Avalon Firestyles PI-1992 User Manual

SAFETY PRECAUTIONS
VIEWING DOOR AND ASHPAN MUST BE CLOSED
AND LATCHED DURING OPERATION.
THIS UNIT MUST BE PROPERLY INSTALLED IN
ORDER TO PREVENT THE POSSIBILITY OF A HOUSE FIRE. FOR YOUR SAFETY THE INSTALLATION INSTRUCTIONS MUST BE STRICTLY ADHERED TO. DO NOT USE MAKESHIFT METHODS OR COM­PROMISE INSTALLATION.
CONTACT YOUR LOCAL BUILDING OFFICIALS TO
OBTAIN A PERMIT AND INFORMATION ON ANY IN­STALLATION RESTRICTIONS OR INSPECTION RE­QUIREMENTS IN YOUR AREA. ALSO, NOTIFY YOUR INSURANCE COMPANY THAT YOU ARE IN­STALLING A PELLET BURNING APPLIANCE.
THIS UNIT'S EXHAUST SYSTEM WORKS WITH A
NEGATIVE COMBUSTION CHAMBER PRESSURE AND A LOW POSITIVE CHIMNEY PRESSURE. IT IS VERY IMPORTANT THAT THE EXHAUST SYSTEM BE COMPLETELY AIRTIGHT AND PROPERLY IN­STALLED. THE CHIMNEY JOINTS SHOULD BE SEALED WITH RTV 500 DEGREES FAHRENHEIT (500° F) (260° C) SILICONE SEALANT. IMPROPERLY INSTALLED STOVES ARE THE MAJOR CAUSE OF HOME FIRES.
THE AVALON 900 APPLIANCE IS DESIGNED AND
APPROVED FOR THE BURNING OF PELLETIZED WOOD FUEL ONLY. THE BURNING OF ANY TYPE OF FUEL OTHER THAN THAT LISTED WILL VOID ALL WARRANTIES AND THE SAFETY LISTING OF THE UNIT. DO NOT ATTEMPT TO BURN ANY OTHER FUEL THAN SPECIFIED IN THIS MANUAL.
THE EXHAUST SYSTEM SHOULD BE CHECKED
TWICE A YEAR MINIMUM FOR ANY BUILD-UP OF SOOT OR CREOSOTE.
GASOLINE OR OTHER FLAMMABLE LIQUIDS MUST
NEVER BE USED TO START THE FIRE OR "FRESHEN UP" THE FIRE. DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS IN THE VICINITY OF THIS APPLIANCE.
ASHES MUST BE DISPOSED OF IN A METAL
CONTAINER WITH A TIGHT FITTING LID, AND PLACED ON A NON-COMBUSTIBLE SURFACE BEFORE FINAL DISPOSAL.
THIS UNIT MUST BE CONNECTED TO A GROUND-
ED, STANDARD 110 VOLT, 60 HZ ELECTRICAL OUTLET. NEVER ROUTE THE POWER CORD UNDER OR IN FRONT OF THE UNIT.
NEVER BLOCK FREE AIRFLOW THROUGH THE
OPEN VENTS OF THE UNIT.
NEVER TRY TO REPAIR OR REPLACE ANY PART
OF THE APPLIANCE UNLESS INSTRUCTIONS ARE GIVEN IN THIS MANUAL. ALL OTHER WORK SHOULD BE DONE BY A TRAINED TECHNICIAN.
WAIT UNTIL THE APPLIANCE HAS COOLED BE-
FORE CARRYING OUT MAINTENANCE PRO­CEDURES.
TRAVIS INDUSTRIES, INC. GRANTS NO WAR-
RANTY, IMPLIED OR STATED, FOR THE INSTALLA­TION OR MAINTENANCE OF YOUR STOVE, AND ASSUMES NO RESPONSIBILITY FOR ANY CONSE­QUENTIAL DAMAGE(S).
DO NOT INSTALL IN A BEDROOM OF A MOBILE
HOME.
KEEP FOREIGN OBJECTS OUT OF THE HOPPER.
ALWAYS FOLLOW THE INSTRUCTIONS IN THE
OWNER'S MANUAL.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE GROUNDING PRONG FROM THE POWER CORD.
DO NOT USE AN ADAPTOR PLUG.
