AXISA1001NetworkDoorController
InstallationGuide

English
EN
France:Français
Deutschland:Deutsch
Italia:Italiano
España:Español
FR
DE
IT
ES

Liability
Everycarehasbeentakeninthepreparationofthis
document.PleaseinformyourlocalAxisofceofany
inaccuraciesoromissions.AxisCommunicationsABcannot
beheldresponsibleforanytechnicalortypographicalerrors
andreservestherighttomakechangestotheproductand
manualswithoutpriornotice.AxisCommunicationsAB
makesnowarrantyofanykindwithregardtothematerial
containedwithinthisdocument,including,butnotlimited
to,theimpliedwarrantiesofmerchantabilityandtnessfor
aparticularpurpose.AxisCommunicationsABshallnot
beliablenorresponsibleforincidentalorconsequential
damagesinconnectionwiththefurnishing,performance
oruseofthismaterial.Thisproductisonlytobeusedfor
itsintendedpurpose.
Intellectualpropertyrights
AxisABhasintellectualpropertyrightsrelatingto
technologyembodiedintheproductdescribedinthis
document.Inparticular,andwithoutlimitation,these
intellectualpropertyrightsmayincludeoneormoreof
thepatentslistedataxis.com/patentandoneormore
additionalpatentsorpendingpatentapplicationsinthe
USandothercountries.
ThisproductcontainssourcecodecopyrightApple
Computer,Inc.,underthetermsofApplePublicSource
License2.0(seeopensource.apple.com/apsl).Thesource
codeisavailablefromdeveloper.apple.com/bonjour/
Equipmentmodications
Thisequipmentmustbeinstalledandusedin
strictaccordancewiththeinstructionsgiveninthe
userdocumentation.Thisequipmentcontainsno
user-serviceablecomponents.Unauthorizedequipment
changesormodicationswillinvalidateallapplicable
regulatorycerticationsandapprovals.
Trademarkacknowledgements
AXISCOMMUNICATIONS,AXISandVAPIXareregistered
trademarksortrademarkapplicationsofAxisABinvarious
jurisdictions.Allothercompanynamesandproductsare
trademarksorregisteredtrademarksoftheirrespective
companies.
AssaandAperioaretrademarksorregisteredtrademarksof
ASSAABLOYAB.
SimonsVossandSmartIntegoaretrademarksorregistered
trademarksbelongingSimonsVossTechnologiesGmbH
HID,HIDGlobal,theHIDBlueBricklogo,HIDMobileAccess,
iCLASSSE,Seos,Prox,andSecureIdentityServicesare
trademarksorregisteredtrademarksofHIDGlobalinthe
U.S.and/orothercountries.
NetworkTimeProtocolVersion4Distributioniscopyright
ofUniversityofDelaware–©UniversityofDelaware
1992–201 1.Thefollowingcopyrightnoticeappliestoall
lescollectivelycalledtheNetworkTimeProtocolVersion
4Distribution.Unlessspecicallydeclaredotherwisein
anindividualle,thisnoticeappliesasifthetextwas
explicitlyincludedinthele.Permissiontouse,copy,
modify,anddistributethissoftwareanditsdocumentation
foranypurposewithorwithoutfeeisherebygranted,
providedthattheabovecopyrightnoticeappearsin
allcopiesandthatboththecopyrightnoticeandthis
permissionnoticeappearinsupportingdocumentation,
andthatthenameUniversityofDelawarenotbeusedin
advertisingorpertainingtodistributionofthesoftware
withoutspecic,writtenpriorpermission.TheUniversity
ofDelawaremakesnorepresentationsaboutthesuitability
thissoftwareforanypurpose.Itisprovided"asis"without
expressorimpliedwarranty.
Support
Shouldyourequireanytechnicalassistance,pleasecontact
yourAxisreseller.Ifyourquestionscannotbeanswered
immediately,yourresellerwillforwardyourqueriesthrough
theappropriatechannelstoensurearapidresponse.Ifyou
areconnectedtotheInternet,youcan:
•downloaduserdocumentationandsoftwareupdates
•ndanswerstoresolvedproblemsintheFAQdatabase,
searchbyproduct,category,orphrase
•reportproblemstoAxissupportstaffbylogginginto
yourprivatesupportarea
•chatwithAxissupportstaff
•visitAxisSupportataxis.com/support
Learnmore!
VisitAxislearningcenteraxis.com/academyforuseful
trainings,webinars,tutorialsandguides.
Regulatoryinformation
Europe
ThisproductcomplieswiththeapplicableCEmarking
directivesandharmonizedstandards:
•ElectromagneticCompatibility(EMC)Directive
2014/30/EU.SeeElectromagneticcompatibility(EMC)
onpage4.
•LowVoltageDirective(LVD)2014/35/EU.SeeSafety
onpage5.
•RestrictionofHazardousSubstances(RoHS)Directive
201 1/65/EU,includinganyamendments,updatesor
replacements.SeeDisposalandrecyclingonpage5.
Acopyoftheoriginaldeclarationofconformitymaybe
obtainedfromAxisCommunicationsAB.SeeContact
informationonpage5.
Electromagneticcompatibility(EMC)
Thisequipmenthasbeendesignedandtestedtofulll
applicablestandardsfor:
•Radiofrequencyemissionwheninstalledaccordingto
theinstructionsandusedinitsintendedenvironment.
•Immunitytoelectricalandelectromagneticphenomena
wheninstalledaccordingtotheinstructionsandused
initsintendedenvironment.
USA
Thisequipmenthasbeentestedusingashieldednetwork
cable(STP)andfoundtocomplywiththelimitsfora
ClassBdigitaldevice,pursuanttopart15oftheFCC
Rules.Theselimitsaredesignedtoprovidereasonable
protectionagainstharmfulinterferenceinaresidential
installation.Thisequipmentgenerates,usesandcan
radiateradiofrequencyenergyand,ifnotinstalledand
usedinaccordancewiththeinstructions,maycause
harmfulinterferencetoradiocommunications.However,
thereisnoguaranteethatinterferencewillnotoccurin
aparticularinstallation.Ifthisequipmentdoescause
harmfulinterferencetoradioortelevisionreception,which
canbedeterminedbyturningtheequipmentoffandon,
theuserisencouragedtotrytocorrecttheinterferenceby
oneormoreofthefollowingmeasures:
•Reorientorrelocatethereceivingantenna.
•Increasetheseparationbetweentheequipmentand
receiver.
•Connecttheequipmentintoanoutletonacircuit
differentfromthattowhichthereceiverisconnected.

