Azbil C15 Quick Reference Manual

CP-SP-1213E
Quick Reference Guide for Model C15
This guide offers a summary of key operations, parameter flowcharts, and settings, for convenient reference at the operation site. This guide is made for repeated use. Dirt wipes off easily and even notes written with an oil­based felt-tip pen can be removed with an eraser. If more detailed information on model C15 is needed, refer to the user's manuals: CP-SP-1147E for basic operation and CP-SP-1148E for installation and configuration.
The most convenient way to configure the C15 is with the Smart Loader Package (model No. SLP-C35J50). Please contact the azbil Group or a distributor for more information.
Upper display
Indicators during AT
Lower display
[mode] key
Various indicators
Mode indicators
[para] key
[ ], [ ], and [ ] keys
Loader connector (bottom panel)
Upper display This display shows either the PV value or the display value and set value for each displayed item. If an alarm is triggered, the
normal display and alarm code are displayed alternately. During auto tuning (AT), the rightmost decimal point flashes twice repeatedly.
Lower display This display shows either the SP/MV/CT or the display value and set value for each displayed item. The rightmost decimal
point lights up or flashes to show RUN/READY mode or communications status, depending on the setting.
Mode indicators rdy: Lights when READY (RUN mode if not lit)
man: Lights when MANUAL (AUTO mode if not lit) ev1, ev2, ev3: Lights when event relays are ON ot1, ot2: Lights when the control output is ON (always lit when the current output is used)
[mode] key
When this key is pressed and held for more than 1 second in the operation display mode, any of the following operations
from 0 to 7 which have been set previously can be executed: 0 : Mode key does not operate (Initial value) 1 : AUTO/MANUAL mode selection 2 : RUN/READY mode selection 3 : AT (Auto Tuning) start/stop selection 4 : LSP (Local SP) group selection 5 : Release all DO (Digital Output) latches 6 : Mode key does not operate 7 : ON/OFF selection of communication DI1
When pressing the [mode] key in the setup display mode, the display is changed to the operation display
[para] key
[<], [
] , [ ] keys
Loader connector The Smart Loader connector is on the bottom of the C15. Use the dedicated cable that is included with the Smart Loader
: Initial value
(Not for use in Japan)
This key is used to change the display item.
When this key is kept pressed for 2 s. or longer in the operation display mode, the display is then changed to the setup
display
Theses keys are used to increase or decrease the numeric value, or to shift the digit.
Package to connect the controller to a PC.
1
Flowchart of key operations and displays
When the power is turned ON
PV value
LSP group number
Manipulated variable
Heat manipulated variable
Cool manipulated variable
Upper and lower displays remain off for 6s after power ON. Each mode indicator lights sequentially, and then the operation display appears.
[mode]
(AUTO)
For change from
MANUAL to AUTO
to
(2)
(2) (1)
3
[para] key
*
2-second press + hold of [para] key
(A)
(MANUAL)
For change from
AUTO to MANUAL
to
(1)
SP value
SP value
1
*
MV value
MV value
[SP] [Event] [PID] [Parameter] [Extended tuning]
MV value
Timer remaining time 3
Internal event 3 delay time
[para] key
3
*
[para] key
to
(A)
2-second press + hold of [para] key
2
Some items are not displayed depending on the availability of optional functions, model number, display setup (
) and display level (
C78
Pressing [para] key while changing settings has the effect of canceling and moving to the next item.
C79
).
Operation displays
C73
to
Analog inputControl actions
PV value
AT progress value
Internal event 3 sub setting
Setting value
to
(2)
2-second press + hold of [para] key
2
*
[Setup] [
(B)
SPContinuous outputsCommunications
CT1
Current value
CT2
Current value
Internal event 3 main setting
Setting value
Event configuration
] [
DI assignment
Internal event 1 main setting
Setting value
Timer remaining time 2
Internal event 2 delay time
] [
DO assignment
] [
User function
Internal event 1 sub setting
Setting value
Internal event 2 sub setting
Setting value
] [
Timer remaining time 1
Internal event 1 delay time
Internal event 2 main setting
Setting value
Setting displays
Instrument information
][Lock]
Key operations and displays
[para] key
4
*
to
(B)
*1 The parameters and numerical values registered as user functions UF are displayed.
*2 If no k ey is pressed for 3 minutes, the display automatically returns to (2) , PV display.
*3 If the [<] key is pressed while holding down the [para] key, various displys/settings can be
navigated in re verse order.
*4 Cannot be selected if ROM version 1 (
4
*
ear lier.
Explanation of arrows
[para] key : 2-second press +
hold of [para] key
:
) of the instrument information bank is 2.26 or
id02
Movement through each setup menu
[para] key Forward movement
[para] key + [<] key Backward movement
3
Operation examples
Red letters : Items before operation
Blue letters : Items during operation
Setup of PV input range type
1
3
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
If the sensor has not been wired or is discon­nected, an alarm for abnormal PV input (any one from may appear on the upper display.
Press and hold [para] for more than 2s again to get the setup setting display. The current set value for C0 1 (PV input range type) is displayed.
AL0 1
to AL11)
2
4
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
In case of ON/OFF con­trol,
r--r
the upper display.
When the [<], [ ] or [ ] key is pressed, the rightmost digit on the lower display flashes. If no key is pressed for more than 2s after chang­ing to the desired value in the PV input range list, the display changes from flash­ing to continuously lit, and the displayed value is now set.
a--M
appears on
Setup of event operation type
In this example, the event 1 operation type is set to deviation high limit.
