AWA 28K, 30K, 44K, 50K, 80K Installation Instructions Manual

Page 1
P/No. : 3A02045N
PACKAGE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS
• Please read this instruction sheet completely before installing the product.
• When the power cable is wanted to replace, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Applied Model:
(1) 28K/30K(Btu/h)
(2) 44K/50K(Btu/h)
(3) 80K(Btu/h)
Page 2
2
Contents
1. The following should always be observed for safety
.....................................
3
2. Installation of Indoor, Outdoor Unit
..................................................................
4
1) Selection of the best location
2) Indoor unit installation
3) Outdoor unit installation
4) Refrigerant amount
3. Installation Method
.............................................................................................
7
1) Procedure
2) Preparation of installation parts and tools
4. Piping of Indoor Unit
..........................................................................................
9
1) Preparation of piping
2) Connection of piping
3) Precautions in bending
5. Connecting the Cable to Indoor Unit
................................................................
11
6. Connecting piping and the Cable to Outdoor Unit
..........................................
12
1) Connecting the piping to the outdoor unit
2) Connecting the cable to the outdoor unit
7. Power Supply and Wiring
..................................................................................
14
1) Power spply
2) Wiring
8. Air Purging of the Piping and Indoor Unit
........................................................
15
9. Checking the Drainage and Form the Piping
...................................................
17
1) Checking the Drainage
2) Form the Piping
10. Final Check and Test Run
................................................................................
19
Page 3
3
1. The following should always be observed for safety
• Please report to or take consent by the supply authority before connection to the system.
• Be sure to read "THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY" before installing the air conditioner.
• Be sure to observe the cautions specified here as they include important items related to safety.
• The indications and meanings are as follows.
• After reading this manual, be sure to keep it together with the instruction manual in a handy place on the customer's site.
Could lead to death, serious injury, etc.
Do not install it yourself (customer).
Perform the installation securely referring to the installation manual.
Install the unit securely in a place which can bear the weight of the unit.
Perform electrical work according to the installation manual and be sure to use an exclusive circuit.
Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely.
Be sure to use the part provided or specified parts for the installation work.
Check that the refrigerant gas due not leak after installation is completed.
Perform grounding
Do not install the unit in a place where an inflammable gas leaks.
Perform the drainage/piping work securely according to the installation manual.
Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal board connecting sections so the stress of the wires is not applied to the sections.
• Incomplete installation could cause injury due to fire, electric shock, the unit falling or a leakage of water. Consult the dealer from whom you purchased the unit or special installer.
• Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or a leakage of water.
• When installed in an insufficient strong place, the unit could fall causing injured.
• Incomplete connecting and fixing could cause fire.
• If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
• The use of defective parts could cause an injury or leakage of water due to a fire, electric shock, the unit falling, etc.
• If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
• If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
• Do not connect the ground wire to a gas pipe, water pipe arrester or telephone ground wire. Defective grounding could cause an electric shock.
• If the electrical part cover if the indoor unit and/or the service panel if the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Could lead to serious injury in particular environments when operated incorrectly.
WARNING
WARNING
CAUTION
CAUTION
Page 4
4
2. Installation of Indoor, Outdoor unit
5cm
40cm
5cm
100cm
50cm
50cm
50cm
100cm
1) Selection of the best location
¤ Indoor unit
¤ŁOutdoor unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by discharged hot air.
• Ensure the space indicated by arrows from the wall, ceiling, fence, or other obstacles.
Page 5
5
5/8" 3/8" 25 20 5/8" 3/8" 25 20 3/4" 3/8" 30 25 3/4" 3/8" 30 25
1" 5/8" 40 25 1" 5/8" 40 25
¤ØPiping length and the elevation
Cooling Only Model
28K/30K
(BTU/h)
50Hz 60Hz
44K/50K
(BTU/h)
50Hz 60Hz
80K
(BTU/h)
50Hz 60Hz
PIPE SIZE
MODEL
GAS SIDE LIQUID SIDE
Max.
Length
A (m)
Max.
