This symbol indicates that there are important operating and maintenance instructions in the
literature accompanying this unit. Read, Keep and Follow all instructions.
Prior to installation and use of this product, observe the following warnings.
1. Installation and servicing should only be carried out by qualified service personnel and
2. It is essential that provision is made for overload, short circuit and earth fault protection
3. A readily accessible disconnection device shall be incorporated in the electrical
4. Only use tools and replacement parts supplied or recommended by EATON.
5. Care must be taken to ensure selection of suitable cables connecting to these units,
6. The equipment is designed to satisfy the requirements of UL60065 7
7. Be aware that aggressive substances may require extra protection of the equipment to
8. The equipment may need additional means of protection if it is to be installed in
9. Any repairs or replacement parts must be done by the manufacturer or a suitably
10. Due to the large weight of the units, correct planning and equipment must be used
11. Systems can be fitted with integral Fibre Optic transmitters, this means that the fibre
NFPA 70 500.8 (F)
12. When batteries are fitted to electronic equipment they must be removed and are not to
13. After installation, operatives must adhere to the following warning on the units label:
This symbol indicates that dangerous voltage constituting a risk of electric shock may be present
within this unit.
14. Illuminator “CAUTION Possibly hazardous optical radiation emitted from this product.”
1.1 Important Safeguards and Warnings
in accordance with all local/national codes of practice and standards e.g. UL1203
Edn.5, NFPA 70 no modification to the certified product allowed.
for this equipment. Therefore we recommend that a double pole, mains rated,
miniature circuit breaker rated to the max power consumption of the unit, must be
incorporated in the electrical installation of the power supply to this product.
installation wiring, to provide all pole isolation of the supply to the equipment.
This unit does not contain any user serviceable parts.
when installed in operating temperatures above +70°C.
th
Edition
2013/07/24. CSA C22.2 No. 60065-03 2012/08/01 Safety Requirements ANNEX II of
ATEX directive 94/9/EC.
maintain its integrity and explosion protection.
locations where it may be exposed to excessive external stresses e.g. vibration, heat,
impact and damage.
qualified repair agent.
when unpacking and installing also for the P&T units the correct lifting points must be
adhered to (see section 3.1.2)
optic cabling used has additional protective measures to ensure that the optical
radiation is confined within the cabling, by the use of a robust conduit covering
externally, and Kevlar braided cable inside the conduit and the enclosure.
The 2400 & 1400 series camera assemblies have been developed to meet the rigorous
requirements of Flame proof and dust-ignition-proof electrical equipment for installation and use
in hazardous locations found in the onshore and offshore, oil & gas and petro-chemical
installations. The units may also be used in marine and industrial hazardous environments.
The housing body and all external parts are manufactured entirely of AISI 316L stainless steel for
low maintenance and protection from corrosion.
Each of the main end covers is fixed to the body by five (5), M6 x 16-mm stainless steel hex cap
screws, with the cable entry cover of the XP and XT systems using five M5 x 12-mm stainless
steel hex cap screws or M110x1.5 screw on cover; all conforming to the requirements of UL 1203
The weatherproof seal of the union between the body and end covers is maintained by use of ‘O’
ring seals fitted in purpose made grooves.
The camera housings feature an internal sliding camera mounting rail which is fitted with an
internal heating element/de-mister, thermostatically controlled, to maintain operating
temperature, and ensure clarity of vision through the window, together with the optional
integral window wiper mechanism.
The viewing window is made with toughened glass, or in the case of the Thermal Imager and
Dual Imager versions, is made from Infra red transparent material and which is factory fitted with
a mechanical window guard.
The mechanical thermal window guard MUST not be removed.
There are four system types that are made up from different combinations of the 2400 and 1400
series certified units; these are:
XF series, fixed camera housings.
XC series, P&T units with integral tilt shaft only.
XP series, P&T units with integral pan and tilt shafts and a fixed base section for cable
connection.
XT series, P&T units with integral pan and tilt shafts and a fixed base section for cable
connection, also a secondary housing for integrated illuminator.
The XF series fixed housings comprise a single tube section with either 3 cable entries in the rear
cover or 1 in the side (model dependant).
