AXOR 10452181 Installation Manual

Philippe Starck Two-Handle Tub Filler
Rough-In 10452181 Installation
Installation Considerations:
The 10458XX1 two-handle tub filler is designed to be installed with bathrooms that will be fitted with water impervious flooring such as tile, marble, or decorative stone.
The 10452181 rough-in kit may be secured directly to concrete sub-flooring using the supplied anchors. A three-inch minimum*, six-inch maximum* grout bed must be laid over the completed rough-in assembly.
*THESE MINIMUM-MAXIMUM MEASURE-
MENTS ARE FOR THE GROUT BED ONLY.
THESE MEASUREMENTS ASSUME 1/4TILE
BE LAID OVER THE GROUT BED. FOR
WILL
THICKER THAN 1/4, SUBTRACT ANY
TILES THICKNESS THICKNESS
USED, THE MINIMUM GROUT BED THICKNESS
IS WOULD WOULD SUBFLOOR THICKNESS
OVER 1/4 FROM THE GROUT BED . FOR EXAMPLE, IF 1/2 THICK TILE
BE 2 3/4 AND THE MAXIMUM BE 5 3/4. MEASURING FROM THE
UP, THE MINIMUM OVERALL FLOOR
IS 3 1/4 AND THE MAXIMUM IS 6
1/4. SPECIAL CONSIDERATION WILL BE
NECESSARY PORTION ALLOW MENTS
DURING THE FLOOR FRAMING
OF THE CONSTRUCTION PROCESS TO
FOR THESE FLOOR THICKNESS REQUIRE-
55
Installation
Installation Instructions
Apply plumbers thread sealing tape on two six-inch brass threaded pipe
nipples (not supplied) and tighten them into the brass rough-in flange. Hot and cold connections will be made to these nipples.
If the water connections are to be made below the floor, elbows can be
fitted to the brass nipples and turned down through the floor. The water piping can be routed alternately along the surface of the sub-flooring if desired.
Note: It is important to have at least six inches of hot and cold piping
on top of the sub-flooring as it lends stability to the tub filler when embedded in the grout floor. Strap all support piping to the sub-flooring.
Remove and set aside the six hex-head screws securing the black plastic
plaster guard from the brass rough-in flange. Position the brass rough-in flange in the desired location of the two-handle tub mixer. Orient the two water inlets to allow convenient connection to the hot and cold supplies. Using the rough-in flange as a template, mark the six screw holes using a 3/16 drill bit. Secure the rough-in flange to the floor using the supplied lag screws.
IMPORTANT: Make sure to keep the brass rough-in flange
level in all planes.
The brass rough-in flange can also be through-bolted to the wood sub-
flooring, if desired (hardware not included).
The same procedure is used for a concrete sub-floor, with the exception
that an eight-millimeter masonry drill bit is used for the screw holes. The plastic masonry anchors (supplied) are inserted into the six screw holes and the rough-in flange is secured to the concrete sub-floor using the supplied screws. Once again, the flange must be level in all planes, and grout and tile built up to the same dimensions over the completed rough in, just as in a wood sub floor installation.
56
Installation
Loading...
+ 3 hidden pages