1
3
5
Similarly, use
for event 3.
e3.C1
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
Press and hold [para] for more than 2s again to get the setup setting display. The current set value for C0 1 (PV input range type) is displayed.
When the [ ] or [ ] key is pressed, the rightmost digit on the lower display flashes. Change the flashing digit to 4 by pressing [ ] or [ ]. If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continuously lit.
on the lower display indicates that the event operation type is set for
4
deviation high limit.
to set the event 2 operation type, and use
e2.C 1
2
4
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
Press [para] repeat­edly to get e the upper display. 0 is displayed on the lower display.
on the lower display
0
indicates that the event operation type is set to "none."
a--M
1.c 1
on
Execution of auto tuning (AT )
AT forces ON/OFF of the MV a number of times (a limit cycle) to cal­culate PID values. Check that this operation does not create any problems for the as­sociated equipment before executing AT.
1
3
5
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
Press [para] twice. The upper display says at and the lower display says
If the control method is ON/OFF control and if Bit 3 (AT stop/start display) of the mode display setup ( to "disabled: 0," nothing is displayed.
[Press [ ] once. The lower display starts to flash
at.Of
) is set
C73
at.On
.
2
4
6
.
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
When [ ] or [ ] is pressed, flashes.
Flashing occurs only in RUN and AUTO modes, if there is no PV input abnormality. Also, if "AT stop/start" is selected for DI assign­ment, the display does not blink and no change can be made.
If no key is pressed for more than 2s,
at.ON
steadily lit and AT begins. During AT, the rightmost decimal point flashes twice repeatedly. (When AT is done, the light goes off and the new PID values go into effect.)
During the AT process, if the mode is changed to READY or MANUAL, if PV input is faulty, or if a power failure occurs, AT stops automatically without changing the PID values. AT can also be stopped by changing the setting from
(return to step 3 above).
At.OF
At.ON
Setup of SP value
1
3
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
When the [<], [ ] or [
] key is pressed, the rightmost digit on the lower display flashes and the SP can be changed to the desired value. In this case, the flash­ing of the numerical value implies that it is not yet set. A nu­merical setting that is being changed flashes the same way.
If an SP limit is in effect, the numerical value cannot be changed to a value above the limit. The SP limit must be changed first.
2
4
Check that the op­eration display is displaying the SP. (If not, press [para] repeatedly until the SP is displayed.)
If no key is pressed for more than 2s, the displayed value is set and the display changes from flash­ing to continuously lit.
If the [mode] key is pressed when the display is flashing, the status returns to that of step 1.
at.Of
remains
to
a--M
4
For step numbers indicated in red like 4 , the following precaution applies:
If the key lock is set, the numerical value does not flash, and the value cannot be changed. To change a numerical value, cancel the key lock first.
1
3
5
RUN/READY mode selection
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
Press the [para] key once. The upper dis­play says the lower display says
rdy
The current mode is in­dicated by mode or mode.
When [ ] or [ ] is pressed,
) on the lower
rdy
display flashes.
rdy
(or
run
run
r--r
and
run
for RUN
for READY
(or
).
2
4
6
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
In case of ON/OFF con­trol, the upper display.
When [ ] or [ ] is pressed, the lower display flashes.
If the DI assignment is set to "RUN/READY se­lection," the display does not flash and no change can be made.
If no key is pressed for more than 2s, the displayed value is set and the display changes from flash­ing to continuously lit.
r appears on
r--
a--M
Setup of event value
1
3
5
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
Press [para] repeat­edly to get e 1 on the upper display. The lower display says 0.
on the lower display
0
indicates that the event main set value is "zero."
If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continuously lit.
If the [mode] key is pressed when the display is flashing, the status returns to that of step 1.
2
4
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
When [<], [ ] or [ ] is pressed, the right­most digit on the lower display flashes, and can be changed to the desired value for the event. In this case, the flash­ing of the numerical value implies that it is not yet set. A numerical set­ting that is being changed flashes the same way.
a--M
1
3
Setup of PID value
Start from the opera­tion display (if neces­sary press [mode] once to get the op­eration display).
Press [para] repeat­edly to get proportional band) on the upper display. The value set for is displayed on the lower display.
If the control method is "ON/OFF control," noth­ing is displayed.
p-1
(for
p-1
Similarly, use e2 to set a value for event 2, and e3 to set a value for event 3.
2
4
Press and hold [para] for more than 2s to get the parameter setup display. is shown on the upper display.
When [<], [ ] or [ ] is pressed, the right­most digit on the lower display flashes, and can be changed to the desired value for the proportional band. In this case, the flash­ing of the numerical value implies that it is not yet set. A nu­merical setting that is being changed flashes the same way.
The proportional band can be set in a range from 0.1 to 999.9%.
a--M
6
Similarly, use to set a hysteresis value for event 3.
Memo
To set hysteresis as well, press [para] once (or twice, depending on the settings) to display
on the upper
e 1.hy
display. The lower display says 5.
on the lower display
5
indicates that the cur­rent set value for event hysteresis is 5.
to set a hysteresis value for event 2, and
e2.hy
7
When [<], [ ] or [ ] is pressed, the right­most digit on the lower display flashes, and can be changed to the desired value for hysteresis. If no key is pressed for more than 2s, the displayed value is set and the display changes from flash­ing to continuously lit.
e3.hy
5
Similarly, use
If no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continuously lit.
