W Please pay attention to the general safety instructions and
notice the content of the user manual, before you install,
start up, put pressure or electrical power to the devices.
W The devices should be used only in areas and systems they
are specified for and also comply with the tolerances of the
technical data. In case of non compliance and upon
exceeding the limits, which are mentioned under the point:
technical data, the danger of overheating can be caused as
well as damage to the device, interference in the function
and/or the electrical security.
W The AVENTICS devices have been generally developed to be
used within the industrial sector. If devices shall be used in
living quarters (living and business and industry sector) a
special permission has to be procured from the licensing
authority. In Germany licences are issued by the
Regulierungsbehörde für Telekommunikation und Post
(RegTP).
W To observe the technical data you should only use cables
and wires, being mentioned in the user manual or quotation
drawing.
W The devices have to be grounded according to the
instructions. The relevant DIN/VDE standards or the country
specific standards have to be observed upon installation.
Note especially:
- VDE 0160 (EN 50178)
- VDE 0100
W The supply voltage has to be applied from a powerpack with
protective separation according to EN 60742, classification
VDE 0551. Please pay attention that the external fuse of the
devices is in accordance with the description.
W A faultless and safe operation of the devices requires an
appropriate transport, storage, installation and start up.
W The devices have to be opened only by qualified staff.
Electrostatic accidentally dangerous parts.
English
10AVENTICS | DDL | R499050031–BAL–001–AH
Safety Precautions
W The installation of the devices has to be effected only by
qualified staff and without power supply and pressure.
Please observe the installation position, mentioned in the
user manual.
W To avoid dangerous movements, the electrical start up has
to be made on in depressurized state.
W Start up the device only after installation and tests have
been completely finished.
W Plugs must not be plugged or unplugged under voltage.
To avoid electrical damage to the device, switch off the
power supply before plugs are plugged/unplugged.
W To achieve the protection class and function all seals have to
be intact and fit in correct position.
W The protection class can only be achieved if all unused plugs
are sealed with covers or endplugs.
W Switches and configuration must not be changed during
operation. Changed settings only become valid after power
recycle.
W No equalizing currents due to potential differences must run
via the shield, otherwise the earthing have to be made via
separate wires.
W Use in explosive Area:
Some DDL participants can be used in explosive areas. For
these certified devices at the end of the corresponding
chapter important notes can be found. If the devices are
used in explosive areas, these notes have to be read and
attention has to be paid.
W Further safety precautions in the user manual have to be
followed.
W We refuse all liability for nonobservance of these notes, for
handling of the device or use in an improper way.
Furthermore the guarantee on our devices and accessories
expires.
AVENTICS | DDL | R499050031–BAL–001–AH11
DDL General
2DDL General
The Drive & Diagnostic Link (DDL) from AVENTICS is a system to
use solenoids, pressure control valves and digital and analog
I/O modules with different field bus systems. Independent from
the used field bus, the systems can be projected and with the
corresponding bus coupler connected to common field busses
like PROFIBUS DP, Interbus S, ControlNet and DeviceNet. DDL
provides, independent from fieldbus, 128 inputs and 128
outputs per bus coupler. For the reason of the transfer mode
system, there is a high data security which is even increased by
the diagnostic functionality. In this way the DDL participants and
the supply voltages are controlled and reported to the
diagnostics. Furthermore the coils of valve units are observed
according to open load and short circuit. Therefore errors can
be quickly recorded up to the affected valve and measures
initiated. In addition some DDL participants offer the possibility
to determine via parameter the reaction upon failure of fieldbus
and DDL. On the basis of the employment of M12 connectors the
connection is very simple and safe. A total length of the cable of
40 m is permitted and offers a high flexibility with the DDL. Here
the gap between the modules is regardless. Because of the high
modularity most of the AVENTICS valve families can be
employed with DDL.
