Technische Informationen | Technical information
Drucksensor
Pressure sensor
IO-Link PE5
R412013190/02.2015,
Replaces: –, DE/EN
AVENTICS GmbH
Ulmer Straße 4
30880 Laatzen
Phone +49 (0) 5 11-21 36-0
Fax: +49 (0) 511-21 36-2 69
www.aventics.com
info@aventics.com
Further addresses:
www.aventics.com/contact
The data specified above only serve to
describe the product. No statements
concerning a certain condition or suitability
for a certain application can be derived from
our information. The given information does
not release the user from the obligation of
own judgement and verification. It must be
remembered that our products are subject
to a natural process of wear and aging.
An example configuration is depicted on the
title page. The delivered product may thus
vary from that in the illustration.
Translation of the original operating
instructions. The original operating
instructions were created in the German
language.
R412023190–BPZ–001–AA/02.2015
Subject to modifications. © All rights
reserved by AVENTICS GmbH, even and
especially in cases of proprietary rights
applications. It may not be reproduced or
given to third parties without its consent.
1 Drucksensor im IO-Link-System
konfigurieren | Configuring the pressure
sensor in the IO-Link system
Die IODD-Dateien und die Technischen Informationen mit
englischen und deutschen Texten für den Drucksensor IOLink PE5 finden Sie im Medienverzeichnis.
Zur IO-Link-Konfiguration können Sie Konfigurationsprogramme
verschiedener Hersteller einsetzen.
Bevor Sie den Drucksensor nutzen können, muss dieser vom IOLink-Master erkannt werden. Dies geschieht entweder automatisch oder muss manuell ausgeführt werden.
O Beachten Sie dazu die Dokumentation des verwendeten IO-
Link-Masters.
The IODD files and the technical information for the
pressure sensor IO-Link PE5 with English and German
language content are located in the media directory.
You can use configuration software from various manufacturers
for the IO-Link configuration.
Before you can use the pressure sensor, it has to be recognized by
the IO-Link master. This process is either automatic or must be
completed manually
O Observe the documentation for the IO-Link master used.
2 Physikalische Schicht | Physical layer
SIO Modus | SIO Modus ja | yes
Min. Zykluszeit | Min Cycle Time 54400 μs
Baudrate | Baudrate COM2/38,4 kBaud
Prozessdatenlänge | Process Data
Length
16 Bit
3 Prozessdatenformel | Process data
formula
p = PDV * PD_Gradient + PD_Offset
p = Druck | pressure [bar]
PDV = Prozessdatenvariable | Process data variable
PD_Gradient = Prozessdatensteigung | Process data gradient
PD_Offset = Prozessdatenversatz | Process data offset
PD_Gradient (ISDU 69) 0,000125 0,00025 0,00075 0,00125
PD_Offset (ISDU 70) -1,125 -1,25 -0,75 -1,25
[-1..0] bar [-1..+1] bar [0..6] bar [0..10] bar
4 Prozessdatenobjekt Index 40 (0x28) | Process data object index 40 (0x28)
Byte 1 Byte 0
Bit offset 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IN
Datenbit | Data bit 13 12 11 10 9 8 7 6 5 4 3 2 1 0 2 1
Prozessdaten
Process data
1)
BDC2 = 0 für Geräte mit nur einem Schaltausgang | BDC2 = 0 for devices with only one switching output
BDC = Binärer Datenkanal | Binary Data Channel
PDV BDC
1)
5 Servicedaten | Service data
Die folgenden ISDUs werden nicht über Data-Storage gesichert: Direkte Parameter 1, Direkte Parameter 2, Gerätezugriffssperren,
