Avaya XBU48 Installation And Operator's Manual

Page 1
Site Preparation,
Installation and Operator’s Manual
for
48 Vdc Extended Battery Cabinet (XBU48)
for use with
Series 1
1500–2000 VA
Uninterruptible Power Systems
Page 2
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN 50091-2
Some configurations are classified under EN 50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in which
case, the user may be required to take additional measures.
Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions.
ECopyright 2001–2006 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Avaya Inc.
Page 3
Table of Contents
1 Introduction 1.........................................................
UPS Model and Battery Configurations 1......................................................
XBU48 System Recharge Time 1.........................................................
XBU48 Battery Times 2................................................................
2 Installation 3..........................................................
Safety Warnings 3......................................................................
Installing the XBU48 5...................................................................
Important Safeguards 10................................................................
XBU48 Fault LED 10......................................................................
Alarm Contacts 11.......................................................................
3 Specifications 12.......................................................
4 Troubleshooting 13......................................................
Obtaining Service 14.....................................................................
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
i
Page 4
TABLE OF CONTENTS
ii
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 5
Chapter 1 Introduction
Thank you for your purchase of the Avaya 48 Vdc Extended Battery Cabinet (XBU48). The Avaya XBU48 is an accessory for your Series 1 (1500–2000 VA) UPS that extends the battery-backup runtimes for the UPS.
The XBU48 is a 48 Vdc model with a charger. Up to three XBU48s can be attached to customize the battery runtime for your application.
UPS Model and Battery Configurations
There are two important considerations you need to evaluate when selecting the UPS model and battery configuration for your equipment:
Load requirements of the equipment you want to protect. Select the UPS
1.
model that meets the power consumption requirements of the equipment you want to protect.
Battery protection time. During a power failure, the UPS operates on
2.
battery, providing time to complete your computing activities prior to UPS shutdown. The duration of this time period is directly related to the UPS battery configuration and the amount of load on the UPS.
XBU48 System Recharge Time
The following table displays the estimated minimum recharge time, after a discharge at the rated load, to return the XBU48 batteries to 90% capacity.
Battery Time Used
1 Hour 2 Hours 4 Hours 8 Hours
Recharge Time to >90% 17 hours 20 hours 23 hours 27 hours
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
1
Page 6
INTRODUCTION
XBU48 Battery Times
The following table displays the number of cabinets required for the number of hours of battery time.
Battery
Number of XBU48s Required for Battery Time (by UPS Load*)
Time
(in
2000VA1800VA1600VA1500VA1400VA1200VA1000VA800VA650
Hours)
3.5 1 1 1 1 1 1 1 1 1
4.0 2 1 1 1 1 1 1 1 1
4.5 2 2 1 1 1 1 1 1 1
5.0 2 2 2 1 1 1 1 1 1
5.5 2 2 2 2 1 1 1 1 1
6.0 2 2 2 2 2 1 1 1 1
6.5 2 2 2 2 2 1 1 1 1
7.0 2 2 2 2 2 2 1 1 1
7.5 2 2 2 2 2 2 1 1 1
8.0 2 2 2 2 2 2 1 1 1
8.5 3 2 2 2 2 2 2 1 1
9.0 3 2 2 2 2 2 2 1 1
9.5 3 2 2 2 2 2 2 1 1
10.0 3 3 2 2 2 2 2 1 1
VA
10.5 3 3 2 2 2 2 2 1 1
11.0 3 3 2 2 2 2 2 1 1
11.5 3 3 3 2 2 2 2 2 1
12.0 3 3 3 3 2 2 2 2 1
* Based on load power factor of 0.70.
NOTE Do not connect more than three XBU48s to the UPS.
2
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 7
Chapter 2 Installation
The following sections describe the installation and physical setup of the 48 Vdc Extended Battery Cabinet.
Safety Warnings
This manual contains important instructions for your Avaya XBU48 that should be followed during installation and maintenance of the UPS and batteries.
DO NOT use any other sizes or types of batteries with the XBU48.
Read all of the caution and warning statements in “Safety Warnings” of your Avaya UPS operator’s manual before performing the installation.
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
SAVE THESE INSTRUCTIONS
DANGER
Risk of electrical shock. Installation of battery cabinets must be done by trained service personnel.
CAUTION
S To reduce the risk of fire, connect only to a circuit provided with 15A maximum branch
circuit overload protection in accordance with the National Electrical Code, ANSI/NFPA 70.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flames. In
the event of a fire involving the UPS and its batteries, use only carbon dioxide fire extinguishers or those approved for use in electrical fire fighting.
S Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.
S Never open or mutilate batteries. Released electrolyte is harmful to the skin and eyes,
and may be extremely toxic.
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
3
Page 8
INSTALLATION
S Batteries can present a risk of electrical shock or burn from high short-circuit current,
fire, or explosion from vented gases. Observe proper precautions.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect charging source prior to connecting or disconnecting battery terminals.
S Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
4
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 9
Installing the XBU48
The following instructions assume you have already removed the XBU48s from the pallets according to the unloading instructions on the outside of the shipping box.
To install the XBU48:
1. Place the XBU48 near the operating site. The UPS should be well
NOTE It is recommended to allow a minimum of 4.5” of space from the rear of the cabinet for proper ventilation.
2. If you are using only one XBU48 and want increased stability or a
INSTALLATION
ventilated and away from direct sunlight or other heat source.
seismic installation, remove the mounting plates from the pallet (see Figure 1). Otherwise, skip to Step 6.
Mounting Plates
5/16” Bolts
Figure 1. Seismic Installation Mounting Plates
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
5
Page 10
INSTALLATION
3. A seismic installation of the XBU48 requires that the mounting
plates be bolted to the floor. See Figure 2 for a detailed drill and mounting pattern.
NOTE For Zone 4, it is recommended to use 5/16” self-drill bolts and hardware with 1 5/16” minimum embedment for 3000PSI-strength concrete. Refer to your local building codes for seismic mounting requirements.
8.50”
7.50” TYP
0.44”
1.563”
13.00”
Ø0.375” Mounting Holes
Front of Unit
13.50” Minimum from Wall
13.00”
7.60” from Front of Units
Figure 2. Seismic Installation Mounting Pattern
4. Using customer-supplied bolts, attach the mounting plates to the
floor.
NOTE The floor mounting bolts are customer-supplied and should fit the 0.375” diameter mounting holes on the mounting plates.
5. Using the 5/16bolts removed when unloading the cabinet from its
pallet, resecure the XBU48 to the mounting plate.
6. Verify that the UPS is turned off.
6
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 11
INSTALLATION
7. Align the U-shaped mounting bracket with the two holes closest to
the front of the XBU48 and secure using two of the countersink screws from the start-up kit.
8. Align the L-shaped mounting bracket with the two holes closest to
the rear of the XBU48 and secure using two of the countersink screws from the start-up kit.
NOTE The vertical section of the L-bracket must be to the left of the UPS.
9. Place the UPS on top of the XBU48, aligning the mounting brackets
with the holes on the sides of the UPS chassis. Secure the brackets to the UPS using the six supplied screws.
Figure 3. Maximum Configuration (UPS with Three XBU48s)
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
7
Page 12
INSTALLATION
10. Verify that the circuit breaker on all XBU48s is in the OFF (O)
position (see Figure 4).
11. Plug the XBU48 battery output cord into the battery connector on
the UPS rear panel. All battery connectors are polarized to prevent incorrect connection.
12. If additional XBU48s are to be used, plug the battery output cord of
the second cabinet into the battery connector of the first cabinet. Follow this procedure for each additional XBU48.
13. Plug the detachable power cord into the charger AC input
receptacle.
14. Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance with NEC specifications or national wiring rules.
For 240V installations, use a NEMA 6-15P/IEC 320-C13, 6-ft, detachable power supply cord that is UL-listed. Wire gauge should be #16 AWG and the insulation type should be begin with SJ, SE, or SO.
NOTE DO NOT plug the AC cord from the charger into any of the UPS receptacles.
NOTE The wall outlet must be within two meters of the equipment and accessible to the
operator.
8
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 13
INSTALLATION
Charger AC
Input
Receptacle
Charger
Charger Air
Exhaust
Charger LED
Power Switch
Alarm Contacts
Battery Connector
Battery Circuit Breaker
Breaker Tie
Battery Output Cord
Unit Rating Label
Figure 4. XBU48 Rear View
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
9
Page 14
INSTALLATION
15. Verify that the charger LED on the XBU48 rear panel is illuminated,
indicating the charger is on.
If the charger LED is not on, turn the power switch on the XBU48 rear panel to the ON position.
16. Remove the breaker tie from the circuit breaker on all XBU48s.
XBU48 Fault LED
17. Switch the circuit breaker to the ON (
| ) position on each XBU48.