BEFORE REMOVING PANELS, DISCONNECT THE
POWER CORD FROM THE ELECTRICAL OUTLET. NOTE: TURNING THE CONTROL SWITCH OFF DOES NOT DISCONNECT THE POWER TO ALL ELECTRICAL COMPONENTS.
WHEN INSTALLED IN A MOBILE HOME, THE UNIT
MUST BE GROUNDED TO THE STEEL CHASSIS OF THE MOBILE HOME AND BOLTED TO THE FLOOR IN COMPLIANCE WITH AND ACCORDING TO H.U.D. REQUIREMENTS.
THE APPLIANCE WILL NOT OPERATE USING
NATURAL DRAFT OR WITHOUT A POWER SOURCE FOR THE BLOWERS AND FUEL-FEEDING SYSTEMS.
KEEP THIS MANUAL FOR LATER USE.
PAGE 2
TABLE OF CONTENTS
Introduction and Important Information --------------------------------------------------------------------------------- 1 Safety Precautions ----------------------------------------------------------------------------------------------------------- 2
Features and Specifications - Stove & Insert-------------------------------------------------------------------------- 4
STOVE INSTALLATION:
Preparation for Installation ------------------------------------------------------------------------------------------------- 5 Freestanding Installation Specifications -------------------------------------------------------------------------------- 8 Horizontal Corner Installation --------------------------------------------------------------------------------------------- 9 Vertical Exterior Flue Installation ----------------------------------------------------------------------------------------- 11 Inside Vertical Installation with Roof Termination -------------------------------------------------------------------- 12 Hearth Stove Installation into existing Masonry Fireplace or Zero Clearance (Metal) Fireplace --------- 13 Vertical Installation into existing Factory-Built Chimney ------------------------------------------------------------ 14 Horizontal Installation ------------------------------------------------------------------------------------------------------- 15
Page
Freestanding Mobile Home Installation --------------------------------------------------------------------------------- 16 Freestanding Residential Alcove Installation -------------------------------------------------------------------------- 17
INSERT INSTALLATION:
Preparation For Installation ------------------------------------------------------------------------------------------------ 18 Insert Installation Specifications ----------------------------------------------------------------------------------------- 20 Insert Installation into Existing Masonry Fireplaces ----------------------------------------------------------------- 23 Insert Installation into Existing Zero Clearance (Metal) Fireplaces ---------------------------------------------- 25
Insert Installation - Zero Clearance (Built-In) Installation----------------------------------------------------------- 26
USE AND CARE: Pellet Stove and Pellet Insert
Location and Use of Controls --------------------------------------------------------------------------------------------- 28 Operating your Pellet Appliance ------------------------------------------------------------------------------------------ 29 Normal Operating Sounds ------------------------------------------------------------------------------------------------- 31 Care and Maintenance Schedule ---------------------------------------------------------------------------------------- 32 Care & Maintenance Instructions----------------------------------------------------------------------------------------- 33 Before Calling for Service -------------------------------------------------------------------------------------------------- 39 Replacement Parts List ----------------------------------------------------------------------------------------------------- 40
Limited Warranty ------------------------------------------------------------------------------------------------------------- 43 Product Listing Information ------------------------------------------------------------------------------------------------ 44
PAGE 3
FEA TURES AND SPECIFICA TIONS
* FREESTANDING
CONVENIENT LONG BURN TIME
* ALCOVE
VERSATILE CLOSE CLEARANCES
* MOBILE HOME
DURABLE
* MASONRY FIREPLACE INSERT * FACTORY-BUILT (Z.C.)
