AVENTICS System Description Drive & Diagnostic Link (DDL) Manuals & Guides

Operating instructions
System description Drive & Diagnostic Link
DDL
R499050031/2016-12, Replaces: 08.2014, EN
English
AVENTICS | DDL | R499050031–BAL–001–AH 3
Contents
Contents
2 DDL General ................................................................. 11
2.1 DDL System Overview........................................................... 11
2.2 DDL Addressing ...................................................................... 12
2.2.1 Manual Addressing .............................................................. 13
2.2.2 Automatic Addressing ......................................................... 13
2.2.3 Error Upon Addressing ....................................................... 14
2.3 DDL Diagnosis ......................................................................... 15
2.4 DDL Data ................................................................................... 15
2.4.1 DDL Connection ..................................................................... 15
2.4.2 DDL Cable Length ................................................................. 16
2.4.3 DDL Cycle Times ................................................................... 16
2.4.4 Standards ............................................................................... 17
3 Bus Coupler ................................................................. 17
3.1 PROFIBUS DP 337 500 025 0/337 500 026 0 ................ 18
3.1.1 Overview .................................................................................. 18
3.1.2 Master Module ....................................................................... 19
3.1.3 Slave Module .......................................................................... 26
3.1.4 Connectors ............................................................................. 32
3.1.5 Technical Data ....................................................................... 35
3.1.6 Dimensions ............................................................................. 36
3.1.7 ATEX-Relevant Information ............................................... 37
3.2 DeviceNet R412006999/R412006998.............................. 37
3.2.1 Overview .................................................................................. 37
3.2.2 Master Module ....................................................................... 38
3.2.3 Slave Module .......................................................................... 43
3.2.4 Connectors ............................................................................. 48
3.2.5 Technical Data ....................................................................... 50
3.2.6 Dimensions ............................................................................. 51
3.2.7 ATEX-Relevant Information ............................................... 52
3.3 Interbus S 337 500 045 0/337 500 046 0 ....................... 52
3.3.1 Overview .................................................................................. 52
3.3.2 Master Module ....................................................................... 54
3.3.3 Slave Module .......................................................................... 65
3.3.4 Connectors ............................................................................. 70
3.3.5 Technical Data ....................................................................... 72
English
4 AVENTICS | DDL | R499050031–BAL–001–AH
Contents
3.3.6 Dimensions ............................................................................. 73
3.3.7 ATEX-Relevant Information ............................................... 74
3.4 ControlNet 337 500 056 0 .................................................... 74
3.4.1 Overview .................................................................................. 74
3.4.2 Master Module ....................................................................... 75
3.4.3 Slave Module .......................................................................... 80
3.4.4 Connections ............................................................................ 85
3.4.5 Technical Data ....................................................................... 87
3.4.6 Dimensions ............................................................................. 88
3.5 CANopen R412008000/R412008002................................ 89
3.5.1 Overview .................................................................................. 89
3.5.2 Master Module ....................................................................... 90
3.5.3 Slave Module .......................................................................... 95
3.5.4 Connectors ........................................................................... 101
3.5.5 Technical Data ..................................................................... 103
3.5.6 Dimensions ........................................................................... 104
3.5.7 ATEX-Relevant Information ............................................. 105
3.6 ATEX-Relevant Information for Bus Couplers..............105
3.6.1 Ex-Relevant Excerpt from the Operating Instructions
for S-Design Bus Couplers .............................................. 105
4 DDL Participants ....................................................... 111
4.1.1 Overview ................................................................................ 111
4.1.2 DDL Address ........................................................................ 112
4.1.3 DDL Mode .............................................................................. 112
4.1.4 Output Data Length ............................................................ 112
4.1.5 Output Data Range in the Control .................................. 113
4.1.6 Diagnosis ............................................................................... 114
4.1.7 Parameter ............................................................................. 116
4.1.8 Connections .......................................................................... 117
4.1.9 Technical Data ..................................................................... 119
4.1.10 Dimensions ........................................................................... 120
4.2 Valve Driver V-Design
1 827 030 189 0/1 827 030 190 0 ...................................120
4.2.1 Overview ................................................................................ 121
4.2.2 DDL Address ........................................................................ 121
4.2.3 DDL Mode .............................................................................. 121
4.2.4 Output Data Length ............................................................ 122
AVENTICS | DDL | R499050031–BAL–001–AH 5
Contents
4.2.5 Output Data Range in the Control .................................. 122
4.2.6 Diagnosis ............................................................................... 123