English
2.1DDL System Overview
Basically the DDL consists of two types of participants:
W The bus coupler makes it possible to transfer data between
the fieldbus system (PROFIBUS DP, Interbus S, DeviceNet, ...)
and the DDL. The bus coupler is therefore the DDL master
and has to be existent once.
W The DDL participant is therefore the slave within the DDL
system. Up to 14 participants can be connected to the DDL.
12AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
The bus coupler with drivers contains, in addition to the Master
module, which is the real bus coupler, also a Slave module
which represents the DDL participant. This Slave module is
therefore a DDL participant and up to 13 other DDL participants
can be connected.
2.2DDL Addressing
In the DDL system a definite address has to be assigned to each
participant (except for the Master module of the bus coupler).
This is effected via a hex rotary switch at the devices.
Table 1:DDL address switch
Position of SwitchMeaning
0automatic addressing
1DDL address 1
2DDL address 2
3DDL address 3
4DDL address 4
5DDL address 5
6DDL address 6
7DDL address 7
8DDL address 8
9DDL address 9
ADDL address 10
BDDL address 11
CDDL address 12
DDDL address 13
EDDL address 14
Fno function
The addressing can be effected in two different ways:
1. Manual addressing
2. Automatic addressing
AVENTICS | DDL | R499050031–BAL–001–AH13
Manual and automatic addressing cannot be effected at the
same time.
Please take into consideration that upon effecting the address
adjustments, changes will only be taken over after a reset of
voltage.
2.2.1Manual Addressing
A definite address, between 1 and 14, is allocated to each
participant. No participant must have the address 0.
Furthermore the lowest address must be 1 and there must not
be any gaps between the addresses. The addressing is,
however, independent from the physical position of the
participant in the DDL and its type.
Example: 5 DDL participants are connected to a bus coupler
Stand alone (needs no DDL address).
Table 2:Example for manual DDL addressing
Correct:Incorrect: Gap (4) and
lowest address 1
DDL General
Incorrect:
Address 0 is used
DDL
Address
1pressure control
2valve driver3valve driver1valve driver
3valve driver5valve driver2valve driver
4input module6input module3input module
5output module7output module4output module
DDL NodeDDL
Address
2pressure control
valve
DDL NodeDDL
Address
0pressure control
valve
DDL Node
valve
2.2.2Automatic Addressing
If there is only one participant per type in the DDL system, the
DDL can automatically address itself. For this the address 0 has
to be allocated to all DDL participants. In this case the DDL
system allocates the address automatically to the participants.
The following table shows, what kinds of module types are
available and where to find them in the data and the diagnosis
range.
English
14AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
If not all module types are used, the following modules move up.
If the automatic addressing is used, addresses between 1 ... 14
must not be used.
Table 3:Data range at automatic DDL addressing
Output
Data
Position
1EP pressure
2valve driver–valve driver1EP pressure control
–input module2input module2valve driver
3output module–output module3input module
1)
4
––––5combi module
1)
only, if input or output data are configured.
DDL Node TypeInput
control valve
combi module3
Data
Position
1EP pressure
1)
DDL Node TypeDiagnosis
Data
Position
BCbus coupler
control valve
combi module4output module
DDL Node Type
valve
2.2.3Error Upon Addressing
In order that the DDL is able to recognize and control all
participants, the above mentioned regulations have to be
observed. If the DDL has not been addressed correctly, this will
be indicated by the participant’s red DDL LED. If two participants
have the same address, this cannot be recognized that safely
that the DDL gets not into Run mode. This type of wrong
addressing can be recognized by checking the number of
livebits. In case of a DDL communication diagnosis, the
addressing of all participants shall be checked. Furthermore
the same baud rate has to be adjusted with all participants, also
with the Master module. In addition it has to be checked that all
cables have been correctly connected. Upon problems with very
long cables we recommend to run the DDL with 125 kBaud. For
further information on the baud rate adjustments, please refer
to the description of the device.