•Consultthedealeroranexperiencedradio/TV
technicianforhelp.
Theproductshallbeconnectedusingashieldednetwork
cable(STP)thatisproperlygrounded.
Canada
ThisdigitalapparatuscomplieswithCANICES-3(ClassB).
Theproductshallbeconnectedusingashieldednetwork
cable(STP)thatisproperlygrounded.Cetappareil
numériqueestconformeàlanormeCANNMB-3(classeB).
Leproduitdoitêtreconnectéàl'aided'uncâbleréseau
blindé(STP)quiestcorrectementmisàlaterre.
Europe
ThisdigitalequipmentfulllstherequirementsforRF
emissionaccordingtotheClassBlimitofEN55022.The
productshallbeconnectedusingashieldednetworkcable
(STP)thatisproperlygrounded.
Australia/NewZealand
ThisdigitalequipmentfulllstherequirementsforRF
emissionaccordingtotheClassBlimitofAS/NZSCISPR22.
Theproductshallbeconnectedusingashieldednetwork
cable(STP)thatisproperlygrounded.
Japan
この装置は、クラスB情報技術装置です。この装置
は、家庭環境で使⽤することを⽬的としています
が、この装置がラジオやテレビジョン受信機に近
接して使⽤されると、受信障害を引き起こすこと
があります。取扱説明書に従って正しい取り扱い
をして下さい。本製品は、シールドネットワーク
ケーブル(STP)を使⽤して接続してください。また
適切に接地してください。
Safety
ThisproductcomplieswithIEC/EN60950-1,Safetyof
InformationTechnologyEquipment.
Ifitsconnectingcablesareroutedoutdoors,theproduct
shallbegroundedeitherthroughashieldednetworkcable
(STP)orotherappropriatemethod.
Thepowersupplyusedwiththisproductshallfullloneof
thefollowingrequirements:
•SafetyExtraLowVoltage(SELV)accordingtoclause
2.2ofIEC/EN/UL60950-1andLimitedPowerSource
(LPS)accordingtoclause2.5ofIEC/EN/UL60950-1or
CEC/NECClass2sourceofsupplyasdenedinthe
CanadianElectricalCode,CSAC22.1andNational
ElectricalCode,ANSI/NFPA70
•Class1electricalenergysource(ES1)andClass2power
source(PS2)ratedoutputpowerlimitedto
≤100WaccordingtoIEC/EN/UL62368-1
Disposalandrecycling
Whenthisproducthasreachedtheendofitsusefullife,
disposeofitaccordingtolocallawsandregulations.For
informationaboutyournearestdesignatedcollectionpoint,
contactyourlocalauthorityresponsibleforwastedisposal.
Inaccordancewithlocallegislation,penaltiesmaybe
applicableforincorrectdisposalofthiswaste.
Europe
Thissymbolmeansthattheproductshallnotbe
disposedoftogetherwithhouseholdorcommercialwaste.
Directive2012/19/EUonwasteelectricalandelectronic
equipment(WEEE)isapplicableintheEuropeanUnion
memberstates.Topreventpotentialharmtohumanhealth
andtheenvironment,theproductmustbedisposedofin
anapprovedandenvironmentallysaferecyclingprocess.
Forinformationaboutyournearestdesignatedcollection
point,contactyourlocalauthorityresponsibleforwaste
disposal.Businessesshouldcontacttheproductsupplierfor
informationabouthowtodisposeofthisproductcorrectly.
Thisproductcomplieswiththerequirementsof
Directive201 1/65/EUontherestrictionoftheuseof
certainhazardoussubstancesinelectricalandelectronic
equipment(RoHS).
China
Thisproductcomplieswiththerequirementsof
SJ/T1 1364-2014,Markingfortherestrictionofhazardous
substancesinelectricalandelectronicproducts.
有毒有害物质或元素
部
件
名
称
电
气
实
装
部
分
0:表示该有毒有害物质在该部件所有均质材料中
的含量均在GB/T26572标准规定的限量要求以下。
X:表示该有毒有害物质至少在该部件的某一均质
材料中的含量超出GB/T26572标准规定的限量要
求。
Contactinformation
AxisCommunicationsAB
Emdalavägen14
22369Lund
Sweden
Tel:+46462721800
Fax:+4646136130
axis.com
SupportedReaders
Thislistofsupportedreadersissubjecttochangewithout
notice.ContactyourAxisresellerforinformationabout
supportedreaders.
ThisproductiscompatiblewithULListedWiegandaccess
controlreaders
ThisproductiscompatiblewiththefollowingRS485access
controlreaders:
AXISA4011-EReader
HIDiCLASS®RW100:6101CG40000,6101CGM0000,
6101CK40000,6101CK40002,6101CK40100,
6101CK403C0,6101CKM0000,6101CKM0002,
6101CKM0203;RW300:611 1CG40000,611 1CG400C0,
61 11CGM0000,6111CK40000,6111CK4000Z,
61 11CKM0000;RW400:6121CG40000,6121CGM0000,
6121CK40000,6121CK40003,6121CK40007-G3.0,
6121CK4000D-G3.0,6121CKM0000;R40:
6122CKP00P0,6122CKP05P0,6122CKP06P0;RWK400:
6131CG4020000,6131CK4000000,6131CK4000014,
汞
铅
(Pb)
X
镉
(Hg)
(Cd)
00000
六价
多溴
铬
(Cr(VI))
多溴
联苯
二苯
(PB-
醚
B)
(PBDE)