If the [mode] key is pressed when the display is flashing, the status re­turns to that of step 1.
to set the integral time (0 to 9999s), and
i-1
the derivative time (0 to 9999s).
d-1
to set
5
List of parameters
List of operation displays
Display Upper display: PV Lower display: SP
PV SP
(
LSP 1
LSP
Out
MV
HEAt
Numeric value
COOL
Numeric value PV
(
Display example
At 1 Ct 1
Numeric value
Ct2
Numeric value
E 1
Numeric value
E 1.Sb
Numeric value
t 1.--
Numeric value
E2
Numeric value
E2.Sb
Numeric value
t2.--
Numeric value
E3
Numeric value
E3.Sb
Numeric value
t3.--
Numeric value
MOdE
Display Item Contents
A--M r--r At dO.Lt C.dI 1
[SP bank]
SP
Display Item Contents
to
SP- 1
[Event bank]
Ev
Display Item Contents
to
E 1
E5
E 1.Sb
E 1.Hy
E 1.On
E 1.OF
* The decimal point position varies by meeting the internal event operation type.
PI D
Display Item Contents
P- 1
I - 1
d- 1
rE- 1
OL- 1
OH- 1
P- 1C
I - 1C
d- 1C
OL. 1C
OH. 1C
PARA
CtrL
At. OL
At. OH
Control
dI FF
OFFS
FL
rA
PV
bI
CyU
Cy
CyU2
Cy2
tP. ty
Time proportional output
SPU
SP
SPd
*1 0: Unit of "1s" 1: Fixed at 0.5s 2: Fixed at 0.2s 3: Fixed at 0.1s *2 5 to 120s when output includes the relay output
SP (Target value) SP low limit to SP high limit 0
LSP No.
Display example
)
( MV (Manipulated Variable) -10.0 to +110.0%
Heat MV (Manipulated Variable) Setting is disabled.
Cool MV (Manipulated Variable)
AT progress display
)
( CT current value 1 Setting is disabled.
CT current value 2 Setting is disabled.
Internal Event 1 main setting -1999 to +9999U or 0 to 9999U 0
Internal Event 1 sub setting 0
Timer remaining time 1 Setting is disabled.
(
Display example
)
Internal Event 2 main setting Same as Internal Event 1 main setting 0
Internal Event 2 sub setting Same as Internal Event 1 sub setting 0
Timer remaining time 2 Same as Timer remaining time 1
(
Display example
)
Internal Event 3 main setting Same as Internal Event 1 main setting 0
Internal Event 3 sub setting Same as Internal Event 1 sub setting 0
Timer remaining time 3 Same as Timer remaining time 1
(
Display example
)
[Mode bank]
AUTO/MANUAL RUN/READY AT stop/start Release all DO latches Communication DI1
SP (for LSP1 to 4) SP low limit to SP high limit 0
SP-4
to
E5.Sb
to
E5.Hy
to
E5.On
to
E5.OF
[PID bank]
 
 
[Parameter bank]
Display Item Contents
 
Item Contents Initial
1st digit: Value at the right end digit
1st digit=Numeric value at right end digit
1 to LSP system group (Max. 4) 1
)
Setting is enabled in MANUAL mode (Numeric value flashed)
-10.0 to +110.0%
Setting is disabled.
)
Upper display: The distinction by ON delay or OFF delay is displayed at the side location of “t1.”.
List of parameter setting displays
: AUTO mode
AUTO
: RUN mode
RUN
: AT stop
At.OF
: Latch continue
Lt.ON
: OFF dI
dI .OF
Internal Event 1 to 5 main setting
Internal Event 1 to 5 sub setting
Internal Event 1 to 5 hysteresis
Internal Event 1 to 5 ON delay time
Internal Event 1 to 5 OFF delay time
Proportional band (PID1) 0.1 to 999.9% 5.0
Integration time (PID1) 0 to 9999s (
Derivative time (PID1) 0 to 9999s (
Manual reset (PID1) -10.0 to +110.0% 50.0
MV low limit (PID1) -10.0 to +110.0% 0.0
MV high limit (PID1) -10.0 to +110.0% 100.0
Cool-side proportional band
Cool-side integration time
Cool-side derivative time
Cool-side MV low limit (PID1) -10.0 to +110.0% 0.0
Cool-side MV high limit (PID1) -10.0 to +110.0% 100.0
Control method 0: ON/OFF control 1: Fixed PID 2: ST(Self-tuning) 0 or 1
MV low limit at AT -10.0 to +110.0% 0.0
MV high limit at AT -10.0 to +110.0% 100.0
ON/OFF control differential 0 to 9999U 5
ON/OFF control operating point offset
PV filter 0.0 to 120.0s 0.0
PV ratio 0.001 to 9.999 1.000
PV bias -1999 to +9999U 0
Time proportional cycle unit 1 0 to 3 *
Time proportional cycle 1 5 to 120s or 1 to 120s *
Time proportional cycle unit 2 0 to 3 *
Time proportional cycle 2 5 to 120s or 1 to 120s *
Time proportional cycle mode
SP up ramp (U/min) 0.0 to 999.9U(No ramp when set at "0.0U") 0.0
SP down ramp (U/min) 0.0
-1999 to +9999 or 0 to 9999 * 0
0 to 9999 * 5
0.0 to 999.9 or 0 to 9999 0
(PID1) 0.1 to 999.9% 5.0
(PID1) 0 to 9999s (
(PID1) 0 to 9999s (
-1999 to +9999U 0
1
1
0: Controllability aiming type 1:
Operation end service life aiming type (Only ON/ OFF operation within Time proportional cycle)
: MANUAL mode
MAN
: READY mode
RDY
: AT start
At.ON
: Latch release
Lt.OF
: ON
.On
No integration control action when set at "0"
No derivative control action when set at "0"
No integration control action when set at "0"
No derivative control action when set at "0"
2
2
U: Unit Maximum unit of Industrial volume in
PV range (°C, Pa,L/min, etc.)
