Features ............................................................................................................................................ 2
Basic System Architecture ................................................................................................................... 2
Appendix I: Approximate Back-up Time Table ............................................................................. 34
Appendix II: Parallel function ....................................................................................................... 35
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read
this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and
keep this manual for future reference.
1. Before using the unit, read all instructions and warnings marked on the unit, the batteries and all
appropriate sections of this manual.
2. CAUTION --To reduce risk of injury, charge it with only deep-cycle lead acid type rechargeable
batteries. It might cause burst or result in physical injury and damage if you charge it with other types
of the batteries.
3. Do not disassemble the unit at will. For servicing or repairs, it’s advised to take it to an authorized
service center. Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce the risk of electric shock, unplug all wirings from the wall outlet before any maintenance or
cleaning. Turning off the unit will not reduce this risk.
5. CAUTION – Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around the batteries. A potential risk exists when
you drop tools on or around the batteries. Spark, short circuited batteries or other electrical parts might
cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to the INSTALLATION section of this manual for the details.
10. Fuses are provided for over-current protection of the battery supply.
11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
13. Warning!! Only qualified service staffs are able to operate this device. If errors still persist after
following the troubleshooting table, please send this inverter/charger back to the local dealer or service
center for maintenance.
1
INTRODUCTION
This is a multi-functional inverter/charger, combining the functions of inverter, MPPT solar charger and battery
charger to offer uninterruptible power support with portability. Its comprehensive LCD display offers
user-configurable and easy-accessible button operation such as battery charging current, priority setting for
AC/solar charger, and acceptable input voltage setting to suit different applications.
Features
Pure sine wave inverter
Built-in MPPT solar charge controller
Configurable input voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current to suit different applications via LCD setting
Configurable priority of AC/Solar Charger via LCD setting
Compatible to mains voltage or generator power
Automatic restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design to optimize battery performance
Cold start function
Basic System Architecture
The following illustration shows basic application of this inverter/charger. It also includes the following devices
to complete the whole running system:
Generator or Utility.
PV modules
Consult your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances at home or in the office, including motor-type appliances such as
tube light, fan, refrigerator and air conditioner.
Figure 1 Hybrid Power System
2
Product Overview
1. Battery input
2. Power on/off switch
3. Dry contact
4. USB communication port
5. RS232 communication port
6. PV input
7. Parallel communication port (only for parallel model)
8. Current sharing port (only for parallel model)
9. Parallel ID
10. AC output
11. Circuit breaker
12. AC input
13. LCD display
14. Status indicator
15. Charging indicator
16. Fault indicator
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside the package:
The unit x 1
User manual x 1
Communication cable x 1
Software CD x 1
Preparation
Before connecting all wirings, please take off the cover of the bottom by removing the six screws as shown
below.
Mounting the Unit
Consider the following points before selecting where to install:
Do not mount the inverter on any flammable construction
materials.
Mount this inverter on a solid surface
Install this inverter at eye level in order to read the LCD display at
all times.
The ambient temperature should be between 0°C and 55°C to
ensure optimal operation.
The inverter should be adhered to the wall vertically.
Be sure to keep other objects away and leave the space in a
minimum as shown in the right diagram to guarantee sufficient
heat dissipation and enough space for replacing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing four screws as shown in the diagram.
It’s recommended to use M5 screws.
4
5
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect the device between battery and inverter. It may not be necessary to disconnect the
device for some applications, however, it’s requested to have over-current protection installed. Please refer to
the typical amperage in the table below as required fuse or size of the breaker.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use proper
cables and suitable size of terminal recommended below.
Recommended battery cables and size of terminal:
Ring terminal:
Model Typical
Amperage
Battery
Capacity
Wire SizeRing Terminal Torque
Cable
2
mm
Dimensions
D (mm)L (mm)
Value
1*1/0AWG 60 8.4 49.7
5KW 220A 200AH
5~6 Nm
2*4AWG 44 8.4 49.7
Please follow the steps below to implement the battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Connect all battery packs as units requires. It’s suggested to connect at least 200Ah capacity battery for
5KW model.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are
tightened with torque of 5-6 Nm. Make sure polarity at both the battery and the inverter is correctly
connected and ring terminals are tightly screwed to the battery terminals.
4. Connect all battery packs as below chart.
6
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply any anti-oxidant substance on the terminals before the terminals are
connected tightly.
CAUTION!! Before making the f inal DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 40A
for 5KVA.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING! All wiring must be performed by the qualified personnel.
WARNING! The AC input N wire must be connected, Otherwise, the inverter will NOT detect AC input;
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the recommended cable size as below.