Elevation
B (m)
A
B
Indoor unit
Outdoor unit
5/8" 3/8" 25 20 5/8" 3/8" 25 20 3/4" 5/8" 30 25
30 25 1" 5/8" 40 25 1" 5/8" 40 25
Heat Pump Model
28K/30K
(BTU/h)
50Hz 60Hz
44K/50K
(BTU/h)
50Hz 60Hz
3/4" 3/8" 1ø 3/4" 5/8"
80K
(BTU/h)
50Hz 60Hz
PIPE SIZE
MODEL
GAS SIDE LIQUID SIDE
Max.
Length
A (m)
Max.
Elevation
B (m)
Page 6
2) Indoor Unit installation
¥L
The mounting floor should be strong and solid enough to prevent it from vibration.
¥M
Drill the piping hole with 70mm diameter hole-core drill at either the right or the left of
indoor unit. The hole should be sightly slant to the outdoor side.
¥N
Insert the plastic tube through the hole.
¥O Cut the extruded outside part of the plastic
tube, if necessary.
3) Outdoor unit Installation
¥L
Install the outdoor unit on the concrete or any solid base securely and horizontally by
securing it with bolts (Ø12mm) and nuts.
¥M
If there is any vibration transmitted to the building, mount the rubber underneath the outdoor unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with the rated amount of refrigerant including additional amount required for air-purging, subject to 5m piping length. (The rated amount of refrigerant is indicated on the name plate.) But when the piping length exceeds 5 meters, additional charge is required according to the following table.
(Unit: g)
Example) 28K/30K In case of 10m long pipe(one-way), the amount of refrigerant to be replenished is:
(10 - 5) x 30 = 150g
200mm
70mm
70mm
90mm
Wall
Core Drill
Tilt
Cut if necessary
More than 15mm
Wall
Plastic tube (Bushing)
INSIDE OUTSIDE
MODEL
28K/30K
(BTU/h)
44K/50
(BUT/h)
80K
(BUT/h)
REFRIGERANT CHARGE
30 per 1m
40 per 1m
50 per 1m
6
Page 7
7
3. Installation Method
No. Installation works Descriptions
1 Preparation of tools and installation parts Preparation of installation 2 Flaring the pipes To insert the flare nuts, mounted on the
connection parts of both indoor and
outdoor unit, onto the copper pipes. 3 Pipe bending To reduce the flow resistance of refrigerant. 4 Connection of installation parts Connection of long piping
(elbows, socket etc) 5 Tighten the flare nut (outdoor) Connecting the pipings of the outdoor unit. 6 Blowing the pipings To remove dust and scale in working. 7 Tighten the flare nut (indoor) Connecting the pipings of the indoor unit. 8 Check a gas-leakage of the connecting
part of the pipings. 9 Air purging of the piping and indoor unit The air which contains moisture and which
remains in the refrigeration cycle may cause a malfunction on the compressor
10 Open the 3-way (liquid side) and
3-way (gas side) valves.
11 Form the pipings To prevent heat loss and sweat 12 Checking the drainage (indoor unit) To ensure if water flow drain hose of indoor unit. 13 Connecting the cable between outdoor Preparation of the operating
and indoor unit
14 Connecting the main cable to outdoor unit 15 Supply the power to the crankcase heater To prevent the liquid back to the compressor.
(Before the operating the unit) (Heat pump only)
16 Cooling operation
(Use the remote control or display of the
indoor unit)
1) Procedure
Page 8
8
2) Preparation of installation parts and tools
No. Installation Parts, Tools Use
1 Flaring tool (Ø 6,35 - Ø 19,05) Flaring the pipes 2 Remear Remove burrs from cut edges of pipes. 3 Pipe cutter (MAX 35mm Copper pipe) Cutting the pipings 4 Wrench (H5, H4 hexagonal wrench) To open the service valve 5 Pipe bender Bending the pipings 6 Leak detector Check a gas-leakage of connecting part
of the pipings
7 Manifold gauge
To measure the pressure, to charge the refrigerant 8 Charge-nipple To connect the bombe 9 Vacuum pump To remove the air in the pipe.