Initial value
AUTO
RUN
AT stop
Latch continue
OFF
Initial value
Initial value
Initial value
) 120
) 30
) 120
) 30
Initial value
10 or 2
10 or 2
0 or 1
value
0
0
0
0
: Essential parameters for PV measurement and control : Basic parameters : Required parameters when using optional functions
[Extended tuning bank]
Et
Setting
value
Display Item Contents
At.ty JF.bd
SP.LG
At-P
At-I
At-d
Ctr.A
JF.Ov
St.SA
St.Sb
St.Hb
St.ud
*1 Normal = Standard control characteristics, Immediate response = Control characteristics that respond immediately to
external disturbance, Stable = Control characteristics having less up/down fluctuation of PV
AT type 0: Normal 1: Immediate response 2: Stable *11 Just-FiTTER setting band 0.00 to 10.00 0.30
SP lag constant 0.0 to 999.9 0.0
AT Proportional Band adjust 0.00 to 99.99 1.00
AT Integral time adjust 0.00 to 99.99 1.00
AT Derivative time adjust 0.00 to 99.99 1.00
Control algorithm 0: PID(Conventional PID)
Just-FiTTER assistance coefficient
ST step execution resolution band
ST step setting band 0.0 to 10.00 0.50
ST hunting setting band 0.0 to 10.00 1.00
ST step ramp change 0: ST is executed when the PV moves up or down.
1: Ra-PID(High-performance PID) 0 to 100 0
0.0 to 99.99 10.0
1: ST is executed only when the PV moves up.
List of setup setting displays
[Setup bank]
StUP
Setting value
Setting value
Setting value
Setting value
Setting value
Display Item Contents
C0 1
C02
C03
C04
C05
C06
Analog input
C07
C08
C09
C 13
C 14
C 15
C 16
C 17
C 18
C 19
C20
Control action
C2 1
C22
C26
C27
C28
C29
C30
C32
C36
C37
SP
C38
C39
C40
C4 1
C42
C43
C44
C45
C46
C47
Continuous output
C48
C49
C50
C5 1
C64
C65
C66
C67
C68
Communication
C69
C70
C7 1
C72
C73
C74
C75
Key operation • display
C76
C77
C78
PV input range type For details, refer to the PV Input Range Table
Temperature unit 0: Celsius (°C) 1: Fahrenheit (°F) 0
Cold junction compensation
Decimal point position 0: No decimal point
PV range low limit
PV range high limit 1000
SP low limit PV input range low limit to PV input range high
SP high limit
PV square root extraction dropout
PID calculation adjustment function *20: Enabled 1: Disabled 0
Control action (Direct/Reverse)
Output operation at PV alarm 0: Control calculation is continued.
Output at PV alarm -10.0 to +110.0% 0.0
Output at READY (Heat) -10.0 to +110.0% 0.0
Output at READY (Cool) -10.0 to +110.0% 0.0
Output operation at changing AUTO/MANUAL
Preset MANUAL value -10.0 to +110.0%
Initial output type (mode) of PID control
Initial output of PID control -10.0 to +110.0%
Heat/Cool control 0: Not used 1: Used 0
Heat/Cool 0: Normal 1: Energy saving 0
Heat/Cool control dead zone -100.0 to +100.0% 0.0
Heat/Cool change point -10.0 to +110.0% 50.0
LSP system group 1 to 4 1
SP ramp unit 0: 0.1U/s 1: 0.1U/min 2: 0.1U/h 1
CT1 operation type
CT1 output
CT1 measurement wait time 30 to 300ms 30
CT2 operation type Same as CT1 0
CT2 output Same as CT1 0
CT2 measurement wait time Same as C T1 30
Control output 1 range 1: 4 to 20mA 2: 0 to 20mA 1
Control output 1 type 0: MV 1: Heat MV 2: Cool MV 3: PV
Control output 1 scaling low limit
Control output 1 scaling high limit
Control output 1 MV scaling bandwidth
Control output 2 range Same as control output 1 1
Control output 2 type Same as control output 1 3
Control output 2 scaling low limit
Control output 2 scaling high limit
Control output 2 MV scaling bandwidth
Communication type 0: CPL 1: Modbus (ASCII format)
Station address
Transmission speed (bps) 0: 4800 1: 9600 2: 19200 3: 38400 2
Data format (Data length) 0: 7 bits 1: 8 bits 1
Data format (Parity) 0: Even parity 1: Odd parity 2: No parity 0
Data format (Stop bit) 0: 1 bit 1: 2 bits 0
Communication minimum response time
Key operation type 0: Standard type 1: Special type 0
[mode] key function 0: Invalid 1: AUTO/MANUAL selection
MODE display setup
(Sum of the weighting)
PV/SP display setup
(Sum of the weighting)
MV display setup
(Sum of the weighting)
EV display setup
(Operation display)
Event remaining time display setup
(Operation display)
CT input current value display setup
(Operation display)
0: Performed (internal) 1: Not performed (external)
1 to 3: 1 to 3 digits below decimal point * When the PV input type is DC voltage/DC current,
-1999 to +9999U
limit
0.0 to 100.0% (PV square root extraction is not performed when set at "0.0".)
