Azbil VY51 J0012, VY51 J0015, VY51 J0013, VY51 J0011, VY51 J0014 Specifications & Instructions

...
AB-7057
Specifications/Instructions
ACTIVAL
TM
Motorized Two-Way Valve with Flanged-End Connection
(PN16 / GG-20)
Overview
ACTIVALTM Model VY51_ _J is a series of motorized two-
way valves with anged-end connection. Rotary valve and actuator are integrated in a single unit.
Valve size ranges from DN15 (1/2”) to DN80 (3”), and valve body rating corresponds to ISO PN16.
Actuator has a reversible synchronous motor, which operates at a low voltage of 24 V AC.
5 kinds of control signals are available to operate ACTIVAL.
1. Nominal 135 Ω feedback potentiometer (built-in): Provides proportional control in combination with a DDC controller (e.g., Inlex
2. Nominal 135 Ω resistance input: Provides proportional control in combination with a proportional controlled electric controller (e.g, Neostat Model TY900_Z, Model TY9800).
3. 4-20 mA DC input: Provides proportional control in combination with a DDC controller (e.g., Inlex R36).
4. 2-10 V DC input: Provides proportional control in combination with a DDC controller (e.g., Inlex
5. 0-10 V DC input: Provides proportional control in combination with a DDC controller.
TM
GC Model WY5111).
TM
GC Model WY5111, Model R35/
TM
AC Model WY5117).
DDC: Direct Digital Control
*
Features
Durable actuator with low power consumption.
Compact and lightweight:
Rotary motor actualizes small body and light weight.
Valve and actuator integrated in a single unit:
Pre-assembled body requires no adjustment.
A variety of control signals available:
- Nominal 135 Ω feedback potentiometer
- Nominal 135 Ω resistance input
- 4-20 mA DC input
- 2-10 V DC input
- 0-10 V DC input
Valve for chilled/hot water control and for steam control
applicable to high di󰀨erential pressure, with large Cv value, wide rangeability, and low leakage.
* Although our company name changed from Yamatake Corporation to Azbil Corporation on April 1, 2012, our former logo remains on this product.
Equal percentage ow characteristic.
2-10 V DC output (for position feedback) available with
4-20 mA DC input, 2-10 V DC input, and 0-10 V DC input types.
1
© 2010–2017 Azbil Corporation All Rights Reserved.
AB-7057
Safety Precautions
Please read instructions carefully and use the product as specied in this manual. Be sure to keep this manual near by for ready reference.
Restrictions on Use
This product was developed, designed, and manufactured for general air conditioning use. Do not use the product in a situation where human life may be at risk or for nuclear applications in radiation controlled areas.
If you wish to use the product in a radiation controlled area, please contact Azbil Corporation. Particularly when the product is used in the following applications where safety is required, implementation of fail-safe
design, redundant design, regular maintenance, etc., should be considered in order to use the product safely and reliably.
Safety devices for protecting the human body
Start/stop control devices for transportation machines
Aeronautical/aerospace machines
For system design, application design, instructions for use, or product applications, please contact Azbil Corporation. Azbil Corporation bears no responsibility for any result, or lack of result, deriving from the customer's use of the product.
WARNING
A
This product weighs 18 kg or over (depending on the models). To prevent hazardous accident and severe injury,
a U
move or carry the product with enough manpower or using a vehicle.
Do not disassemble the product. Disassembly may result in electrical shock or equipment damage.
a a a a
a a
a a a a
a a
a S a a a
CAUTION (1/2)
A
This product must be operated under the operating conditions (power, temperature, humidity, vibration, shock,
installation position, atmospheric condition, etc) specied in this manual to prevent equipment damage.
This product must be operated within its rated operating ranges specied in this manual. Failure to comply will
cause equipment damage.
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety
standards.
Avoid application that keeps the operating cycle of the product excessively frequent. Excessively frequent
operation may cause re or equipment failure.
All wiring must comply with local codes of indoor wiring and electric installation rules.
Install externally the protective device such as fuse or circuit breaker for your safety.
Install the product in the position as specied in this manual. Excessively tight connection of the valve to a pipe
and improper installation position may damage the valve.
After installation, make sure no uid leaks from the connecting parts of valve and pipes. Incorrect piping may
cause uid leakage.
Do not allow any foreign substance inside the piping. Flush the piping so that no foreign substance remains.
Attach a strainer in a pipe on the inow side of the product to prevent equipment damage.
Avoid using the product in an atmosphere containing oxidizing gas, explosive gas, etc. since it may damage the
actuator, valve, or their components.