AVENTICS | DDL | R499050031–BAL–001–AH15
DDL General
2.3DDL Diagnosis
The DDL participants/bus couplers have two kinds of diagnosis.
On the one hand, each DDL device has LEDs to indicate the
diagnosis visually. On the other hand the DDL participants send
diagnosis data via the DDL to the bus coupler, which transmits
its own data and the diagnosis data of the DDL participants to
the control. The meaning of the diagnosis data and further
information can be taken from the corresponding chapters. The
DDL communication respectively the availability of the DDL
participants is constantly controlled by the bus coupler. As soon
as all configured DDL participants exist and communicate, the
red DDL LED turns off. If a participant does not communicate
any more, the red DDL LED will light at the corresponding
participant and the bus coupler reports the interference. In
addition the corresponding livebit and the DDL LED at the bus
coupler (Master module) lights (if existing). The communication
to the other DDL participants will however be maintained. If the
bus coupler recognizes the recurring participant (DDL LED at
the participant will go off), that way the configuration will be all
right, the DDL LED at the bus coupler will also go off.
In order to initialize the system correctly, the valves must not be
controlled. All supply voltages must exist correspondingly.
2.4DDL Data
2.4.1DDL Connection
The connection of the DDL is effected via 5 pin M12x1 plugs.
5-wire, shielded lines have to be used as connecting cables. The
shield has to be connected to the thread of the plug. The
diameter of the wires is 0.34 mm
connection is performed by a mounting male plug and the DDL
OUT connection as mounting female plug at the DDL
participants. As DDL participants can be damaged if 24 V are
applied to the signal line DDL H and DDL L or the supply lines
have been exchanged, we recommend to use pre fabricated and
2
minimum. The DDL IN
English
16AVENTICS | DDL | R499050031–BAL–001–AH
DDL General
examined wiring. This is also mentioned in chapter 5 “DDL
Accessories“.
2
1
5
4
3
Fig. 1:DDL connection
1 Pin 1 = 24 V electronics4Pin 4 = DDL H
2 Pin 2 = 24 V valves5 Pin 5 = DDL L
3 Pin 3 = 0 V
2.4.2DDL Cable Length
The total cable length of DDL system is limited to 40 m. Thereby
it is irrelevant, whether the length between the two participants
will be used or distributed equally.
With great cable length and great consumption of electricity, the
voltage drop over the cables can provoke, that the supply
voltages at the DDL participants fall below the respective
tolerance limits. In such cases the DDL valve drivers can be
used with an external power supply (337 500 015 0 or
1 827 030 190 0), which, because of the additional supply,
indicate the voltage supply level.
2.4.3DDL Cycle Times
DDL is constructed for a fast and secure data transfer. The DDL
cycle times depend on several parameters. In that way the baud
rate, number of participants and configured in and output data
length (max. 128 bit) have influence on the cycle time.
In table 4 some applications and the corresponding DDL cycle
times are shown.
The process times in the bus coupler (approx. 0.8 ms) and the
cycle time of the field bus are not included in this overview. The
cycle time can be seen as an average value. With an ideal data
transmission the signal can be transmitted considerably earlier.
With critical applications it should be taken into consideration
that with an unfavorable data transmission it could take a cycle
time twice as long, until the signals are output or transmitted to
the field bus.
AVENTICS | DDL | R499050031–BAL–001–AH17
Bus Coupler
Table 4:Examples for DDL cycle times with different DDL configurations
ExampleDDL Baud ratesDDL Participants DDL Data length I/ODDL Cycletime
1250 kBaud20/323.0 ms
2250 kBaud5128/1287.0 ms
3250 kBaud14128/12814.0 ms
4125 kBaud20/164.2 ms
5125 kBaud5128/12813.0 ms
2.4.4Standards
The DDL system fulfills the standards for EMC, listed below:
W EN 61000-6-4
W EN 61000-6-2
3Bus Coupler
AVENTICS bus couplers allow to connect pressure control
valves, valve units and digital and analog in and output modules
to a programmable logic control (PLC) by using a field bus
system like PROFIBUS DP, Interbus S, ControlNet, DeviceNet,
CANopen,... . One advantage of a serial control is the saving of
the parallel output cards in the PLC as well as the necessary
wiring. Another one is the possibility to transfer further
information like Diagnosis and parameters.
