AVTECH RMA-RE1-SEN User Manual

Room Entry Sensor (RMA-RE1-SEN)
Installation Note
AVTECH’s Room Entry Sensor monitors the open/closed state of building doors, windows, cabinet doors, drawers, etc. This two­piece sensor does not require a power supply and operates very simply. The first piece has an embedded proximity switch which opens or closes when the second piece, the magnet, is pulled away or pushed near. By pairing the Room Entry Sensor with your Room Alert monitor, you gain a simple, reliable open/closed room entry status indicator.
Room Entry Sensor Package Contents
One (1) proximity switch with 11.81" leads
One (1) magnet
One (1) 25' speaker cable
One (1) Installation Note (You’re reading it now.)
Install Your Room Entry Sensor
Do not use the Room Entry Sensor in hazardous (classified) locations or life/safety applications.
Proximity Switch
Magnet
Leads
Step 1: Prepare the included 25' speaker cable.
1. Separate the leads on both ends of the speaker cable
included with your Room Entry Sensor package.
2. Strip one end to expose about ½" of wire and the other
end to expose about ¼".
Step 2: Connect the speaker cable to the Room Entry Sensor.
1. Twist the speaker cable leads with ½" exposed wire to the proximity
switch leads. The proximity switch leads are non-polarized, so you may connect either side of the speaker cable to either side of the proximity switch wires.
2. Cap or tape the connected leads to avoid a short.
Step 3: Mount your Room Entry Sensor on an entry point.
1. Position the proximity switch (the piece with wires) against the vertical or horizontal
edge of a door frame, window casing, etc.
AVTECH Software, Inc.
Temperature & Environment Monitoring …Made Easy!
AVTECH.com
Room Entry Sensor (RMA-RE1-SEN)
2. Position the magnet (the piece without wires) on the edge
of the door or window so that when it closes, the magnet closely abuts the proximity switch without actually touching it. The two pieces may directly face one another or form a right angle, as shown here, giving you more installation options.
3. Mount the two pieces securely with screws through their
flange holes, as shown here, or with an adhesive.
Step 4: Connect your Room Entry Sensor to Room Alert.
1. Run the speaker wire from the proximity switch back to your
Room Alert monitor.
2. Connect the free ends (the ¼" leads) of the speaker cable to an
open switch sensor port on your Room Alert. Again, the proximity sensor’s leads are non-polarized, so you may connect either lead to either of the port’s dry contacts.
Do not connect the dry contacts on AVTECH products or other electrical appliances to any live circuit.
Use only low-voltage 2-wire cable to connect dry contacts.
Configure Your Room Entry Sensor
With Room Alert’s Built-In Web Interface
Navigate to SettingsÆSensors in your Room Alert web interface. The options you see below will vary depending on your Room Alert model.
AVTECH Software, Inc. Page 2 of 3 AVTECH.com
Room Entry Sensor (RMA-RE1-SEN)
1. Scroll down to “Switch Sensor Settings.”
2. Find the switch sensor label that matches the port you connected your Room Entry
Sensor to. For example, if you used the first switch sensor port on your Room Alert, look for “Sensor 1 Label”; if you used the second, look for “Sensor 2 Label,” and so on.
3. In “Sensor X Label,” you may leave the default name or enter something more
descriptive, such as “Ext Room Entry,” as shown here.
4. In “Alarm On,” choose “Open” if you want alerts sent when the entry point is open (i.e.,
the magnet and proximity switch are apart); choose “Closed” if you want alerts sent when the entry point is closed (i.e., the magnet and proximity switch are together).
5. If you have any “Alarm Profiles” configured, you may choose one from the drop-down
list. Otherwise, you may leave the default, “No Alarm.”
6. Click Accept Changes at the bottom of your screen to temporarily save your settings.
You may now navigate to another screen; however, if you close the web interface before the next step, you will lose your changes.
7. Click Save Settings in the navigation bar to the left of your screen. Your Room Alert
will automatically reboot and commit your changes.
With AVTECH’s Device ManageR Software For Advanced Functionality
For advanced functionality and easy management of multiple units, configure your Room Entry Sensor with AVTECH’s Device ManageR, the software that comes FREE with the purchase of any Room Alert monitor.
You may download the current version from your customer account at AVTECH.com/Downloads while your Maintenance, Support & Update Service (MSUS) is current. If your service and access has lapsed, please contact your Product Specialist about reactivating them.
Room Entry Sensor Features & Specifications
Environment Condition Monitored .................. Proximity (Open/Closed)
Type Of Sensor ................................................... Switch
Normal State ................................................... Closed (Proximity switch & magnet together)
Power Supply ...................................................... Monitoring unit
Sensor Cable Type ............................................. Low-voltage, two-wire speaker cable
Included .......................................................... Yes
Length ............................................................. 25'
Maximum Extendible Length ......................... 900'
Operating Temperature Range......................... -40º F to 221º F (-40º C to 105º C)
Compatible Room Alert Monitors .................... Any Room Alert or Wireless Sensor Hub model