Do not leave the controlled uid frozen to prevent equipment damage or uid leakage.
Do not put heavy load on the actuator.
Do not install the product nearby a steam coil or a hot-water (in high temperature) coil. High heat radiation may
result in an actuator malfunction.
Avoid touching the installed product (valve body, yoke, joint). When being used to control hot water or steam, it
may reach high temperature and may cause burn injury.
Disconnect power from the product (including the optional devices) before performing any wiring or maintenance
to prevent equipment damage.
Use crimp terminal lugs with insulation for electric wires to be connected to the screw terminals. Short-circuit or
electrical shock may occur without insulation.
Make sure all the wires are tightly connected to the screw terminals. Loose connection may cause re or heat
generation.
2
CAUTION (2/2)
A
Do not touch the moving parts of the product to prevent personal injury.
S
Do not stack unpacked products. Piled products without package will be polluted or damaged.
a
Dispose of this product as an industrial waste in accordance with your local regulations. Do not reuse all or part
a
of this product.
IMPORTANT: To control ACTIVAL with a third-party controller, please consult with Azbil Corporations’ sales personnel.
Model Numbers
Model VY51_ _J00_ _ is the model for the valve and actuator integrated into a single unit. The model number label is attached to the yoke. The control signal is indicated on the actuator label and on the wiring diagram label, as shown below.
Nominal 135 Ω feedback potentiometer: F.B. Pot
AB-7057
Nominal 135 Ω resistance input: 135
Ω
4-20 mA DC input: 4-20 mA
2-10 V DC input: 2-10 V
0-10 V DC input: 0-10 V
Base
model
number
VY51 Motorized two-way valve with anged-end connection
Actuator/valve Actuator Valve
Control
signal
Rating/
material
1 Nominal 135 Ω feedback potentiometer
2 Nominal 135 Ω resistance input 3 4 mA DC to 20 mA DC input with 2 V DC to 10 V DC position feedback output 4 2 V DC to 10 V DC input with 2 V DC to 10 V DC position feedback output 5 0 V DC to 10 V DC input with 2 V DC to 10 V DC position feedback output
Type
7 PN16 / GG-20 [for water] 8 PN16 / GG-20 [for steam]
J
00
Nominal
size/Cv
IEC IP54 protected and standard torque type actuator with terminal block (Mountable valve sizes: DN15 to DN80)
11 DN15 (1/2”) / 1.0 in Cv value 12 DN15 (1/2”) / 2.5 in Cv value 13 DN15 (1/2”) / 6.0 in Cv value 14 DN15 (1/2”) / 1.6 in Cv value 15 DN15 (1/2”) / 4.0 in Cv value 21 DN25 (1”) / 10 in Cv value 22 DN25 (1”) / 16 in Cv value 41 DN40 (1 42 DN40 (1 51 DN50 (2”) / 65 in Cv value 61 DN65 (2 81 DN80 (3”) / 125 in Cv value
1
/2”) / 25 in Cv value
1
/2”) / 40 in Cv value
1
/2”) / 95 in Cv value
Description
3
AB-7057
Specications
For weight, refer to the table shown in the section Dimensions.
zValve specications
Item Specication
Model Two-way valve with anged-end connection (raised face ange), proportional control
Body pressure rating PN16 (Max. working pressure: 1.6 MPa) End connection PN16 anged-end (equivalent to ISO 7005-2: 1988) Size, Cv, Close-o󰀨 rating
Note:
Close-o󰀨 ratings of the actuator in combination are shown on the right. Practical close-o󰀨 rating required for the valve controlling 175 °C steam is 0.8 MPa.
Materials Body Gray cast iron (GG-20)
Applicable uid
Allowable uid temperature 0 °C to 175 °C (Non-freezing) Flow characteristic Equal percentage Rangeability 100 : 1 Seat leakage 0.01 % of rated Cv value (0.0006 Cv or less for DN15 model) Paint Gray Actuator to be combined Integrated with the valve
Model number Nominal size Cv Close-o󰀨 ratings VY51_ _J0011 DN15 (1/2”) 1.0 1.0 MPa VY51_ _J0012 DN15 (1/2”) 2.5 1.0 MPa VY51_ _J0013 DN15 (1/2”) 6.0 1.0 MPa VY51_ _J0014 DN15 (1/2”) 1.6 1.0 MPa VY51_ _J0015 DN15 (1/2”) 4.0 1.0 MPa VY51_ _J0021 DN25 (1”) 10 1.0 MPa VY51_ _J0022 DN25 (1”) 16 1.0 MPa VY51_ _J0041 DN40 (1 VY51_ _J0042 DN40 (1 VY51_ _J0051 DN50 (2”) 65 1.0 MPa VY51_ _J0061 DN65 (2
1
/2”) 25 1.0 MPa
1
/2”) 40 1.0 MPa
1
/2”) 95 1.0 MPa
VY51_ _J0081 DN80 (3”) 125 0.7 MPa
Plug, stem Stainless steel Seat ring Heat-resistant PTFE Gland packing Inorganic ber Gasket Non-asbestos joint sheet Chilled/hot water, high temperature water, steam, brine (ethylene glycol solutions, 50 % max.)