Gerätespezifische Kennzeichnung und Passwort
The following ISDUs will not be saved via Data-Storage: Direct Parameters 1, Direct Parameters 2, Device Access Locks, Device Specific
Tag and Display Password
IO-Link spezifisch | IO-Link specific
Index dez
(hex)
12 (0x0C) Gerätezugriffssperren
16 (0x10) Herstellername
17 (0x11) Herstellertext
18 (0x12) Produktname
19 (0x13) Produkt-ID
20 (0x14) Produkttext
21 (0x15) Seriennummer
22 (0x16) Hardwareversion
23 (0x17) Firmwareversion
24 (0x18) Anwendungsspezifische Markierung
40 (0x28) Prozessdaten Eingang
1)
ro = read only (nur lesen), wo = write only (nur schreiben), rw = read/write (lesen/schreiben)
AVENTICS spezifisch | AVENTICS device specific
Index dez
(hex)
64 (0x40) Gerätespezifische
65 (0x41) Einstellungen BDC1
1 (0x01) Schaltpunkt
2 (0x02) Rückschaltpunkt
3 (0x03) obere Fenstergrenze
4 (0x04) untere Fenstergrenze
66 (0x42) Schaltfunktion BDC1
1 (0x01) Schaltpunktlogik
2 (0x02) Schaltfunktion
Name
Device Access Locks
Vendor Name
Vendor Text
Product Name
Produkt ID
Product Text
Serial Number
Hardware-Version
Firmwa re-Version
Application Specific Tag
Process Data Input
Name
Kennzeichnung
Device Specific Tag
BDC1 Settings
Switching point
Reset point
High window limit
Low window limit
Switching function BDC1
Switchpoint logic
Switching function
Forma t
Länge
(Offset)
Length
String 16 Byte rw ********
Record 16 Byte rw
Bit (96) 32 Bit rw 9000 1016...9000
Bit (64) 32 Bit rw 8200 1000...8984
Bit (32) 32 Bit rw 9000 1016...9000
Bit (0) 32 Bit rw 8200 1000...8984
Record 4 Byte rw Konfiguration der Schaltfunktion Q1
Bit (24) 8 Bit rw 0 0 = Schließer | Normally open
Bit (16) 8 Bit rw 3 2 = Fensterfunktion | Window function
Form at
(Offset)
Record 2 Byte rw
String 13 Byte ro Aventics GmbH
String 20 Byte ro www.aventics.com
String 23 Byte ro PE5
String 10 Byte ro R412010xxx
String 42 Byte ro Pressure switch for pneumatic
String 8 Byte ro
String 6 Byte ro
String 6 Byte ro
String 16 Byte rw ********
PD In 2 Byte ro
1)
Zugriff
1)
Access
Länge Length
Standardwert
Default Value
********
Wertebereich
Valu e/Ra nge
Setzen des Schaltpunkts und des Rückschaltpunkts von Q1
Setting of switching point and reset point of Q1
Configures the switching function Q1
1 = Öffner | Normally closed
3 = Hysteresefunktion | Hysteresis function
1)
Zugriff
Access
AVENTICS | IO-Link PE5 | R412023190–BPZ–001–AA 1
Standardwert
1)
Default Value
applications
********
Bemerkung [Einheit]
Remark [Unit]
2)
2)
2)
2)

AVENTICS spezifisch | AVENTICS device specific
Index dez
(hex)
3 (0x03) Hysterese
67 (0x43) Einstellungen BDC2
1 (0x01) Schaltpunkt
2 (0x02) Rückschaltpunkt
3 (0x03) obere Fenstergrenze
4 (0x04) untere Fenstergrenze
68 (0x44) Schaltfunktion BDC2
1 (0x01) Schaltpunktlogik
2 (0x02) Schaltfunktion
3 (0x03) Hysterese
69 (0x45) PD Steigung
70 (0x46) PD Versatz
72 (0x48) Druckeinheit der Anzeige
73 (0x49) höchster Druck
74 (0x4A) niedrigster Druck
80 (0x50) Aktualisierungsrate Anzeige
121 (0x79) Schaltmodus des Q2
122 (0x7A) Konfiguration analoger
126 (0x7E) Schaltverzögerung BDC1
127 (0x7F) Rückschaltverzögerung BDC1
128 (0x80) Schaltverzögerung BDC2
129 (0x81) Rückschaltverzögerung BDC2
Name
Hysteresis
BDC2 Settings
Switching point
Reset point
High window limit
Low window limit
Switching function BDC2
Switchpoint logic
Switching function
Hysteresis
PD_Gradient
PD_Offset
Display unit
Pressure high
Pressure low
