitor
network status. The password can be alphanumeric.
The unit is shipped with password protection OFF. Entering a password in ADM Setup Screen #1 enables
password protection. Once protection is enabled the user will be prompted to enter the password when they
first attempt to edit a setup parameter.
To enter a password:
1. From the top level System Screen press the ADM SETUP key to go to ADM Setup Screen #1.
2. From ADM Setup Screen #1, press the PASSWORD key.
3. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
4. Press ENTER to accept the new password or QUIT to revert to the previous setting.
After entering the password, a 30 minute time period will be allowed for entries; after which, the user will again
be prompted to re-enter the password.
IMPORTANT: Please make note and save your password.
ADM Setup Screen #1
Password
32Instruction 3015-4275
ADM800 - Setup Programming
Setting the Clock
From the top level System Screen press the key adjacent to the date/time field to go to the Clock Setup
Screen.
Clock Setup Screen
Use the LEFT/RIGHT cursor keys to move the cursor across the field to the value you wish to edit. Use the
UP/DOWN cursor keys to modify the field value and press the ENTER key to accept your entries. When you are
through editing the date/time value, do one of the following:
• Press the SET AGM CLOCKS key to synchronize all AGM300 monitors to the current date/time setting.
• Press the QUIT key to reject all edits and revert to the previous setting.
• Press the SET ADM CLOCK key to accept the current date/time setting.
Instruction 3015-4275 33
Navigating to the 1st ADM Setup Screen
From the top level System Screen press the ADM SETUP key to go to ADM Setup Screen #1.
ADM Setup Screen #1
Contrast
This value sets the screen brightness.
1. Press the CONTRAST key to adjust its setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Number of AGM Units
This is the number of AGM300 monitors from 1–4 connected to the ADM800.
1. Press the #OF AGMS ON NET key to adjust the number.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: When first powered up, the ADM800 will automatically detect all AGM300s on the network with
unique node addresses. Refer to the heading AGM Node Address Dip Switch Settings on Page
AGM Baud Rate
This is the baud rate of all AGM300 monitors connected to the network.
1. Press the AGM BAUD key to adjust the baud rate.
2. Use the UP/DOWN cursor keys to scroll the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
4. The default valve is 19200.
NOTE: All AGM300s on the network must have the same baud rate.
11.
34Instruction 3015-4275
Audible Alarm
This parameter selects the function of the ADM800’s internal audible alarm.
1. Press the AUDIBLE ALARM key to adjust the setting.
2. Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Enabling Building Management System Connection
This enables or disables the connection to a Building Management System.
1. Press the BMS key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Building Management System Stop Bits
This value is the number of stop bits for the ADM800 on a Building Management System.
1. Press the BMS STOPBITS key to adjust the setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Building Management System Baud Rate
This is the baud rate of the Building Management System.
1. Press the BMS BAUD key to adjust the setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Password
This field is used to define a system password. The default setting is 000, which provides no password
protection.
1. Press the PASSWORD key to enter a password.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
3. Press ENTER to accept the new password or QUIT to revert to the previous setting.
Instruction 3015-4275 35
Navigating to the 2nd ADM Setup Screen
From ADM Setup Screen #1 press the MORE key to go to ADM Setup Screen #2. Press the BACK key to
return to ADM Setup Screen #1.
ADM Setup Screen #2
Setting Relay Parameters
This setting determines the function of relays 1 and 2 mounted inside the ADM unit.
1. Press the key adjacent to the relay parameter you want to adjust.
2. Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
AGM Node Address
This value is the node address from 1 to 15 assigned to each AGM300 that is on the network. These values
must match the DIP switch settings on each AGM300 circuit board. Refer to the heading AGM Node Address Dip Switch Settings on Page
1. Press the key adjacent to the AGM# NODE you want to set.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
11.
Node Address DIP
Switches in AGM Unit
36Instruction 3015-4275
AGM300 - Setup Programming
Navigating to the 1st and then 2nd AGM Setup Screen
From the System Screen, press the key adjacent to the target AGM300 to go to that unit's AGM Setup
Screen #1.
AGM Setup Screen #1
From AGM Setup Screen #1 press the SETUP key to go to AGM Setup Screen #2. Press the QUIT key to
return to the System Screen.
AGM Setup Screen #2
Instruction 3015-4275 37
Location
This is the name you assign to the AGM300 to identify its location. It may have up to 12 alphanumeric
characters.
1. Press the LOCATION key to modify the setting.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Number of Zones Installed
IMPORTANT: Do not change the number of zones to deactivate excess zones. Instead, go to the individual
zone that you wish to disable and set its distance to zero (refer to
41). The monitor will perform a self-check on power-up, and if the number of zones detected does not
Page
agree with the number of zones installed a fault will occur.
1. Press the NUM ZONES INSTALLED key to adjust the setting.
2. Use the UP/DOWN cursor keys to modify the number.
3. Press ENTER to accept the new number or QUIT to revert to the previous setting.
NOTE: The AGM300 auto setting detects the number of zones present on power-up. DO NOT PLUG ANY
ZONES. Plugging a zone will give the monitor a false indication during power up. The number detected on
power up is the default value for this parameter.
Navigating to the 1st Zone Setup Screen on
Alarm Ack Mode
This function programs the relays in the AGM unit for latching or non-latching operation.
1. Press the ALARM ACK MODE key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle between settings.
AUTO – Non-latching (Alarm relay will automatically de-energize when the gas level drops below
its alarm point.)
MANUAL – Latching (Alarm relay remains energized, and will not release until the alarm condition has
been manually acknowledged. Refer to Acknowledging Alarms on Page
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
52.)
Audible Alarm
This parameter selects the function of the AGM300’s internal audible alarm device.
1. Press the AUDIBLE ALARM key to adjust the setting.
2. Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Zone Hold Time
Sets the length of time a zone will be monitored when the zone hold feature is actuated (see Zone Hold Mode
on Page
45). The default is 15 minutes. This parameter can be set to any value between 1 and 999 minutes.
1. Press the ZONE HOLD MINUTES key to adjust this setting.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Detection Limit
This is essentially a squelch setting that instructs the instrument to interpret PPM readings below the
designated level as 0. You can set this value from 1 to 99 PPM.
1. Press the DETECTION LIMIT key to adjust this setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
38Instruction 3015-4275
Loop 2 Factor
This sets the PPM scale factor for current loop number 2. To calculate the current output, multiply the scale factor
by the PPM and add 4. For example, at the default scale factor of 0.016, a measurement of 100 PPM would
generate a current of 5.6 mA. In no case can current output exceed the 20 mA capacity of the interface.
1. Press the LOOP2 FACTOR key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Re-Zero Mode
This parameter defines the frequency at which the instrument re-zeros the optical sensor.
1. Press the REZERO MODE key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle between settings.
AUTO – Sets the instrument to re-zero every 10 minutes.
ZONE CHANGE – Sets the instrument to re-zero at each zone change. This is the most accurate
setting but increases the time interval between measurement cycles.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Instruction 3015-4275 39
Navigating to the 3rd AGM Setup Screen
From AGM Setup Screen #2, press the MORE key to go to AGM Setup Screen #3. Press the BACK key to
return to AGM Setup Screen #2.
AGM Setup #3 Screen
Service Timeout
Sets the length of time the Service Mode is in effect. Stops the monitor for up to 240 minutes (4 hrs) to allow for
servicing the unit. See Service Mode on Page
1. Press the SERV TIMEOUT key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
61.
40Instruction 3015-4275
ADM800 - Zone Setup Programming
Navigating to the 1st Zone Setup Screen
There are two ways to display Zone Setup Screen #1:
• From the System Screen (Page 31) press the key adjacent to the AGM300 unit associated with the zone you
wish to work with. Next, press the ZONES key; and then press the key adjacent to the desired zone.
• From the top level Zone Screen (Page 44) press the key adjacent to the zone you wish to work with. To
select a different zone, use the UP/DOWN cursor keys or the NEXT key to scroll the screen display.
Zone Setup Screen #1
At Zone Setup Screen #1, use the LEFT/RIGHT cursor keys to switch the display to a different zone.
Location
This is the name you assign to the monitoring zone. It may have up to 12 alphanumeric characters.
1. Press the LOCATION key to enter or modify the name of the zone.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Distance
This is the tubing length in feet from the AGM300 to the termination of the gas sample intake line. This value
may range from 0 to 500 feet. The default value is 100 feet. Note that setting this value to “0” causes the zone
to be bypassed during normal operation, and the word “DISABLED” in appear in place of the zone’s PPM
reading in the Zone Screen (Page 44).