10 Charge cylinder balance To measure the refrigerant amount 11 Bombe (Freon-22) Gas charge
Air purge
Cleaning the pipe
12 Spanner To tighten the connecting parts of the pipings 13 Monkey spanner
14 Driver( , ) 15 Benchi (150mm) Cutting the wires 16 Tapeline To measure the length 17 Core drill
To make holes through the concrete wall and blocks
18 Voltmeter, Amperemeter, Clampmeter To measure the current and voltage 19 Insulation resistance tester To measure the insulation resistance 20 Glass thermometer
To measure the intake and outlet air temperature of the indoor unit
21 Copper tubes To use the connecting pipings 22 Insulation material To cover the connecting pipings 23 Tape To finish the connecting pipings 24 Electrical Leakage Breaker To shut off the main power 25 Cable
To connect the cable from outdoor unit to indoor unit
26 Drain hose sockets, elbows To remote the condensing water
Page 9
1) Preparation of piping
¤ Cut the pipes and the cable
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m longer than the pipe length.
¤ŁRemove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end down to avoid the metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
¤ØFlaring the pipes.
• Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrigerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustaration)
• Flare the pipe ends.
¤ŒTape the flaring part to protect it from dust
or damages.
90°
Pipe cutter
Slanted Rough
Pipe
Point down
Reamer
Bar
0~0.5mm
Copper pipe
Clamp handle
Bar
Handle
Yoke
Cone
Red arrow mark
4321
= Improper flaring =
Inclined Cracked Surface
damaged
Uneven thickness
4. Piping of Indoor Unit
9
Page 10
• Align the center of the pipings and suffciently tighten the flare nut with fingers.
• Finally, tighten the flare nut with troque wrench until the wrench clicks. When tightening the flare nut with troque wrench, ensure the direction for tightening follows the arrow on the wrench.
3) Precautions in bending
¤
If it is necessary to bend or stretch the tubing, use the spring which is attached
to the tubing in stead of pipe bender.
• Please make a careful notice to make a smooth line.
• Hold the tubing with your two hands closely and then bend or stretch it slowly not to make any crack.
• Remember that the radius (R) should not exceed 70mm (Refer to Fig. 1)
¤ŁDo not repeat the bending process to
prevent the tubing from cracking or crushing.
¤ØKeep in mind that the bending part should
not be cracked and make the radius (R) as long as possible (Refer to Fig. 2)
PIPE SIZE TORQUE
3/8" 4.2 Kg.m
1/2" 5.5 Kg.m
5/8" 5.5 Kg.m 3/4" 6.5 Kg.m
Indoor unit tubing
Flare nut
Pipings
Torque wrench
Spanner
Spring
R70mm
(Fig. 1)
(Fig. 2)
R
2) Connection of piping
¤ Move the indoor tubing and drain hose to the hole
• Remove tubing holder and pull the tubing out of the chassis.
¤ŁReplace the tubing holder into original position ¤ØRoute the tubing and the drain hose staight backwards. ¤ŒInsert the connecting cable into the indoor unit through the hole.
• Do not connect the cable to the indoor unit
• Make a small loop with the cable for easy connection later.
¤ºTape the tubing and the connecting cable. ¤ Indoor unit installation. ¤ Connecting the pipings to the indoor unit.
10
Page 11
11
5. Connecting the Cable to Indoor Unit
The inside and outside connecting cable can be connected after opening the inlet grille.
Method
"A"
"B"
¤ Open the inlet grille manually.
¤ŁOpen the control cover with Driver(
§§]]
).
¤ØConnect the supplied cables to the
connector in the control box. (Method "A") (Heat pump Model only)
¤ŒConnet the supplied cables to the
connector in the control box. (Method "B") (Cooling Model only)
¤ºSecure the control cover to the original
position with the screw.
¤ Close the inlet grille.
Knock-out holes
Page 12
1) Connecting pipings to the outdoor unit .
¥LAlign the center of the pipings and
sufficiently tighten the flare nut with fingers.
¥MFinally tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
2) Connecting the cables to the outdoor unit
12
6. Connecting Piping and the Cable to Outdoor Unit
¤ Open the control board cover from the
outdoor unit by removing the screws.