Display update rate
Switching output mode Q2
Ausgang
Analog out config
Time delay on BDC 1
Time delay off BDC1
Time delay on BDC 2
Time delay off BDC2
Forma t
Länge
(Offset)
Length
Bit (0) 16 Bit rw 0 0
Record 16 Byte rw
Bit (96) 32 Bit rw 9000 1016...9000
Bit (64) 32 Bit rw 8200 1000...8984
Bit (32) 32 Bit rw 9000 1016...9000
Bit (0) 32 Bit rw 8200 1000...8984
Record 4 Byte rw Konfiguration der Schaltfunktion Q2
Bit (24) 8 Bit rw 0 0 = Schließer | Normally open
Bit (16) 8 Bit rw 3 2 = Fensterfunktion | Window function
Bit (0) 16 Bit rw 0 0
Float 4 Byte ro Steigung der analogen Prozessdaten
Float 4 Byte ro Versatz der analogen Prozessdaten
UInt 8 Bit rw 0 0 = bar
Int 32 Bit ro Zeigt den höchsten gemessenen
Int 32 Bit ro Zeigt den niedrigsten gemessenen
UInt 8 Bit rw 50 10 = 10 Hz
UInt 8 Bit rw 128 128 = PNP
UInt 8 Bit rw 7 3 = I
UInt 16 Bit rw 0 0...50000 Schaltverzögerung [ms]
UInt 16 Bit rw 0 0...50000 Rückschaltverzögerung [ms]
UInt 16 Bit rw 0 0...50000 Schaltverzögerung [ms]
UInt 16 Bit rw 0 0...50000 Rückschaltverzögerung [ms]
240 (0xF0) MBA Int 32 Bit ro Untere Messgrenze
241 (0xF1) MBE Int 32 Bit ro Obere Messgrenze
Zugriff
Access
1)
Standardwert
1)
Default Value
Wertebereich
Valu e/Rang e
Setzen des Schaltpunkts und des Rückschaltpunkts von Q2
Setting of switching point and reset point of Q2
Bemerkung [Einheit]
Remark [Unit]
2)
2)
2)
2)
Configures the switching function Q2
1 = Öffner | Normally closed
3 = Hysteresefunktion| Hysteresis function
128 = Diagnosefunktion | Diagnostic function
Gradient of pressure value
Offset of pressure value
Einheit des Druckwertes auf der Anzeige
1 = Mpa
2 = kPa
3 = PSI
4 = inHg
20 = 5 Hz
50 = 2 Hz
100 = 1 Hz
129 = NPN
130 = Pushpull
4 = I invertiert
| inverted
5 = U
6 = U
invertiert |
inverted
7 = Auto
Unit of displayed pressure value
Druckwert seit dem letzten Rücksetzen
Displays the maximum pressure value
applied since last reset
Druckwert seit dem letzten Rücksetzen
Displays the minimum pressure value
applied since last reset
Frequenz der Aktualisierung der Anzeige
Frequency of the display update
Konfiguration des analogen Ausgangs
(wenn verfügbar)
Configures the analog output (if available)
Switching delay [ms]
Reset delay [ms]
Switching delay [ms]
Reset delay [ms]
Lower end of measuring range
Upper end of measuring range
AVENTICS spezifisch | AVENTICS device specific
Index dez
(hex)
249 (0xF9) Displayfarbe
250 (0xFA) Anzeigenorientierung
251 (0xFB) Anzeigemodus
252 (0xFC) Passwort
1)
2)
Name
Display color
Display rotation
Display Mode
Display Password
ro = read only (nur lesen), wo = write only (nur schreiben), rw = read/write (lesen/schreiben)
gemäß Prozessdatenformel in bar umrechenbar | convertible in bar according to process data formula
Forma t
Länge
(Offset)
Length
UInt 8 Bit rw 0 0 = OD
UInt 8 Bit rw 0 0 = 0°
UInt 8 Bit rw 0 0 = SPRP
UInt 8 Bit rw 0...9999 Setzt das Passwort der Anzeigensperre
Zugriff
Access
1)
Standardwert
1)
Default Value
Wertebereich
Valu e/Ra nge
1 = DU
2 = Rot | Red
3 = Grün| Green
4 = Aus | Off
1 = 180°
1 = HighLow
Bemerkung [Einheit]
Remark [Unit]
Aktiviert die elektrische Rotation der
Anzeige um 180°
Enables electronic rotation of display by 180°
Angezeigte Information in Bereichen C und E
Information indicated in display areas C and E
Sets the password for the display lock
Standardkommando | Standard command
Index dec (hex) Zugrif f1) | Access