1. Press the DISTANCE key to adjust the distance value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Instruction 3015-4275 41
Average Temperature
This temperature reading may be changed to the exact temperature at the sample point for greater accuracy.
The adjustment range is from –50 to +70 degrees C.
1. Press the AVG TEMP key to adjust the temperature value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Current PPM
This box displays the last PPM measurement recorded in this zone. You cannot modify this value.
Log Interval
Sets the length of time between entries in the trend log. The default is one entry every 1440 minutes (24 hours).
A value of 000 indicates that each measurement for a given zone is logged into the trend log.
1. Press the LOG INTERVAL key to adjust the log interval value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Navigating To the 2nd Zone Setup Screen
From Zone Setup Screen #1 press the MORE key to go to Zone Setup Screen #2. Press the BACK key to
return to Zone Setup Screen #1.
Zone Setup Screen #2
Leak Level
This is the concentration level in PPM that will activate a leak alarm condition.
1. Press the LEAK LEVEL key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: This value must be less than the spill level.
42Instruction 3015-4275
Spill Level
This is the concentration level in PPM that will activate a spill alarm condition.
1. Press the SPILL LEVEL key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: This value must be less than the evacuate level and greater than the leak level.
Evacuation Level
This is the concentration level in PPM that will activate an evacuate alarm condition.
1. Press the EVAC LEVEL key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: This value must be greater than the spill level.
Re-Setting the Peak PPM Value
Pressing this key resets the current peak PPM level stored in memory and displays it at the top of the screen.
Instruction 3015-4275 43
General Operation
Functional Overview
Normally each AGM300 will sequentially perform measurements on its active zones without user input. The
total time it takes an AGM300 to complete a measurement cycle is directly proportional to the number of active
zones and the physical length of the sample-gas lines. Monitors linked together on a network operate
independently of each other and consequently complete their respective measurement cycles at different rates.
The ADM800 operates by polling the network approximately once every 12 seconds to determine the current
status of each AGM300 monitor. If more than one AGM300 is connected to the network, it will sequentially poll
each monitor for its status. As a practical matter this simply means that the more complicated the network, the
longer it will take the ADM800 to update the status information for all zones.
To display all the zones being monitored, go to the System Screen (page
31) and press the ZONES key.
Working with the Zone Screen
The top level Zone Screen provides a summary view of zone activity across the network. Each screen displays
information from a single AGM300 monitor as indicated at the top of the display. Each screen can display
information for up to 8 zones, and depending on the configuration of the system, there can be up to two screens
for each AGM300. Use the UP/DOWN cursor keys or the NEXT key to scroll the screen display.
Each box displays the zone location and the last PPM measurement. A blinking box indicates that a
measurement is currently being taken in that location. An inverse flashing box indicates an alarm condition in
that zone.
Use the LEFT/RIGHT cursor keys to scroll through the zones.
Zone Screen
To further investigate the status of any zone, press the adjacent key to go to the Zone Setup #1 Screen
(Page
41). You may also press the SYSTEM key to go to the System Screen (Page 31).
44Instruction 3015-4275
Zone Hold Mode
A zone can be placed on hold and continuously monitored for a length of time determined by the Zone Hold
Time value (Page
hear a beep. The word "HOLDING" appears to identify which zone is being held.
Zone on Hold
38). To place a zone on hold, press and hold down the key adjacent to that zone until you
Zone Screen (Hold Mode)
Once in the hold mode you can further investigate the status of the zone by pressing the adjacent key and going
to the Zone Setup #1 Screen (Page
41). To release the zone from the hold mode, press and hold down the
adjacent key until the unit beeps and the screen display reverts to normal. You may also press and hold down
the key adjacent to any other zone to release the current zone and put the new zone on hold.
Alarm Conditions
When an alarm condition is detected anywhere on the network the red ALARM LED will glow. Additionally, an
external alarm device may activate and an audible alarm may sound if those features have been enabled
(Pages
An inverse flashing box indicates an alarm condition in the affected zone.
28 & 35).
Zone Screen (Alarm Mode)
Zone in Alarm
Instruction 3015-4275 45
If the current Zone Screen appears normal, scroll through the displays using the NEXT/BACK keys or the
UP/DOWN cursor keys until you locate the affected zone. You can further investigate the status of the affected
zone by pressing the adjacent key and going to the Zone Setup #1 Screen (Page
ALARM key to go directly to the Alarm Summary Screen (Page
learn more about responding to alarms.
50). See Working with Alarms on Page 50 to
41). You may also press the
Fault Conditions
If a system malfunction occurs, the yellow FAULT LED will glow. Additionally, an external alarm device may
activate and an audible alarm may sound if those features have been enabled (Pages
28 & 35).
From the top level Zone Screen (Page
then press the FAULT key to go to the Fault Screen (Page
learn more about responding to system faults.
44), press the SYSTEM key to go to the System Screen (Page 31) and
54). See Working with System Faults on Page 54 to
46Instruction 3015-4275
Working with the System Screen
C
The System Screen provides a summary view of the entire AGM300 network. The boxes on the left side of the
screen indicate the status of each AGM300 monitor including the name, the current zone, and whether fault or
alarm conditions are present on the network.
System Screen
Alarm Conditions
When an alarm condition is detected anywhere on the network the red ALARM LED will glow. Additionally, an
external alarm device may activate and an audible alarm may sound if those features have been enabled
(Pages
The ALARM box in the upper right hand corner of the screen will blink and the count value will change to
indicate the total number of alarm conditions on the network. To investigate an alarm, press the ALARMS key to
go to the Alarm Summary Screen (Page
responding to alarms.
28 & 35).
50). See Working with Alarms on Page 50 to learn more about
System Screen (Alarm Mode)
Alarm
ondition
Instruction 3015-4275 47
Alarm Log
From the System Screen press the key adjacent to the AGM300 unit that you wish to view.
AGM Setup #1 Screen
Press the ALARM EVENT LOG key to display Alarm Log Screen.
Alarm Log Screen
Use the LEFT/RIGHT and UP/DOWN cursor keys to move through the log.
The Alarm log shows the last 20 alarm events. An alarm event is the occurrence of any alarm, any change in
alarm level, or the clearing of any alarm. The alarm level is indicated by an L (leak), S (spill), or E (evacuate).
The time and date of the alarm are displayed when the cursor is placed over the alarm.
48Instruction 3015-4275
Fault Conditions
Conditio
If a system malfunction occurs, the yellow FAULT LED will glow. Additionally, an external alarm device may
activate and an audible alarm may sound if those features have been enabled (Pages
The FAULT box on the right of the screen will blink and then counts the number of AGM units on the system
with a fault. To investigate a fault, press the FAULTS key to go to the Fault Screen (Page
with System Faults on Page
54 to learn more about responding to system faults.
System Screen (Fault Mode)
28 & 35).
154). See Working
Fault
n
Instruction 3015-4275 49
Working with Alarms
Functional Overview
If the PPM level for any zone exceed its designated spill, leak, or evacuate thresholds, an alarm condition will
be created. Once the AGM300 completes a measurement cycle in the affected zone the alarm condition will be
indicated. At that time the red ALARM LED on the AGM300 will glow. Additionally, an external alarm device
may activate and an audible alarm may sound if those features have been enabled (Pages
The next time the ADM800 polls the affected monitor its red ALARM LED will glow. Additionally, an
external alarm device may activate and an audible alarm may sound if those features have been enabled
(Pages
The alarm condition may or may not have to be acknowledged for the system to return to normal operation.
28 & 35).
Responding To Alarms
There are two screens from which an operator can respond to alarms:
17 & 38).
• From the System Screen (Page Summary Screen.
• From the top level Zone Screen (Page
to the Alarm Summary Screen.
31) press the key adjacent to the blinking ALARMS field to go to the Alarm
44) press the ALARMS key at the bottom of the display window to go
Alarm Summary Screen
The Alarm Summary Screen displays a list of all alarm conditions pending across the network. The screen is
divided into 8 boxes, with each box representing a single alarm. If more than 8 alarms are pending additional
pages can be displayed by pressing the MORE key.
Each box displays the zone number, zone name, and the current PPM reading. A flashing box indicates an
alarm that has not been acknowledged. A static box represents an alarm that has been acknowledged but has
not yet been cleared from the system.