0: Heat control (Reverse action) 1: Cool control (Direct action)
1: Output at PV alarm is output.
0: Bumpless transfer 1: Preset 0
0: Auto 1: Not initialized 2: Initialized 0
0: Heater burnout detection 1: Current value measurement
0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3
4: PV before ratio, bias, and filter 5: SP 6: Deviation 7: CT1 current value 8: CT2 current value 10: SP+MV 11: PV+MV
-1999 to +9999U 0.0
0 to 9999 (Valid when control output 1 type is 10 or 11)
Same as control output 1 0
Same as control output 1 1000
Same as control output 1 200
2: Modbus (RTU format) 0 to 127 (Communication is disabled when set at "0".)
1 to 250ms 3
2: RUN/READY selection 3: AT Stop/Start 4: LSP group selection 5: Release all DO latches 6: Invalid 7:
Communication DI1 selection
Bit 0: AUTO/MANUAL display (Enabled: +1) Bit 1: RUN/READY display (Enabled: +2) Bit 3: AT Stop/Start display (Enabled: +8) Bit 4:
Release all DO latches display (Enabled: +16)
Bit 5:
Communication DI1 ON/OFF display (Enabled: +32)
Other invalid setting, 0, +4, +64, +128 Bit 0: PV display (Enabled: +1)
Bit 1: SP display (Enabled: +2) Bit 2: LSP group number display (Enabled: +4) Other invalid setting, 0, +8
Bit 0: MV display (Enabled: +1) Bit 1: Heat MV/cool MV display (Enabled: +2) Bit 3: AT progress display (Enabled: +8) Other invalid setting: 0, +4
0: Not displayed 1: Set value of Internal event 1 is displayed 2: Set values of Internal event 1 to 2 are displayed 3: Set values of Internal event 1 to 3 are displayed
0: Not displayed 1: Internal event 1 is displayed 2: Internal event 1 to 2 is displayed 3: Internal event 1 to 3 is displayed
0: Not displayed 1: CT1 current value is displayed 2: CT1 to 2 current values are displayed
Initial value
Setting value
0
0
Initial value
Setting value
Depending on Model No.
0
0
1
0
0.0
0
0
0.0 or 50.0
0.0 or 50.0
0
0
0
100.0
200
0
0
0
8:
Invalid
255
15
15
0
0
0
6
• Items marked  in the tables are displayed in standard and/or high function configuration.
• To change a user level, refer to
Display Item Contents
C79
C80
C90
C9 1
C92
C93
Key operation • display
C97
*1 Cannot be set for a thermocouple if ROM version 1 ( *2 Cannot be selected if ROM version 1 (
EvCF
Display Item Contents
to
E 1.C 1
to
E 1.C2
to
E 1.C3
User level 0: Simple configuration 1: Standard configuration
LED monitor 0: Not used
Number of CT1 turns 0: 800 turns 1 to 40: CT turns divided by 100 8
Number of CT1 power wire loops
Number of CT2 turns 0: 800 turns 1 to 40: CT turns divided by 100 8
Number of CT2 power wire loops
PV input failure (under range)
2
type *
) of the instrument information bank is 2.26 or earlier.
id02
[Event configuration bank]
Internal event 1 to 5 Configuration 1
E5.C 1
Internal event 1 to 5 Configuration 2
E5.C2
1st digit: Direct/Reverse 0: Direct 1: Reverse 0 2nd digit: Standby 0: None 1: Standby 2:
EVENT state at READY
3rd digit: 4th digit: Undefined 0 0 Internal event 1 to 5 Configuration 3
E5.C3
1st digit: Alarm OR 0: None 1: Alarm direct + OR operation
2nd digit: Special OFF 0: As usual
3rd digit: Delay time unit 0: 0.1s 1: 1s 2: 1min 0 4th digit: Undefined 0 0
Changing the user level
2: High function configuration
1:
Flashing while data is sending through RS-485 communication.
2:
Flashing while data is receiving through RS-485 communication 3: Logical OR of all DI statuses 4: Flashing in READY mode
0: 1 time 1 to 6: Number of times 1
0: 1 time 1 to 6: Number of times 1
0: 10 %FS 1: 5 mV (This setting is applicable if C01 (PV input
range type) is set for sensor type B (No.17) or
PR40-20 (No. 23))
) of the instrument information bank is 2.26 or earlier.
id02
Refer to event type (see page 8) 0 The digits are determined to 1st, 2nd, 3rd, and
4th digit from the right end.
0: Continue 1: Forced OFF 0
The digits are determined to 1st, 2nd, 3rd, and 4th digit from the right end.
2: Alarm direct + AND operation 3: Alarm reverse + OR operation 4: Alarm reverse + AND operation
1: When the event set value (main setting) is 0,
the event is "OFF".
Standby + Standby at SP change
in the lower right part of this page.