4.2.7 Parameter ............................................................................. 126
4.2.8 Connections .......................................................................... 127
4.2.9 Technical Data ..................................................................... 130
4.2.10 Dimensions ........................................................................... 131
4.3.1 Overview ................................................................................ 132
4.3.2 DDL address ......................................................................... 132
4.3.3 DDL Mode .............................................................................. 133
4.3.4 Output Data Length ............................................................ 133
4.3.5 Output Data Range in the Control .................................. 133
4.3.6 Diagnosis ............................................................................... 134
4.3.7 Parameter ............................................................................. 137
4.3.8 Connections .......................................................................... 138
4.3.9 Technical Data ..................................................................... 139
4.3.10 Dimensions ........................................................................... 140
4.3.11 Extension for LP04 Valve System with Inputs ........... 141
4.4 Pressure Control Valve ED05 561 014 155 0...............145
4.4.1 Overview ................................................................................ 146
4.4.2 DDL Address ........................................................................ 146
4.4.3 DDL Mode .............................................................................. 147
4.4.4 Data Format ......................................................................... 147
4.4.5 Diagnosis ............................................................................... 149
4.4.6 Parameter ............................................................................. 150
4.4.7 Controller .............................................................................. 150
4.4.8 Connections .......................................................................... 151
4.4.9 Technical Data ..................................................................... 153
4.4.10 Dimensions ........................................................................... 154
4.5 Digital Input Module 337 500 200 0 ................................154
4.5.1 Overview ................................................................................ 155
4.5.2 DDL Address ........................................................................ 155
4.5.3 DDL Mode and Data Length ............................................. 156
4.5.4 Input Data Range in the Control ..................................... 156
4.5.5 Diagnosis ............................................................................... 157
4.5.6 Overload Protection and Parameter ............................. 158
4.5.7 Connections .......................................................................... 159
4.5.8 Technical Data ..................................................................... 160
English
6 AVENTICS | DDL | R499050031–BAL–001–AH
Contents
4.5.9 Dimensions ........................................................................... 161
4.5.10 ATEX-Relevant Information ............................................. 161
4.6.1 Overview ................................................................................ 163
4.6.2 DDL Address ........................................................................ 164
4.6.3 DDL Mode .............................................................................. 164
4.6.4 Output Data Range in the Control .................................. 164
4.6.5 Diagnosis ............................................................................... 165
4.6.6 Parameter ............................................................................. 167
4.6.7 Connections .......................................................................... 168
4.6.8 Technical Data ..................................................................... 170
4.6.9 Dimensions ........................................................................... 171
4.6.10 ATEX-Relevant Information ............................................. 172
4.7.1 Overview ................................................................................ 173
4.7.2 DDL Address ........................................................................ 173
4.7.3 DDL Mode and Data Length ............................................. 174
4.7.4 Data Range in the Control ................................................ 174
4.7.5 Diagnosis ............................................................................... 176
4.7.6 Parameter ............................................................................. 179
4.7.7 Connections .......................................................................... 180
4.7.8 Technical Data ..................................................................... 182
4.7.9 Dimensions ........................................................................... 183
4.7.10 ATEX-Relevant Information ............................................. 183
4.8 ATEX-Relevant Information for I/O Modules ................184
4.8.1 Ex-Relevant Excerpt from the Operating Instructions
for I/O Modules .................................................................... 184
5 DDL Accessories ....................................................... 190
5.1.1 DDL Cable ............................................................................. 190
5.1.2 Sensor Cables ...................................................................... 190
5.2 Plugs......................................................................................... 191
5.2.1 Terminating Plugs .............................................................. 191
5.2.2 Data Plugs ............................................................................. 191
5.2.3 Power Supply Plugs ........................................................... 191
5.2.4 Other Connectors ................................................................ 192
5.3 Subplates (for Pressure Control Valves) .......................192
5.3.1 Pressure Control Valve ED05 .......................................... 192
AVENTICS | DDL | R499050031–BAL–001–AH 7
Contents
5.3.2 Pressure Control Valve ED07 .......................................... 193
6 List of Abbreviations ................................................. 193
7 Declaration of Conformity (ATEX) ............................ 194
7.1 Bus Coupler (3375000250, 3375000450,
R412006999, R412008000)...............................................194
7.2 DDL Input and Output Modules (33750020x0,
R412006712).......................................................................... 194
English
8 AVENTICS | DDL | R499050031–BAL–001–AH
Contents
AVENTICS | DDL | R499050031–BAL–001–AH 9
Safety Precautions