50Instruction 3015-4275
Alarm Detail Screen
To further investigate an alarm, press the adjacent key to go to the Alarm Detail Screen.
Alarm Detail Screen
The Alarm Detail Screen displays more comprehensive information about the nature of the alarm including:
• Complete location information
• Current PPM
• Peak PPM and peak time
• Type of alarm, alarm time, and date
This screen includes three active navigation keys at the bottom of the display.
ACK Acknowledges the alarm as described in the next section
QUIT Returns you to the Alarm Summary Screen
SETUP Takes you to the Zone Setup #1 Screen (Page
41), which enables you to review the zone setup
parameters and access the Trend Screen.
Instruction 3015-4275 51
Acknowledging Alarms
Each pending alarm may require, depending upon selected alarm mode, acknowledgment before the system
returns to normal operation (refer to Alarm Ack Mode
Alarm Detail Screen and press the ACK key as previously described. You will then be returned to the Alarm
Summary Screen and the box associated with that alarm will no longer be blinking, indicating that the alarm
has been acknowledged. Repeat this procedure to acknowledge any remaining alarms.
Alarm Summary Screen (Acknowledge Mode)
11 on Page 38). To acknowledge an alarm, navigate to the
Once all the alarms associated with a given AGM300 are acknowledged, its red ALARM LED will turn off and
any external alarms connected to the AGM300 relays will de-activate. All pending alarms across the entire
network must be acknowledged before the ADM800 returns to normal operation. Once that occurs, its red
ALARM LED will turn off and any associated external alarms connected to the ADM800 relays will de-activate.
Keep in mind that the system will continue to generate new alarms if PPM values above the alarm thresholds
are detected.
52Instruction 3015-4275
Working with the Trend Screen
Overview - Log Interval
The AGM300 retains a data log of 100 measurements for each zone. The log interval is the number of minutes
from 1 to 1440 between each log point. This parameter can be changed from the Zone Setup #1 Screen
41).
(Page
The default setting for this parameter is 1440 minutes (24 hours). If the log interval time is set to 0, then a
measurement is recorded in the trend log after every measurement cycle. Therefore, after the trend log is filled it
will contain the last 100 measurement points for a zone. If you want the data logged less frequently you should
increase this value. It is important to remember that cycle time is dependent on many factors, including the
number of zones being monitored, input line length, and the run zeroing mode selected. Before changing this
value it may be useful to first review the log data using the Trend Screen to determine the nominal cycle time.
Navigating To the Trend Screen
Access the Trend Screen from either the System Screen or Zone Screen as follows:
• From the System Screen (Page
wish to work with to display that monitor's AGM Setup Screen #1. Next, press the ZONES key to go to Zone Setup Screen #1, and then press the TREND key at the bottom of the display to go to the Trend Screen.
• From the top level Zone Screen (Page
display its Zone Setup Screen #1. Then press the TREND key at the bottom of the display to go to the Trend Screen.
31) press the key adjacent to the AGM300 unit associated with the zone you
44) press the key adjacent to the zone you wish to work with to first
Trend Screen
The trend graph opens with the cursor located over the most recent data point. Use the LEFT/RIGHT cursor
keys to move the cursor to different data points. Holding a key down will cause cursor to move rapidly across
the screen. As you move the cursor position, the date and time of that reading, along with the PPM value, are
displayed at the top of the screen above the graph. The trend graph is automatically scaled to accommodate
the largest PPM value displayed. The ZOOM OUT and ZOOM IN keys allow you to adjust the vertical scale of
the graph.
The trend data is stored on a first-in, first-out basis. After 100 trend values have been stored the 101
replace the first value stored. Therefore, in normal operation, when entering the trend mode the cursor will be
located at the most recent data point. The data points to the left of the initial cursor location will be the next
most recent. The data point to the right will be the oldest data point in the buffer and will be over written by the
next data point.
Instruction 3015-4275 53
st
value will
Working with System Faults
Functional Overview
If a system malfunction occurs, the AGM300 will detect the problem and cause its yellow FAULT LED to glow.
Additionally, an external alarm device may activate and an audible alarm may sound if those features have
been enabled (Pages
The next time the ADM800 polls the affected monitor its yellow FAULT LED will also glow. Additionally, an
external alarm device may activate and an audible alarm may sound if those features have been enabled
(Pages
Depending on the nature of the fault, the AGM300 may or may not continue to operate normally. Under a noncritical fault condition, the AGM300 will continue to measure and log data, but some peripheral functions may
be compromised. Under a critical fault condition, action is required for the AGM300 to operate normally. The
table on the following page lists the various fault conditions and explains what action should be taken to correct
the problem.
28 & 35).
Navigating to the Fault Screen
First, display the System Screen (Page 31). Next, press the key adjacent to the target AGM300 unit to go to
that monitor’s AGM Setup Screen #1 (Page
the selected monitor.
17 & 38).
37). Finally, press the FAULTS key to display the Fault Screen of
Fault Screen
54Instruction 3015-4275
CRITICAL FAULTS
•NO FLOW ON ZONE – Go to the System Screen (Page
Screen (Page
44) will display a “NO FLOW” message in each individual zone affected. Check for a
47) and press the ZONES key. The Zone
blockage in the air sample line or at the line end filter. Once the blockage has been cleared, the
AGM300 will return to normal operation after the zone has been sampled. NOTE: This can take some several minutes since it is dependent upon how many zones there are and their lengths. The AGM300
will clear the fault the next time it polls the effected zone and the ADM800 will return to normal
operation the next time that it polls the AGM300.
•NO FLOW ON PURGE – Check the purge line for a blockage. Verify that the length of the purge line
and exhaust line do not exceed 300 feet in length.
• NO FLOW DETECTED – Check for proper pump operation. Check the water trap – drain if necessary.
• CLIPPING FAULT – The detector voltage may be out of tolerance. Check the Diagnostic Screen
59) for the DET voltage, AVE voltage and ZERO voltage. Call the factory with this information for
(Page
further instructions.
•REZERO VOLT TOL – The detector output voltage is out of tolerance. Check the Diagnostic Screen
as in item 4 and contact the factory for assistance.
•TRIGGER FAULT – No trigger from IR source pulser. Contact factory with all information from the
Diagnostic Screen for further instructions.
NON CRITICAL FAULTS
•BOX TEMP FAULT – Enclosure’s internal temperature is outside normal range (or IR sensor has
failed). Check the installation to verify that the monitor is not being subjected to extreme temperatures.
Verify that the ventilation holes are not obstructed. Check the Diagnostic Screen for the ZERO
temperature, BNCH temperature and BOX temperature. Call the factory with this information for further
instructions.
•BENCH TEMP FAULT – Optical bench is outside of normal operating range (or sensor has failed).
Check the installation to verify that the monitor is not being subjected to extreme temperatures. Check
the Diagnostic Screen for the ZERO temperature, BNCH temperature and BOX temperature. Call the
factory with this information for further instructions.
•PRESSURE SENSOR – Manifold pressure is outside normal operating range (or sensor has failed).
Check the Diagnostic Screen and record ALL data. Call the factory with this information for further
instructions.
•LOOP FAULT – This would only be displayed if the dual 4–20 mA option was installed and one or both
current loops are open. Check the wiring to load/monitoring circuit on both 4–20 mA loops.
•CONFIG FAULT – There is an error in AGM Setup Screen #2 – Number Zones Installed field, or in
ADM Setup Screen #1 – Number of AGMS on Network field. Check that the number of zones installed
for each AGM unit and the number of AGM units on the network are properly programmed. Check to
ensure that the manifold solenoid cable connector in each AGM unit is securely fastened to its terminal
connector. Check for an illegal parameter. If necessary, reset to the factory default settings.
Reset to Factory Default Settings
IMPORTANT: Performing this function wipes out all program parameters, alarms, faults, trends and log files.
Resetting the AGM300
cycle the AC power OFF and then ON; listen for five beeps; and then release the switch. Reprogram the
AGM300 per Section AGM300 – Setup Programming on Page
Resetting the ADM800
From the System Screen (Page
power OFF and then ON; listen for five beeps; and then release the key.
Instruction 3015-4275 55
– Press and hold down the Factory Default switch inside the AGM300 (Page 7);
37.
– Occasionally it will be necessary to rest the ADM800 to factory default settings.