[Lock bank]
Initial value
0
0
0
Initial value
0
0
0
Setting value
Setting value
LOC
Display Item Contents
LOC
C.LOC
L.LOC
PASS
PS 1A
PS2A
PS 1b
PS2b
[Instrument information bank]
I d
Display Item Contents
I d0 1
I d02
I d03
I d04
I d05
I d06
I d07
I d08
Key lock 0: All settings are possible
Communication lock 0: read/write enabled 1: read/write disabled 0
Loader lock 0: read/write enabled 1: read/write disabled 0
Password display 0 to 15 (5: Password 1A to 2B display) 0
Password 1A 0000 to FFFF (Hexadecimal value) 0000
Password 2A 0000 to FFFF (Hexadecimal value) 0000
Password 1B 0000 to FFFF (Hexadecimal value) 0000
Password 2B 0000 to FFFF (Hexadecimal value) 0000
ROM ID 0: Fixed 0
ROM Version 1 XX. XX (2 digits after decimal point)
ROM Version 2 XX. XX (2 digits after decimal point)
Loader information
EST information
Manufacturing date code
(year) Manufacturing date code
(month, day) Serial No.
Precaution for setup
The type of auto tuning can be changed by changing the value of (AT type) in the extended tuning bank. Set it to match the
At.ty
control characteristics.
1: Mode, event, operation display, SP, UF, lock,
manual MV, [mode] key can be set
2: Operation display, SP, UF, lock, manual MV,
[mode] key can be set
3: UF, lock, manual MV, [mode] key can be set
Subtract 2000 from the year. Example: "3" means the year 2003.
Month + day divided by 100. Example: "12.01" means the 1st day of December.
Initial value
0
Initial value
Setting value
Setting value
[DI assignment bank]
di
Display Item Contents
to dI 3.
dI 1. 1
to dI
dI 1.2
to dI
dI 1.3
to dI
dI 1.4
to dI
dI 1.5
to dI
dI 1.6
to dI
dI 1.7
to dI
dI 1.8
to dI
dI 1.9
[DO assignment bank]
dO
Display Item Contents
to
Ot 1. 1
1. 1 to
Ev
to
Ot 1.2
to
Ev
1.2
to
Ot 1.3
to
Ev
1.3
to
Ot 1.4
to
Ev
1.4
to
Ot 1.5
to
Ev
1.5
to
Ot 1.6
to
Ev
1.6
to
Ot 1.7
to
Ev
1.7
to
Ot 1.8
to
Ev
1.8
[User function bank]
UF
Display Item Contents
to
UF- 1
Internal contact 1 to 3
1
Operation type
Internal contact 1 to 3
3.2
Input bit operation
Internal contact 1 to 3
3.3
Input assignment A
Internal contact 1 to 3
3.4
Input assignment B Internal contact 1 to 3
3.5
Input assignment C Internal contact 1 to 3
3.6
Input assignment D
Internal contact 1 to 3
3.7
Polarity A to D 1st digit: Polarity A 0: Direct 1: Reverse 0 2nd digit: Polarity B 0 3rd digit: Polarity C 0 4th digit: Polarity D 0 Internal contact 1 to 3 Polarity 0: Direct 1: Reverse 0
3.8
Internal contact 1 to 3
3.9
Internal event No. assignment
Control output 1 to 2, event
Ot2. 1�
output 1 to 3 Operation type
Ev3. 1
Control output 1 to 2, event
Ot2.2�
output 1 to 3 Output assign-
Ev3.2
ment A
Control output 1 to 2, event
Ot2.3�
output 1 to 3 Output assign-
Ev3.3
ment B Control output 1 to 2, event
Ot2.4�
output 1 to 3 Output assign-
Ev3.4
ment C Control output 1 to 2, event
Ot2.5�
output 1 to 3 Output assign-
Ev3.5
ment D Control output 1 to 2, event
Ot2.6�
output 1 to 3 Polarity A to D
Ev3.6
1st digit: Polarity A 0: Direct 2nd digit: Polarity B 0 3rd digit: Polarity C 0 4the digit: Polarity D 0 Control output 1 to 2, event
Ot2.7�
output 1 to 3 Polarity
Ev3.7
Control output 1 to 2, event
Ot2.8�
output 1 to 3 Latch
Ev3.8
User function 1 to 8
UF-8
0: No function 1: LSP group selection (0/+1) 2: LSP group selection (0/+2) 3: LSP group selection (0/+4) 4: Invalid 5: Invalid 6: Invalid 7: RUN/READY selection 8: AUTO/MANUAL selection 9: LSP/RSP selection 10: AT Stop/Start 11: ST disabled/enabled 12: Control action direct/reverse 13: SP Ramp enabled/disabled 14: PV Hold 15: PV Maximum value hold 16: PV Minimum value hold 17: Timer Stop/Start 18: Release all DO latches (Continue/Release) 19: Invalid 20: Invalid
0: Not used (Default input) 1: Function 1 ((A and B) or (C and D)) 2: Function 2 ((A or B) and (C or D)) 3: Function 3 (A or B or C or D) 4: Function 4 (A and B and C and D)
0: Normally opened 1: Normally closed 2: DI1 3: DI2 4 to 9: Undefined 10 to 14: Internal Event 1to 5 15 to 17: Undefined 18 to 21: Communication DI1 to 4 22: MANUAL 23: READY 24: Undefined 25:
AT running
26: 28: Alarm occurs 29: PV alarm occurs 30: Undefined 31: mode key pressing status 32:
Event output 1 status
The digits are determined to 1st, 2nd, 3rd and 4th digit from the right end.