FIREPLACE INSERT
Stove
Heating Capacity SQ/FT ........................ 800 to 2000 Maximum ..................800 to 2000 Maximum
Burn Rate lbs/hr .................................... 1.2 to 4.7 ..................1.2 to 4.7
Emissions Grams/per hour..................... .8 (EPA Exempt) .................. .8 (EPA Exempt)
Maximum Burning Time (Hours) ............ Up to 50 ..................Up to 40
Flue Opening Diameter ..........................3.0" (76 mm) ..................3.0" (76mm)
Height from floor to top of stove on:
Pedestal.............................. 31 3/4" (806 mm) Depth Into Fireplace............ 12 1/4 " (311mm)
Legs, Brass......................... 27 7/8" (708 mm) Extension on to Hearth ....... 12 7/8" (326mm)
Legs, Cast .......................... 27 7/8" (708 mm) Width into Fireplace *.......... See Page 20
Legs, Black .........................26 3/8" (670 mm) Overall Height (Add 1" for flue)....19 " (483mm)
Overall Width..........................................24" (610 mm) .................. 24 1/4" (616 mm)
Overall Depth (Add 2 1/4" for flue) ........25 1/4" (641 mm) .................. 25 3/16 " (640 mm)
Hopper Capacity (lbs) ............................ 60 (27 KG) (Estimated) ..................50 (23 KG) (Estimated)
Unit Weight (lbs).....................................260 (118 KG) ..................240 (109 KG)
Electrical Rating ..................................... 115 Volts, 3 Amps, 60 HZ ..................115 Volts, 3 Amps, 60 HZ
Watts ............................................ 180 (Approx.) ..................180 (Approx.)
POWERFUL EFFICIENT FANS SUPERIOR AUGER SYSTEM HUGE HOPPER STAINLESS STEEL FIREPOT QUIET OPERATION
Insert
* See Page 20 for exact fireplace sizing FUEL: The unit is designed to operate using 1/4 inch diameter pellets that comply with A.P.F.I.• standards. If the fuel
does not comply to this standard, the unit may not operate as designed. If the pellets are larger that 1/4 inch diameter the unit may need adjustments; consult with your dealer.
NOTE: Store pellets in a clean dry place.
Emissions information and efficiency information based on tests conducted by E.E.M.C. Laboratory.
BTU. output will vary depending on pellet size, moisture content, burn rate and pellet type. Heating capacity is subject to variations due to pellet type, relative moisture content, floor plan, degree of home insulation, and temperature zone.
A.F.P.I. - Association of Pellet Fuel Industries.
Heating Capacity is based on maximum burn rate.
Maximum burn time is based on low burn rate.
PAGE 4
PREPARATION FOR INSTALLATION — PELLET STOVE
READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW APPLIANCE. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
PREPARATION:
1. Remove all tape and packaging.
2. Remove the wood shipping frame from around and under the appliance.
3. Check that no parts have become loose and the appliance has not been damaged during shipping.
4. Remove the hardware pack from the appliance.
5. READ THE OWNER'S MANUAL BEFORE PROCEEDING. * Appliance should be located such that no doors, drapes, furniture or other combustibles can be placed close or
swing closer than the minimum stated clearances. * The appliance must be installed in a level, secure position.
* Required Floor Protection:
Minimum size 26 1/8"W x 31 1/2"D (664mmW x 800 mmD) of non-combustible material with a minimum thickness of 26 gauge (.018", .5mm) floor protection must extend
Chimney Lengths
Vertical
Horizontal
Combined Horizontal &
Vertical
NOTE #1: On chimneys with vertical heights that exceed 15' and/or horizontal runs that exceed 4', a 4" diameter pellet vent is recommended.
NOTE #2: When this unit is installed above 4000' in altitude, 4" diameter pellet vent should be used. * Do not obtain combustion air from attic, garage, unventilated crawl space or any other enclosed space. Do not
locate combustion air inlet at an elevation higher than exhaust termination. * Outside air (combustion air intake) is recommended, but not required, for all residential installations, but is
required for mobile home installations. If an outside air intake (combustion air intake) is used, it must be connected to a 1-3/4", or larger, metal or aluminium duct with a rodent screen fixed to the termination. Do not use P.V.C .duct.
NOTE: TRAVIS INDUSTRIES, INC., recommends that an outside air (combustion air) intake be used in all installations. If one is not used, there is a possibility of combustion gases (smoke) being released into your home, if there is a power outage while the unit is in operation.
Maximum
33' (10.06 m)
10' (3.05 m)
4' Horizontal 30' Vertical 10' Horizontal 25' Vertical
Front - 6" (152 mm) Sides - 0" ( 0 mm) Back - 0" ( 0 mm)
Minimum
Subject to installation. See Fig. 9 Subject to installation. See Fig. 4&9
Any Lesser Combination is Acceptable.