31), press and hold the key adjacent to the ALARMS function; cycle AC
Clearing System Faults
If the fault condition is associated with an AGM300, the monitor will return to normal operation soon after the
problem is corrected. At that time the YELLOW LED will turn off and any external alarms connected to the
monitor’s alarm relays will also turn off. The ADM800 will return to normal operation the next time it polls the
affected AGM300 monitor.
Once the system malfunction has been corrected it may take some time for the fault condition to clear
completely. If the fault is associated with a specific zone, the AGM300 must first cycle back to the affected
zone before it returns to its normal operating mode. At that time the yellow FAULT LED will turn off and any
external alarms connected to the AGM300 unit will de-activate. The ADM800 will return to normal operation the
next time it polls the affected monitor.
Viewing Fault Log
A data log of the last 20 fault conditions is retained in memory. From the Fault Screen (Page 54) press the
LOG key to view a display of the fault log.
Fault Log Screen
This screen lists potential fault conditions in the left column and displays a check mark indicating which
problems were associated with each fault condition as represented by the vertical cursor bar. As you move the
bar horizontally using the LEFT/RIGHT cursor keys, the date and time the fault condition was detected is
displayed in the upper right hand corner of the display window.
Anytime the fault status changes, there is an entry in the fault log, both when the fault occurs and when it is
cleared.
56Instruction 3015-4275
Working with the Calibration Screen
Overview
The Calibration Screen is used to adjust the IR sensor’s calibration factor.
IMPORTANT: Changing information on CAL FACTORS will VOID the factory calibration. Typically, the unit will
remain within the factory-calibrated accuracy indefinitely and no calibration is required. Complex software
algorithms adjust for temperature drift, IR source aging, and pressure changes in order to keep the unit within
factory accuracy specifications.
Navigating to the Calibration Screen
First, display the System Screen (Page 31). Next, press the key adjacent to the target AGM300 unit to go to
that monitor’s AGM Setup Screen #1 (Page
Calibration Screen.
37). Finally, press the CAL key to go to the selected monitor’s
Calibration Screen
Adjusting Calibration Factor
The factory default cal factor for standard units is 1.000.
Proceed as follows to adjust the current calibration factor:
1. Press the CAL FACTOR key to edit the value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Instruction 3015-4275 57
Calibration Procedure
The CAL FACTOR is determined by sampling a known dilution of ammonia gas. The sample must be prepared
to less than half the desired accuracy, and the concentration must be corrected for ambient temperature and
pressure at the time of measurement.
Calibration is best performed at or near full scale (10,000 PPM). It can, however, be done at any concentration,
and ideally in the range where maximum accuracy is desired down to, but not below, 100 PPM.
A cylinder of ammonia gas at a certified PPM level must be used to assure sampling occurs at ambient
conditions. A minimum sample size of 5 liters is required.
The AGM should be operating for at least one hour prior to performing a calibration.
Prepare the AGM300 for sampling by initially setting its CAL FACTOR to 1.000 (Page
AGM300 for a logging interval of zero minutes (Page
zone you wish to set up (Page
Connect the sample bag directly to the intake port for the zone you have set up and allow the AGM300 to
sample the entire bag. When sampling is complete view the trend data for the zone used to sample (Page
Read the measured PPM by placing the cursor on the spikes cause by the sample. If the bag was large enough
for multiple samples, average the most stable ones.
The new CAL factor is computed by dividing the known gas value by the measured value. Typically this value
will be between 0.95 and 1.05. Enter the computed CAL factor into the monitor using the ADM800 (Page
PC interface. This value is stored in non-volatile memory.
45).
42), and place the AGM300 in its zone hold mode for the
57). Next, set up the
53).
57) or
58Instruction 3015-4275
Working with the Diagnostic Screen
Overview
The Diagnostic Screen displays reference values for use by repair technicians for troubleshooting purposes.
Navigating to the Diagnostic Screen
Display the System Screen (Page 31); press the key adjacent to the target AGM300 unit to go to that
monitor’s AGM Setup Screen #1 (Page
Diagnostic Screen.
37); and then press the DIAG key to go to the selected monitor’s
Diagnostic Screen
Diagnostic Screen Overview
The Diagnostic Screen contains sensor data and status information useful for troubleshooting various fault
conditions. An explanation of each line is given below along with normal operating ranges.
LINE 1: Detector Voltage – This is the peak-to-peak output of the IR sensor, in the absence of ammonia
gas this value can range from 3.900V to 4.500V.
LINE 2: Average Detector Voltage – This is simply a running average of the values displayed in line 1.
LINE 3: Zero Voltage – This is the IR sensor output that was stored during the last purge cycle and has
the same range as line 1.
LINE 4: Noise – This is a 16 point running average of the noise portion of IR bench output. This reading is
valuable mainly when ammonia gas is NOT
present.
LINE 5: Average Absorbency – This is the optical absorbency computed from the values in lines 2 and 3.
In the absence of ammonia gas the absorbency is 0.000AU. When sampling gas, its value varies
proportionally with the gas concentration.
LINE 6: uMoles/L – This is the absolute concentration in micro-moles per liter of ammonia gas based on
line 4 and the internal calibration. There are two figures given. The first (which is annotated by a B) is the
actual measurement at the IR bench. The second is the calculated value corrected to ambient conditions
(temperature + pressure).
Instruction 3015-4275 59
LINE 7: PPM – Parts Per Million is the volume concentration referenced to standard temperature and
pressure and is computed from lines 5, 8 and 13. There are two figures given. The first (annotated by a B)
is the actual PPM at the IR bench. The second is a PPM reading normalized to standard temperature and
pressure.
LINE 8: Zero Temperature – This line contains the sensor and enclosure temperature measured and
stored during the last purge cycle in degrees C.
LINE 9: Bench Temperature – This is the current IR sensor temperature in degrees C as well as the raw
voltage coming from the temperature sensor itself. This value can range from ambient to ambient +15
degrees C.
LINE 10: Box Temperature – This is the current internal enclosure temperature along with the raw
voltage from the temperature sensor, and has the same range as line 9.
LINE 11: Pressure – This is the current absolute manifold pressure in PSIA along with the output voltage
of the pressure sensor. This value should always be 0.2 to 1.0 PSIA below ambient (line 13).
LINE 12: Vacuum – The vacuum pressure is measured every purge cycle by closing all sample valves.
Its value is typically 2.5 to 4.0 PSIA below ambient (line 13).
LINE 13: Ambient – Ambient pressure is measured every purge cycle with the sample pump off and the
manifold open. Its value is weather and altitude dependent and can range from 10.0 to 15.5 PSIA.
60Instruction 3015-4275
Service Mode
When activated, the Service Mode will disable a specific AGM300 unit for a specified length of time. The default
is 60 minutes. This time interval can be changed per Section
IMPORTANT: Note that while in the Service Mode no measurements are made, nor are any alarms activated.
Service Timeout on Page 40.
From the System Screen (Page
Mode. From AGM Setup Screen #1 (Page
3 seconds.
Note that the System Screen will show what monitors are in the Service Mode.
To exit the Service Mode, again press the SERVICE MODE ENTRY key twice within 3 seconds.
31), select the key adjacent to the AGM unit you wish to place into its Service
37) press the SERVICE MODE ENTRY key twice within
AGM Setup Screen #1
Press this key
twice within
3 seconds to
place the
selected AGM
unit into its
Service Mode
Monitor in
Service
Mode
System Screen (Service Mode)
Instruction 3015-4275 61
Notes:
62Instruction 3015-4275
Appendix
Instruction 3015-4275 63
AGM300 / ADM800 Maintenance
Warnings and Cautions
WARNING - Always remove AC input power to the monitor before working on the interior of the instrument.
CAUTION - When working inside the instrument be very
careful not to dislodge any electrical wiring or pneumatic
tubing. The AGM300 contains sensitive electronic
components that can be easily damaged. Be careful not to
touch or disturb any of these components.
Servicing Inline Filter
Locate the inline filter (Page 6) and inspect it for obvious signs of contamination. If the filter is contaminated or
has started to turn red in color it should be replaced with P/N 3015-3071.
To replace the filter, remove it from the retaining clip and carefully slide the two pieces of tubing off the fittings.
Re-fit the tubing on the new filter, making sure the flow arrow points to the right. Complete the installation by
pushing the new filter back into the retaining clip.
Servicing Air Lines
System air lines should be checked periodically for obvious signs of kinks, damage, and contamination.
Replace the tubing as required with P/N 304-2742 or equivalent.
The end-line filters should be checked periodically and replaced when there are obvious signs of contamination.