0: Every Internal Event 1 to 5: Internal Event No.
0: Default output 1 to 2: MV1 to 2 3 to 6: Function 1 to 4
0: Normally opened 1: Normally closed 2 to 6: Internal Event 1 to 5 7 to 13: Undefined 14 to 15: MV1 to 2 16 to 17: Undefined 18 to 19: DI1 to 2 20 to 25: Undefined 26 to 28: Internal Contact 1 to 3 29 to 33: Undefined 34 to 37: DI1 to 4 38: MANUAL 39: READY 40: Undefined 41: AT running 42: During SP ramp 43: Undefined 44: Alarm occurs 45: PV alarm occurs 46: Undefined 47: Mode key pressing status 48: Event output 1 status 49: Control output 1 status
The digits are determined to 1st, 2nd, 3rd, and 4 th digit from the right end.
1: Reverse
0: Direct 1: Reverse
0: None 1: Latch (Latch at ON) 2: Latch (Latch at OFF except for initialization
at power ON)
During SP ramp
33:
Control output 1 status
27:
Undefined
Initial value
0
0
2: Contact 1 3: Contact 2 4: Contact 3
0
0
0
0
Initial value
0
14:
Output 1
15:
Output 2 2: Event 1 3: Event 2 4: Event 3
0
0
0
0
0
0
Initial value
Setting value
Memo
Changing the user level
This controller's user level can be set to 1 of 3 types in setup The number of possible displays and settings decreases according to the user level: high function > standard > simple. All items are displayed when high function is selected.
1
Setting value
3
Setting value
If necessary press [mode] once to change to the op­eration display. Next, press and hold [para] for more than 2s to get the param­eter setup display.
a--M
or
r--r
ap­pears on the upper display.
Press [para] repeat­edly to change the upper display to
c79
(user level).
2
4
.
C79
Press and hold [para] for more than 2s again to display
on the upper
c0 1
display.
When [<], [ ] or [ ] is pressed, the lower display flashes and can be changed to the desired numerical value. Then, if no key is pressed for more than 2s, the displayed value is set and the display changes from flashing to continu­ously lit.
0: Simple configuration
(initial value) 1: Standard configuration 2:
High function configuration
7
: https://www.azbil.com
(11)
PV input range table
PV
PV
PV
Main setting
PV
Main setting
PV
PV
PV
PV
PV
SP + Main set ting
PV
PV
PV
PV
PV
PV
SP + Main set ting
PV
PV
PV
CT1 at out put ON
Main setting
CT1 at out put ON
CT1 at out put OFF
CT1 at out put OFF
CT2 at ou tput ON
CT2 at ou tput ON
CT2 at ou tput OFF
CT2 at ou tput OFF
[Thermocouple] [RTD]
Sensor
C0 1
set value
1 K -200 to +1200 -300 to +2200 41 Pt100 -200 to +500 -300 to +900
2 K 0 to 1200 0 to 2200 42 JPt100 -200 to +500 -300 to +900
3 K 0.0 to 800.0 0 to 1500 43 P t100 -200 to +200 -300 to +400
4 K 0.0 to 600.0 0 to 1100 44 JPt100 -200 to +200 -300 to +400
5 K 0.0 to 400.0 0 to 700 45 Pt100 -100 to +300 -150 to +500
6 K -200.0 to +400.0 -300 to +700 46 JPt100 -100 to +300 -150 to +500
9 J 0.0 to 800.0 0 to 1500 51 Pt100 -50.0 to +200.0 -50 to +400
10 J 0.0 to 600.0 0 to 1100 52 JPt100 -50.0 to +200.0 -50 to +400
11 J -200.0 to +400.0 -300 to +700 53 Pt100 -50.0 to +100.0 -50 to +200
13 E 0.0 to 600.0 0 to 1100 54 JPt100 -50.0 to +100.0 -50 to +200
14 T -200.0 to +400.0 -300 to +700 63 Pt100 0.0 to 200.0 0 to 400
15 R 0 to 1600 0 to 3000 64 JPt100 0.0 to 200.0 0 to 400
16 S 0 to 1600 0 to 3000 67 Pt100 0 to 500 0 to 900
17 B 0 to 1800 0 to 3300 68 JPt100 0 to 500 0 to 900
18 N 0 to 1300 0 to 2300
19 PL II 0 to 1300 0 to 2300
WRe5-26
20
WRe5-26
21
PR40-20
23
24 DIN U -200.0 to +400.0 -300 to +700 86 1 to 5 V
25 DIN L -100.0 to +800.0 -150 to +1500 87 0 to 5 V
Initial value 90 4 to 20 mA
Accuracy for No. 17 (B thermocouple) is as follows. 260 °C or less: ±5 %FS. 260–800 °C: ±1 %FS.
*1
The PV values under 20 °C are not shown. However, if ROM version 1 ( information bank is 2.04 or earlier, the indicated low limi value is -180 °C.
Accuracy for No. 23 (sensor type PR40-20) is as follows. 300 °C or less: undefined. 300–800 °C:
±5 % FS. 800–1900 °C: ±2 % FS. However, if ROM version 1 ( bank is 2.26 or earlier, No. 23 cannot be selected.
*2 PL II thermocouple is a range, which has been added to the units manufactured from July, 2003.