Suggested cable requirement for AC wires
Model Gauge Torque Value
5KVA 10 AWG 1.4~ 1.6Nm
There are three applications for different AC input as shown in the figure below. For phase angle operation,
please refer to LCD #28
7
When the phase angle between L1 and L2 is 0°.
Grid
connection
L1
Grid
connection
L2
L1
L2
L1
120V
N
0V
120V
When the phase angle between L1 and L2 is 120°.
120V
N
208V
120V
When the phase angle between L1 and L2 is 180°.
MLV 5KW
N
L2L2
L1
MLV 5KW
N
L2L2
L1
N
L1
N
120V
120V
120V
120V
N
N
0V
208V
L1
Load
Output
L2
L1
Load
Output
L2
L1
Grid
connection
L2
240V
N
120V
120V
L1
MLV 5KW
N
L2L2
L1
N
120V
120V
N
240V
L1
Load
Output
L2
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm from the six conductors. And short-circuit phase L and neutral conductor N
3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor (
) first.
→ Ground (yellow-green)
L1→ LINE (black)
L2→ LINE (brown)
N→ Neutral (blue)
8
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and fasten the terminal
screws. Be sure to connect PE protective conductor (
→ Ground (yellow-green)
L1→ LINE (black)
L2→ LINE (brown)
N→ Neutral (blue)
) first.
5. Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause
utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check with
the manufacturer of the air conditioner if it’s equipped with time-delay function before installation. Otherwise,
this inverter/charger will cause overload fault and cut off the output to protect your appliance but sometimes it
still causes internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
9
and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV
module connection. To reduce risk of injury, please use the recommended cable size as below.
NOTICE! When only one MPPT is used, please use MPPT1 first.
Model Typical Amperage Cable Size Torque
5KVA 80A 8 AWG 1.4~1.6 Nm
PV Module Selection:
When selecting proper PV modules, please be sure to consider the parameters below:
1. Open circuit Voltage (Voc) of PV modules can’t exceed the maximum voltage of the PV array open circuit of
the inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than the minimum voltage of the battery.
Solar Charging Mode
Solar Charger Type MPPT
Number of MPPT 2
Max. PV Array Open Circuit Voltage145Vdc
PV Array MPPT Voltage Range 60~115Vdc
Min. battery voltage for PV charge 34Vdc
Please follow the steps below to implement PV module connection:
1. Remove insulation sleeve 10 mm from positive and negative conductors.
2. Check the correct polarity of connected cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.
Final Assembly
After connecting all wirings, please put the bottom cover back by fixing two screws as shown below.
10
11
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and
follow the on-screen instructions to install the monitoring software. For the detailed software operations,
please check user manual of software inside the CD.
Dry Contact Signal
There is one dry contact (3A/120VAC) available on the rear panel. It could be used to deliver signal to external
device when battery voltage reaches warning level.
Unit
Status
Power Off Unit is off and no output is powered. Close Open
Output is powered from Utility. Close Open
Output is
powered
from Battery
or Solar.
Power On
Program
01 set as
Utility
Program
01 is set
as SBU or
Solar first
Condition
Battery voltage < Low DC warning
voltage
Battery voltage > Setting value in
Program 13 or battery charging
reaches floating stage
Battery voltage < Setting value in
Program 12
Battery voltage > Setting value in
Program 13 or the battery
charging reaches the floating
stage
Dry contact port:
NC & C NO & C
Open Close
Open
Close
Close
Open
Close Open
Parallel ID
1 2 3 4
OFF OFF OFF * 0
ON OFF OFF * 1
OFF ON OFF * 2
ON ON OFF * 3
OFF OFF ON * 4
ON OFF ON * 5
OFF ON ON * 6
ON ON ON * 7
* Not used
12
Parallel ID
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch
(located on the right corner of the rear panel) to turn on the unit.
Operation and Display Panel
The operation and display panel, as shown in the chart below, are on the front panel of the inverter. It
includes three indicators, four function keys and an LCD display, indicating the operating status and
input/output power information.
LED Indicator
LED Indicator
Green
Function Keys
Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode
Green
Red
Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
Solid On Battery is fully charged.
Flashing Battery is charging.
Solid On Fault occurs in the inverter.
Flashing
Warning occurs in the inverter.
Messages
LCD display
LED indicators
Function keys
13
LCD Display Icons
Icon Function description
Input Source Information
Configuration Program and Fault Information
Indicates the AC input.
Indicates the PV input
Indicates the input 1, output 1.
Indicates the input 2, output 2.