6131CK4000300,6131CK4020000,6131CKM000000,
6131CKM000214;RK40:6132BKP00Q709-G3.0,
6132CKP000009,6132CKP000011,6132CKP000700-G3.0,
6132CKP000709-G3.0,6132CKP001009,6132CKP00101 1,
6132CKP00P000,6132CKP00P009,6132CKP00P709-G3.0,
6132CKP00Q709-G3.0,6132CKP030014,6132CKP060514,
6132CKP06P009,6132CKP06P609,6132CKP070209;
RW150:6141CG40000,6141CGM0000,6141CK40000,
6141CKM0000;R15:6142CKP000Z,6142CKP00P0,
6142CKP0100;RWKL550:6171BK4000000,
6171BK4000009,6171BK4000014,6171BK4000214,
6171BK4000500,6171BK4040Z14,6171BK4060000,
6171BK4060209,6171BK4060Z09,6171BK4061000,
6171BKM000000,6171BKM000200,6171BKM000300,
6171BKM040400;RWKLB575:6181BK4000000,
6181BK4000009,6181BK4000014,6181BK4000022,
6181BK406C009;
HIDSmartid®:8031DSAP
HIDpivClass®R10-H:900LHRNAK00000,
900LHRTAK00000,900NHRNAK00000,900NHRTAK00000,
900PHRNAK00000,900PHRTAK00000,910LHRNAK00000,
910LHRTAK00000,910NHRNAK00000,910NHRTAK00000,
910PHRNAK00000,910PHRTAK00000,920LHRNAK00000,
920LHRTAK00000,920NHRNAK00000,920NHRTAK00000,
920PHRNAK00000,920PHRTAK00000,921LHRNAK00000,
921LHRTAK00000,921NHRNAK00000,921NHRTAK00000,
921PHRNAK00000,921PHRTAK00000;RPKCL40-P:
923LPRNAK00000,923LPRTAK00000,923NPRTAK00000,
923PPRNAK00000,923PPRTAK00000
TM
Aptiq
:M1 1,MTK15,MTMSK15,MT15,MTMS15
ForinformationaboutwhichcompatibleRS485access
controlreadershavebeenveriedbyUL,seeRequirements
forCompliancewithUL2946thEditiononpage7.

AXISA1001NetworkDoorController
RequirementsforCompliancewithUL2946thEdition
ThissectioncontainsinformationandinstructionsrequiredforULcompliance.Tomakesurethe
installationisULcompliant,followtheinstructionsbelowinadditiontothegeneralinformation
andinstructionsprovidedthroughoutthisdocument.Incaseswherepiecesofinformation
contradicteachother,therequirementsforULcompliancealwaysreplacegeneralinformation
andinstructions.
Supportedreaders
•CompatibilitywiththefollowingRS485readershasbeenveriedbyUL:HIDiClassRK40,
HIDSmartID8031DSHM,andAptiqQMTMSK15.
Safetyinstructions
•TheAxisproductshallbeinstalledandservicedbyafactorytrainedprofessional.
•TheAxisproductshallbeinstalledwithintheprotectedpremises(securedarea).
•TheAxisproductshallbemountedindoors.Outdoorusehasnotbeenevaluatedor
approvedbyUL.
•AllinterconnectingdevicesshallbeULListedandClass2low-voltagepowerlimited.
•AllwiringmethodsshallbeperformedinaccordancewithNFPA70,localcodesand
authoritieshavingjurisdiction.
•WhentheAxisproducthasreachedtheendofitsusefullife,disposeofitaccording
tolocallawsandregulations.Theproductshouldnotbedisposedoftogetherwith
householdorcommercialwaste.SeeDisposalandrecycling.
•Battery
-The3.0VlithiumbatteryusedbytheAxisproductisaULRecognized
component.(Type:BR2032,diameter:20mm(0.78in),manufacturers:
Rayovac,Panasonic).ThefollowingbatterytypeisalsoaULRecognized
component:TypeCR2032,manufacturers:Fuji,Maxell,Renata,Varta,
Panasonic,JHIH
-Usersshallnotreplacethebattery.Ifthebatteryneedsreplacing,
afactorytrainedserviceprofessionalshallcontactAxissupport
atwww.axis.com/techsupforassistance.
-Usedbatteriesshallbedisposedofaccordingtolocallawsandregulations,
whichmayvaryfromstatetostate.WasteBR/CRlithiumcellsareneither
listednorexemptedfromtheUSEPAhazardouswasteregulations.Waste
lithiumbatteriescanbeconsideredreactivehazardouswasteifthereisa
signicantamountofunreacted,orunconsumedlithiumremaining.For
informationabouthowtodisposeofusedlithiumbatteries,contactyourlocal
authorityforwastedisposal.
Specications
•Operatingconditions
-Temperatures0°Cto50°C(32°Fto122°F).
7