The XC series comprise a camera housing fixed to a P&T unit via an integrated tilt shaft; there are
3 cable entries in the rear cover of the housing or 1 into the blank side of the T unit (model
dependant).
The XP and XT units have dual cable entries into the fixed base section, this prevents any trailing
cables.
The 2400 & 1400 series housings and integrated pan/tilt units have been designed and certified
to UL1203, with the following rating:
Class I Div 1 Group B,C,D
Class II Div 1 Groups E,F,G
T4 T135°C IP66/67
Note: T class and ambient temperature, is dependent on the assembly configuration and
maximum internal power dissipation.
*=T class
## = Ambient Temperature range
The project requirements and unit certification label must be checked by the installer before
installation, to confirm that the product supplied is suitable for the intended installation zone
and environment.
Manufactured in accordance with
There are various camera configurations available within the range; these include Day/Night
cameras with optional wiper, integral washer or external washer, Thermal Imager and Dual
Camera Day/Night and Thermal units.
The range also includes options for Standard Analogue Video and Data, HD IP cameras, Hybrid IP
encoders, Digital Fibre optic convertors and Media convertors.
Due to the large variations of possible configurations, this manual only covers the standard
installation of the units.
For detailed connection and configuration of units, the installer should refer to individual project
specific drawings and information.
In addition to this manual there are various addendums available that cover the specific function
of electronics that can be included within the camera assemblies.
2.2 Supplied Equipment
Contained in the package are the following items:
Camera system
Installation/Technical Manual
Optional Sunshield and Fixings
Optional Washer Nozzle Kit
2.4 Recommended Tools
For installation and maintenance purposes, we recommend the following hand tools:
Voltmeter/Ohmmeter
Torque wrench kit Set to 7.5Nm, Hex Allen wrench bits of 5, 4, 3 & 1.5mm
Spanners 5.5mm, 8mm, 10mm & 13mm A/F
Screw drivers standard and Phillips head
Pliers side cutting and long nose
2.5 Recommended Spares
For Maintenance purposes, we recommend the following spares:
PTZ Seal Kit: O Ring seal kit, spare M6 x 16 & M3 x 6 screws PX99902901
Wiper Assembly (for systems with integrated wiper) PX99902849
XP40 Washer Nozzle (for systems with optional washer system) PX99902864
XP26 Washer Nozzle (for systems with optional washer system) PX99902848
XF Fixed Washer Nozzle (for systems with optional washer system) PX99902865
In order to ensure proper wiring and system operation of all components, it is recommended
that all units and all associated control equipment be tested at your Factory before field
installation is attempted.
3.1 Unpacking and Handling
3.1.1 Unpacking
On receipt of the units ensure that the cartons are undamaged and that the contents are all
correct and complete.
After unpacking it is recommended that the packing materials are kept safe in case they are
needed for returning the unit for repair or maintenance.
The protective white film should be removed from sunshields prior to fitting.
3.1.2 Handling
Due to the large weights of the products, correct handling is of great importance.
Lifting into position of P&T units should always be completed using suitable lifting equipment
that is capable of supporting loads in excess of 65Kg. P&T systems should only be lifted using
the T section of the P&T, with equal support on both sides; the camera housing section of the
unit must not be used for lifting. To avoid causing damage to the unit do not rotate by hand.
The units should not be handled having direct contact with ferrous metal equipment. (see
section 4.1 for details)
3.2 Mounting
To prevent injury ensure the mounting surface and the selected mount can support four
times the combined weight of the complete unit.
Do not stand or place objects “directly under” installed system.
Due care must be taken to ensure sufficient clearance is allowed to permit full rotation of the
unit with its associated equipment mounted and that the moving unit cannot make contact
with personnel.
It is strongly suggested that where possible the Eaton range of mounting brackets are used
3.2.1 Mounting the XP & XT Series (Horizontal or Inverted Only)
The XP and XT pan/tilt/housing assembly may be mounted onto various structures such as
bulkheads, walls or towers, it can be mounted in the Horizontal or inverted position but the
inverted option must be specified upon order.
The complete assembly is mounted to the support structure via its base mount which has
11mm clearance holes for four (4) No. M10 fixings. (Fig 1)
The type and size of these fixings to be supplied by the user/installer and must be suitable
for the specific installation requirements.