Indicates input voltage, input frequency, PV voltage, battery voltage and
charger current.
Indicates the setting programs.
Indicates the warning and fault codes.
Warning:
Fault:
flashing with warning code.
lighting with fault code
Output Information
Indicate output voltage, output frequency, load percent, load in VA, load in
Watt and discharging current.
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery
In AC mode, it will present battery charging status.
Status Battery voltage LCD Display
Constant
Current mode /
Constant
mode and charging status in line mode.
<2V/cell 4 bars will flash in turns.
2 ~ 2.083V/cell
2.083 ~ 2.167V/cell
Bottom bar will be on and the other three
bars will flash in turns.
Bottom two bars will be on and the other
two bars will flash in turns.
14
Voltage mode
In floating mode, batteries are fully charged. 4 bars will be on.
> 2.167 V/cell
Bottom three bars will be on and the top
bar will flash.
In battery mode, it will present battery capacity.
Load Percentage Battery Voltage LCD Display
< 1.717V/cell
1.717V/cell ~ 1.8V/cell
Load >50%
1.8 ~ 1.883V/cell
50%> Load > 20%
Load < 20%
Load Information
> 1.883 V/cell
< 1.817V/cell
1.817V/cell ~ 1.9V/cell
1.9 ~ 1.983V/cell
> 1.983
< 1.867V/cell
1.867V/cell ~ 1.95V/cell
1.95 ~ 2.033V/cell
> 2.033
Indicates overload.
Indicates the load level by 0-24%, 25-50%, 50-74% and 75-100%.
0%~25% 25%~50% 50%~75% 75%~100%
Mode Operation Information
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Indicates the PV charger circuit is working.
15
Mute Operation
Indicates the alarm is disabled.
LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or
“DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC
button to exit.
Setting Programs:
Program Description Selectable option
Escape
00 Exit setting mode
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the loads
at the same time.
Utility provides power to the loads
only when any one condition stated
below happens:
- Solar energy is not available
- Battery voltage drops to either low
DC warning voltage or the setting
point in program 12.
Utility will provide power to the loads
as first priority.
Solar and battery energy will provide
power to the loads only when utility
power is not available.
Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the loads
at the same time.
Utility provides power to the loads
only when battery voltage drops to
either low DC warning voltage or the
setting point in program 12.
30A
01
02
Output source priority:
To configure load power
source priority
Maximum charging current:
To configure the total
charging current for solar
and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
Solar first
Utility first (default)
SBU priority
20A
16
40A
50A
02
Maximum charging
current: To configure the
total charging current for
solar and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A
70A
80A 90A
100A 110A
120A
130A (only for 5KVA with MPPT
models)
140A
150A
160A
170A
03 AC input voltage range
05 Battery type
180A
200A
220A
190A
210A
Appliances (default)
If selected, acceptable AC input
voltage range will be within
90-280VAC.
UPS If selected, acceptable AC input
voltage range will be within
170-280VAC.
AGM (default)
Flooded
17
06
07
Automatically restart when
overload occurs
Automatically restart when
over temperature occurs
User-Defined
Restart disable
(default)
Restart disable
(default)
If “User-Defined” is selected, battery
charge voltage and low DC cut-off
voltage can be set up in program 26,
27 and 29.
Restart enable
Restart enable
08 Output voltage
09 Output frequency
11
Maximum utility charging
current
110V
50Hz (default)
2A
120V (default)
60Hz
10A
20A 30A (default)
40A 50A
60A
44.0V
45.0V (default)
12
Setting voltage point back
to utility source when
selecting “SBU priority” or
“Solar first” in program 01.
46.0V
48.0V
50.0V
18
47.0V
49.0V
51.0V
Battery fully charged
13
Setting voltage point back
to battery mode when
selecting “SBU priority” or
“Solar first” in program 01.
48.0V
50.0V
52.0V
54.0V
56.0V
49.0V
51.0V
53.0V
55.0V
57.0V
16
Charger source priority:
To configure the priority of
charger source
58.0V
If this inverter/charger is working in Line, Standby or Fault
mode, charger source can be programmed as below:
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only when
solar energy is not available.
Utility first
Utility will charge battery as first
priority.
Solar energy will charge battery only
when utility power is not available.
Solar and Utility
Solar energy and utility will charge
battery at the same time.
Only Solar Solar energy will be the only charger
source no matter utility is available or
not.
If this inverter/charger is working in Battery mode, only solar
energy can charge battery. Solar energy will charge battery if
it's available and sufficient.