18. The UPS may now be turned on according to your Avaya UPS
operator’s manual.
Important Safeguards
S Do not connect or disconnect XBU48s while the UPS is operating in
Battery mode.
S When connecting or disconnecting XBU48s, verify the circuit breaker
on all XBU48s is in the OFF (O) position.
The Fault LED on the front panel of the XBU48 illuminates to indicate an over temperature condition. The Fault LED remains lit until the system cools, typically a few hours.
Fault LED
10
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Figure 5. Fault LED
Page 15
Alarm Contacts
INSTALLATION
A set of normally open alarm contacts is provided on the rear panel of the XBU48. The contacts will close if there is an overload or overtemperature condition.
Optional: To use the alarm contacts, connect alarm leads to the two contacts on the alarm contact strip. The alarm contact is rated at 1A/30 Vac or 1A/60 Vdc.
Normally Open Contact Inside the XBU48
User Connection
Points
Figure 6. Alarm Contact Strip
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
11
Page 16
Chapter 3 Specifications
Table 1. 48 Vdc Extended Battery Cabinet Technical Specifications
Battery Type Valve-regulated lead acid (VRLA); Hawker 12HR-300 or C & D Dynasty UPS12-270
Expected Life 8 years @ 20-hr rate, 25°C(77°F)
Nominal Battery String Voltage 48 Vdc
Nominal Float Voltage 2.3V/cell
Recharge Current 5A per string, 10A total
Charger AC Input 120/240 Vac, 7/4A, 50/60 Hz (625 VA nominal); automatically selected
IEC 320-C13 input connector
Circuit Protection Circuit breaker protection
Alarm Contact 1A/30 Vac or 1A/60 Vdc
Dimensions (WxDxH)
Weight Shipping weight: 750 lb (341 kg)
Operating Environment Temperature: 10°Cto40°C(50°F to 104°F)
Recommended use: 25°C(77°F); For each 8°C(15°F) rise in temperature,
Humidity: 10 to 95% (noncondensing)
Altitude: -300 to +10,000 ft
Safety Conformance UL 1778, CAN/CSA C22.2, No. 107.1-M91, EN 50091-1-1 and IEC 60950
Agency Markings UL, cUL
EMC (Class A) FCC Part 15, EN 50091-2, ICES-003
17.2x 24.6x 28.3
(43.7 x 62.5 x 71.9 cm)
Installed weight: 665 lb (302 kg)
the battery loses approximately 50% of its rated life.
Table 2. Part Number
XBU48 Model Avaya Comcode
48 Vdc 700404486
12
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Page 17
Chapter 4 Troubleshooting
p
p
The 48 Vdc Extended Battery Cabinet is shipped with the battery charged. However, it may lose some of its charge during shipping and storage. You can use the XBU48 immediately after unpacking, but it may not provide the full-rated backup time during a power failure. Upon initial startup, the XBU48 may need to operate for approximately 24 hours to fully charge the battery and provide full battery-backup time.
Condition Possible Cause Action
System does not provide the expected backup time.
Charger LED is not on.
XBU48 Fault LED is on. The XBU48 internal
Alarm contact is closed. The XBU48 internal
Battery Service
Battery circuit breakers are in the OFF (O) position.
The XBU48 is not properly connected to the UPS.
Low battery capacity. Allow the battery to charge for 24 hours, then retest.
Protected equipment power requirements exceed UPS capacity.
XBU48 connections are not secure.
Charger has failed. Contact your Avaya service representative.
temperature is too high.
temperature is too high or there is an overload condition.
The battery may be fully discharged.
Switch the battery circuit breaker to the ON ( | ) position for all connected XBU48s.
Verify that the XBU48 cords are connected.
Reduce load, then retest.
Verify that the XBU48 is plugged in and turned on.
Allow the unit to cool. If the condition persists, contact your Avaya service representative.
Allow the unit to cool or reduce the load. If the condition persists, contact your Avaya service representative.
Plug the UPS and XBU48 into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the
indicator. If the indicator is still on, see “UPS Maintenance” in your Avaya UPS operator’s manual.
The battery is not connected correctly.
Avayat XBU48 Site Preparation, Installation and Operator’s Manual S 700071244 Issue 3
Check the battery connections. Call your Avaya service representative if the problem persists.
13
Page 18
TROUBLESHOOTING
Obtaining Service
The troubleshooting chart covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with your UPS, call your Avaya service representative or the appropriate telephone number on the service label of your UPS.
Please have the following information ready when you call:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
14