Babbitt LS8000-2 User Manual

LLSS88000000//22 LLEEVVEELL SSWWIITTCCHH
OOWWNNEERRSS MMAANNUUAALL
♦♦ IINNSSTTAALLLLAATTIIOONN ♦♦ CCAALLIIBBRRAATTIIOONN ♦♦ TTRROOUUBBLLEESSHHOOOOTTIINNGG
♦ WWAARRRRAANNTTYY
BABBITT INTERNATIONAL, INC.
P.O. Box 70094 Houston, Texas 77270 (713) 467-4438
TABLE OF CONTENTS
Page
1. Description -------------------------------------------------------------- 1
A. General Description ----------------------------------- 1
B. Specifications -------------------------------------------- 2
C. Ordering Information ----------------------------------- 2
2. Theory of Operation -------------------------------------------- 3
3. Installation-------------------------------------------------------------- 3
A. Inspection ----------------------------------------------------- 3
B. Physical Installation -------------------------------------------- 3
C. Installing the Receiver ----------------------------------- 12
D. Typical Applications and Wiring Diagrams ----------------- 4-11
4. Calibration -------------------------------------------------------------- 12
A. Set Switches 1 and 2 for FSH or FSL ----------------- 12
B. Setting POR and LATCH Dip Switches ----------------- 12
C. Calibrate the Low Setpoint ----------------------------------- 13
D. Calibrate the High Setpoint -------------------------- 13
E. 2 Probe Calibration -------------------------------------------- 13
5. Maintenance and Troubleshooting -------------------------- 14
6. Warranty -------------------------------------------------------------- 15
1. DESCRIPTION
A. General Description
The LS8000/2 dual point level switch is designed to sense material at two points in a tank, hopper or sump. The unit consists of a receiver which may be remote mounted from the sensing probe(s).
The receiver is designed to work in 4 different modes:
1. Sense 2 points along a vertically mounted probe and maintain a level between them. (Fig 1A)
2. Control 2 separate probes in the same tank and maintain a level between them.( Fig 2A)
3. Control 2 probes in different locations. (Fig 3A)
4. Four set points on one probe. (See page 10 )
The receiver has 3 SPDT 5 amp relays for control: one relay for the high set point, 1 for the low setpoint and a latching relay for automatic filling or emptying between the 2 setpoints. The latching relay would not configured as Fig. 3A.
Whenever the LS8000/2 is used in the “2 points or 4 points on 1 probe” configuration, a coated probe (not bare steel rod) must be used.
LS8000/2 DUAL POINT
LEVEL SWITCH
be used if
1
B. Specifications
Electrical
Environmental
Electronics: -40° F to 185° F
C. Ordering Information
Power: 115 VAC (±15%) 50/60 Hz. 3 watts,
standard.
(12 VDC, 24 VDC or 230 VAC optional)
Output: 3 relays, each with 1 form C contact, SPDT,
10 amp resistive at 115 vac, 8 amp at 220 VAC, 5 amp at 30 VDC
Fuse: On board, 250 mA RF Frequency: Approximately 700 KHz
Hazardous Area: Class I, Group C & D, Class II, Group E, F
and G Receiver: open printed circuit board can be put in enclosure as required by application.
Temperature: Probe: -30° F to 400° F (Higher on request)
Pressure: Probe: 1500 psi @ 75° F. (Higher ranges available on request). Construction: Probe: All wetted parts, 316 SS, Teflon and Viton. (A coating is applied in
some applications to the 316SS probe.)
2
2. THEORY OF OPERATION
The LS8000/2 employs a radio frequency (RF) balanced impedance bridge circuit to detect the level of material along a vertically mounted probe. As the fluid level rises along the probe, the output of the bridge changes proportionally to the fluid level. The setpoint potentiometers determine at what level the circuit detects the low and high setpoints. The receiver may also control 2 independent probes in the same or different tanks. Each probe has a separate transmitter and is connected to the receiver with a twisted, shielded pair of wires.
3. INSTALLATION
*CAUTION: ALL INSTALLATION AND WIRING MUST CONFORM TO NEC AND ALL OTHER LOCAL ELECTRICAL CODES. TAKE SPECIAL CARE IN OBSERVING HAZARDOUS AREA SAFETY PROCEDURES. WE ASSUME NO LIABILITY FOR IMPROPERLY INSTALLED OR WIRED UNITS.
A. Inspection
After unpacking the LS8000/2, visually inspect the unit for any damages. Please advise the factory or your local distributor of any damage.
A complete unit should consist of the following:
1. An explosion proof enclosure(s) with probe(s) attached.
2. A transmitter module in each explosion proof enclosure.
3. The LS8000/2/R receiver card.
4. A plastic snaptrack to mount the receiver card.
B. Physical Installation of Transmitter Module and Probe
1) The LS8000/2 is installed into the vessel wall using a ¾” NPT connection. This can be either a threaded coupling or a tapped entry such as a flange.
2) The teflon insulator should always extend at least 2” through the vessel wall.
3) Always check for physical room around the location you have chosen to allow for installation. Allow 2 ¾” turning radius to screw the probe in and clearance above for the length of the probe.
4) CAUTION: Always take the necessary safety precautions when cutting or welding in the coupling for the LS8000/2.
a) Tag and lock out the electrical power to the equipment that services the vessels. b) Check liquid or dry powders that create a gas in the vessel for oxygen as well as the explosion factor.
(All dust will explode.)
c) Vessels that are cross vented have to be isolated.
5) Screw the LS8000/2 into the connection provided. In dry material application, no sealant on threads is required. In liquid, Teflon or a good pipe thread sealant may be used.
6) The LS8000/2 has a ¾” NPT conduit entry. When wiring these units, conform to the National Electrical Code and any other city or company codes.
7) Always install the electrical connection into the ¾” NPT conduit entry so water will not follow the connection routing into the threads of the conduit hub. To guarantee that condensation and water will stay outside the unit, install a EYSM unilet before each LS8000/2 and fill with explosion proof sealing cement
8) When required, the LS8000/2 probe can be bent to meet your special application. Remember to allow 2” of clearance between the probe and the vessel wall. If the probe is to be used in a pressure application, the factory must bend the probe to your specifications.
9) Location of probes on high level installations is more critical on dry material than liquids. Note the following: a) For dry materials, mount the LS8000/2 in the top of the vessel whenever possible. (This allows you to
lengthen the probe if necessary.)
b) Avoid mounting the LS8000/2 near the product inlet, vent return lines, dust collectors and vessel
discharge openings on dry materials. Turbulence around these areas can cause erratic detection unless the probe is long enough. On old installations it might be wise to fill the vessel first to determine the length or location of the probe.
CAUTION: Always take safety precautions before opening vessels inspection.
c) On gravity filled vessels, take into consideration the angle of repose formed by the product. d) When using the LS8000/2 to stop the flow by means of a butterfly valve or knifegate, make sure the
probe is long enough to allow time to close these slow moving valves.
e) In small vessels where a good location is hard to find, it may be necessary to put a baffle plate between
the probe and the product inlet to keep product off of the probe as it fills.
3
4