AXISA1001NetworkDoorController
•Wirearea
-ULListedorR/CAWMwiresthathaveanconductorgaugerangeof
AWG22–14shallbeused.
-Theminimumconductorgaugeforconnectionbetweenthepowersourcing
equipment(PSE)orpowerinjectorandthepowereddevice(PD)is26AWG.
•Connectors
-ThisproductisnotintendedforoutsidewiringascoveredbyArticle800inthe
NationalElectricalCode,NFPA70.
-Powerconnector–ForULsecurityapplications,theproductshallbepowered
byaUL294ListedorUL603ListedClass2low-voltagepowerlimitedpower
supplythatiscapableof4hoursofstandbypower.
-Networkconnector–PoweroverEthernet(PoE)shallbesuppliedbyaUL294
ListedClass2powerlimitedinjectorthatprovides44–57VDC,15.4Wand4
hoursofstandbypower.CompliancewithIEEE802.3(atoraf)specications
hasnotbeenveriedaspartofUL294/B.
-Tamperingalarmpinheader–TocomplywithUL294/7.2.1(Enclosure),the
tamperingalarmshallbeconnectedtoasoundalarm.
•Systemconsiderations
-TheAxisproduct,whetheritisastandalonedoorcontrollerorasystemof
doorcontrollers,shallnotimpairtheintendedoperationofthepanichardware
usedinconjunctionwithit.
•Wallandceilingmount
-IfusingajunctionboxtomounttheAxisproduct,thejunctionboxshallbe
ULListed.
•AssignanIPaddress
-ThefunctionalityofAXISDeviceManager,seetheUserManual,hasnotbeen
evaluatedbyUL.
•Maintenanceinstructions
-Formaintenanceinstructions(somestepsrequireaccesstotheproduct’s
webpages),seetheUserManual.Forinformationabouthowtocongure
theAxisproductusingtheproduct’swebpages(AXISEntryManager),see
theUserManual.
•Furtherinformation
-Firmwareversion:DoorController,ModelA1001–1.20.2
8

AXISA1001NetworkDoorController
Safetyinformation
Hazardlevels
DANGER
Indicatesahazardoussituationwhich,ifnotavoided,willresultindeathorseriousinjury.
WARNING
Indicatesahazardoussituationwhich,ifnotavoided,couldresultindeathorseriousinjury.
CAUTION
Indicatesahazardoussituationwhich,ifnotavoided,couldresultinminorormoderate
injury.
NO
TICE
NO NO
TICE TICE
Indicatesasituationwhich,ifnotavoided,couldresultindamagetoproperty.
Othermessagelevels
Important
Indicatessignicantinformationwhichisessentialfortheproducttofunctioncorrectly.
Note
Indicatesusefulinformationwhichhelpsingettingthemostoutoftheproduct.
EN
9

AXISA1001NetworkDoorController
Safetyinstructions
WARNING
TheAxisproductshallbeinstalledbyatrainedprofessional,andincompliancewithlocal
lawsandregulations.
NO
TICE
NO NO
TICE TICE
•TheAxisproductshallbeusedincompliancewithlocallawsandregulations.
•Axisrecommendsusingashieldednetworkcable(STP)CAT5orhigher.
•TousetheAxisproductoutdoors,orinsimilarenvironments,itshallbeinstalledinan
approvedoutdoorhousing.
•StoretheAxisproductinadryandventilatedenvironment.
•AvoidexposingtheAxisproducttoshocksorheavypressure.
•Donotinstalltheproductonunstablepoles,brackets,surfacesorwalls.
•UseonlyapplicabletoolswheninstallingtheAxisproduct.Usingexcessiveforcewith
powertoolscouldcausedamagetotheproduct.
•Donotusechemicals,causticagents,oraerosolcleaners.
•Useacleanclothdampenedwithpurewaterforcleaning.
•Useonlyaccessoriesthatcomplywiththetechnicalspecicationofyourproduct.These
canbeprovidedbyAxisorathirdparty.AxisrecommendsusingAxispowersource
equipmentcompatiblewithyourproduct.
•UseonlysparepartsprovidedbyorrecommendedbyAxis.
•Donotattempttorepairtheproductyourself.ContactAxissupportoryourAxisreseller
forservicematters.
•Thepowersupplyshallbepluggedintoasocketoutletinstalledneartheproductand
shallbeeasilyaccessible.
•Usealimitedpowersource(LPS)witheitheraratedoutputpowerlimitedto≤100Wora
ratedoutputcurrentlimitedto≤5A.
Transportation
NO
TICE
NO NO
TICE TICE
•WhentransportingtheAxisproduct,usetheoriginalpackagingorequivalenttoprevent
damagetotheproduct.
Battery
TheAxisproductusesa3.0VCR2032lithiumbatteryasthepowersupplyforitsinternalreal-time
clock(RTC).Undernormalconditionsthisbatterywilllastforaminimumofveyears.
10