2 (0x02) Standardkommando
Standard Command
wo 130 Auslieferungszustand wiederherstellen
1)
Wert |Val ue Bemerkung [Einheit] | Remark [Unit]
Restore Factory Settings
163 Tastensperre | Key Lock
164 keine Tastensperre | Key unlock
192 max/min Werte zurück setzen | Reset HIGH and LOW values
1)
ro = read only (nur lesen), wo = write only (nur schreiben), rw = read/write (lesen/schreiben)
193 Korrektur Nullpunktoffset | Zero offset correction
Events | Events
Code dec (hex) Name Typ e Bemerkung [Einheit] | Remark [Unit]
6144 (0x1800) Überdruck
6145 (0x1801) Unterdruck
20752 (0x5110) Überspannung in der Hauptversorgung
20753 (0x5111) Unterspannung in der Hauptversorgung
Overpressure
Underpressure
Primary supply voltage over-run
Primary supply voltage under-run
Warning Fehler: Anliegender Druck > Messbereichsende
Warning Fehler: Anliegender Druck < Messbereichsanfang
Warning Überprüfen Sie den zulässigen Spannungsbereich
Warning Überprüfen Sie den zulässigen Spannungsbereich
Error: pressure > upper end of measuring range
Error: pressure < lower end of measuring range
Check tolerance
Check tolerance
30480 (0x7710) Kurzschluss | Short circuit Error Überprüfen Sie die Installation | Check installation
Fehle rcodes | Erro r
Code dec
(hex)
128 (0x80) 17 (0x11) Index nicht vorhanden
128 (0x80) 18 (0x12) Subindex nicht vorhanden
128 (0x80) 32 (0x20) Service zur Zeit nicht verfügbar
128 (0x80) 35 (0x23) Zugriff verweigert
128 (0x80) 48 (0x30) Parameterwert außerhalb des
128 (0x80) 51 (0x33) Parameterlänge zu groß
128 (0x80) 52 (0x34) Parameterlänge zu klein
128 (0x80) 53 (0x35) Funktion nicht verfügbar
128 (0x80) 54 (0x36) Funktion zur Zeit nicht verfügbar
128 (0x80) 65 (0x41) Inkonsistenter Parametersatz
Additional
Code
Name
Index not available
Subindex not available
Service temporarily not available
Access denied
gültigen Bereichs
Parameter value out of range
Parameter length overrun
Parameter length underrun
Function not available
Function temporarily unavailable
Inconsistent parameter set
Bemerkung [Einheit]
Remark [U nit]
Zugriff auf einen nicht existierenden Index
Access occurs to a not existing index
Zugriff auf einen nicht existierenden Subindex
Access occurs to a not existing subindex
Auf den Parameter kann gerade nicht zugegriffen werden. Das Gerät erlaubt
dies im aktuellen Zustand nicht.
Parameter is not accessible due to the current state of the device application
Schreibzugriff auf einen schreibgeschützten Parameter
Write access on a read-only parameter
Geschriebener Parameterwert liegt außerhalb des zulässigen Wertebereichs
Written parameter value is outside its permitted value range
Geschriebene Parameterlänge ist größer als erlaubt
Written parameter length is above its predefined length
Geschriebene Parameterlänge ist kleiner als erlaubt
Written parameter length is below its predefined length
Geschriebenes Kommando wird vom Gerät nicht unterstützt
Written command is not supported by the device application
Geschriebenes Kommando wird vom Gerät im aktuellen Zustand nicht unterstützt
Written command is not available due to the current state of the device application
Am Ende des Blockparametertransfers wurden Inkonsistenzen erkannt. Der
Geräteplausibilitätscheck schlug fehl | Parameter inconsistencies were found at
the end of block parameter transfer, device plausibility check failed
AVENTICS | IO-Link PE5 | R412023190–BPZ–001–AA 2