19
18 Alarm control
19
Automatically return to
default display screen
Alarm on (default)
Return to default
display screen
(default)
Stay at latest screen
Alarm off
If selected, no matter how users
switch display screen, it will
automatically return to default display
screen (Input voltage /output voltage)
after no button is pressed for 1
minute.
If selected, the display screen will stay
at the latest screen user finally
switches.
20 Backlight control
22
Beeps while primary
source is interrupted
Overload bypass:
When enabled, the unit
23
will transfer to line mode if
overload occurs in battery
mode.
25 Record Fault code
26
Bulk charging voltage
(C.V voltage)
Backlight on (default)
Alarm on (default)
Backlight off
Alarm off
Bypass disable
(default)
Bypass enable
Record enable Record disable (default)
default setting: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 48.0V to 58.4V. Increment of each
click is 0.1V.
Default setting: 54.0V
27
28
Floating charging voltage
AC output mode
*This setting is able to set
up only when the inverter
is in standby mode. Be
If self-defined is selected in program 5, this program can be set
up. Setting range is from 48.0V to 58.4V. Increment of each
click is 0.1V.
parallel output(0°)
20
Phase 1 of 3 Phase output
sure that on/off switch is
in “OFF” status.
Phase 2 of 3 Phase output
Phase 3 of 3 Phase output
29 Low DC cut-off voltage
PV judge condition
30
(Only apply for setting
“Solar first” in program
1: Output source priority)
Parallel output (120°)
parallel output(180°)
Default setting: 42.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 40.0V to 48.0V. Increment of each
click is 0.1V. Low DC cut-off voltage will be fixed to setting value
no matter what percentage of load is connected.
When “ONE” is selected, as
long as one of the inverters
has been connected to PV
modules and PV input is
normal, parallel or 3-phase
system will continue working
according to rule of “solar
first” setting.
One Inverter (Default):
For example, two units are
connected in parallel and set
“SOL” in output source priority.
If one of the two units has
connected to PV modules and
PV input is normal, the parallel
system will provide power to
loads from solar or battery
power. If both of them are not
sufficient, the system will
provide power to loads from
utility.
When “ALL” is selected,
parallel or 3-phase system will
continue working according to
rule of “solar first” setting only
when all of inverters are
connected to PV modules.
For example, two units are
connected in parallel and set
All of Inverters:
“SOL” in output source priority.
When “ALL” is selected in
program 30, it’s necessary to
have all inverters connected to
PV modules and PV input is
normal to allow the system to
provide power to loads from
solar and battery power.
Otherwise, the system will
provide power to loads from
utility.
21
31
Solar power balance:
When enabled, solar input
power will be
automatically adjusted
according to the
connected load power.
Solar power balance
enable (Default):
Solar power balance
disable:
Automatically (Default):
If selected, solar input power will be
automatically adjusted according to
the following formula:
Max. input solar power = Max.
battery charging power +
Connected load power.
If selected, the solar input power
will be the same as max. battery
charging power no matter how
many loads are connected. The
max. battery charging power will be
based on the setting current in
program 02.
(Max. solar power = Max. battery
charging power)
If selected, inverter will judge this
charging time automatically.
Bulk charging time
32
(C.V stage)
(Only available for
4KVA/5KVA model)
33 Battery equalization
34
35
Battery equalization
voltage
Battery equalized time
5 min
The setting range is from 5 min to
900 min. Increment of each click is 5
min.
900 min
If “USE” is selected in program 05, this program can be set up.
Battery equalization
Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
4KVA/5KVA default setting: 58.4V. Setting range is from 48V ~
58.4V. Increment of each click is 0.1V.
60min (default)
Setting range is from 5min to 900min.
Increment of each click is 5min.
36
37
39
Battery equalized timeout
Equalization interval
Equalization activated
immediately
120min (default)
30days (default)
Enable
22
Setting range is from 5min to 900 min.
Increment of each click is 5 min.
Setting range is from 0 to 90 days.
Increment of each click is 1 day
Disable (default)
If equalization function is enabled in program 33, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows “
equalization function until next activated equalization time
arrives based on program 37 setting. At this time, “
be shown in LCD main page.
”. If “Disable” is selected, it will cancel
” will not
Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched as below orde
Selectable information LCD display
AC Input 1 voltage/ AC output 1 voltage
(Default Display Screen)
.