AXISA1001NetworkDoorController
LowbatterypoweraffectstheoperationoftheRTC,causingittoresetateverypower-up.When
thebatteryneedsreplacing,alogmessagewillappearintheproduct’sserverreport.Formore
informationabouttheserverreport,seetheproduct´swebpageorcontactAxissupport.
Lithiumcoincell3.0Vbatteriescontain1,2-dimethoxyethane;ethyleneglycoldimethylether
(EGDME),CASno.110-71-4.
WARNING
•Riskofexplosionifthebatteryisincorrectlyreplaced.
•Thebatteryshouldbereplacedwithanidenticalbatteryonly.
•Usedbatteriesshouldbedisposedofaccordingtolocalregulationsorthebattery
manufacturer'sinstructions.
EN
11

12

AXISA1001NetworkDoorController
InstallationGuide-FullReference
ThisfullreferenceinstallationguideprovidesinstructionsforhowtoinstallAXISA1001Network
DoorControlleronyournetwork.
•Foraquickreferenceguide,seetheprintedAXISA1001InstallationGuide–Quick
Referencethatisincludedinthepackagecontents.Thequickreferenceguideisalso
availableonwww.axis.com
•Forotheraspectsofusingtheproduct,seetheAXISA1001UserManualavailable
onwww.axis.com
InstallationSteps
1.Makesurethepackagecontents,toolsandothermaterialsnecessaryfortheinstallation
areinorder.Seepage13.
2.Studythehardwareoverview.Seepage15.
3.Studythespecications.Seepage20.
4.Installthehardware.Seepage30.
5.Accesstheproduct.SeeAccesstheProductonpage37.
Packagecontents
•AXISA1001NetworkDoorController
•Cabletie(4x)
•Coverscrew
•6-pinplugconnector(5x)(pluggedintoterminalconnectors)
-ReaderI/O(blue)
-ReaderI/O(red)
-Readerdata(white)
-Readerdata(yellow)
-Power&Relay(orange)
•4-pinplugconnector(5x)(pluggedintoterminalconnectors)
-Audio(white)
-Auxiliary(yellow)
-Doorin(blue)
-Doorin(red)
-Powerlock(orange)
•2-pinplugconnector(pluggedintoterminalconnector)
-Power(black)
EN
13

AXISA1001NetworkDoorController
•Printedmaterials
-AXISA1001InstallationGuide–QuickReference
-Extraserialnumberlabel(2x)
-AVHSAuthenticationkey
RecommendedTools
•Drill–ifmountingonwallorceiling
•Screwdriver–ifmountingonwallorceiling
•Slottedscrewdriver–foropeningthecover
•Torxscrewdriver(T10)–fortighteningthecoverscrew
•Wirestrippingtool
14

Hardwareoverview
AXISA1001NetworkDoorController
EN
Frontandback:
1
Cover
2
Coverscrew
3
Coverremovalslot
4
Base
5
DINclip–upper
6
Tamperingalarmswitch–back
7
DINclip–lower
8
Partnumber(P/N)&Serialnumber(S/N)
15

AXISA1001NetworkDoorController
I/Ointerface:
1
Readerdataconnector(READERDATA1)
10
Readerdataconnector(READERDATA2)
3
ReaderI/Oconnector(READERI/O1)
8
ReaderI/Oconnector(READERI/O2)
4
Doorconnector(DOORIN1)
7
Doorconnector(DOORIN2)
6
Auxiliaryconnector(AUX)
5
Audioconnector(AUDIO)(notused)
Externalpowerinputs:
2
Powerconnector(DCIN)
12
Networkconnector(PoE)
Poweroutputs:
9
Powerlockconnector(LOCK)
11
Power&Relayconnector(PWR,RELAY)
16

AXISA1001NetworkDoorController
LEDindicators,buttonsandotherhardware:
1
PowerLEDindicator
2
StatusLEDindicator
3
NetworkLEDindicator
4
Reader2LEDindicator(notused)
5
Reader1LEDindicator(notused)
6
Tamperingalarmpinheader–front(TF)
7
Tamperingalarmpinheader–back(TB)
8
LockLEDindicator
9
LockLEDindicator
10
Tamperingalarmsensor–front
11
SDcardslot(microSDHC)(notused)
12
Controlbutton
13
Partnumber(P/N)&Serialnumber(S/N)
EN
17

AXISA1001NetworkDoorController
LEDIndicators
LED
Network
Status
Power
Lock
Note
•TheStatusLEDcanbeconguredtoashwhileaneventisactive.
•TheStatusLEDcanbeconguredtoashforidentifyingtheunit.GotoSetup>
Color
Green
Amber
UnlitNonetworkconnection.
GreenSteadygreenfornormaloperation.
Amber
Red
Green
Amber
GreenSteadywhennotenergized.
Red
UnlitFloating.
AdditionalControllerConguration>SystemOptions>Maintenance.
Indication
Steadyforconnectiontoa100MBit/snetwork.Flashesfor
networkactivity.
Steadyforconnectiontoa10MBit/snetwork.Flashesfornetwork
activity.
Steadyduringstartupandwhenrestoringsettings.
Slowashforfailedupgrade.
Normaloperation.
Flashesgreen/amberduringrmwareupgrade.
Steadywhenenergized.
ConnectorsandButtons
Forspecicationsandoperatingconditions,seepage20.
I/OInterface
ReaderDataConnectors
Two6-pinterminalblockssupportingRS485andWiegandprotocolsforcommunicationwiththe
reader.Forspecications,seepage22.
ReaderI/OConnectors
Two6-pinterminalblocksforreaderinputandoutput.Inadditiontothe0VDCreferencepoint
andpower(DCoutput),thereaderI/Oconnectorprovidestheinterfaceto:
•Digitalinput–Forconnecting,forexample,readertamperingalarms.
•Digitaloutput–Forconnecting,forexample,readerbeepersandreaderLEDs.
Forspecications,seepage23.
18