zActuator specications
Item Specication Power supply 24 V AC ± 15 %, 50 Hz/60 Hz Power consumption Nominal 135 Ω feedback potentiometer type (Model VY511_J): 7 VA
Nominal 135 Ω resistance input type (Model VY512_J), 4-20 mA DC input type (Model VY513_J), 2-10 V DC input type (Model VY514_J),
0-10 V DC input type (Model VY515_J): 8 VA Timing 63 ± 5 sec (50 Hz) / 53 ± 5 sec (60 Hz) Control signal input - Nominal 135 Ω feedback potentiometer
(Total resistance: Nominal 135 Ω, Max. applied voltage: 5 V DC)
- Nominal 135 Ω resistance input
- 4 mA DC to 20 mA DC input (Input impedance: 100 Ω)
* Input impedance uctuates depending on temperature and other environmental conditions.
Therefore, a controller with 200 Ω or higher allowable load resistance is recommended.
- 2 V DC to 10 V DC input (Input impedance: 150 kΩ or higher)
* A controller with 100 kΩ or lower allowable load resistance is recommended.
- 0 V DC to 10 V DC input (Input impedance: 150 kΩ or higher)
* A controller with 100 kΩ or lower allowable load resistance is recommended.
Feedback signal output (only with 4-20 mA DC input, 2-10 V DC input, 0-10 V DC input types) Materials Case Cast aluminum alloy
Surface nishing Case None
Valve position indication Pointer located at the bottom of the actuator shows the position by pointing at the value of
Manual operation Available. Refer to the section Manually opening/closing the ACTIVAL. Wires connection M3.5 screw terminal connection Enclosure rating IEC IP54 (dust-proof and splash-proof) Insulation resistance Between terminal and case: 5 MΩ or higher at 500 V DC Dielectric strength Between terminal and case: 500 V AC/min with 5 mA or less leakage current
Range: 2 V DC (0 % position) to 10 V DC (100 % position)
Allowable load resistance: 10 kΩ or higher (Max. output current: 1mA)
Top cover, terminal cover Polycarbonate resin (Color: gray)
Yoke Steel plate
Yoke Electro-galvanized (Bright chromate nish)
the scale (0: close to 100: open) on front, rear, and bottom sides.
4
zValve and actuator (as a single unit) specications
A
50
100
175
0
F
Item Specication
Environmental conditions
Ambient temperature*
1
Rated operating condition Limit operating condition
-20 °C to 50 °C
-20 °C to 60 °C -20 °C to 70 °C
(Fluid temperature 0 °C to 150 °C)
-20 °C to 40 °C (Fluid temperature 150 °C to 175 °C)
Ambient humidity 5 %RH to 95 %RH Vibration
4.9 m/s2 (10 Hz to 150 Hz) 9.8 m/s2 (10 Hz to 150 Hz)
Notes: *1 Do not allow the uid to freeze.
2 Actuator shall be packed during transport and storage.
*
40
mbient temperature (°C)
-20 150
luid temperature (°C)
Installation locations Indoor / outdoor (Keep away from direct sunlight.) Installation orientation Installable in any position ranging from upright to sideways (90° tilted.)
* Always install in upright position outdoors.
Position for shipment 100 % (fully open) preset at factory.
Transport/storage
conditions (packaged*
19.6 m/s (10 Hz to 150 Hz)
2
AB-7057
2
)
zOptions
For options, separate order is required.
Item Specication Seal connector (Part No. 83104346-003) Auxiliary switches*
1
(Part No. 83174063-101)
Auxiliary potentiometer*
1
(Part No. 83165275-001)
Note: *1 Either the auxiliary switch or auxiliary potentiometer can be added, but not both. *2 If the applied current exceeds 100 mA, please contact Azbil Corporation.