Bus couplers are available in two different designs. On the one
hand there is the Stand alone module. It consists only of the
Master module. The Master module communicates with the
field bus system and controls the DDL. On the other hand bus
couplers with drivers to control the valve via a 25 pin D-Sub
plug, are available. They have, in addition to the Master module,
also a Slave module which operates like a single DDL
participant, but is situated within the same housing.
English
18AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
3.1PROFIBUS DP 337 500 025 0/337 500 026 0
The bus coupler for PROFIBUS DP is available in two different
designs. The bus coupler with drivers (337 500 026 0) can be
directly mounted onto a valve unit. Apart from controlling this
unit, the DDL is also available for other DDL participants.
The bus coupler Stand alone (337 500 025 0) is mounted
separately and offers only the DDL. The parts of description of
the Slave module, do not apply to the bus coupler Stand alone.
Both modules are connected to the PROFIBUS DP via a shielded
2 wire cable.
3.1.1Overview
PROFIBUS DP
The field bus system PROFIBUS DP which is used for the
communication with the control, is a fast working bus system
for the cyclic exchange of user data. PROFIBUS DP is a master
slave bus system, where 2 master and 122 passive participants
maximum can be connected to. Two designs as transmission
medium are available:
W 2 wire line (shielded)
W optical fibre
For installation information of the networks and for the
configuration of the lines, please refer to the documentation
of the PROFIBUS association. http://www.profibus.com
The Master module is the interface between the PROFIBUS DP
and the DDL. It controls the DDL and monitors the supply
voltages.
PROFIBUS DP Addresses
Before a connection to the PROFIBUS DP System, an address
will have to be assigned to the bus coupler. After opening the
sealing cap, the address is assigned by two rotary switches.
Addresses from 0 ... 99 can be assigned. With switch S1 the ten
digit is set, with S2 the one digit is set. In the factory the devices
are already adjusted to address 3.
English
20AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
The switches must not be changed during operation.
Changed switch positions will only become valid, after the
device has been turned off and restarted.
PROFIBUS DP – Baud Rates
The PROFIBUS transfer rates are adjusted with the PROFIBUS
master (PLC) and are then automatically recognized by the slave
(bus coupler). The following values can be adjusted as rates of
transmission:
For the PLC configuration software, e. g. COM PROFIBUS the
device master file RXP_05EF.gsd will be needed. This file is
included in the delivery or can be ordered separately under the
following no.: 546 046 941 2. The file has to be copied into the
directory which was defined by the PLC configuration software.
On this disk are also two Icon files for this bus coupler
(RX_D05EF.dip/RX_R05EF.dib).
For the configuration of the bus coupler, the type of station bus
coupler has to be selected (above folder Valves/AVENTICS).
After selection of the field "configuration" and modules, the
corresponding DDL modules have to be inserted. Each
participant of the DDL has to be singly configured as a module.
The DDL participant with address 1 has to be configured as
module 0, participant 2 as module 1 etc.
Combi modules need 2 modules, but only one DDL address.
Thereby the number of the module moves one digit per
module towards the DDL address.
Also the length of the data of the valve unit and the input module
must be correctly adjusted. Arbitrary addresses in the address
area of the control can be assigned to each module (if the
control permits this).
If the configuration differs from the real DDL system, the bus
coupler will not be recognized correctly by the PROFIBUS
master!