1 Safety Precautions

W Please pay attention to the general safety instructions and
notice the content of the user manual, before you install, start up, put pressure or electrical power to the devices.
W The devices should be used only in areas and systems they
are specified for and also comply with the tolerances of the technical data. In case of non compliance and upon exceeding the limits, which are mentioned under the point: technical data, the danger of overheating can be caused as well as damage to the device, interference in the function and/or the electrical security.
W The AVENTICS devices have been generally developed to be
used within the industrial sector. If devices shall be used in living quarters (living and business and industry sector) a special permission has to be procured from the licensing authority. In Germany licences are issued by the Regulierungsbehörde für Telekommunikation und Post (RegTP).
W To observe the technical data you should only use cables
and wires, being mentioned in the user manual or quotation drawing.
W The devices have to be grounded according to the
instructions. The relevant DIN/VDE standards or the country specific standards have to be observed upon installation. Note especially:
- VDE 0160 (EN 50178)
- VDE 0100
W The supply voltage has to be applied from a powerpack with
protective separation according to EN 60742, classification VDE 0551. Please pay attention that the external fuse of the devices is in accordance with the description.
W A faultless and safe operation of the devices requires an
appropriate transport, storage, installation and start up.
W The devices have to be opened only by qualified staff.
Electrostatic accidentally dangerous parts.
English
10 AVENTICS | DDL | R499050031–BAL–001–AH
Safety Precautions
W The installation of the devices has to be effected only by
qualified staff and without power supply and pressure. Please observe the installation position, mentioned in the user manual.
W To avoid dangerous movements, the electrical start up has
to be made on in depressurized state.
W Start up the device only after installation and tests have
been completely finished.
W Plugs must not be plugged or unplugged under voltage.
To avoid electrical damage to the device, switch off the power supply before plugs are plugged/unplugged.
be intact and fit in correct position.
W The protection class can only be achieved if all unused plugs
are sealed with covers or endplugs.
W Switches and configuration must not be changed during
operation. Changed settings only become valid after power recycle.
W No equalizing currents due to potential differences must run
via the shield, otherwise the earthing have to be made via separate wires.
W Use in explosive Area:
Some DDL participants can be used in explosive areas. For these certified devices at the end of the corresponding chapter important notes can be found. If the devices are used in explosive areas, these notes have to be read and attention has to be paid.
W Further safety precautions in the user manual have to be
followed.
handling of the device or use in an improper way. Furthermore the guarantee on our devices and accessories expires.
AVENTICS | DDL | R499050031–BAL–001–AH 11
DDL General

2 DDL General

The Drive & Diagnostic Link (DDL) from AVENTICS is a system to use solenoids, pressure control valves and digital and analog I/O modules with different field bus systems. Independent from the used field bus, the systems can be projected and with the corresponding bus coupler connected to common field busses like PROFIBUS DP, Interbus S, ControlNet and DeviceNet. DDL provides, independent from fieldbus, 128 inputs and 128 outputs per bus coupler. For the reason of the transfer mode system, there is a high data security which is even increased by the diagnostic functionality. In this way the DDL participants and the supply voltages are controlled and reported to the diagnostics. Furthermore the coils of valve units are observed according to open load and short circuit. Therefore errors can be quickly recorded up to the affected valve and measures initiated. In addition some DDL participants offer the possibility to determine via parameter the reaction upon failure of fieldbus and DDL. On the basis of the employment of M12 connectors the connection is very simple and safe. A total length of the cable of 40 m is permitted and offers a high flexibility with the DDL. Here the gap between the modules is regardless. Because of the high modularity most of the AVENTICS valve families can be employed with DDL.
English

2.1 DDL System Overview

Basically the DDL consists of two types of participants:
the fieldbus system (PROFIBUS DP, Interbus S, DeviceNet, ...) and the DDL. The bus coupler is therefore the DDL master and has to be existent once.
W The DDL participant is therefore the slave within the DDL
system. Up to 14 participants can be connected to the DDL.
12 AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
The bus coupler with drivers contains, in addition to the Master module, which is the real bus coupler, also a Slave module which represents the DDL participant. This Slave module is therefore a DDL participant and up to 13 other DDL participants can be connected.

2.2 DDL Addressing

In the DDL system a definite address has to be assigned to each participant (except for the Master module of the bus coupler). This is effected via a hex rotary switch at the devices.
Table 1: DDL address switch
Position of Switch Meaning
0 automatic addressing
1 DDL address 1
2 DDL address 2
3 DDL address 3
4 DDL address 4
5 DDL address 5
6 DDL address 6
7 DDL address 7
8 DDL address 8
9 DDL address 9
A DDL address 10
B DDL address 11
C DDL address 12
D DDL address 13
E DDL address 14
F no function
The addressing can be effected in two different ways:
1. Manual addressing
2. Automatic addressing
AVENTICS | DDL | R499050031–BAL–001–AH 13
Manual and automatic addressing cannot be effected at the same time. Please take into consideration that upon effecting the address adjustments, changes will only be taken over after a reset of voltage.