* The AVALON 900 pellet stove exhaust vent accepts 3" diameter pellet vent pipe. Some of the brands available for use with the AVALON 900 are:
1. Duravent Model PL-Vent Simpson Dura-Vent P.O. Box 1510 Vacaville, CA 95688 (707) 446-1786 or 1-800-227-8846
NOTE: 4" diameter may be substituted when a 3" to 4" adapter is used. See manufacturer’s installation instructions for precautions required for passing vent through a combustible wall
or ceiling. Do not connect this appliance to a vent serving another appliance. All sections of pellet vent must be fastened to each other with sheet metal screws and silicone sealed with type
500 degree Fahrenheit (260°C) RTV (high heat) silicone sealer, to ensure that the joints are airtight.
2. James A. Ryder MFG Model PL-Vent Ryder Mfg., Inc. 241 Arvin Avenue Stoney Creek, Ontario Canada (416) 662-1701
PAGE 5
3. MetalFab Model Pellet Vent P.O. Box 1138 Wichita, KS 67201 (316) 943-2351
PREPARATION FOR INSTALLATION Ð
PELLET STOVE (cont.)
Your Pellet Stove appliance comes completely assembled. Options are available for the different types of installations. The options are listed below and are boxed separately from the appliance. They require assembly.
1. Pedestal.
2. Leg Kit, Black.
3. Leg Kit, Brass.
4. Leg Kit, Cast Black
5. Vertical Pipe Adapter
When lifting the appliance, you may choose to remove the interior components to make it lighter. Refer to the care & maintenance instructions in this manual for the proper sequence of removal and replacement of internal components.
1. Pedestal Assembly:
Open the box marked Pedestal and remove the pedestal and the two attachment bolts and washers (3/8" diameter - 16 X 3/4" hex. head bolt).
Lift the stove onto the pedestal. Line up the threaded bolt holes in the bottom of the stove with the two holes in the mounting angle of the pedestal (some models use clips that attach to the side of the pedestal -- the same directions apply). Using a 9/16" open-end or socket wrench, fasten the pedestal to the stove with the supplied bolts and washers. NOTE: Keep the two front leg bolts in place when installing on a pedestal -- otherwise air will enter through these holes.
2. Leg Kit, Black Assembly:
Open the box marked Leg Kit, Black and remove the four 6-1/2" high black steel legs, complete with rubber­tipped leveling bolts (on certain models they are not rubber tipped Ð the same directions apply), the four attachment bolts (3/8" diameter - 16 X 3/4" hex. head bolt) and the washers.
Raise the stove on some pieces of lumber to a height of about 7". Make sure to level the stove at this point using shims under the pieces of lumber. Line up the hole in the top of the leg with the threaded bolt hole in each corner of the stove bottom. Using a 9/16" open end or socket wrench, fasten the leg to the stove with the supplied attachment bolts and washers, making sure the legs are flush with the corners of the stove.
To level the stove, first make sure the leveling bolts with the rubber ends (some models come with steel bolts -­the same directions apply) are screwed into position and backed off just enough to penetrate below the steel portion of the leg. Unscrew each leveling bolts just enough so each leveling bolt is an equal distance from the floor. You may wish to use a piece of wood or other spacer to measure this distance. As long as the lumber holding the stove in place is properly leveled, the stove will be level when the leveling bolts are adjusted properly and the lumber is removed. Next, lower the stove onto the ground and check for a level position. If slight adjustments need to be made, make sure to first raise the stove before turning the leveling bolts. The rubber tips of the leveling bolts will tear if they are adjusted while weight is applied to them.
3. & 4. Leg Kit, Brass or Cast Black Assembly:
Open the box marked Leg Kit, Brass (or Cast) and remove the four 7-7/8" high legs, complete with rubber-tipped leveling bolts(on certain models they are not rubber tipped Ð the same directions apply), the four attachment bolts (3/8" diameter - 16 X 3/4" hex. head bolt) and the washers.
Use the same directions listed above for the Leg Kit, Black assembly. The one difference is that the Brass (or Cast) legs are taller, and the stove should be lifted approximately 8 1/2" above the floor before attachment.
PAGE 6
Attach Bolt (with washer) to Stove From Below
Attach Bolt (with washer) to Stove From Below
PREPARATION FOR INSTALLATION Ð
PELLET STOVE (cont.)