An alternative is to use the BPW6800 Wall mount bracket (Fig 2)
3.2.2 Mounting the XC Series
The XC pan/tilt/housing assembly may be mounted onto various structures such as bulkheads,
walls or towers, it can be mounted in the inverted position but this must be specified upon
order.
The complete assembly is mounted to the support structure via its Pan shaft and this has four
(4) No. M8 Threaded fixing points on an industry standard spacing PCD of 101.6mm (4”). (Fig 3)
The type and size of these fixings to be supplied by the user/installer and must be suitable for
the specific installation requirements. An alternative is to use the BFW5000 Wall mount
bracket (Fig 4) or one of the BFP**00 Column Spacers. (Fig 5)
Fig.6 XF60VN Example XF Series unit showing mount plate fixing points
Fig.7 BFP00SW Swivel Joint & Pole Top Adaptor
Fig.8 BFW32SW Swivel Joint & Pole Top Adaptor
3.2.3 Mounting the XF Series
The XF Series fixed housing assemblies may be mounted onto various structures such as
bulkheads, walls or towers. The units have a mounting plate on the bottom of the housing tube
that have
four (4) No. M6 Threaded fixing points. (Fig 6)
The type and size of these fixings to be supplied by the user/installer and must be suitable for
the specific installation requirements.
To gain flexibility of the cameras view direction one of the Eaton brackets is needed, these
comprise of the BFP00SW Swivel joint (Fig 7), the BFW32SW (Fig 8) or a combination of the
BFW5000 and BFP00SW. (Figs 4 & 7)
Depending on Housing length, some wall brackets do not allow for the camera to view directly
away from the Wall and must be rotated or tilted to allow room for gland entry.
Sunshields are supplied uninstalled to prevent damage during shipping and unpacking. They are
supplied with a protective white film that must be removed prior to installation.
The correct sunshield fixings, for each model, are supplied with the camera system and should
be positioned as detailed below.
To mount the sunshields, first they must be positioned correctly and fixed with a Nylon spacer
between the sunshield and the camera housing, the M6 A4 Button head screws supplied must
have the red fibre washer fitted before fixing the sunshield. (Fig 9 & 10)
Long and Medium sunshield have four equally sized fixings for each corner but the short
sunshield has two fixing types, one for the front and shorter screws and nylon spacer at the
rear. (Fig 10)
Fig.13 Non-continuous Rotation P&Ts and Fixed housings washer nozzle
3.3.2 Washer Nozzle Installation
A continuous rotation P&T system, if supplied with an external washer unit, is supplied with a
suitable washer nozzle and mounting bracket. These should be fitted during installation with
the supplied fixing and positioned to allow cleaning fluid to reach the camera housing window
when the wash command is sent. The supplied washer nozzle brackets are specific to housing
type and are delivered pre-aligned for use.(Fig. 11 & 12)
When a wash command is sent to the camera, the unit will move to the factory set position to
allow for the screen to be washed.
For non-continuous rotation P&Ts and fixed housings the washer nozzle is installed on the front
window flange. (Fig. 13)
Electrical installation and servicing should only be carried out by qualified skilled personnel
the class of wiring shall be marked adjacent to the mains terminals and in accordance with all
local/national codes of practice and standards e.g. UL 1203 Edn. 5, CSA22.2 No30-M1986
reaffirmed 2014, CSA C22.2 No25-1966 reaffirmed 2014, CSA C22.2 No 60065-03 Edn. 1,
UL60065 Edn. 7,
Due to the large variations of possible configurations, this manual only covers the standard
installation of the units.
For detailed connection and configuration of units, the installer should refer to individual
project specific drawings and information.
Units can be supplied, as required, with either 24VAC, 110VAC~ or 230VAC~ Supply; all ±10%
The units should only be powered from the specified voltage; no allowance is made for
varying voltage supply.
Warning : Irreparable damage to the unit will result from the application of
1. Always use colour-coded conductors or other identification of conductors for ease
of wiring and identification of function at a later date.
2. Keep a wiring diagram with the system for later use and reference.
3. Provision is made for one or two cable entries, at the base mount of the pan tilt.(Fig
14A to 14E)
To maintain the certification requirements of the unit all cables/conduits must be
fitted at the entry, with certified Class / Div Flameproof, compound filled barrier
glands, or conduit sealing fittings within 2” or 50mm of the enclosure.