2.2.1 Manual Addressing

A definite address, between 1 and 14, is allocated to each participant. No participant must have the address 0. Furthermore the lowest address must be 1 and there must not be any gaps between the addresses. The addressing is, however, independent from the physical position of the participant in the DDL and its type. Example: 5 DDL participants are connected to a bus coupler Stand alone (needs no DDL address).
Table 2: Example for manual DDL addressing
Correct: Incorrect: Gap (4) and
lowest address 1
DDL General
Incorrect: Address 0 is used
DDL Address
1 pressure control
2 valve driver 3 valve driver 1 valve driver
3 valve driver 5 valve driver 2 valve driver
4 input module 6 input module 3 input module
5 output module 7 output module 4 output module
DDL Node DDL
Address
2 pressure control
valve
DDL Node DDL
Address
0 pressure control
valve
DDL Node
valve

2.2.2 Automatic Addressing

If there is only one participant per type in the DDL system, the DDL can automatically address itself. For this the address 0 has to be allocated to all DDL participants. In this case the DDL system allocates the address automatically to the participants. The following table shows, what kinds of module types are available and where to find them in the data and the diagnosis range.
English
14 AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
If not all module types are used, the following modules move up. If the automatic addressing is used, addresses between 1 ... 14 must not be used.
Table 3: Data range at automatic DDL addressing
Output Data Position
1 EP pressure
2 valve driver valve driver 1 EP pressure control
input module 2 input module 2 valve driver
3 output module output module 3 input module
1)
4
5 combi module
1)
only, if input or output data are configured.
DDL Node Type Input
control valve
combi module 3
Data Position
1 EP pressure
1)
DDL Node Type Diagnosis
Data Position
BC bus coupler
control valve
combi module 4 output module
DDL Node Type
valve

2.2.3 Error Upon Addressing

In order that the DDL is able to recognize and control all participants, the above mentioned regulations have to be observed. If the DDL has not been addressed correctly, this will be indicated by the participant’s red DDL LED. If two participants have the same address, this cannot be recognized that safely that the DDL gets not into Run mode. This type of wrong addressing can be recognized by checking the number of livebits. In case of a DDL communication diagnosis, the addressing of all participants shall be checked. Furthermore the same baud rate has to be adjusted with all participants, also with the Master module. In addition it has to be checked that all cables have been correctly connected. Upon problems with very long cables we recommend to run the DDL with 125 kBaud. For further information on the baud rate adjustments, please refer to the description of the device.
AVENTICS | DDL | R499050031–BAL–001–AH 15
DDL General

2.3 DDL Diagnosis

The DDL participants/bus couplers have two kinds of diagnosis. On the one hand, each DDL device has LEDs to indicate the diagnosis visually. On the other hand the DDL participants send diagnosis data via the DDL to the bus coupler, which transmits its own data and the diagnosis data of the DDL participants to the control. The meaning of the diagnosis data and further information can be taken from the corresponding chapters. The DDL communication respectively the availability of the DDL participants is constantly controlled by the bus coupler. As soon as all configured DDL participants exist and communicate, the red DDL LED turns off. If a participant does not communicate any more, the red DDL LED will light at the corresponding participant and the bus coupler reports the interference. In addition the corresponding livebit and the DDL LED at the bus coupler (Master module) lights (if existing). The communication to the other DDL participants will however be maintained. If the bus coupler recognizes the recurring participant (DDL LED at the participant will go off), that way the configuration will be all right, the DDL LED at the bus coupler will also go off. In order to initialize the system correctly, the valves must not be controlled. All supply voltages must exist correspondingly.

2.4 DDL Data

2.4.1 DDL Connection

The connection of the DDL is effected via 5 pin M12x1 plugs. 5-wire, shielded lines have to be used as connecting cables. The shield has to be connected to the thread of the plug. The diameter of the wires is 0.34 mm connection is performed by a mounting male plug and the DDL OUT connection as mounting female plug at the DDL participants. As DDL participants can be damaged if 24 V are applied to the signal line DDL H and DDL L or the supply lines have been exchanged, we recommend to use pre fabricated and
2
minimum. The DDL IN
English
16 AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
examined wiring. This is also mentioned in chapter 5 “DDL Accessories“.
2
1
5
4
3
Fig. 1: DDL connection
1 Pin 1 = 24 V electronics 4 Pin 4 = DDL H 2 Pin 2 = 24 V valves 5 Pin 5 = DDL L 3 Pin 3 = 0 V

2.4.2 DDL Cable Length

The total cable length of DDL system is limited to 40 m. Thereby it is irrelevant, whether the length between the two participants will be used or distributed equally. With great cable length and great consumption of electricity, the voltage drop over the cables can provoke, that the supply voltages at the DDL participants fall below the respective tolerance limits. In such cases the DDL valve drivers can be used with an external power supply (337 500 015 0 or 1 827 030 190 0), which, because of the additional supply, indicate the voltage supply level.