5. Vertical Pipe Adapter:
The vertical pipe adapter is an optional item used to center the pellet vent on the pellet stove. It allows for a more compact installation then using offsets on the pellet vent. To install the vertical pipe adapter, follow the directions below.
1. Take the vertical pipe adapter, along with the 5 screws, out of the box and inspect for any damage.
2. When determining the final position of the stove, take into consideration the location of the vertical pipe adapter once it is installed. It is best to install the vertical pipe adapter before determining the location of the stove, making the final alignment with the pellet vent more accurate.
3. The vertical pipe adapter allows for the use of 3" pellet vent or 6" singlewall or doublewall stovepipe. Use the appropriate collar for the vent type used.
4. Insert the vertical pipe adapter onto the pellet stove and align it so the length of the adapter is vertical. On the the vertical pipe adapter where it connects to the exhaust pipe there are three holes. One is on the outward side, one is on the top, and one is located on the bottom. Make a mark on the exhaust tube where these holes line up. Make sure the pipe adapter is all the way against the exhaust pipe and properly aligned when making these marks. Take the vertical pipe adapter off and drill a 9/64" hole where the three marks where placed on the exhaust pipe.
5. Apply a high-temperature silicone sealant (type 500 degree RTV) around the outside perimeter of the exhaust pipe near the end and slide the vertical pipe adapter into place. Attach the vertical pipe adapter to the exhaust pipe by sliding it into place and screwing in the three sheet-metal screws through the vertical pipe adapter and into the holes that were drilled in step 4. Inspect the connection between the exhaust pipe and vertical pipe adater for an airtight seal. Apply more high-temperature silicone sealant if necessary.
6. The vertical pipe adapter has a sheet metal bracket used to secure the vertical pipe adapter to the stove. It attaches to the back of the stove in two locations. Drill the 9/64" holes in the back of the stove. Drill only enough to penetrate the first layer of metal. Screw in the remaining two sheet-metal screws with a phillips-head screwdriver.
7. The vertical pipe adapter can now be attached to the vent. Make sure to seal the connection between the vertical pipe adapter and vent with a high-temperature silicone sealant (type 500 degree RTV).
Drill Three Holes for the Screws that hold the Vertical Pipe Adapter to the Exhaust Pipe
Collar for 3" Pellet vent
Collar for 6" Stovepipe
Sheet Metal Bracket Used to Secure the Vertical Pipe Adapter to the Stove
Remove this Plate to Clean the Vertical Pipe Adapter
Use the Three Holes on the Verttical Pipe Adapter to mark the Three Holes that will be drilled into the Exhaust Pipe (Make sure the Vertical Pipe Adapter is Vertical and fully inserted)
PAGE 7
FREESTANDING INSTALLATION - SPECIFICATIONS
24 1/4" [616 mm]
3 3/16"
83 mm
Accepts 3" DIA
Pellet Vent
1 3/4" O.D.
(44mm)
"A"
23 " Min. [603]
“A”
PEDESTAL 13 3/4" (348mm) 14 7/8" (387mm) LEGS, BRASS 9 3/4" (248mm) 10 7/8" (276mm) LEGS, CAST 9 3/4" (248mm) 10 7/8" (276mm) LEGS, BLACK 8 3/8" (213mm) 9 1/2" (241mm)
FIGURE 1
“B”
"B"
PAGE 8
FREESTANDING INSTALLATION SPECIFICATIONS (cont.)
FLOOR PROTECTION: (Fig. 2 & 3)
G. Front 6" (152 mm) NOTE: Front floor protection is measured from the door opening. H. Sides 0" (0mm) H. Back 0" (0mm)
NOTE: Floor protector should extend to areas below and 2" (50 mm) to each side of a "tee" when used (See Fig. 6).
CLEARANCE TO COMBUSTIBLES:
INTERIOR VERTICAL FLUE INSTALLATION
Figures 2 & 3
A Sidewall to unit 9" - (229 mm) B Backwall to unit 11" - (279 mm) C Corner wall to unit 2" - ( 51 mm) D Flue vent/chimney 3" - ( 76 mm)
NOTE: Dimension "C" , corner to unit, and "B", backwall to unit, will vary depending on the type and brand of pellet vent or interior connector used. Always maintain the "D" dimension, pellet vent/interior connector clearance, when installing this unit. Check your pellet vent/interior connector instructions for information on its size and clearance required to comustibles. NOTE: Singlewall interior connectors require a minimum 3" clearance to combustibles.