*3 The decimal point for thermocouples can be displayed if the ROM version is 2.26 or later.
type
Range
(°C)
Range
(°F)
C0 1
set value
Sensor
type
Range
(°C)
[DC voltage/DC current]
0 to 1400 0 to 2400
0 to 2300 0 to 4200
0 to 1900 0 to 3400 84 0 to 1 V The scaling and decimal
Input type Range
C0 1
set value
88 0 to 10 V
89 0 to 20 mA
i d02
point position can be changed variably in a range of –1999 to +9999
) of the instrument information
i d02
List of alarm codes
Alarm
AL0 1
AL02
AL03
Input failure
AL 1 1
AL70
AL95
AL96
Unit failure
AL97
AL98
AL99
Handling Precautions
Failure name Cause Corrective action
code
PV input failure (Over-range)
Sensor burnout, incorrect wiring, incorrect PV input type setting
PV input failure (Under-range)
Sensor burnout, incorrect wiring, incorrect PV input type setting
CJ failure Terminal temperature is
faulty (thermocouple).
PV input failure (RTD)
CT input failure (Over-range) (CT input 1 or 2, or both)
Sensor burnout, incorrect wiring
A current exceeding the upper limit of the display range was measured. The number of CT turns or the number of CT power wire loops is incorrectly set, or wiring is incorrect.
A/D conversion
A/D converter is faulty. Replace the unit.
failure
Parameter failure Power is shut-down while
the data is being set, or data is corrupted by noise.
Adjustment data failure
Power is shut-down while the data is being set, or data is corrupted by noise.
Parameter failure
Data is corrupted by noise.
(RAM area)
Adjustment data
Data is corrupted by noise.
failure (RAM area) ROM failure ROM (memory) is faulty. Reset the unit.
If ROM version 1 (i
2.04 or earlier, CT input failure (
) of the instrument information bank is
d02
) is not displayed.
AL 1 1
Check the wiring. Set the PV input type again.
Check the ambient temperature.
Check the wiring.
Use a CT with the cor-
rect number of turns for the display range.
Reset the number of
CT turns.
Reset the number of CT
power wire loops.
Check the wiring.
Restart the unit.
Set the data again (set
data for adjustment data for
AL96/98
Replace the unit.
Replace the unit.
Range
(°F)
) of the instrument
and
AL95/97
.
Event type
Operation
No event 0 Always OFF Always OFF PV high limit
PV low limit 2
PV high/low limit
Deviation high limit
Deviation low limit
Deviation high/low limit
Deviation high limit (Final SP reference) Deviation low limit (Final SP reference) Deviation high/ low limit (Final SP reference) Heater 1 burnout/ Over-current
Heater 1 short-circuit
Heater 2 burnout/ Over-current
Heater 2 short-circuit
Alarm (status)
*: If the main setting is greater than the sub-setting, operations are performed with the
main setting and sub-setting automatically swapped.
Event types other than the above:
Operation type Set
SP high limit 10 Loop diagnosis 1 20 During AT (status) 27
SP low limit 11 Loop diagnosis 2 21 During SP ramp 28
SP high/low limit 12 Loop diagnosis 3 22 Control action (status) 29
MV high limit 13 READY (status) 24 ST setting standby (status) 30
MV low limit 14 MANUAL (status) 25 Timer (status) 32
MV high/low limit 15
1-12-2 Kawana, Fujisawa Kanagawa 251-8522 Japan
URL
8
Set
:
shows that the ON/OFF is changed at this value.
type
value
:
shows that the ON/OFF is changed at a point that "1U" is added to this value.
1
ON
Main setting
3
ON HYS ONHYS
4
SP + Main set ting
5
6
7
8
9
16
17
18
19
23 ON if alarm occurs (alarm code AL01
ON HYS
ON HYS
Main setting Sub-setting
SP + Main set ting
ON HYS
ON HYS
Main setting Sub-setting
ON HYS
OFF before measuring the CT1 current value
HYS
Main setting
OFF before measuring CT1 current value OFF before measuring CT1 current value
ON H YS
Main setitng
OFF before measuring CT2 current value OFF before measuirng CT2 current value
HYS
Main setting
OFF before measuring CT2 current value OFF before measuring C T2 current value
to 99). OFF in other cases.
: initial value
value
Direct action
ONHYS
Main setting
HYS
*
Sub-setting
*
ONHYS
ONHYS
SP
ONHYS
ONHYS
SP
ON
*
ON
ONHYS
Sub-setting
ONHYS
Sub-setting
*
*
*
Operation type Set
Specifi cations are subjec t to change without n otice.
Reverse action
:
shows that the ON/OFF is changed at this value.
:
shows that the ON/OFF is changed at a point that "1U" is added to this value.
ON
HYS
Main setting
HYS
ONHYS
Main setting *Sub-setting
ON
HYS
SP + Main set ting
ONHYS HYS
Main setting
ON
Main setting
Main setting
OFF before measuring CT1 current value
ON
Main setting
ON
OFF if alarm occurs (alarm code AL01 to 99). ON in other cases.
value
Sub-setting
SP
HYS
SP + Main set ting
ONHYS HYS
Sub-setting
SP
ONHYS HYS
*
HYS
Main setting
ONHYS HYS
*
Sub-setting
HYS
Main setting
Operation type Set
1st edition: Mar. 2007 (W)
3rd edition: Apr. 2019 (B) © 2007–2019 Azbil Corporation. All Rights Reserved.
ON
HYS
ONHYS
ONHYS
Sub-setting
*
*
*
value
Loading...