AC Input 1 Voltage=230V, AC output 1 voltage=230V
AC Input 2 voltage/ AC output 2 voltage
AC Input 1 frequency/AC output 1 frequency
AC Input 2 Voltage=230V,AC output 2 voltage=230V
AC Input 1 frequency=50Hz,AC output 1 frequency=50Hz
AC Input 2 frequency=50Hz, AC output 2 frequency=50Hz
AC Input 2 frequency /AC output 2 frequency
23
MPPT Input 1 Charging current / MPPT Input
1 Charging power
MPPT Input 2 Charging current / MPPT Input
2 Charging power
PV1 voltage=60V , PV1 Power = 200W
PV2 voltage=60V ,PV2 Power = 200W
Load 1 Watt/ Load 1 percentage
Load 2 Watt/ Load 2 percentage
Load 1 Watt=200W, Load 1 percent=60%
Load 2 Watt=200W, Load 2 percent=60%
Load 1 Watt=200W, Load 1 in VA=600VA
Load 1 Watt/ Load 1 in VA
24
Load 2 Watt/ Load 2 in VA
Load 2 Watt 200W, Load 2 in VA=600VA
DC charging current / Battery voltage
Battery voltage/ DC discharging current
Charging current=25A, Battery voltage=56.0V
Battery voltage=53.0V, discharging current=1A
Main CPU version 00014.04
Main CPU version checking
Secondary CPU version: 00003.03
Secondary CPU version checking
Operating Mode Description
Operation mode Description LCD display
25
Standby mode
Note:
*Standby mode: The inverter
is not turned on yet but at this
time, the inverter can charge
battery without AC output.
Fault mode
Note:
*Fault mode: Errors are
caused by internal circuit
errors or external reasons
such as over temperature,
output short circuited and so
on.
No output is supplied by the
unit but it still can charge
the batteries.
PV energy can charge the
batteries.
Charging by utility.
Charging by PV energy.
Charging by PV energy and utility
No charging.
Charging by PV energy.
No charging.
Charging by PV energy
Charging by utility.
The unit will provide output
Line Mode
power from the mains. It
will also charge the battery
in line mode.
Charging by PV energy and utility
Battery Mode The unit will provide output Power from battery and PV energy.
26
power from battery and PV
power.
Power from battery only.
Fault Reference Code
Fault Code Fault Event Icon on
01 Fan is locked when inverter is off.
02 Over temperature
03 Battery voltage is too high
04 Battery voltage is too low
05
06 Output voltage is too high.
07 Overload time out
08 Bus voltage is too high
09 Bus soft start failed
11 Main relay failed
51 Over current or surge
52 Bus voltage is too low
Output short circuited or over temperature is detected
by internal converter components.
53 Inverter soft start failed
55 Over DC voltage in AC output
56 Battery connection is open
57 Current sensor failed
58 Output voltage is too low
87 Internal host and slave mismatching
88 Parallel ID missing
89 Parallel ID clash
91 Working mode synchronization loss
27
Warning Indicator
Warning
Code
01
Warning Event Audible Alarm Icon flashing
Fan is locked when
inverter is on.
Beep three times every
second
03 Battery is over-charged Beep once every second
04 Low battery Beep once every second
07 Overload Beep once every 0.5 second
10 Output power derating Beep twice every 3 seconds
12
13
14
15
Solar charger stops due
to low battery.
Solar charger stops due
to high PV voltage.
Solar charger stops due
to overload.
LCD connects to slave
units
28
SPECIFICATIONS
Table 1: Line Mode Specifications
INVERTER MODEL 5KVA
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage 140Vac±7V
High Loss Return Voltage 135Vac±7V
Max AC Input Voltage 150Vac
Nominal Input Frequency 50Hz / 60Hz (Auto-detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit
Protection
110/120Vac(L-N or L1-N-L2)
95Vac±7V (UPS)
65Vac±7V (Appliances)
100Vac±7V (UPS);
70Vac±7V (Appliances)
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Max bypass current 40A
Efficiency (Line Mode) >95% ( Rated R load, battery full charged )
Transfer Time (P1-N-P2)
Transfer Time (P-N)
Output power derating:
When AC input voltage drops to
95V, the output power will be
derated.