HORIZONTAL THROUGH THE WALL INSTALLATION OR VERTICAL EXTERIOR INSTALLATION
Figures 2 & 3
A Sidewall to unit 9" - (229 mm) B Backwall to unit 3" - ( 76 mm) C Corner Wall to unit 2" - ( 51 mm) D Flue vent/chimney 3" - ( 76 mm)
VERTICAL PIPE ADAPTER
3" Pellet Vent 6" Stovepipe
9" - (229 mm) 9" - (229 mm) 7" - (178 mm) 9" - (229 mm) 2" - ( 51 mm) 2" - ( 51 mm) 3" - ( 76 mm) 3" - ( 76 mm)
SIDEWALL
BACKWALL
B
A
D
G
H
H (0")
FIGURES 2 & 3
PAGE 9
CORNER WALL
CORNER WALL
C
H
H (0")
C
G
HORIZONTAL CORNER INSTALLATION
OPTIONAL AIR INTAKE
PELLET VENT
CHIMNEY CAP
FIGURE 4
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door or window that opens, or any opening into a building.
A minimum of 2 feet (610 mm) from any adjacent building.
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 10
VERTICAL EXTERIOR FLUE SYSTEM
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
PELLET VENT
OPTIONAL
6" MIN.
(152mm)
FIGURE 5
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door or window that opens, or any opening into a building.
A minimum of 2 feet (610 mm) from any adjacent building.
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 11
INSIDE VERTICAL INSTALLATION
WITH ROOF TERMINATION
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
PELLET VENT
3" MIN. (76MM)
OPTIONAL
6" MIN.
(152mm)
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
FIGURE 6
NON-COMBUSTIBLE MATERIAL TO EXTEND UNDER TEE
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door or window that opens, or any opening into a building.
A minimum of 2 feet (610 mm) from any adjacent building.
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 12
HEARTH STOVE INSTALLATION INTO EXISTING
MASONRY & ZERO CLEARANCE (METAL) FIREPLACE
SEAL COVER PLATE TO CHIMNEY WITH SILICONE SEALER.
POSITIVE CONNECTION (COMPLETE RELINE)
3" STAINLESS STEEL SINGLE
WALL PIPE OR FLEXIBLE LINER CAN BE USED. (SEE NOTE BELOW).
SINGLE WALL TEE CAN BE USED AS AN OPTION.
BLOCK-OFF PLATE OR
NON-COMBUSTIBLE MATERIAL MAY BE USED AT THE FIREPLACE DAMPER LOCATION. THIS SEAL MUST BE AIRTIGHT. (SEE BELOW)
TERMINATION OF
12"
DIRECT CONNECTION.
OPTIONAL
6" MIN.
(152mm)
NOTE: Masonry fireplace installations require a direct connection or positive (complete reline) connection to the
chimney flue. With a direct connection a block-off plate made of metal or other non-combustible material (i.e. Kaowool or high temperature fiberglass insulation) must be used at the damper location and sealed airtight. The singlewall pipe or flexible liner must extend past the block-off plate or insulation by one (1) foot (305 mm) or to the first flue tile if the chimney has a tile lining.
With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate is required at the top of the chimney. A positive connection (complete reline) is recommended for ease of cleaning. Zero clearance (metal) fireplace installations require a complete reline to top of chimney.
FIGURE 7
PAGE 13
VERTICAL INSTALLATION INTO EXISTING
FACTORY BUILT CHIMNEY
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
Flashing
24" Min. (610mm)
OPTION 1. Wall Or Ceiling Thimble
OPTION 2. Firestop With 3" (76mm) Clearance
Keep Clearance Specified By Factory Built Chimney Manufacturer
6" Min.
(152mm)
3" Min. (76mm)
Pellet Vent To Factory Built Adaptor Required
Pellet Vent
Tee With Clean Out Cover
Optional Combustion Air Intake With 90˚ Elbow Or Hood
Non-Combustible Material To Extend Under The Tee
FIGURE 8
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door or window that opens, or any opening into a building.
A minimum of 2 feet (610 mm) from any adjacent building.
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
PAGE 14
Loading...
+ 30 hidden pages