2.4.3 DDL Cycle Times

DDL is constructed for a fast and secure data transfer. The DDL cycle times depend on several parameters. In that way the baud rate, number of participants and configured in and output data length (max. 128 bit) have influence on the cycle time. In table 4 some applications and the corresponding DDL cycle times are shown. The process times in the bus coupler (approx. 0.8 ms) and the cycle time of the field bus are not included in this overview. The cycle time can be seen as an average value. With an ideal data transmission the signal can be transmitted considerably earlier. With critical applications it should be taken into consideration that with an unfavorable data transmission it could take a cycle time twice as long, until the signals are output or transmitted to the field bus.
AVENTICS | DDL | R499050031–BAL–001–AH 17
Bus Coupler
Table 4: Examples for DDL cycle times with different DDL configurations
Example DDL Baud rates DDL Participants DDL Data length I/O DDL Cycletime
1 250 kBaud 2 0/32 3.0 ms
2 250 kBaud 5 128/128 7.0 ms
3 250 kBaud 14 128/128 14.0 ms
4 125 kBaud 2 0/16 4.2 ms
5 125 kBaud 5 128/128 13.0 ms

2.4.4 Standards

The DDL system fulfills the standards for EMC, listed below:
W EN 61000-6-4 W EN 61000-6-2

3 Bus Coupler

AVENTICS bus couplers allow to connect pressure control valves, valve units and digital and analog in and output modules to a programmable logic control (PLC) by using a field bus system like PROFIBUS DP, Interbus S, ControlNet, DeviceNet,
CANopen,... . One advantage of a serial control is the saving of
the parallel output cards in the PLC as well as the necessary wiring. Another one is the possibility to transfer further information like Diagnosis and parameters. Bus couplers are available in two different designs. On the one hand there is the Stand alone module. It consists only of the Master module. The Master module communicates with the field bus system and controls the DDL. On the other hand bus couplers with drivers to control the valve via a 25 pin D-Sub plug, are available. They have, in addition to the Master module, also a Slave module which operates like a single DDL participant, but is situated within the same housing.
English
18 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler

3.1 PROFIBUS DP 337 500 025 0/337 500 026 0

The bus coupler for PROFIBUS DP is available in two different designs. The bus coupler with drivers (337 500 026 0) can be directly mounted onto a valve unit. Apart from controlling this unit, the DDL is also available for other DDL participants. The bus coupler Stand alone (337 500 025 0) is mounted separately and offers only the DDL. The parts of description of the Slave module, do not apply to the bus coupler Stand alone. Both modules are connected to the PROFIBUS DP via a shielded 2 wire cable.

3.1.1 Overview

PROFIBUS DP
The field bus system PROFIBUS DP which is used for the communication with the control, is a fast working bus system for the cyclic exchange of user data. PROFIBUS DP is a master slave bus system, where 2 master and 122 passive participants maximum can be connected to. Two designs as transmission medium are available:
W 2 wire line (shielded) W optical fibre
For installation information of the networks and for the configuration of the lines, please refer to the documentation of the PROFIBUS association. http://www.profibus.com
Bus Coupler PROFIBUS DP
1
POWER SUPPLY
2
DDL
STOP
RUN
VALVE
SENSOR
POWER SUPPLY
12141214121412
VALVESENSOR
3
0
1
9
2
8
3
7
9
4
8
7
21
4321
4
6
5
0
1
2 3
4
6
5
9
8
A
7
B
6
C
5
D
4
E
3
F
2
1
0
5
6
Fig. 2: LED and switch of 337 500 026 0
AVENTICS | DDL | R499050031–BAL–001–AH 19
Bus Coupler
7
8
1
9
1 DDL LEDs 2 PROFIBUS LEDs 3 DP address S1 4 DP address S2
6 DDL mode S3 7 DDL mode S4 8 Slave module 9 DDL address S5
5 Master module