AVENTICS | DDL | R499050031–BAL–001–AH21
Parameter
These functions are deposited in the GSD file and can be
displayed as plain text via a configuration tool (e.g. COM
PROFIBUS or S7 Hardware configuration). Per each DDL
participant one byte is transferred and also one byte for the bus
coupler. Each single parameter byte for the participants can be
individually adjusted. If no parameters are adjusted, the DDL
participants use their default parameter.
Changed parameters only become valid if the device has been
turned off and on again.
Bus Coupler Parameter
Table 5:Bus coupler parameter
BitName of ParameterBit = 0Bit = 1
7reserved
6reserved
5reserved
4reserved
3reserved
2reserved
1diagnosis send to PLCno (default)yes
0reaction upon PROFIBUS failurevalues at 0 (default)freeze values
Bus Coupler
Bit 0 = 0Upon failure of the PROFIBUS DP, the output data in the bus
coupler are set at 0 (default).
Bit 0 = 1Upon failure of the PROFIBUS DP, the output data in the bus
coupler remain with the last value and the coils will be kept
driven (values frozen).
Upon return of the PROFIBUS communication the outputs
can be set at 0 of short duration.
Bit 1 = 0No diagnosis data which go beyond the PROFIBUS DP standard
diagnosis are sent to PLC (default).
English
22AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Bit 1 = 1User diagnosis data (DDL diagnosis) are send to the PLC via the
PROFIBUS DP.
DDL Participant Parameter
The parameter descriptions of the individual DDL participants
can be taken from the corresponding chapters.
DDL Address
At the Master module respectively. Stand alone bus coupler no
DDL Address has to be set.
For correct function of the DDL (Drive & Diagnostic Link)
following items must be fulfilled.
W same Baud rate at all DDL modules
W DDL Address within 1 ... 14, starting with 1, without gap, no
double used Address
W DDL Address 0: see chapter 2.2 “DDL Addressing“.
DDL Mode
The transmission rate of the DDL is adjusted with the 2 bit DIP
switch S3, next to the PROFIBUS DP address switches at the
forefront. All DDL participants have to be adjusted to the same
transmission rate.
Table 6:DDL baud rate
BitOpenOn
1DDL 125 kBaudDDL 250 kBaud (default)
2no functionno function
AVENTICS | DDL | R499050031–BAL–001–AH23
Bus Coupler
0
1
9
2
8
3
7
4
6
5
0
1
9
2
8
3
7
4
6
5
21
ON OPEN
OPEN
ON
Fig. 3:DIP switch S3:
DDL mode
Table 7:Overview on the LED indications
DescriptionColor of LEDMeaning
STOPred lightingbus stop / DDL configuration not ok / Hardware not OK
Rungreenbus in operation / configuration ok / DATA exchange
SUPPLY
SENSOR
SUPPLY
VALVE
S3
red flashingbus stop / DDL configuration ok / PROFIBUS configuration
green lightingvoltage within the tolerance
green flashingvoltage below or beyond the tolerance
green offno voltage at connection of sensor supply (X1S, Pin 1)
green lightingvoltage within the tolerance
green flashingvoltage below or beyond the tolerance
green offno voltage at connection of sensor supply (X1S, Pin 1)
Diagnosis
LED Diagnosis
On the top side of the device LEDs indicate the state of the
PROFIBUS DP interface as well as of the power supply.
meets not the actual DDL configuration
English
Voltage MonitoringThe applied voltage is indicated by two green LEDs. The voltages
at plug DDL are indicated. The liminal supply voltage is at
19.2 V/21.6 V for low voltage and at 26.4 V/28.8 V for
overvoltage.
Short Circuit MonitoringThe bus coupler has a short circuit monitoring for the DDL. Both
power supplies are monitored independently from each other. If
the short circuit monitoring in the bus coupler starts up, the
corresponding green LED begins to flash.
24AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Software DiagnosisIn case of error, an „EXT_DIAG“ message is send via the
PROFIBUS DP, to the control. The length of the ext. diagnosis
message depends on the number of participants. For the bus
coupler Stand alone 337 500 025 0 the length is 4 byte diagnosis
+ 1 byte header (PROFIBUS Norm). After the bus coupler the
diagnosis for the participants is sorted upwards, according to
the DDL addresses. For each further DDL participant the
commensurate diagnosis bytes are added. The diagnosis length
of a valve driver consists of 1 Byte + the configurated data
length. The Diagnosis data length for other DDL nodes can be
read up on the corresponding chapters.
The bus coupler with drivers (337 500 026 0) behaves like the
Stand alone module and an additional DDL participant for valve
control (see Slave Module).
To use the diagnosis function, the corresponding parameter has
to be adjusted (see table 5, parameter for the bus coupler).
AVENTICS | DDL | R499050031–BAL–001–AH25
Bus Coupler
Table 8:Example: diagnosis fieldbus module PROFIBUS DP with one valve unit incl. standard diagnosis
– Bit 0 ... 5: total length of the diagnosis data in byte
W Byte 7:
– Bit 0: Electronic power supply of succeeding DDL modules
below 19.2 V or beyond 28.8 V
– Bit 1: Valve power supply of succeeding DDL modules
below 21.6 V or beyond 26.4 V
– Bit 2: Power supply of Master module electronics below
19.2 V or beyond 28.8 V
– Bit 3: No external modules connected to DDL
– Bit 4: Gaps between addresses, address 0 and 1 ... 14 have
been mixed up or addresses have been assigned twice.
(It cannot be assured that double addresses are
recognized safely)
W Byte 8:
– free
W Byte 9 + 10:
– Bit 0 ... 7: For each existing address the corresponding bit
will be set.
With automatic addressing the following is valid:
W Byte 9:
– Bit 0: Pressure control valve
– Bit 1: Valve driver
– Bit 2: Input module
– Bit 3: Output module
– Bit 4: Combi module
3.1.3Slave Module
The Slave module behaves like a DDL participant for valve
control but it is situated within the housing of the bus coupler.
According to this a DDL address and a baud rate have to be
adjusted! The connection to the valve unit is effected via a 25 pin
D-Sub plug at the bottom side of the module.
OPEN ON
S4
2
1
0
F
OPEN
Fig. 4:DIP switch S4
AVENTICS | DDL | R499050031–BAL–001–AH27
Bus Coupler
DDL Address
The DDL address is adjusted with the switch S5. The regulation for
the adjustment can be found in chapter 2.2 “DDL Addressing“.
DDL Mode
The DDL baud rate is adjusted with switch S4. All participants
have to be adjusted to the same baud rate.
Table 9:DDL baud rate
BitOpenOn
1DDL 125 kBaudDDL 250 kBaud (default)
2no functionno function
Output Data Length
With switch S4 the number of outputs is adjusted. With this it is
possible to optimize the needed data range of the control for
43
21
5
4
3
6
7
8
9
A
B
E
C
D
ON
smaller valve units.
Table 10:Data length
Bit 3Bit 4Data length
OpenOpen1 Byte
OnOpen2 Byte
OpenOn3 Byte
OnOn4 Byte (default)
English
The 4 byte mode offers a conformity with 16 bit PLC systems.
But only the first 3 bytes are transferred to the outputs of the
D-Sub plug.
The switches must not be changed during operation.
Changed switch positions will only become valid, after the
device has been turned off and restarted.
28AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
Output Data Range of the Control
The DDL address determines the position of the output data in
the data range of bus coupler and therefore the position in the
address range of the control. The valve driver occupies,
depending on the length set, 1 ... 4 byte in the output range of the
control. Whereby the 4th byte does not represent real outputs
and serves only for the 16 bit conformity.
At Pin 25 of 25 pol. D-Sub plug 0 V is connected.