To service the filter simply remove it from the air line and replace it with P/N 3015-3420.
Replacing Fuses
Locate the fuse holders (Pages 7 & 23) and remove the fuses from their holders. Visually inspect and test the
fuses with an ohm meter for continuity. If necessary, replace any defective fuses.
AGM300, 120 VAC Input, Power Supply P/N 3015-3167
F1: 0.5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2538
F2: 250 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2537
F3: 5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2539
F4: 63 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2535
AGM300, 230 VAC Input, Power Supply P/N 3015-3161
F1: 250 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2537
F2: 125 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2536
F3: 5 A, 250V Fast Acting, 5mm x 20mm, P/N 604-2539
F4: 32 mA, 250V Fast Acting, 5mm x 20mm, P/N 604-2534
ADM800
F1 & F2: 1 A, 250VAC, Fast Acting, 5mm x 20mm, P/N 3015-4011
64Instruction 3015-4275
Optional Accessories
Intake Manifolds
Up to three additional intake manifolds (P/N 3015-3419 & P/N 3015-3411) can be installed in the AGM300 to
increase the total capacity to 16 zones. Each manifold requires a sample line-end filter for each of the 4 zones.
Please follow the instructions provided to install the manifolds. Then follow the instructions earlier in this manual
to install the air lines and complete the zone programming steps. The AGM300 setup must also be updated to
recognize the new zones.
4–20 mA Interface Board
The optional 4–20 mA Interface Board (P/N 3015-3133) (Page 7) allows the operator to take advantage of the
current loop interfaces provided for connection of external devices to the AGM300. The interface board plugs
into the socket provided on the main circuit board, and the external devices are then cabled to the AGM300 as
described on Page
16.
Instruction 3015-4275 65
ADM800 - Logic Diagram
66Instruction 3015-4275
RS-485 Communication Protocol
Overview
The following instructions are intended as a guide for integrating the AGM300 network into a Building
Management System. If you are unfamiliar with complex systems of this type, it is recommended that you
contact Bacharach for technical assistance.
MODBUS RTU Protocol
The AGM300 monitor communicates with master devices (such as the ADM800 or a Building Management
System) over the RS-485 serial interface. The monitor is configured with a two wire RS-485 serial bus, and
therefore, data transmission occurs in ‘half-duplex’ mode. Consequently, only one device may be in transmit
mode at any given time.
Programmers should refer to the MODBUS Protocol Reference Guide for details and more comprehensive
instructions. The guide is available on the Modicon web site at:
The AGM300 and ADM800 are equipped to communicate with other equipment using the MODBUS RTU
protocol. Using this communication channel a MODBUS master device may communicate with up to 15
AGM300s on a communications network, exchanging measurement information, alarm data, fault data, history
(logs and trends) and setup information. Additionally, the MODBUS master can control the operating state of
an AGM300, placing the AGM300 in any of its different operating modes. The network may be configured such
that the AGM300s are connected directly to the MODBUS master device, or the MODBUS master device may
communicate with the AGM300s through the ADM800.
(NOTE: This document will assume that the reader is familiar with the various parameters used to set up the
AGM300, as well as the different operational modes that the AGM300 may be placed in. If you are unfamiliar
with this information, please reference the AGM300 operations manual.)
Protocol Details
A 2 wire RS-485 bus is used for transmission, therefore communication occurs in a Half-Duplex mode. The
AGM300 is a slave device and will respond to queries in the MODBUS RTU format from a master device.
Two MODBUS functions are supported. They are function 03 (read holding register) and function 16 (Preset
Multiple registers). Please refer to the MODBUS Protocol Reference Guide (available at
www.modicon.com/techpubs/techPubNew/PI_MBUS_300.pdf) for protocol detail and use instructions.
Using the two MODBUS functions, a master device may read, modify and write data and status information to
any AGM on the network. AGM data is organized into structures (internal to the AGM300) which can be
accessed by the MODBUS registers defined in this document. A corresponding set of data structures should
be maintained by the master device. These master device data structures become the destination for
responses to read queries and sources for preset register commands. When a read holding register query is
made by the master device the AGM300 responds by sending the contents of the structure referenced by the
specified register. After the master validates the AGM300 response using the CRC bytes, it must then move
the data into its matching data structure before individual items may be accessed or modified. Therefore, the
master data structure should correspond to the AGM300 data structure byte for byte. Note that some data
structures have been divided into multiple registers due to MODBUS RTU message length constrains. To
change a setting in the AGM300, the master device first reads the register structure that contains the data item
to be modified, makes the desired change, then sends the structure back using the preset multiple register
function. If the transaction is successful, the AGM300 sends the appropriate MODBUS response. It is the
responsibility of the master device when making modifications to insure that all parameters trasfered fall inside
the working limits of the AGM300.
Notes on AGM300 Polling
After the AGM300s are setup and operating, the master device need only poll each AGM for its status register
which contains summary data of the AGM’s alarms, faults, and operating state. If exceptions are detected
through the status register and more details are required, additional registers can be examined. Also if current
PPM values are required, the PPM register provides access to current PPM values for all zones. The AGM300
requires a minimum of 20 seconds to complete a gas concentration measurement for a single zone. Therefore,
it is not necessary to poll the AGM300 more frequently than once every 15-20 seconds, as there will not be any
new data available/obtained by more frequent polling. In fact, excessive polling will slow the operation of the
AGM300. Under no circumstances should the AGM300 be continuously polled at rate faster than 500mS, as
this could result in erroneous readings by the AGM300.
68Instruction 3015-4275
Notes on Network Topologies
AGM300s may be connected directly to the MODBUS network or they may be connected to the network
through an ADM800. In either case, each AGM300 must have a unique node ID. Up to 15 AGM300s can be
connected directly to the MODBUS network.
If AGM300s are accessed via an ADM800 connected to a MODBUS network, the ADM800 “BMS enabled”
parameter must be set equal to “1” via the “ADM SETUP” screen on the ADM800. The same commands and
registers are used to communicate with the AGM300 directly or through the ADM800. If the communications is
through the ADM800, it monitors each MODBUS message to determine if the message is intended for one of
the AGM300s it is connected to. If it is, the ADM800 passes the message through to the AGM300s. If it is not,
the message is not passed through. The ADM800 does not make any modifications to MODBUS messages. It
simply passes the query through to the AGM300, and passes the response back to the MODBUS master. In
other words, it allows the AGM300s to be logically connected to the MODBUS network, when physically they
are connected to the local ADM800 network. It is very important
messages through to the AGM300 when the ADM800 is either in the “SYSTEM” screen or the “ZONE VIEW”
screen. If the ADM800 is in any other screen
code 06).
All ADM800 screens except the SYSTEM and ZONE VIEW screens have a 10 minute timeout interval, after
which the screen will return to either the SYSTEM or ZONE VIEW screen, depending on which one it was last
in. Also, the ADM800 can be password protected such that a password entry is required in order to view
screens other than the SYSTEM or ZONE VIEW screen.
, it will return a MODBUS “busy” exception response (exception
to understand that the ADM800 will only pass
Key Comm Protocol Parameters
MODBUS Mode: RTU only
AGM300 Baud Rate: Default is 19,200. Programmable as defined in System data register
Parity: No Parity
Stop Bits: Default is 1. Can be set for 2 via System data register
Maximum Response Time: 4000mS when directly accessing the AGM300. 8,000mS when accessing the
AGM300 through the ADM800.