3.1.2 Master Module

The Master module is the interface between the PROFIBUS DP and the DDL. It controls the DDL and monitors the supply voltages.
PROFIBUS DP Addresses
Before a connection to the PROFIBUS DP System, an address will have to be assigned to the bus coupler. After opening the sealing cap, the address is assigned by two rotary switches. Addresses from 0 ... 99 can be assigned. With switch S1 the ten digit is set, with S2 the one digit is set. In the factory the devices are already adjusted to address 3.
English
20 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
The switches must not be changed during operation. Changed switch positions will only become valid, after the device has been turned off and restarted.
PROFIBUS DP – Baud Rates
The PROFIBUS transfer rates are adjusted with the PROFIBUS master (PLC) and are then automatically recognized by the slave (bus coupler). The following values can be adjusted as rates of transmission:
9.6 / 19.2 / 93.75 / 187.5 / 500 / 1500 / 3000 / 6000 / 12000 kBaud.
PROFIBUS DP Configuration
For the PLC configuration software, e. g. COM PROFIBUS the device master file RXP_05EF.gsd will be needed. This file is included in the delivery or can be ordered separately under the following no.: 546 046 941 2. The file has to be copied into the directory which was defined by the PLC configuration software. On this disk are also two Icon files for this bus coupler (RX_D05EF.dip/RX_R05EF.dib). For the configuration of the bus coupler, the type of station bus coupler has to be selected (above folder Valves/AVENTICS). After selection of the field "configuration" and modules, the corresponding DDL modules have to be inserted. Each participant of the DDL has to be singly configured as a module. The DDL participant with address 1 has to be configured as module 0, participant 2 as module 1 etc.
Combi modules need 2 modules, but only one DDL address. Thereby the number of the module moves one digit per module towards the DDL address.
Also the length of the data of the valve unit and the input module must be correctly adjusted. Arbitrary addresses in the address area of the control can be assigned to each module (if the control permits this). If the configuration differs from the real DDL system, the bus coupler will not be recognized correctly by the PROFIBUS master!
AVENTICS | DDL | R499050031–BAL–001–AH 21
Parameter
These functions are deposited in the GSD file and can be displayed as plain text via a configuration tool (e.g. COM PROFIBUS or S7 Hardware configuration). Per each DDL participant one byte is transferred and also one byte for the bus coupler. Each single parameter byte for the participants can be individually adjusted. If no parameters are adjusted, the DDL participants use their default parameter.
Changed parameters only become valid if the device has been turned off and on again.
Bus Coupler Parameter
Table 5: Bus coupler parameter
Bit Name of Parameter Bit = 0 Bit = 1
7 reserved
6 reserved
5 reserved
4 reserved
3 reserved
2 reserved
1 diagnosis send to PLC no (default) yes
0 reaction upon PROFIBUS failure values at 0 (default) freeze values
Bus Coupler
Bit 0 = 0 Upon failure of the PROFIBUS DP, the output data in the bus
coupler are set at 0 (default).
Bit 0 = 1 Upon failure of the PROFIBUS DP, the output data in the bus
coupler remain with the last value and the coils will be kept driven (values frozen).
Upon return of the PROFIBUS communication the outputs can be set at 0 of short duration.
Bit 1 = 0 No diagnosis data which go beyond the PROFIBUS DP standard
diagnosis are sent to PLC (default).
English
22 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Bit 1 = 1 User diagnosis data (DDL diagnosis) are send to the PLC via the
PROFIBUS DP.
DDL Participant Parameter
The parameter descriptions of the individual DDL participants can be taken from the corresponding chapters.
DDL Address
At the Master module respectively. Stand alone bus coupler no DDL Address has to be set. For correct function of the DDL (Drive & Diagnostic Link) following items must be fulfilled.
W same Baud rate at all DDL modules W DDL Address within 1 ... 14, starting with 1, without gap, no
double used Address
W DDL Address 0: see chapter 2.2 “DDL Addressing“.
DDL Mode
The transmission rate of the DDL is adjusted with the 2 bit DIP switch S3, next to the PROFIBUS DP address switches at the forefront. All DDL participants have to be adjusted to the same transmission rate.
Table 6: DDL baud rate
Bit Open On
1 DDL 125 kBaud DDL 250 kBaud (default)
2 no function no function
AVENTICS | DDL | R499050031–BAL–001–AH 23
Bus Coupler
0
1
9
2
8
3
7
4
6
5
0
1
9
2
8
3
7
4
6
5
21
ON OPEN
OPEN
ON
Fig. 3: DIP switch S3:
DDL mode
Table 7: Overview on the LED indications
Description Color of LED Meaning