10ms typical, 12ms maximum @50Hz (UPS);
20ms typical, 25ms maximum @50Hz (Appliances)
30ms @50Hz
120Vac model:
29
Table 2: Inverter Mode Specifications
INVERTER MODEL 5KVA
Rated Output Power
Output Voltage Waveform
Nominal DC Input Voltage 48Vdc
Cold Start Voltage 46.0Vdc
Low DC Warning Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Warning Return
Voltage
@ load < 20%
44.0Vdc
42.8Vdc
40.4Vdc
46.0Vdc
@ 20% ≤ load < 50%
@ load ≥ 50%
44.8Vdc
42.4Vdc
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
42.0Vdc
40.8Vdc
38.4Vdc
High DC Recovery Voltage 58Vdc
High DC Cut-off Voltage
60Vdc
No Load Power Consumption <100W
30
Table 3: Charging Mode Specifications
Utility Charging Mode
INVERTER MODEL 5KVA
Charging Current (UPS)
@ Nominal Input Voltage
Bulk
Charging
Voltage
Flooded Battery 58.4Vdc
AGM / Gel
Battery
2A/10A/20A/30A/40A/50A/60A
56.4Vdc
Floating Charging Voltage 54Vdc
Overcharge Protection 60Vdc
Charging Algorithm 3-Step
Charging Curve
Solar Charging Mode(Per number of MPPT)
INVERTER MODEL
5KVA
Rated Power 4000*2 W
Max. efficiency 96%
Max. PV Array Open Voltage 145Vdc
PV Array MPPT Voltage
Range
Min. battery voltage for PV
charge
60~115Vdc
34Vdc
Standby Power Consumption <23W
Battery Voltage Accuracy +/-0.3%
PV Voltage Accuracy +/-2V
Charging Algorithm 3-Step
Joint Utility and Solar Charging
INVERTER MODEL 5KVA
Max. Charging Current
Default Charging Current
220A
60Amp
31
Table 4 General Specifications
INVERTER MODEL 5KVA
Safety Certification CE
Operating Temperature Range
0°C to 55°C
Storage temperature -15°C~ 60°C
Dimension (D*W*H), mm
Net Weight, kg
130 x 622.6 x 610
30
32
TROUBLESHOOTING
Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down
automatically
during startup
process.
No response after
power on.
Mains exist but the
unit works in
battery mode.
When the unit is
turned on, internal
relay is switched on
and off repeatedly.
Buzzer beeps
continuously and
red LED is on.
LCD/LEDs and buzzer
will be active for 3
seconds and then
completely off.
No indication.
Input voltage is
displayed as 0 on the
LCD and green LED is
flashing.
Green LED is flashing.
Green LED is flashing.
LCD display and LEDs
are flashing
Fault code 07
Fault code 05
Fault code 02
Fault code 03
Fault code 01 Fan fault Replace the fan.
Fault code 06/58
Fault code
08/09/53/57
Fault code 51 Over current or surge.
Fault code 52 Bus voltage is too low.
Fault code 55 Output voltage is unbalanced.
Fault code 56
The battery voltage is too low
(<1.91V/Cell)
1. The battery voltage is far too
low. (<1.4V/Cell)
2. Battery polarity is connected
reversely.
Input protector is tripped
Insufficient quality of AC power.
(Shore or Generator)
Set “Solar First” as the priority of
output source.
Battery is disconnected.
Overload error. The inverter is
overload by 110% and time is up.
Output short circuited.
The temperature of internal
converter is over 120°C. (Only
available for 1-5KVA models.)
The internal temperature of the
inverter is over 100°C.
Battery is over-charged. Return to repair center.
The battery voltage is too high.
Output abnormal (Inverter voltage
is lower than 190Vac or is higher
than 260Vac)
Internal components failed. Return it to repair center.
Battery is not connected well or
fuse is burnt.
1. Re-charge the battery.
2. Replace the battery.
1. Check if batteries and the
wiring are connected well.
2. Re-charge the battery.
3. Replace the battery.
Check if AC breaker is tripped
and AC wiring is connected
well.
1. Check if AC wires are too
thin and/or too long.
2. Check if generator (if
applied) is working well or if
the setting range of input
voltage is correct.
(UPSAppliance)
Change output source priority
to Utility first.
Check if battery wires are
connected well.
Reduce the connected load by
switching off some
equipment.
Check if wiring is connected
well and remove abnormal
load.
Check whether the air flow of
the unit is blocked or whether
the ambient temperature is
too high.
Check if spec and quantity of
the batteries meet the
requirements.
1. Reduce the connected
load.
2. Return it to repair center
Restart the unit, if the error
happens again, please return
it to repair center.
If the battery is connected
well, please return it to repair
center.
33
Appendix I: Approximate Back-up Time Table
Model Load (VA) Backup Time @48Vdc 200Ah (min) Backup Time @48Vdc 400Ah (min)
500 1226 2576
1000 536 1226
1500 316 804
2000 222 542
5KVA
Note: Backup time depends on the quality of the battery, age of battery and type of battery.
Specifications of batteries may vary depending on different manufacturers.
2500 180 430
3000 152 364
3500 130 282
4000 100 224
4500 88 200
5000 80 180
34
Appendix II: Parallel function
1. Introduction
This inverter can be used in parallel with three different operation modes.