Error Checking: CRC per MODBUS specifications
Also of note is the fact that all data
byte followed by most significant byte). This should be taken into account if the master that process the data is
a “big endian” type. Non-data information (starting address, number of points, etc.) follows normal MODBUS
protocol, which is Big Endian.
sent out from the AGM-300 is in “little endian” byte order (Least significant
Instruction 3015-4275 69
Summary of Registers
Register Name Number Type Description
System Data 0x0010h R/W AGM System Setup Data
Status 0x0011h R/W Operating summary of faults, alarms
and status
Zone Data 0x12xxh R/W Setup data for up to 16 zones (xx
defines zone number)
CAL Data 0x0014h R/W Cal Factors for all gases
Date/Time 0x0015h R/W Set AGM300 date & time
Sensor Data 0x0016h R Raw measurement of sensors
Rel. Hold 0x0017h W Release AGM300 out of hold mode
Hold Zone 0x0018h W Put AGM300 into hold mode
Fault Log 0x19xxh R 20 most recent fault events (xx = 00
or 01)
Alarm Log 0x1Axxh R 20 most recent alarm events (xx = 00,
01, or 02)
Serv. Mode 0x001Bh W Puts AGM300 into service mode
Rel Serv. 0x001Ch W Release AGM300 from service mode
PPM 0x001Eh R PPM values for all zones
Zone Log 0x3yxxh R Trend data for each AGM300 zone (y
= zone number (starting at 0), xx = 00 – 06)Data
Data Type Abbreviations
C ...................... Character
Float ................. Floating Point
I ........................ Integer
TIM................... Time
UC.................... Unsigned Character
UI ..................... Unsigned Integer
70Instruction 3015-4275
System Data Register Register 0x0010h R/W 54 bytes
Variable Type Length Description
Type UI 2 bytes Indicates EEPPROM has been initialized if value = 300
DO NOT MODIFY
REV Float 4 bytes Firmware Rev Level DO NOT MODIFY
SN UI 2 bytes Firmware Serial Number DO NOT MODIFY
Node UC 1 byte Network Slave Node # (valid values are 1-15). The default
is that indicated by the Node DIP Switch on main board.
Location C 13 bytes Array defining text name of unit
Stop_Bits C 1 byte Number of stop bits used in the AGM300 data stream.
Default = 1. Other available value is 2
Aud_Alarm UC 1 byte Sounds internal board buzzer on condition; 0 = no buzzer;
1= Alarm; 2=Fault; 3=Leak; 4=Spill; 5=Evacuate; 6=Monitor
Off line (DEFAULT = 0)
Alarm_Ack_
Mode
Num_Zones UC 1 byte Number of install zones (Value initialized during auto
UNUSED TIM 13 bytes UNUSED
Rezero_Mode UC 1 byte Defines rezero mode. Auto Rezero = 0; Rezero every
Hold_Time UI 2 byte Length of zone hold interval in minutes (DEFAULT = 15
Det_Limit UC 1 byte Minimum detection limit (in PPM). Concentrations less
Avg_Size UC 1 byte Size of running average used in computing PPM value. DO
than or equal this value will read as 0 PPM (DEFUALT = 0
PPM)
NOT MODIFY.
0.16mA/PPM)
MINUTES)
and AGM300 or MODBUS master and AGM300 depending
on the Network topology). Default=9 (19.2K); other values
are 8=9600, 7=4800
UNUSED UI 2 bytes UNUSED
Instruction 3015-4275 71
Status Register Register 0x0011h R/W 10 bytes
Variable Type Length Description
Mode UC 1 byte Defines Operating Mode of AGM300. 0 = normal Mode; 1
= Zone_Hold Mode; 2 = Diagnostic Mode; 3 = Service
mode. DO NOT MODIFY (use zone hold register or
service mode register to change this parameter)
State UC 1 byte Defines AGM300 Current State. 0 = Idle; 1 = Sampling; 2
= Zeroing; 3 = Warm Up, 4 = Pressure Check DO NOT
MODIFY
Measuring UC 1 byte Value = 1 if unit is acquiring detector signal for running avg.
DO NOT MODIFY
Active_Zone UC 1 byte Current Zone being checked. 0=zone1, 1=zone2, etc.
Max _Alarm UC 1 byte Indicates highest non-acknowledged alarm level DO NOT
MODIFY
Alarm_Count UC 1 byte Number of alarms that are currently active DO NOT
MODIFY
UNUSED UC 1 byte UNUSED
Loop_Card UC 1 byte Value = 1 if 4-20mA card has been detected DO NOT
MODIFY
Fault UI 2 bytes See Note Below
Fault Flag Structure uses bitwise access to 16 bit word as defined below:
Bit 15 (MSB) Clipping Fault A/D out of range
Bit 14 Zero Fault Zero voltage outside factory limits
Bit 13 No Flow No flow on any zone
Bit 12 Purge Flow No flow on purge
Bit 11 Zone Flow No flow on a particular zone(s)
Bit 10 Trigger Fault IR Source clock trigger missing
Bit 9 Unused
Bit 8 Unused
Bit 7 Config. Fault No Zones Enabled
Bit 6 Unused
Bit 5 Unused
Bit 4 Loop Fault Open Current loop
Bit 3 RS-485 Fault Comm Error
Bit 2 Pressure Fault Pressure out of normal operating range
Bit 1 Bench Temp Fault Bench temperature out of normal operating range
Bit 0 (LSB) Box Temp Fault Box temperature fault
72Instruction 3015-4275
Zone Data Register 0x12xxh R/W 78 bytes
Each zone for an AGM300 has a separate Zone data structure that is 78 bytes long. The zone number is the
low order byte in the register address (i.e., Zone 1 data register = 0x1201h)
Variable Type Length Description
Location C 13 bytes 13 byte array, Alpha Numeric Description or Name of Zone
Flow OK UC 1 byte Status of Flow check. Value of 1 indicates flow check is
good. DO NOT MODIFY
Refrig. Type UC 1 byte See note 1 Below (DEFAULT = R134a)
Distance UI 2 bytes Zone Tubing Length (in feet) (DEFAULT = 100 feet)
Zone Temp I 2 bytes
Concentration Float 4 bytes Last Measured concentrations (uM/L) DO NOT MODIFY
Concentration2 Float 4 bytes Last Measured concentration (PPM) DO NOT MODIFY
Alarm Ack UC 1 bytes Set value to 1 to acknowledge Alarm. NOTE: AGM300 will
Leak Level UI 2 bytes Level to trigger a leak alarm (in PPM) (DEFAULT = 100)
Spill Level UI 2 bytes Level to trigger a spill alarm (in PPM) (DEFAULT = 300)
Evac Level UI 2 bytes Level to trigger a evacuate alarm (in PPM) (DEFAULT =
Peak PPM UI 2 bytes Highest Recorded PPM in zone
Peak Time TIM 13 bytes Date an time of highest peak (see note 2 for format)
Alarm Time TIM 13 bytes Date and time of last alarm (see note 2 for format)
Not Used 13 bytes
Log Interval UI 2 bytes Number of minutes between Log entries (DEFAULT =
Avg temp at zone (degrees C) (DEFAULT = 25°C)
reset this byte to 0 when the Alarm byte (below) is = 0 and
zone in alarm is sampled. If the alarm condition/byte
increases (leak>>spill or spill>>evac) the AGM300 will also
reset this byte to 0
evac.
500)
1440)
NOTE 1: Refrigerant Types Defined from 00h to 20h in the following order : 00h=R11, 01h=R12, 02h=R22,
03h=R23, 04h=R113, 05h=R114, 06h=R123, 07h=R124, 08h=R134a, 09h=R401a, 0Ah=R402a, 0Bh=R402b,
0Ch=R404a, 0Dh=R407a, 0Eh=R407c, 0Fh=R409a, 10h=R410a, 11h=R500, 12h=R502, 13h=R503,
14h=R507, 15h=R508b, 16h=H1301, 17h=R408a, 18h=Future2, 19h=Future3, 1Ah=Future4, 1Bh=Future5,
1Ch=Future6, 1Dh=Future7, 1Eh=New1, 1Fh=New2, 20h=New3
NOTE 2: Time Structure Format consists of 13 unsigned character types. They are 1 second digit, 10 second
digit, 1 minute digit, 10 minute digit, 1 hour digit, 10 hour digit, 1 day digit, 10 day digit, 1 month digit, 10 month
digit, 1 year digit, 10 year digit, last byte is unused.
Instruction 3015-4275 73
Notes on Alarms and Alarm Acknowledge
The AGM300 can be operated in two different alarm acknowledge modes, Auto and Manual (set via the
alarm_ack_mode variable in the system data register). For purposes of this discussion, the term “Alarm” refers
to an AGM300 state where the alarm light is on and the appropriate alarm relay is activated. The term “Alarm
condition” refers to the external condition (i.e., refrigerant leak) that initially causes the AGM300 to go into an
alarm. If an alarm occurs it can be handled in one of 3 ways.
1. Non-Latching Mode. This mode is enabled by setting the AUTO_ACK_MODE parameter in the system
register to “1”. In this mode, if an alarm condition occurs an AGM300 alarm will be created. If the alarm
condition is subsequently removed, the AGM300 alarm will automatically be cleared by the AGM300 when
the zone in alarm is sampled “clear”. Note, in this mode of operation, it is possible for an alarm to occur
and be cleared without user or MODBUS master intervention. If this is the case, the only evidence of the
alarm would be contained in the AGM300 alarm log.