AXISA1001NetworkDoorController
DoorConnectors
Two4-pinterminalblocksforconnectingdoormonitoringdevicesandrequesttoexit(REX)devices.
Forspecications,seepage24.
AuxiliaryConnector
4-pincongurableI/Oterminalblock.Usewithexternaldevices,incombinationwith,forexample
tamperingalarms,eventtriggeringandalarmnotications.Inadditiontothe0VDCreference
pointandpower(DCoutput),theauxiliaryconnectorprovidestheinterfaceto:
•Digitalinput–Analarminputforconnectingdevicesthatcantogglebetweenanopen
andclosedcircuit,forexamplePIRsensorsorglassbreakdetectors.
•Digitaloutput–Forconnectingexternaldevicessuchasburglaralarms,sirensorlights.
ConnecteddevicescanbeactivatedbytheVAPIX®applicationprogramminginterfaceor
byanactionrule.
Forspecications,seepage25.
ExternalPowerInputs
NO
TICE
NO NO
TICE TICE
Theproductshallbeconnectedusingashieldednetworkcable(STP).Allcablesconnecting
theproducttothenetworkshallbeintendedfortheirspecicuse.Makesurethatthe
networkdevicesareinstalledinaccordancewiththemanufacturer’sinstructions.For
informationaboutregulatoryrequirements,seeElectromagneticcompatibility(EMC)on
page4.
PowerConnector
2-pinterminalblockforDCpowerinput.UseaSafetyExtraLowVoltage(SELV)compliantlimited
powersource(LPS)witheitheraratedoutputpowerlimitedto≤100Woraratedoutputcurrent
limitedto≤5A.Forspecications,seepage25.
EN
NetworkConnector
RJ45Ethernetconnector.SupportsPoweroverEthernet(PoE).Forspecications,seepage26.
PowerOutputs
PowerLockConnector
4-pinterminalblockforconnectingoneortwolocks.Thelockconnectorcanalsobeusedtopower
externaldevices.Forspecications,seepage26.
Power&RelayConnector
6-pinterminalblockforconnectingpowerandthedoorcontroller’srelaytoexternaldevicessuch
aslocksandsensors.Forspecications,seepage27.
19

AXISA1001NetworkDoorController
ButtonsandOtherHardware
TamperingAlarmPinHeader
Two2-pinheadersfordisconnectingthefrontandbacktamperingalarms.Forspecications,
seepage27.
ControlButton
Thecontrolbuttonisusedfor:
•Resettingtheproducttofactorydefaultsettings.Seepage45.
•ConnectingtoanAXISVideoHostingSystemserviceorAXISInternetDynamicDNS
Service.Formoreinformationabouttheseservices,seetheUserManual.
Specications
OperatingConditions
TheAxisproductisintendedforindooruse.
Classication
IEC60721-4-3Class3K3,
3M3
TemperatureHumidity
0°Cto50°C
(32°Fto122°F)
20–85%RH(non-condensing)
PowerConsumption
NO
TICE
NO NO
TICE TICE
UseaSafetyExtraLowVoltage(SELV)compliantlimitedpowersource(LPS)witheithera
ratedoutputpowerlimitedto≤100Woraratedoutputcurrentlimitedto≤5A.
PowersupplyMaximumloadonoutputs
PoweroverEthernetIEEE802.3af/802.3atType1Class3,
44–57VDC
10–30VDC,max26W
PowerOutputConversion(WtoA)
IfthedeviceconnectingtotheAxisproductonlyhasanampere(A)rating,thefollowingmethod
canbeusedforconversiontowatts(W).
ThetotalmaximumoutputloadoftheAxisproductdependsonthepowersource:
7.5W
14W
20

AXISA1001NetworkDoorController
PowersourceTotalmaximumloadonoutputs
PoweroverEthernetIEEE802.3af/802.3atType1Class3
10–30VDC
ThevoltageontheAxisproduct’spoweroutputsis12VDC(exceptfortheAuxiliaryConnector
whichhasavoltageof3.3VDC).Ifyourconnectingdevicehasamaximumampereratingoffor
example0.3A,thefollowingconversiongivesthepowerinwatts(W):
Power(W)=Voltage(V)xCurrent(I)
Power=12x0.3=3.6W
Thefollowingtableshowstheavailablepowerafterconnectionofthe0.3Adeviceintheexample.
PowersourceAvailablepower
PoweroverEthernetIEEE802.3af/802.3atType1Class3
10–30VDC
TheDCoutputonthefollowingconnectorsareconsideredaspoweroutputs:‘
7.5W
14W
7.5–3.6=3.9W
14–3.6=10.4W
EN
•PowerLockConnector
•Power&RelayConnector
•ReaderI/OConnector
•AuxiliaryConnector
NO
TICE
NO NO
TICE TICE
Thepoweroutputoftheauxiliaryconnectorhasa3.3VDCvoltagerating.
Forconnectorspecications,seePowerConnectoronpage25andNetworkConnectoronpage26.
PerformanceLevelsforAccessControl
ThissectioncontainsperformancelevelinformationrequiredforUL294compliance.
FeatureLevel
DestructiveAttackTestI
LineSecurity
I
21