Gas side piping
Liquid side piping
Torque wrench
Outdoor unit
1(L)
2(N)
1(L)
2(N) 3 4 5
1. 28K/30K HEAT PUMP MODEL(With Electric Heater)
GREEN/YELLOW
CLAMP (Ø12.3)
TO INDOOR UNIT
MAGNETIC CONTACTOR FOR HEATER
TO INDOOR UNIT CONNECTORPOWER SUPPLY
BLUE
BLUE
BROWN
BROWN
BROWN
GREEN/
YELLOW
GREEN/
YELLOW
SNR
T
1(L)
2(N) 3 4 5
2. 44K/50K HEAT PUMP MODEL(With Electric Heater)
GREEN/
YELLOW
CLAMP
(Ø16.0)
TO INDOOR UNIT
MAGNETIC
CONTACTOR
FOR HEATER
TO INDOOR UNIT CONNECTORPOWER SUPPLY
BLUE
BLUE
BROWN
BROWN BROWN GREEN/
YELLOW
BLUE BLACK
BLUE BLACK
¤ŁConnect wires to the terminals on the
control board individually and secure the cables onto the control board with clamp.
PIPE SIZE TORQUE
3/8" 4.2 Kg.m 1/2" 5.5 Kg.m 5/8" 5.5 Kg.m 3/4" 6.5 Kg.m
Page 13
13
¤ØSecure the control board cover to the
original position with the screws.
1(L)
2(N)
1(L)
2(N) 3 4 5
3. 28K/30K COOLING MODEL
GREEN/YELLOW
CLAMP (Ø10.7)
TO INDOOR UNIT CONNECTORPOWER SUPPLY
BLUEBROWN BLACKGREEN/
YELLOW
GREEN/YELLOW
1(L)
2(N)
1(L)
2(N) 3 4 5
4. 44K/50K COOLING MODEL
GREEN/YELLOW
CLAMP (Ø10.7)
TO INDOOR UNIT CONNECTORPOWER SUPPLY
BLUEBROWN BLACKGREEN/
YELLOW
GREEN/YELLOW
CLAMP (Ø16.0)
CLAMP (Ø16.0)
RTS
N
1(L)
2(N) 3 4 5
5. 80K COOLING ONLY MODEL
GREEN/YELLOW
TO INDOOR UNIT CONNECTORPOWER SUPPLY
WHITE REDBLACK
RTS
N
1
2 3 4 5
6
7 8 9 10
6. 80K HEAT PUMP MODEL
GREEN/YELLOW
GREEN/YELLOW
TO INDOOR UNIT CONNECTORPOWER SUPPLY
REDBROWN WHITEBLACK
YELLOW
Page 14
14
H/P
450/750V 4.0mm
2
13.3mm
C/O
450/750V 2.5mm
2
11.8mm
H/P
450/750V 4.0mm
2
17.0mm
C/O
450/750V 4.0mm
2
17.0mm
H/P
450/750V 5.5mm
2
17.0mm
C/O
450/750V 5.5mm
2
17.0mm
UNIT Circuit breaker capacity
Voltage
Time
Starting point
Power source voltage working voltage
Starting voltage
The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with.
1) Power supply
Power source must fulfill the following conditions:
¤ The working voltage should be higher
than 90% and lower than 110% of the rated voltage marked on the name plate.
¤Ł The starting voltage should be higher than
85% of the rated voltage marked on the name plate.
¤Ł Provide a recognized circuit breaker as
below between power source and unit. A disconnection device to adequately disconnect all supply lines must be fitted. (for service operations)
¤Ø The screws which fasten the wiring in the
casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
¤ŒSee to it that the starting voltage is
maintained at more than 90 percent of the rated voltage marked on the name plate.
¤ºThe following troubles would be caused by
voltage drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
2) Wiring
After the confirmation of the above conditions, prepare the wiring as follows:
¤ Use the power supply cord(Rubber
insulation, type Ho7RNF approved by HAR or SAA) suitable for the product's electriccal capacity.
7. Power Supply and Wiring
UNIT VOLTS
Conductor
cross-sectional
area
Outside
diameter
H/P 30A C/O 30A H/P 40A C/O 40A H/P 50A C/O 50A
28K/30K
44K/50K
80K
28K/30K
44K/50K
80K
Page 15
Outdoor unit
To indoor unit
Hexagonal wrench
Service port cap
3-way valve cap (gas side)
3-way valve cap (liquid side)
No leakage found leakage found
leakage ceased
leakage ceased
leakage persists
15
8. Air Purging of the Piping and Indoor Unit
The air which contains moisture and which remains in the Refrigeration cycle may cause a malfunction on the compressor.