1. Parallel operation in single phase with up to three units. The supported maximum output power is
15KW/15KVA.
2. Maximum three units work together to support three-phase equipment. The supported maximum output
power is 15KW/15KVA.
3. Maximum three units work together to support two-phase equipment. One units support two phase. The
supported maximum output power is 15KW/15KVA and one phase can be up to 7.5KW/7.5KVA.
WARNING! The AC input N wires must be connected together; the AC output N wires must be connected
together.
2. Package Contents
In parallel kit, you will find the following items in the package:
Parallel communication cable Current sharing cable
3. Mounting the Unit
When installing multiple units, please follow the illustration below.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same height.
4. Wiring Connection
The size of the cable for each inverter is shown as below:
WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference
between inverter and battery which might cause mal-function of the parallel inverters.
Recommended battery cable and terminal size for each inverter:
Model Wire Size Torque value
35
5KVA 2*4AWG 5~ 6 Nm
Recommended cable size of AC input and output for each inverter:
Model AWG no. Torque
5KVA 10 AWG 1.4~1.6Nm
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use
a connector or bus-bar as a joint to connect the battery cables together, and then connect it to the battery
terminal. The size of the cable used from joint to battery should be X times cable size in the tables above. “X”
indicates the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be
securely disconnected during maintenance and fully protected from over current of battery or AC input. The
recommended mounted location of the breakers is shown in the parallel diagrams in section 5-1 and 5-2.
Recommended specification of battery breaker for each inverter:
Model 1 unit*
5KVA 125A/80VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should
be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended specification of AC input breaker in single phase:
Model
2 units 3 units
5KVA 80A/230VAC 120A/230VAC
Note 1: You also can use only one 40A breaker for each inverter at its AC input.
Note 2: Regarding three-phase system, you can use 3-pole breaker directly and the rating of the breaker
should be compatible with the phase current limitation from the phase with maximum units.
Recommended battery capacity
Inverter parallel numbers 2 3
Battery Capacity 400AH 600AH
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will be
transferred to fault mode.
36
4-1. Parallel Operation in Single phase
❶
❷
Two inverters in parallel(0°):
Power Connection
L1 L2L1 L2
N
L
N
Load
Communication Connection
Three inverters in parallel(0°):
Power Connection
L
37
Communication Connection
38
4-2. Support 2-phase equipment
Two inverters in parallel (120°):
Power Connection
N
L1
L2
Load
L1
L2
Communication Connection
Two inverters in parallel (180°):
Power Connection
39
N
L1
L2
N
Load
L1
L2
Communication Connection
Three inverters in parallel (120°):
Power Connection
40
N
L1
L2
Load
L1
L2
Communication Connection
Three inverters in parallel (180°):
Power Connection
N
L1
L2
N
Load
L1
L2
Communication Connection
41
4-3. Support 3-phase equipment
One inverter in each phase:
Power Connection
Communication Connection
WARNING: Do NOT connect the current sharing cables between the inverters in different phases. Otherwise,
it may damage the inverters.
NOTE:
For parallel model operation, please refer to LCD program 28
5. PV Connection
Please refer to the user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
42
6. LCD Setting and Display
Setting Program:
Program Description Selectable option
parallel output(0°)
28
AC output mode
*This setting is only
available when the
inverter is in
standby mode
(Switch off).
Phase 1 of 3 Phase
output
Phase 2 of 3 Phase
output
Phase 3 of 3 Phase
output
Parallel output (120°)
parallel output(180°)
When the units are used in parallel with
single phase, please select “2A0”、
“2A1”and “2A3” in program 28.
It is required to have at least 3 inverters
or maximum 6 inverters to support
three-phase equipment. It’s required to
have at least one inverter in each phase
or it’s up to four inverters in one phase.
Please refers to 5-2 for detailed
information.
Please select “3P1” in program 28 for the
inverters connected to L1 phase, “3P2” in
program 28 for the inverters connected to
L2 phase and “3P3” in program 28 for the
inverters connected to L3 phase.
Be sure to connect shared current cables
to units in the same phase.
Do NOT connect shared current cables
between units in different phases.
30
PV judge condition
(Only apply for
setting “Solar first”
in program 1:
Output source
priority)
One Inverter (Default):
When “ONE” is selected, as long as one
of the inverters has been connected to PV
modules and PV input is normal, parallel
or 3-phase system will continue working
according to rule of “solar first” setting.
For example, two units are connected in
parallel and set “SOL” in output source
priority. If one of the two units has
connected to PV modules and PV input is
normal, the parallel system will provide
power to loads from solar or battery
power. If both of them are not sufficient,
the system will provide power to loads
from utility.