AXISA1001NetworkDoorController
EnduranceIV
StandbyPower
WireArea
NO
TICE
NO NO
TICE TICE
Eachwireshallhaveanconductorcross-sectionalareathatcorrespondstoanconductor
gaugerangeofAWG28–16(CSA)orAWG22–14(cUL/UL).Selectcablesincompliance
withyourlocalregulations.
I
AWG
28–16
22–14
Diametermm(in)
0.321–1.29(0.0126–0.0508)
0.644–1.63(0.0253–0.0641)
Areamm
0.0810–1.31
0.326–2.08
2
Connectors
Forinformationabouttheconnectors’positions,seeHardwareoverviewonpage15.
Forconnectiondiagramsandinformationaboutthehardwarepinchartgeneratedthroughthe
hardwareconguration,seeConnectionDiagramsonpage28andCongurethehardwareon
page42.
Thefollowingsectiondescribestheconnectors’technicalspecications.
ReaderDataConnector
6-pinterminalblocksupportingRS485andWiegandprotocolsforcommunicationwiththereader.
TheRS485portssupport:
•Two-wireRS485halfduplex
•Four-wireRS485fullduplex
TheWiegandportssupport:
•Two-wireWiegand
22

AXISA1001NetworkDoorController
FunctionPinNotes
RS485
RS485
Wiegand
Important
TheRS485portshaveaxedbaudrateof9600Bit/s.
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
ReaderI/OConnector
6-pinterminalblockfor:
•Auxiliarypower(DCoutput)
•DigitalInput
•DigitalOutput
•0VDC(-)
Pin3onthereaderI/Oconnectorscanbesupervised.Iftheconnectionisinterrupted,aneventis
activated.Tousesupervisedinputs,installendoflineresistors.Usetheconnectiondiagram
forsupervisedinputs.Seepage29.
AB+
AB+
D0(Data0)
D1(Data1)
1
2
3
4
5
6
ForfullduplexRS485
ForhalfduplexRS485
ForfullduplexRS485
ForhalfduplexRS485
ForWiegand
EN
FunctionPinNotes
0VDC(-)
DCoutput
1
2
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedas
powerout.
23
Specications
0VDC
12VDC
Maxload=300mA

AXISA1001NetworkDoorController
Congurable
(Inputor
Output)
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
DoorConnector
Two4-pinterminalblocksfordoormonitoringdevices(digitalinput).
Alldoorinputpinscanbesupervised.Iftheconnectionisinterrupted,analarmistriggered.To
usesupervisedinputs,installendoflineresistors.Usetheconnectiondiagramforsupervised
inputs.Seepage29.
3–6
Digitalinput—Connecttopin1to
activate,orleaveoating(unconnected)
todeactivate.
Digitaloutput—Connecttopin1to
activate,orleaveoating(unconnected)
todeactivate.Ifusedwithaninductive
load,e.g.arelay,adiodemustbe
connectedinparallelwiththeload,for
protectionagainstvoltagetransients.
0tomax40VDC
0tomax40VDC,open
drain,100mA
FunctionPinNotes
0VDC(-)
Input
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
1,3
2,4
Forcommunicatingwithdoormonitor.
Digitalinput—Connectto
pin1or3respectivelytoactivate,
orleaveoating(unconnected)to
deactivate.
Note:Thispincanonlybeusedfor
input.
Specications
0VDC
0tomax40VDC
24

AXISA1001NetworkDoorController
AuxiliaryConnector
4-pincongurableI/Oterminalblockfor:
•Auxiliarypower(DCoutput)
•DigitalInput
•DigitalOutput
•0VDC(-)
Foranexampleconnectiondiagram,seeConnectionDiagramsonpage28.
FunctionPinNotes
0VDC(-)
DCoutput
Congurable
(Inputor
Output)
1
2
3–4
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedas
powerout.
Digitalinput—Connecttopin1to
activate,orleaveoating(unconnected)
todeactivate.
Digitaloutput—Connecttopin1to
activate,orleaveoating(unconnected)
todeactivate.Ifusedwithaninductive
load,e.g.arelay,adiodemustbe
connectedinparallelwiththeload,for
protectionagainstvoltagetransients.
EN
Specications
0VDC
3.3VDC
Maxload=100mA
0tomax40VDC
0tomax40VDC,open
drain,100mA
Important
Therecommendedmaximumcablelengthis30m(98.4ft).
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
PowerConnector
2-pinterminalblockforDCpowerinput.UseaSafetyExtraLowVoltage(SELV)compliantlimited
powersource(LPS)witheitheraratedoutputpowerlimitedto≤100Woraratedoutputcurrent
limitedto≤5A.
25