Applicable wire size: f7 mm to f9 mm (Seal connector is necessary for IEC IP54 protection.) Number of switches: 2 (SW A and SW B) Maximum applied voltage/current: 30 V DC / 100 mA*2 DC (Inductive load includes inrush current.) Actuating position SW A: Adjustable between 0 % (fully closed) and 100 % (fully open) SW B: Adjustable between 0 % (fully closed) and 100 % (fully open) Number of potentiometer: 1 Total resistance: Nominal 1 k
Ω
Operating position: 0 % (fully closed) to 100 % (fully open) Max. applied voltage: 5 V DC
5
AB-7057
Note:
n
70 70
H
H
1
138
L1
L
t
φg φC
φ
Flow direction 82 85
Min. 100 (See Note.) Min. 300
N × φh
Top cover
Terminal cover
Top cover
Knockout hole
Yoke
Actuator
Valve body
P
J
O
P
S
Seat ring
g
g
:
Gland
Dimensions
138
D
Leave a clearance of 300 mm if you open the top cover after installatio (e.g., to set the auxiliary switch).
Model number
VY51_ _J001_ 15 213 75 108 50 16 65 95 46 14 4 4.6 VY51_ _J002_ 25 228 90 127 60 18 85 11 5 65 14 4 6.6 VY51_ _J004_ 40 241 103 165 82.5 20 11 0 150 84 19 4 10.0 VY51_ _J0051 50 245 107 178 89 20 125 165 99 19 4 11.5 VY51_ _J0061 65 262 124 190 90 22 145 185 118 19 4 16.0 VY51_ _J0081 80 263 125 203 100 22 160 200 132 19 8 18.5
Parts Identication
Sprin
Plu
Valve size
(DN)
H (mm) H
Figure 1. Dimensions and maintenance clearance (mm): Models VY51_ _J
(mm) L (mm) L1 (mm) t (mm)fC (mm)fD (mm)fg (mm)fh (mm) N
1
Terminal cover
ointer
oint
-ring
acking
tem
Figure 2. Parts identication
6
Weight
(kg)
Heat insulation
AB-7057
Correct mounting Incorrect mounting
Installation
zPrecautions for installation
CAUTION
A
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety
a a a a a
ACTIVAL Model VY5198J is the valve and actuator integrated into a single unit. Do not combine the valve with any other
actuator, or do not combine the actuator with any other valve.
To remove foreign substances inside the pipes, install a strainer with 40 or more meshes (with 80 or more meshes
recommended for steam control) on the in ow side of each valve. In case that the strainers cannot be installed on the in ow side of each valve, install it on the pipe diverting sections (sections diverting from main piping system to sub piping system).
Install the valve so that the  ow direction of process  uid agrees with the arrow indicated on the valve body.
standards.
Install the product in the position as specified in this manual. Excessively tight connection of piping and
improper installation position may damage the valve.
After piping installation, make sure no  uid leaks from the connecting parts. Incorrect piping may cause  uid
leakage.
Do not allow any foreign substance inside the piping. Flush the piping so that no foreign substance remains.
Attach a strainer in a pipe on the in ow side of the product to prevent equipment damage.
Disconnect power from the product (including the optional devices) before performing any wiring or maintenance
to prevent equipment damage.
zInstallation location
CAUTION
A
Avoid using the product in an atmosphere containing oxidizing gas, explosive gas, etc. since it may damage the
a a
IMPORTANT:
The top and the terminal covers might be corroded by chemicals and organic solvent or their vapor. Do not
expose the ACTIVAL to such substances/vapor.
When the ACTIVAL is used for steam humidifying, install a valve interlocking with air-conditioning unit on the
in ow side in case the ACTIVAL gets damaged.
Although the ACTIVAL can be used in high humidity environments (max. 95 %RH), do not immerse the
actuator in water.
Although the ACTIVAL can be used outdoors, be sure not to expose the ACTIVAL to direct sunlight.
Install the ACTIVAL in a position allowing easy access for maintenance and inspection. Fig. 1 shows the minimum
clearance for maintenance and inspection. When installing the ACTIVAL in a ceiling space, provide an access hole within the 50 cm radius of the ACTIVAL. And, place a drain pan under the valve.
Do not mount the ACTIVAL on a pipe where water hammer occurs, or where solid objects including slug may accumulate.
zMounting position
The ACTIVAL can be mounted in any position ranging from upright to sideways (90° tilted). The ACTIVAL should be installed with its actuator vertically positioned above the valve body. (See Fig. 3.) However, the ACTIVAL must be installed always in upright position outdoors.
actuator, valve, or their components.
Do not install the product nearby a steam coil or a hot-water (in high temperature) coil. High heat radiation may
result in an actuator malfunction.