2. Latching Mode with Silence. This mode is enabled by setting the AUTO_ACK_MODE in the system
register to “0”. In this mode, if an alarm condition occurs, an AGM300 alarm will be created. In order for
the alarm to be removed the MODBUS master will write a “0” to the ALARM parameter in the ZONE
register. This will cause the alarm to be “silenced” in the AGM300 (i.e., the alarm relays will return to their
normal state and the ALARM lamp will be extinguished). The next time the zone with the alarm condition is
sampled, if the alarm condition still exists, the alarm will be reactivated and the alarm parameter will be
reset to “1” in the AGM300. Otherwise, if the alarm condition has cleared, no further action is required and
normal operation will resume.
3. Latching Mode without Silence. This mode is enabled by setting the AUTO_ACK_MODE in the system
register to “0”. In this mode, if an alarm condition occurs, an AGM300 alarm will be created. The AGM300
MODBUS master will then write a “1” to the ALARM ACK parameter in the zone register. The alarm will
continue to persists (i.e., Relays in alarm state and Alarm light on) until the offending zone is sampled and
no alarm condition is detected. At that point, the ALARM ACK parameter is automatically cleared by the
AGM300, as is the ALARM parameter. NOTE: If the ALARM ACK parameter is set to “1” and the ALARM
CONDITION is upgraded (from leak to spill, or spill to evacuate) the ALARM ACK parameter will
automatically be cleared to “0” by the AGM300.
74Instruction 3015-4275
Cal Data Register Register 0x0014h R/W 174 bytes
Variable Type Length Description
Factor Float 132 bytes 33 element array containing cal factors for each of the 33
gases. Order of Cal Factor is defined in Note 1 under Zone
Data
Curve UC 3 bytes Existing Master Curve to use for user defined “NEW GAS”
New Gas Name C 39 bytes 3 x 13 array that contains the names for each of 3 new
gases
NOTE: “Future” Gases are gases that will be added to the library at a later date. They will require generation
of new cal curves that will be added to the code. “New” Gases can be added in the field by selecting a similar
existing cal curve and then defining a cal factor that will bring the accuracy within the desired range. It is
strongly recommended that any New Gas curves that are added be done in conjunction with help from
Bacharach, Inc.
Date Time Register Register 0x0015h R/W 14 bytes
Variable Type Length Description
Date_Time Time 14 bytes Contains current time and date. Structure is defined as in
note 2 of zone data
Time Structure Format consists of 14 unsigned character types. They are 1 second digit, 10 second digit, 1
minute digit, 10 minute digit, 1 hour digit, 10 hour digit, a day digit, 10 day digit, 1 month digit, 10 month digit, 1
year digit, 10 year digit, day of the week, last byte is unused.
Instruction 3015-4275 75
Sensor Data Register Register 0x0016h R 82 bytes
Variable Type Length Description
Pressure Float 4 Manifold Pressure is PSIA
P_Volts Float 4 Pressure sensor output Voltage
Vacuum_P Float 4 Pressure with all value closed and pump on in PSIA
Ambient_P Float 4 Absolute Ambient Pressure in PSIA
Box_T Float 4 Enclosure Temperature in Degrees C
Box_T_Volts Float 4 Box temp sensor output voltage
Bench_T Float 4 Optical bench temperature in Degrees C
Bench_T_Volts Float 4 Bench temp sensor output voltage
Bench_Z_T Float 4 Optical bench temp in degrees C at last zero interval
Box_Z_T Float 4 Box temp in degrees C at last zeroing
PkPk_int UI 2 Current peak to peak A/D counts from detector
PkPk Float 4 Current peak to peak voltage from detector
Ave_PkPk Float 4 Running average voltage from detector
Zero_PkPk Float 4 Voltage measured at last zeroing
Noise Float 4 Largest Change in running average
AU Float 4 Current absorbance value
Ave_AU Float 4 Running Average of absorbance level
Bench_PPM Float 4 PPM in bench based on zone gas selection (uncorrected
for pressure and temperature)
STP_PPM Float 4 PPM corrected to STP (1 atm, 25 deg C)
Bench_UML Float 4 Micromoles/liter in bench (uncorrected0
Ambient_UML Float 4 Micromoles/liter corrected to ambient pressure
76Instruction 3015-4275
Release Zone Hold Register Register 0x0017h W 10 bytes
Variable Type Length Description
Rel_Hold * *
See description of STATUS REGISTER
Hold Zone Register Register 0x0018h W 10 bytes
Variable Type Length Description
Zone_Hold * *
See description of STATUS REGISTER
Notes Concerning the AGM300 Hold Mode
The AGM300 can be made to hold or “dwell” on a particular zone if necessary. The length of the hold time is
defined by the HOLD TIME parameter in the System Data Register. In order to place the AGM300 into hold
mode use the following sequence:
• Read the AGM300 Status Register (0x0011h)
• Modify the content of the status register structure to change the MODE parameter to zone hold mode and
the active zone parameter to the zone which you wish to hold
•Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER
COMMAND to the HOLD ZONE REGISTER (0x0018h).
To Release the Zone Hold Use the Following Sequence of Steps
• Read the AGM300 Status Register (0x0011h)
• Modify the content of the status register to change the MODE parameter to normal mode and the active
zone parameter to the zone which you would like to resume normal activity on
•Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER
COMMAND to the RELEASE HOLD REGISTER (0x0017h).
Instruction 3015-4275 77
Fault Log Register Register 0x1900, 0x1901h R 302 bytes
These registers contain the 20 most recent fault events, the time they occurred, and a pointer to the most
recent event. The data is split into 2 registers. The first register contains 200 bytes and the second register
contains 102 bytes. The results of these two register reads should be recombined into the Fault Log Data
Structure after both have been received
Variable Type Length Description
Fault UI 40 bytes 20 most recent fault events. Each event is decoded as
indicated in Fault Flag Structure given after the Status
Register Description
Time TIM 260 bytes Time of each fault occurrence. TIM value as defined in
NOTE 2 of Zone Data
Ptr UC 1 byte Pointer to most recent event
Unused UC 1 byte
Alarm Log Register Register 0x1A00h, 0x1A01h, 0x1A02h R 582 bytes
These registers contain the 20 most recent alarm events, the time they occurred, and a pointer to the most
recent event. The data is split into 3 registers and should be recombined into an appropriate structure after all
three registers have been received. Register 0x1A00h contain 200 bytes, Register 0x1A01h contains 200
bytes, and register 0x1A02h contains 181 bytes.
Variable Type Length Description
Event UC 320 bytes 20 most recent alarm events. Each event contains 1 byte
for each zone. Each zone Byte is defined as 0=No Alarm,
1=Leak Alarm, 2=Spill Alarm, 3=Evac Alarm.
Time TIM 260 bytes Time of each alarm event. TIM value as defined in NOTE 2
of Zone Data
Ptr UC 1 byte Pointer to most recent event
Unused UC 1 byte
78Instruction 3015-4275
Service Mode Register Register 0x001Bh W 10 bytes
Variable Type Length Description
Rel_Svc_Mode * *
See description of STATUS REGISTER
Release Service Mode Register Register 0x001Ch W 10 bytes
Variable Type Length Description
Ent Svc_Mode * *
See description of STATUS REGISTER
Notes Concerning the AGM300 Service Mode
The AGM300 can be placed into service mode if necessary. During service mode the unit will take no
measurements, any and all alarms are silenced, and all relays are opened. The unit automatically comes out
of service mode after a preset interval defined by the service_mode_TO parameter in the System Data
Register. In order to place the AGM300 into service mode use the following sequence:
• Read the AGM300 Status Register (0x0011h)
• Modify the content of the status register structure to change the MODE parameter to service mode.
• Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER
COMMAND to the SERVICE MODE REGISTER (0x001Bh).
To Release the Unit from Service Mode Use the
Following Sequence of Steps
• Read the AGM300 Status Register (0x0011h)
• Modify the content of the status register to change the MODE parameter to normal mode.
• Send this updated status register structure back to the AGM300 using PRESET MULTIPLE REGISTER
COMMAND to the RELEASE SERVICE MODE REGISTER (0x001Ch).
Instruction 3015-4275 79
PPM Register Register 0x001Eh R 32 bytes
Variable Type Length Description
PPM UI 32 bytes 16 Unsigned Integers that represent the PPM values for
each AGM300 zone
NOTE: 16 values are returned independent of the number of actual zones installed in the unit. The master
device is required to know how many zones are installed in the unit (available in the System Register) in order
to properly interpret the data.