STOP red lighting bus stop / DDL configuration not ok / Hardware not OK
Run green bus in operation / configuration ok / DATA exchange
SUPPLY SENSOR
SUPPLY VALVE
S3
red flashing bus stop / DDL configuration ok / PROFIBUS configuration
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green off no voltage at connection of sensor supply (X1S, Pin 1)
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green off no voltage at connection of sensor supply (X1S, Pin 1)
Diagnosis
LED Diagnosis
On the top side of the device LEDs indicate the state of the PROFIBUS DP interface as well as of the power supply.
meets not the actual DDL configuration
English
Voltage Monitoring The applied voltage is indicated by two green LEDs. The voltages
at plug DDL are indicated. The liminal supply voltage is at
19.2 V/21.6 V for low voltage and at 26.4 V/28.8 V for
overvoltage.
Short Circuit Monitoring The bus coupler has a short circuit monitoring for the DDL. Both
power supplies are monitored independently from each other. If the short circuit monitoring in the bus coupler starts up, the corresponding green LED begins to flash.
24 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Software Diagnosis In case of error, an „EXT_DIAG“ message is send via the
PROFIBUS DP, to the control. The length of the ext. diagnosis message depends on the number of participants. For the bus coupler Stand alone 337 500 025 0 the length is 4 byte diagnosis + 1 byte header (PROFIBUS Norm). After the bus coupler the diagnosis for the participants is sorted upwards, according to the DDL addresses. For each further DDL participant the commensurate diagnosis bytes are added. The diagnosis length of a valve driver consists of 1 Byte + the configurated data length. The Diagnosis data length for other DDL nodes can be read up on the corresponding chapters. The bus coupler with drivers (337 500 026 0) behaves like the Stand alone module and an additional DDL participant for valve control (see Slave Module). To use the diagnosis function, the corresponding parameter has to be adjusted (see table 5, parameter for the bus coupler).
AVENTICS | DDL | R499050031–BAL–001–AH 25
Bus Coupler
Table 8: Example: diagnosis fieldbus module PROFIBUS DP with one valve unit incl. standard diagnosis
DDL gaps
between
or
address 0
and
1
...
14
mixed
DDL
addr.#5
exists
DDL
addr.#13
exists
output
4
output
12
output
20
output
28
Bit
DDL
no units
at DDL
DDL
addr.#4
exists
DDL
addr.#12
exists
output
diagnosis
output
diagnosis
output
diagnosis
output
diagnosis
11
19
27
3
24 V
electronic
input
diagnosis
DDL
addr.#3
exists
DDL
addr.#11
exists
output
2
diagnosis
output
10
diagnosis
output
18
diagnosis
output
26
diagnosis
24 V
valve
voltage at
DDL
output
diagnosis
DDL
addr.#2
exists
DDL
addr.#10
exists
24 V
valve
supply
diagnosis
output
1
diagnosis
output
9
diagnosis
output
17
diagnosis
output
25
diagnosis
24 V
electronic voltage at
DDL
output
diagnosis
DDL
addr.#1
exists
DDL
addr.#9
exists
24 V
electronic
supply
diagnosis
output
0
diagnosis
output
8
diagnosis
output
16
diagnosis
output
24
diagnosis
Regarding
Byte
0 DP Norm 1 DP Norm 2 DP Norm 3 DP Norm 4 DP Norm 5 DP Norm 6 Headerbyte 0 0 block length in Byte
Bus coupler
7
8 Bus coupler
Bus coupler DDL
9
Bus coupler
10
module with address 1
11
(valve unit)
module with
12
address 1 (valve unit) module with
13
address 1 (valve unit) module with
14
address 1 (valve unit) module with
15
address 1 (valve unit)
7 6 5 4 3 2 1 0
addresses
––
have been
addr.#8
exists
––
DDL
comm.
diagnosis
output
7
diagnosis
output
15
diagnosis
output
23
diagnosis
output
31
diagnosis
DDL
addr.#7
exists
output
6
diagnosis
output
14
diagnosis
output
22
diagnosis
output
30
diagnosis
DDL
addr.#6
exists
DDL
addr.#14
exists
––––
output
5
diagnosis
output
diagnosis
output
diagnosis
output
diagnosis
diagnosis
13
diagnosis
21
diagnosis
29
diagnosis
English
26 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Meaning of the
diagnosis bits
W Byte 6:
– Bit 0 ... 5: total length of the diagnosis data in byte
W Byte 7:
– Bit 0: Electronic power supply of succeeding DDL modules
below 19.2 V or beyond 28.8 V
– Bit 1: Valve power supply of succeeding DDL modules
below 21.6 V or beyond 26.4 V
– Bit 2: Power supply of Master module electronics below
19.2 V or beyond 28.8 V
– Bit 3: No external modules connected to DDL
– Bit 4: Gaps between addresses, address 0 and 1 ... 14 have
been mixed up or addresses have been assigned twice. (It cannot be assured that double addresses are recognized safely)
W Byte 8:
– free
W Byte 9 + 10:
– Bit 0 ... 7: For each existing address the corresponding bit
will be set.
With automatic addressing the following is valid:
W Byte 9:
– Bit 0: Pressure control valve
– Bit 1: Valve driver
– Bit 2: Input module
– Bit 3: Output module – Bit 4: Combi module