AXISA1001NetworkDoorController
FunctionPinNotes
0VDC(-)
DCinput
NetworkConnector
RJ45Ethernetconnector.UseCategory5ecablesorhigher.
Function
PowerandEthernet
Powerlockconnector
4-pinterminalblockforpoweringoneortwolocks(DCoutput).Thelockconnectorcanalso
beusedtopowerexternaldevices.
Connectlocksandloadstothepinsaccordingtothehardwarepinchartgeneratedthroughthe
hardwareconguration.
1
2
Forpoweringcontrollerwhennotusing
PoweroverEthernet.
Note:Thispincanonlybeusedas
powerin.
Specications
PoweroverEthernetIEEE802.3af/802.3atType1Class3,
44–57VDC
Maxloadonoutputs=7.5W
Specications
0VDC
10–30VDC,max26W
Maxloadonoutputs=
14W
FunctionPinNotes
0VDC(-)
0VDC,
oating,or
12VDC
1,3
2,4
Forcontrollinguptotwo12Vlocks.Use
thehardwarepinchart.SeeCongure
thehardwareonpage42.
26
Specications
0VDC
12VDC
Maxtotalload=500mA

AXISA1001NetworkDoorController
NO
TICE
NO NO
TICE TICE
Ifthelockisnon-polarized,werecommendyoutoaddanexternalybackdiode.
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
Power&relayconnector
6-pinterminalblockwithbuilt-inrelayfor:
•Externaldevices
•Auxiliarypower(DCoutput)
•0VDC(-)
Connectlocksandloadstothepinsaccordingtothehardwarepinchartgeneratedthroughthe
hardwareconguration.
EN
FunctionPinNotes
0VDC(-)
Relay
12VDC
24VDC
NO
TICE
NO NO
TICE TICE
Ifthelockisnon-polarized,werecommendyoutoaddanexternalybackdiode.
Important
TheoutputcircuitsinthissectionareClass2powerlimited.
TamperingAlarmPinHeader
Two2-pinheadersforbypassing:
1,4
2–3
5
6
Forconnectingrelaydevices.Usethe
hardwarepinchart.SeeCongurethe
hardwareonpage42.
Thetworelaypinsaregalvanically
separatedfromtherestofthecircuitry.
Forpoweringauxiliaryequipment.
Note:Thispincanonlybeusedas
powerout.
Notused
27
Specications
0VDC
Maxcurrent=700mA
Maxvoltage=+30VDC
Maxvoltage=+12VDC
Maxload=500mA

AXISA1001NetworkDoorController
•Backtamperingalarm(TB)
•Fronttamperingalarm(TF)
FunctionPinNotes
Backtamperingalarm
Fronttampering
alarm
Note
Boththefrontandbacktamperingalarmsareconnectedbydefault.Thecasingopen
triggercanbeconguredtoperformanactionifthedoorcontrollerisopenedorifthe
doorcontrollerisremovedfromthewallorceiling.Forinformationabouthowtocongure
alarmsandevents,seetheUserManual.
1–2
1–2
ConnectionDiagrams
Connectdevicesaccordingtothehardwarepinchartgeneratedthroughthehardware
conguration.Formoreinformationabouthardwarecongurationandthehardwarepinchart,see
Congurethehardwareonpage42.
Tobypassthefrontandbacktamperingalarm
simultaneously,connectjumpersbetweenTB1,TB2and
TF1,TF2respectively.Bypassingthetamperingalarms
meansthatthesystemwillnotidentifyanytampering
attempts.
28

AXISA1001NetworkDoorController
AuxiliaryConnector
EN
1
0VDC(-)
2
DCoutput:3.3V,max100mA
A
I/Oconguredasinput
B
I/Oconguredasoutput
SupervisedInputs
Tousesupervisedinputs,installendoflineresistorsaccordingtothediagrambelow.
iInput
ii
0VDC(-)
29

AXISA1001NetworkDoorController
Note
Itisrecommendedtousetwistedandshieldedcables.Connectshieldingto0VDC.
Installthehardware
CAUTION
NevermounttheAxisproductwhilepowerisappliedtotheproduct.Alwaysapplypower
attheendoftheinstallation.
NO
TICE
NO NO
TICE TICE
Toprotectthecircuitsagainstelectrostaticdischarge(ESD),useESDprotectionwhen
handlingtheproductwhilethecomponentsandcontactsareexposed.
Readalltheinstructionsbeforeinstallingtheproduct.
•Tocongurethehardware,seepage42.
•Toinstalltheproductonawall(preferred)orceiling,seepage31.
•ToinstalltheproductonaDINrail,seepage32.
•Toconnectthecables,seepage33.
SystemConsiderations
TheAxisproductshallbeinstalledwithinthesecuredarea.
TheAxisproduct,whetheritisinstalledasasingledoorcontrollerorinasystemofdoorcontrollers,
shallnotlimitorweakentheintendeduseofthedevicesconnectedtoit.
TheAxisproductshouldbeinstalledonawall(preferred)oraceiling,withorwithoutajunction
box.ItcanalsobeinstalledonaDINrail.
Systemsize
TheAxisproductcanbeconnectedtootherAxisNetworkDoorControllersinacontrollercluster
thatcanhandleupto66doorsorwirelessdevices(withinthecluster).EachAxisproductcan
connectuptotwowireddoorsoronewireddoortogetherwithonewirelessgateway.Theamount
ofwirelesslocksconguredtoeachgatewayisdependentonthemanufacturer.
Note
•WirelesslocksarenotsoldanddistributedbyAxisCommunications.Forsupportand
trainingrelatedtowirelesssystems,contactrelevantmanufacturers'partner.
•TheAxisproductisconsideredstandalone,anddoesnotrequireconstantconnectiontoa
computerforproperoperation.Theuseofaconnectedcomputerisforlocalprogramming,
downloading,andsupplementalmonitoringpurposesonly.