Zone Log Registers Register 0x3xyyh R 1502 bytes
These registers are used to transfer the zone log data. Each zone has a circular log of 100 past data points.
The period between data points is defined by the Log Interval parameter in each corresponding Zone Data
Register. The data for each zone is defined by the “x” place in the above register address. For zone 1 the
Register address is 0x30yyh, for zone 2 the register address is 0x31yyh, etc. The data for each zone is sent in
8 consecutive registers due to MODBUS RTU message length constrains. The addresses are defined by the
“yy” place in the above address. For zone 1, all log data can be obtained by reading 0x3000h, 0x3001h,
0x3002h, …… , 0x3007h. The first seven registers contain 200 bytes each and the last register contains 102
bytes. After all registers have been received the data should be reassembled into the full data structure.
Variable Type Length Description
Index UI 2
Time TIM 1300
PPM UI 200
Time record for each of the 100 log points. The format
for the TIM type is defined in note 2 of zone data
Last 100 log points (2 byes per point)
Point to current reading
MODBUS EXCEPTION RESPONSES
The following MODBUS exception response are supported by the AGM300:
01 Illegal Function
02 Illegal Data Address
06 Slave Device Busy (Occurs only when AGM300 is connected to the bus through an ADM800 and the
ADM800 is not in the SYSTEM or ZONE VIEW screen)
80Instruction 3015-4275
WARRANTY and SERVICE
Warranty
Subject to the terms herein, Seller warrants the original equipment cataloged or manufactured by the Seller and
furnished hereunder is free from defects in material and workmanship, and will be of the kind and quality
designated or described on the quotation. The Seller will warrant the original equipment for 24 months from the
date of shipment from the manufacturing facility unless different or additional conditions are specified and shall
be binding through a written contract signed by an officer of the Seller.
Seller also warrants that certain consumable parts as hereunder identified have a one (1) year warranty period
from the date of shipment and will be free from all defects in material during that period. Seller does not
warrant these parts however, beyond the initial installation due to variables associated with normal usage.
These certain consumable parts include, but are not limited to, the air flow filters.
If within 24 months of the date of shipment, the equipment does not meet the warranties specified above, and
Purchaser notified Seller of this promptly, Seller shall there upon correct any such defects or any nonconformance to the specifications within a reasonable time period. Material found to be defective shall be
returned to the seller freight prepaid. At the Seller’s option, the defective material shall be repaired or replaced
and returned to the purchaser via the lowest freight rate available. Any repairs or alternations made by unauthorized personnel will automatically void warranty.
Labor cost for warranty service at the manufacturing facility is the Seller’s responsibility for a period of 90 days
following date of shipment. Beyond 90 days, Purchaser is responsible for all labor costs. Purchaser must
contact the Seller’s Service Department prior to shipment and obtain a Return Authorization (RA) number. The
package must be clearly marked with the assigned RA number. Purchaser may elect to have Seller’s Service
Department repair the equipment at Purchaser’s facility. Purchaser must contact Seller’s Service Department
to arrange for a Service call. Parts will be free under the above terms, but there will be a charge for labor and
travel expenses from Seller’s facility in New Kensington, PA..
The conditions of any tests or equipment hereunder alleged to be defective shall be mutually agreed upon and
Seller shall be notified of, and may be present or represented at all tests that may be made. Seller’s liability to
Purchaser or that of Seller’s Agent/Representative, arising out of the supplying of the equipment or its use,
whether based on warranty, contract, or negligence shall not in any case, exceed the cost of correcting defects
in the equipment as herein provided but shall, in all events, be limited to a maximum of the purchase price.
Upon the expiration of the applicable warranty period mentioned above, all such liability shall terminate. The
foregoing shall constitute Purchaser’s sole remedy and Seller’s sole liability. IN NO EVENT SHALL SELLER
BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Register Your Warranty by Visiting
www.bacharach-inc.com
Service
Pursuant to the stated warranty, Bacharach, Inc. warrants the products to be free of manufacturers defect for
two (2) years from the date of shipment or installation and will replace any part free of charge during that period.
Labor beyond ninety (90) days of shipment or installation is subject to charge. FAILURE TO LOCATE THE
AGM300 OR ADM800 IN A LOCATION COMPATIBLE WITH THE CRITERIA SET FORTH IN THIS MANUAL
CONSTITUTE ABUSE OF THE EQUIPMENT AND MAY VOID THE WARRANTY. Shipments are tracked by
the factory and the purchaser will be responsible for providing acceptable documentation to prove the
installation date. FAILURE TO NOTIFY THE FACTORY WITHIN TWO (2) WEEKS OF INSTALLATION OF THE EQUIPMENT WILL VOID THE COVERAGE OF THE LABOR SPECIFIED IN THE WARRANTY. Should
any of the products covered (refer to following section - Products Covered under Warranty and Service Policy)
incur a failure or damage contact the factory service department (724-334-5051) and request instructions.
Instruction 3015-4275 81
Return Procedure
To return equipment to the factory for repair a Return Authorization (RA) number should be requested from
the factory. Equipment will not be received without an RA number. Returned equipment should be sent to
the factory at the following address:
Bacharach, Inc.
621 Hunt Valley Circle
New Kensington, PA 15068
Attn.: Service Department
Field Repair
Field repair of equipment will be considered after all reasonable attempts to diagnose and rectify the
problem via phone or fax have been exhausted or if return of the equipment to the factory is not practical.
To initiate warranty service in the field, a customer purchase order must be issued, prior to dispatch, for
the estimated travel time, expenses and applicable service fees for a Bacharach representative to travel to
the site. Bacharach will bill expenses to the customer at actual cost. The customer will be invoiced for all
applicable charges for parts, labor and expense at the Non-Warranty rates if it has been determined that
the failure is a result of abuse of the equipment, improper installation, or failure to thoroughly read and
comply with the instructions provided in the Operations and /or Service Manuals. Scheduling of all field
servicing is at the discretion of the Factory Service Department and will be based upon customer need and
the availability of personnel. Warranty field service shall be limited to the continental United States.
Bacharach, Inc. is not liable for any charges, from the customer, purchaser or any third party that may be
acting on the behalf of the purchaser, customer or end user, resulting from non-warranty field service, field
upgrades, preventative maintenance, etc. Bacharach, Inc. is not liable for any charges, from the customer,
purchaser or any third party that may be acting on the behalf of the purchaser, customer or end user,
resulting from warranty field service or repair activities unless prior approval is granted by an authorized
member of Bacharach, Inc. prior the dispatch and performance of the field service or repair activity. This is
to include but not limited to: manpower requirements for Bacharach and/or non-Bacharach personnel to
perform or assist with the field service or repair activity.
Products Covered under Warranty and Service Policy
The following items are covered under the stated warranty for Parts and Labor:
Model
AGM300 Ammonia Gas Monitor
ADM800 Ammonia Display Module
Description
82Instruction 3015-4275
AGM300 - Specifications
Product Type: Ammonia gas, multiple area infrared monitoring system for low level continuous
monitoring of ammonia refrigerant gas used in most commercial refrigeration systems.
System design supports compliance to the refrigerant monitoring requirements of
ANS/BSR ASHRE 15-1994.
Coverage: 4-point standard, expandable to 16 points in 4 point increments
and display functionality to support the AGM300 Ammonia Gas Monitor. The system
design supports compliance to the refrigerant monitoring requirements of ANS/BSR
ASHRE 15-1994.
Inputs:The ADM800 accepts inputs from up to four AGM300 monitors. It offers a wide variety
of displays and can fully program any associated monitor.
Display: Back lit LCD
Power Indication: Green LED glows when AC power is applied
Alarm Indication: Red LED glows and alarm condition is displayed
Fault Indication: Yellow LED glows and fault condition is displayed
Password Protection: The ADM800 can be password protected to prevent the unauthorized editing of setup
parameters without disturbing the ability to monitor system outputs
Power Safety Mode: Fully automatic system reset; all parameters maintained
Monitoring Distance: Up to 4500 feet from furthest AGM300
Communications: Full two-way communication with AGM300 monitors via RS-485 interface. A second
RS-485 interface provided for connection to a Building Management System.
Relays: Two SDDT programmable alarm contacts are provided (Rated 5 amp 120 VAC)