3.1.3 Slave Module

The Slave module behaves like a DDL participant for valve control but it is situated within the housing of the bus coupler. According to this a DDL address and a baud rate have to be adjusted! The connection to the valve unit is effected via a 25 pin D-Sub plug at the bottom side of the module.
OPEN ON
S4
2
1
0
F
OPEN
Fig. 4: DIP switch S4
AVENTICS | DDL | R499050031–BAL–001–AH 27
Bus Coupler
DDL Address
The DDL address is adjusted with the switch S5. The regulation for the adjustment can be found in chapter 2.2 “DDL Addressing“.
DDL Mode
The DDL baud rate is adjusted with switch S4. All participants have to be adjusted to the same baud rate.
Table 9: DDL baud rate
Bit Open On
1 DDL 125 kBaud DDL 250 kBaud (default)
2 no function no function
Output Data Length
With switch S4 the number of outputs is adjusted. With this it is possible to optimize the needed data range of the control for
43
21
5
4
3
6
7
8
9
A
B
E
C
D
ON
smaller valve units.
Table 10: Data length
Bit 3 Bit 4 Data length
Open Open 1 Byte
On Open 2 Byte
Open On 3 Byte
On On 4 Byte (default)
English
The 4 byte mode offers a conformity with 16 bit PLC systems. But only the first 3 bytes are transferred to the outputs of the D-Sub plug.
The switches must not be changed during operation. Changed switch positions will only become valid, after the device has been turned off and restarted.
28 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Output Data Range of the Control
The DDL address determines the position of the output data in the data range of bus coupler and therefore the position in the address range of the control. The valve driver occupies, depending on the length set, 1 ... 4 byte in the output range of the control. Whereby the 4th byte does not represent real outputs and serves only for the 16 bit conformity.
Table 11: Output bits
Byte Regarding
valve unit
X
Pin 25 pol.
D-Sub
valve unit
X + 1
Pin 25 pol.
D-Sub
valve unit
X + 2
Pin 25 pol.
D-Sub
valve unit
X + 3
Pin 25 pol.
D-Sub
7 6 5 4 3 2 1 0
output7output6output5output4output3output2output1output
87654321
output15output14output13output12output11output10output9output
16 15 14 13 12 11 10 9
output23output22output21output20output19output18output17output
24 23 22 21 20 19 18 17
not
existent
Nc Nc Nc Nc Nc Nc Nc Nc
not
existent
not
existent
not
existent
Bit
existent
not
not
existent
not
existent
0
8
16
not
existent
At Pin 25 of 25 pol. D-Sub plug 0 V is connected. If address 0 (automatic addressing) is set, the bus coupler with driver behaves like a valve driver. Further information can be taken from chapter 2.2 “DDL Addressing“. The valve driver does not occupy any data in the input range, only within the diagnosis range of the DDL. Byte X is the start address of the output data range of the DDL participant in the control (see PROFIBUS DP Configuration).
LED Diagnosis
AVENTICS | DDL | R499050031–BAL–001–AH 29
Bus Coupler
Diagnosis
Table 12: Overview of the DDL LED indication
Description Color of LED Meaning
SUPPLY SENSOR
SUPPLY VALVE
DDL red lighting no DDL communication (see below)
The limits of power supply (electronics/valves) are at 19.2 V/
21.6 V for low voltage and at 28.8/26.4 V for overvoltage. The
voltages are measured at plug DDL OUT. The LED DDL indicates that no reference data communication takes place in the DDL system. This can be due to:
W The adjusted baud rate of the DDL modules is not equal W Gaps in the addressing W Same address has been assigned for 2 modules W Address 0 and 1 ... 14 have been assigned at the same time W Configuration has changed during operation
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green off no voltage at connection sensor supply
(X1S, Pin 1)
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green off no voltage at connection sensor supply
(X1S, Pin 1)
Voltage Monitoring The applied voltage supplies are indicated by two green LEDs:
Voltages at the plug DDL are shown. The threshold of the power supply (electronic/valves) are at 19.2 V/21.6 V for under voltage and at 28.8 V/26.4 V for overvoltage.
Software Diagnosis The software diagnosis of the Slave module is 1 byte standard
diagnosis + configured data length long. With bus coupler 337 500 026 0 the outputs from 24 ... 31 are not really existent. For this reason there is no rational diagnosis. With smaller valve units further outputs and their diagnosis can not be used. The address range of the diagnosis drives from the DDL address.
English
30 AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
If address 0 (automatic addressing) is set, the bus coupler with driver behaves like a valve driver. Further information can be taken from chapter 2.2 “DDL Addressing“.
Table 13: Diagnosis bits
Byte
Z + 1
Z + 2
Z + 3
Z + 4
Z
7 6 5 4 3 2 1 0
DDL
comm.
diagnosis
output
7
diagnosis
output
15
diagnosis
output
23
diagnosis
output
31
diagnosis
–––––
output
6
diagnosis
output
14
diagnosis
output
22
diagnosis
output
30
diagnosis
output
5
diagnosis
output
13
diagnosis
output
21
diagnosis
output
29
diagnosis
diagnosis
diagnosis
diagnosis
diagnosis
Bit
output
4
output
12
output
20
output
28
output
3
diagnosis
output
11
diagnosis
output
19
diagnosis
output
27
diagnosis
output
2
diagnosis
output
10
diagnosis
output
18
diagnosis
output
26
diagnosis
24 V
valve
supply
diagnosis
output
1
diagnosis
output
9
diagnosis
output
17
diagnosis
output
25
diagnosis
24 V
electronic
supply
diagnosis
output
0
diagnosis
output
8
diagnosis
output
16
diagnosis
output
24
diagnosis
Meaning of the bits W Byte Z Bit 0: Power supply of the electronics below 19.2 V or
beyond 28.8 V
W Byte Z Bit 1: Power supply of the valves below 21.6 V or
beyond 26.4 V
W Byte Z Bit 7: Communication to the DDL module interrupted W Byte (Z + 1) – (Z + 4) Bit 0 ... 7: Output short circuit or open
(see description of the parameter).
W Byte Z is the start address of the diagnosis range of the DDL
participant in the control.
NOTICE
A short circuit can only be detected if the output is driven. An open output can only be detected if it is not driven.
Loading...
+ 166 hidden pages