4. The cable entry to the unit is either two or one ¾” NPT thread (model dependant),
or ½” NPT using a suitably certified reducer, dependent on what was specified at
order.
5. A minimum of 5 fully engaged threads must be maintained for all glands.
6. All unused threaded openings shall be closed by suitably approved threaded plugs,
recommended EBNV/7 approved.
7. All glands/reducers must be ingress protected to IP67 or better, to maintain the
weatherproof rating of the equipment.
8. For maintenance purposes, consult separately supplied additional wiring drawings
specific to the purchase order, for as built wiring and connection details of the unit.
9. The Dual entry option has an accessible input fuse (f1). Check that the input fuse
matches the voltage requirement – 24VAC – 6.3A ≥110 – 2A
Fig.14 Gaining access to the XP and XT Base junction box (single entry design)
Fig.15 Gaining access to the XP and XT Base junction box (dual entry design)
Fig.16, 17 & 18 Unscrew entry chamber lid, the two M5 button head screws and threaded holes can
be used to assist in rotating the chamber lid.
Fig.19 & 20 Remove connection cover to reveal all connections.
Caution should be taken when
removing and inserting the cable
entry flange to avoid internal
cable becoming snagged on
corners or screws.
THE CABLE ENTRY FLANGE
SHOULD NEVER BE REMOVED
Fig.26 & 27 Removing the connection cover to reveal all connections for high voltage options
To gain access to the internal camera rail, first the rail will need
to be slid out to allow connections to be made. If a wiper is
fitted, first take note of the parked position of the wiper arm
and then remove it by loosening the M4 cap head screw that
clamps to the wiper shaft. Keep the wiper and nylon washer
safe for refitting. This is best done without the sunshield fitted.
Remove the front window flange by first
removing the 5 x M6 screws and then carefully
extracting the flange.
Next slide out the camera mounting rail, if
required.
Remove the rear flange by first removing the 5 x M6
screws and then carefully extracting the flange.
Next slide out the camera mounting rail to reveal
the incoming cable connection terminals.
3.4.3 Electrical Installation XF & XC Series units
1. Cable entry type to the housing is via 1 x ½”NPT entry at the side adaptor of the housing,
or for some version via the triple ¾”NPT cable entry end cover on the rear of the
housing, solely for connection of power and signal wiring, no internal user wiring is
allowed in this unit.(Fig 15, 16 & 17)
2. Keep a wiring diagram with the system for later use and reference.
3. For maintenance purposes, consult separately supplied additional wiring drawings
specific to the purchase order, for as built wiring and connection details of the unit.
Inspect the unit every six months to ensure trouble free operation and extend product life.
Due to the rugged construction of the unit, little or no maintenance should be required.
However when the unit is exposed to extreme weather conditions the ‘O’ ring weather seals
may need replacement approximately every five years.
Fixings and fastenings should be checked for tightness and integrity at regular intervals.
All cable entries and cables should be checked for integrity at regular intervals.
Extremely Harsh Environments may require more frequent inspection and maintenance
checks.
At every Inspection carry out the following:
• Clean the unit.
• Check the ‘O’ ring weather seals and replace if necessary.
• Check and if necessary replace the washer nozzle.
• Check and if necessary replace the window wiper blade assembly.
Please read and be familiar with the instructions before servicing the Pan/Tilt or housing.
4.1 Corrosion Protection
Although all external metal components are produced from 316L Stainless Steel, if the units
are not correctly maintained, handled and cleaned there is the possibility of mild
discolouration due to Oxidation.
If ferrous metal equipment is used when handling the units, small ferrous deposits could be
left on the stainless steel or if ferrous metal particles come to rest upon the units from
nearby works, this can cause accelerated corrosion of the ferrous deposits and discolour the
units due to oxidation. In the event of ferrous deposits, the units should be cleaned
immediately following EATON guidelines.
In atmospheres that are high in corrosive particles the units should be cleaned every 3 to 4
months using only EATON recommended cleaning products and procedures. (contact EATON
for details)
EATON takes no responsibility for oxidisation due to failure in correctly following cleaning
procedures.