If address 0 (automatic addressing) is set, the bus coupler with
driver behaves like a valve driver. Further information can be
taken from chapter 2.2 “DDL Addressing“.
The valve driver does not occupy any data in the input range,
only within the diagnosis range of the DDL.
Byte X is the start address of the output data range of the DDL
participant in the control (see PROFIBUS DP Configuration).
LED Diagnosis
AVENTICS | DDL | R499050031–BAL–001–AH29
Bus Coupler
Diagnosis
Table 12:Overview of the DDL LED indication
Description Color of LEDMeaning
SUPPLY
SENSOR
SUPPLY
VALVE
DDLred lightingno DDL communication (see below)
The limits of power supply (electronics/valves) are at 19.2 V/
21.6 V for low voltage and at 28.8/26.4 V for overvoltage. The
voltages are measured at plug DDL OUT.
The LED DDL indicates that no reference data communication
takes place in the DDL system. This can be due to:
W The adjusted baud rate of the DDL modules is not equal
W Gaps in the addressing
W Same address has been assigned for 2 modules
W Address 0 and 1 ... 14 have been assigned at the same time
W Configuration has changed during operation
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green offno voltage at connection sensor supply
(X1S, Pin 1)
green lighting voltage within the tolerance
green flashing voltage below or beyond the tolerance
green offno voltage at connection sensor supply
(X1S, Pin 1)
Voltage MonitoringThe applied voltage supplies are indicated by two green LEDs:
Voltages at the plug DDL are shown. The threshold of the power
supply (electronic/valves) are at 19.2 V/21.6 V for under voltage
and at 28.8 V/26.4 V for overvoltage.
Software DiagnosisThe software diagnosis of the Slave module is 1 byte standard
diagnosis + configured data length long.
With bus coupler 337 500 026 0 the outputs from 24 ... 31 are
not really existent. For this reason there is no rational diagnosis.
With smaller valve units further outputs and their diagnosis can
not be used.
The address range of the diagnosis drives from the DDL address.
English
30AVENTICS | DDL | R499050031–BAL–001–AH
Bus Coupler
If address 0 (automatic addressing) is set, the bus coupler with
driver behaves like a valve driver. Further information can be
taken from chapter 2.2 “DDL Addressing“.
Table 13:Diagnosis bits
Byte
Z + 1
Z + 2
Z + 3
Z + 4
Z
76543210
DDL
comm.
diagnosis
output
7
diagnosis
output
15
diagnosis
output
23
diagnosis
output
31
diagnosis
–––––
output
6
diagnosis
output
14
diagnosis
output
22
diagnosis
output
30
diagnosis
output
5
diagnosis
output
13
diagnosis
output
21
diagnosis
output
29
diagnosis
diagnosis
diagnosis
diagnosis
diagnosis
Bit
output
4
output
12
output
20
output
28
output
3
diagnosis
output
11
diagnosis
output
19
diagnosis
output
27
diagnosis
output
2
diagnosis
output
10
diagnosis
output
18
diagnosis
output
26
diagnosis
24 V
valve
supply
diagnosis
output
1
diagnosis
output
9
diagnosis
output
17
diagnosis
output
25
diagnosis
24 V
electronic
supply
diagnosis
output
0
diagnosis
output
8
diagnosis
output
16
diagnosis
output
24
diagnosis
Meaning of the bitsW Byte Z Bit 0: Power supply of the electronics below 19.2 V or
beyond 28.8 V
W Byte Z Bit 1: Power supply of the valves below 21.6 V or
beyond 26.4 V
W Byte Z Bit 7: Communication to the DDL module interrupted
W Byte (Z + 1) – (Z + 4) Bit 0 ... 7: Output short circuit or open
(see description of the parameter).
W Byte Z is the start address of the diagnosis range of the DDL
participant in the control.
NOTICE
A short circuit can only be detected if the output is driven. An
open output can only be detected if it is not driven.
Loading...
+ 166 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.