Figure 3. Mounting position
7
AB-7057
Pointer
Joint
Hold the joint using a wrench a
zPiping
Check that the model number of the product is what you ordered. The model number is shown on the label attached to
the yoke.
Install a bypass pipe and gate valves on the inow, outow, and bypass sides. Also, install a strainer with 40 or more
meshes (with 80 or more meshes recommended for steam control) on the inow side.
When installing the ACTIVAL to the pipes, do not allow any object, such as chips, to get inside a pipe or valve. Valve
cannot fully close, or the valve seat may get damaged causing uid leakage, due to an object jammed inside the valve.
When piping, do not apply too much sealing material, such as solidifying liquid and tape, to the pipe connection sections
so that these materials ow into the valve. Valve cannot fully closes, or the valve seat may get damaged causing uid leakage, due to the sealing material jammed inside the valve.
Before activating the ACTIVAL, fully open (in 100 % position) the valve and ush the pipes (with the ACTIVAL installed) at
the maximum ow rate to remove all the foreign substances. (Factory preset position: 100 %)
For steam control, drain retained water (condensate) in piping. Install a trap on a pipe run which may retain condensate.
Condensate may cause water hummer or damage the valve and piping.
zHeat insulation
Do not apply heat insulation to the actuator or to the yoke, as shows in Fig. 2. If the yoke and the actuator are covered with insulation material, the pointer cannot be checked and may be distorted.
zFactory preset position
The actuator shaft is positioned at 100 % (in fully open position) for shipment. The shaft is thus completely turned clockwise, and the pointer points at ‘100’. (See Fig. 4.)
Figure 4. Pointer position for shipment
zManually opening/closing the ACTIVAL
IMPORTANT:
Manually opening/closing the ACTIVAL with the power (24 V AC) applied may damage the actuator.
To manually open/close the ACTIVAL, do not turn the joint beyond the fully open (100)/closed (0) mark.
To manually open/close the ACTIVAL, slowly turn the joint. If shock is sent to the actuator, the actuator may
get damaged.
Disconnect the power from the ACTIVAL before manually operating the ACTIVAL. As shown in Fig. 5, from the front of the ACTIVAL, hold the joint using a tool such as a wrench, and turn the joint slowly toward the set position.
nd turn slowly.
Figure 5. Manual operation
8
AB-7057
Step 1
Step 4
Change the actuator mounting
actuator on the yoke.
Step 2
Step 3
Change the yoke mounting
yoke on the valve.
Thermal insulation sheet
G
Valve stem
zAuxiliary switch / Auxiliary potentiometer (optional)
IMPORTANT:
The auxiliary switch/potentiometer is installed on site. Refer to the instructions supplied with the auxiliary
switch/potentiometer for installation.
Do not open the top cover except when adjusting the auxiliary switch/potentiometer. Close the top cover
instantly after adjusting the auxiliary switch/potentiometer.
Do not put any load on the top cover.
zProcedure to change the actuator mounting position
IMPORTANT:
Do not change the combination of the valve, yoke, and actuator.
Set the ACTIVAL (actuator and valve) in 100 % position when changing the mounting position. If the valve in
0 % position is assembled with the actuator in 100 % position, the actuator puts torque on the closed valve, and the gear of the actuator gets damaged.
1) Remove the screws connecting the actuator and the yoke. Lift the actuator and detach it from the yoke. Make sure that the groove on the top of the valve stem is parallel to the pipes (indicating the valve in 100 % position). <Step 1 in Fig. 6>
2) Remove the screws connecting the yoke and the valve. <Step 2 in Fig. 6>
3) Change the facing direction of the yoke. The yoke and actuator can be horizontally rotated every 90° (0°/90°/180°/270° from the factory preset position) to mount onto the valve.
4) A thermal insulation sheet is inserted between the yoke and the valve. When changing the mounting positions, reinsert the sheet and then t the yoke into the new mounting position.
5) Before xing the yoke to the valve with the screws, check that the actuator engages correctly with the valve stem (at the new mounting position). Check that the pointer of the actuator indicates 100 % position as well. Then, x the yoke to the valve. <Step 3 in Fig. 6>
6) Mount the actuator. Place the actuator, with its facing direction changed, on the yoke, and x them with the screws. <Step 4 in Fig. 6>
7) Check that the ACTIVAL with the mounting position changed operates smoothly (from 0 % to 100 %).
Lift off the actuator.
Detach the yoke from the valve.
position, and remount the
position, and remount the
roove
Figure 6. Changing the actuator mounting position
9
Loading...
+ 19 hidden pages