43
When “ALL” is selected, parallel or
3-phase system will continue working
according to rule of “solar first” setting
only when all of inverters are connected
to PV modules.
All of Inverters:
For example, two units are connected in
parallel and set “SOL” in output source
priority. When “ALL” is selected in
program 30, it’s necessary to have all
inverters connected to PV modules and
PV input is normal to allow the system to
provide power to loads from solar and
battery power. Otherwise, the system will
provide power to loads from utility.
44
Fault code:
Fault Code Fault Event Icon on
60 Power feedback protection
71 Firmware version inconsistent
72 Current sharing fault
80 CAN fault
81 Host loss
82 Synchronization loss
83 Battery voltage detected different
84 Different AC input voltage and frequency detected
85 AC output current unbalance
86 AC output mode setting is different
7. Commissioning
Parallel in single phase
Step 1: Check the following requirements before installation:
Correct wire connection
Ensure all breakers in Line wires at load side are open and each Neutral wires of each unit is connected
together.
Step 2: Turn on all of the units and configure LCD program 28 as 2A0 or 2A1 or 2A2. And then shut down all
units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting cannot be
programmed. All the units must use same selection.
Step 3: Turn on each unit.
LCD display of “2A0” selection LCD display of “2A1” selection LCD display of “2A2” selection
45
Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to connect all of the inverters to the utility
at the same time. If not, it will display fault 82 in the following inverters. However, these inverters will
automatically restart. If detecting AC connection, they will work normally.
LCD display of “2A0” selection LCD display of “2A1” selection LCD display of “2A2” selection
Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Support three-phase equipment
Step 1: Check the following requirements before installation:
Correct wire connection
Ensure all breakers in Line wires at load side are open and each Neutral wires of each unit is connected
together.
Step 2: Turn on all of the units and configure LCD program 28 as 3P1, 3P2 and 3P3 sequentially. And then shut
down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting cannot be
programmed.
Step 3: Turn on all units sequentially.
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are
matched with unit setting, they will work normally. Otherwise, the AC icon
will flash and they will not work
in line mode. Under this circumstance, you can switch wires of AC inputs from L2 phase and L3 phase. Or you
may exchange the LCD program 28 of P2 and P3 to solve this problem.
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit
Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Note 1: To avoid overload occurring, before turning on breakers at load side, it’s better to have the whole
system in operation first.
Note 2: There is some transfer time for this operation. Power interruption may happen to critical devices,
which cannot tolerate transfer time.
46
8. Troubleshooting
If the device fails to function as expected, check the list of common faults below before consulting the service
center.
Situation
Fault
Code
60
71
72
80 CAN data loss
81 Host data loss
82
83
84
85
86
Fault Event Description
Current feedback into
the inverter is
detected.
The firmware version
of each inverter is not
the same.
The output current of
each inverter is
different.
Synchronization data
loss
The battery voltage of
each inverter is not the
same.
AC input voltage and
frequency are detected
different.
AC output current
unbalance
AC output mode
setting is different.
1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the current sharing cables
are connected to all inverters.
For supporting three-phase system, make sure the current sharing
cables are connected to the inverters in the same phase, and
disconnected to the inverters in different phases.
4. If the problem remains, please contact your installer.
1. Update the firmware of all inverter to the same version.
2. Check the version of each inverter via LCD setting and make sure the
CPU versions are the same. If not, please contact your installer to
provide the latest firmware to update.
3. After updating, if the problem still remains, please contact your installer.
1. Check if shared cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
1. Check if communication cables are connected well and restart the
inverter.
2. If the problem remains, please contact your installer.
1. Make sure all inverters share the same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check
battery voltage of all inverters. If the values from all inverters are close,
please check if all battery cables are in the same length and in the same
material type. Otherwise, please contact your installer to provide SOP to
calibrate battery voltage of each inverter.
3. If the problem still remains, please contact your installer.
1. Check the utility wiring conncetion and restart the inverter.
2. Make sure utility starts up at same time. If there are breakers installed
between utility and inverters, please be sure all AC input breakers can be
turned on at same time.
3. If the problem remains, please contact your installer.
1. Restart the inverter.
2. Remove some excessive loads and re-check the load information from
LCD of the inverters. If the values are different, please check if AC input
and output cables are in the same length and in the same material type.
3. If the problem remains, please contact your installer.
1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set
on #28.
For supporting three-phase system, make sure no “PAL” is set on #28.
3. If the problem remains, please contact your installer.
Solution
47
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.