¤ Remove the caps from the 3-way(liquid side)
and 3-way(gas side) valves.
¤Ł Remove the service-port cap from the 3-way
(gas side) valve.
¤ØTo open the valve, turn the valve stem of
3-way (liquid side) valve counter-clockwise approx. 90° and hold it there for ten seconds, then close it.
¤ŒCheck a gas-leakage of the connecting
portion of the pipings.
¤ºTo open 3-way(liquid side) valve
again, turn the valve stem counter-clockwise until it stops.
¤ To purge the air, push the pin on the service port
of 3-way(gas side) valve for three seconds using with a hexagonal wrench and set it free for one minute.
• Repeat this three times.
Result
• Re-tighten the connecting portion with torque wrenches.
Page 16
16
¤
Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the Hexagonal wrench for the unit operation.
¤
Checking a gas leakage for the left piping.
• Connect the manifold gauge to the service port of 3-way(gas side) valve. Measure the pressure.
• Keep it for 5 - 10 minutes. Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
CLOSE CLOSE
Closed
Closed
Indoor unit
Outdoor unit
Liquid side
Gas side
Page 17
17
9. Checking the Drainage and Form the Piping
1) Checking the Drainage
¤ Remove the inlet grille with your hands as
shown (right and left) and pull in the direction indicated by the arrow.
¤Ł Check the drainage
• Pour a glass of water into the drain pan.
• Ensure if water flows drain hose of indoor unit.
Page 18
18
2) Form the Piping
¤ Wrap the connecting portion of indoor unit
with the insulation material and secure it with two Plastic Bands. (for the right piping)
• If you connect an additional drain hose, the end of the drain-outlet should be kept distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
¤ŁTape the Piping, and Connecting Cable from
down to up.
¤ØForm the piping gathered by taping along the
exterior wall and fix it onto the wall by saddle or equivalent.
¤ Tape the piping and connecting cable from
down to up.
¤ŁIn order to prevent water from entering the
room, form a trap and tape the piping.
¤Ø Fix the piping onto the wall with saddle or
bracket.
¤ When using the drain elbow hose, use
a mount of 3cm of higher.
¤ŁIn the cold district (0°c continued for 2~3
day), the drain water is frozen and the fan fail to function, do not use the drain elbow.
In case of the outdoor unit is installed below position of the indoor unit.
In case of the outdoor unit is installed upper position of the indoor unit.
Drain water treatment of outdoor unit(Heat Pump Only)
Trap
Drain elbow
Hose(inner diameter ø20)
Arrange the hose downward slope without waving.
Trap
Seal a small opening around the piping with gum type sealer.
Gas side piping
Main cable
Tube PE
Foam
Connecting Cable (For heater)
Connecting Cable
Trap is required to prevent the electrical parts from entering the water.
Page 19
19
10. Final Check and Test Run
After installing the unit, perform the final check and running test as follows: Final check points
¤ Is the unit securely mounted? ¤ŁIs the installation location adequate? ¤ØIs the water piping work adequately and
without leakage?
¤ŒAre trapped drain lines installed at
condensate drain connections?
¤ºHas the refrigeration cooling cycle been
kept sealed?
¤ Is the electrical wiring adequate and are
the screws tightened on terminals?
After the above final checkings, prepare the running test as follows:
¤ Connect compound gauges to the check
joints at discharge and suction sides of the compressor.
¤ŁTurn all switches "OFF". ¤ØTurn the main switch "ON".
Running test should be accomplished as follows:
¤ Set operation switch at "FAN" and the fan
will start. Check to ensure that the fan sounds normal.
¤ŁNext, set it at "COOL" and the compressor
will start. Check to ensure that the compressor sounds normal.
¤ØCheck discharge and suction pressure on
the compound gauges.
¤ŒCheck working voltage, phase balance and
running current.
¤ºCheck to ensure that the thermistor
functions properly.
¤ Check to ensure that the high pressure
control switch functions correctly.
Loading...