Avalon Firestyles 1080 CF User Manual

1080 CF
Gas Fireplace
Tested and Listed by
OMNI-Test Laboratories, Inc.
Report # 028-F-81-5
ANSI Z21.88a-2007
Built-In Direct Vent Fireplace
Natural Gas or Propane
Residential or Mobile Home
Bedroom Approved
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Installation Manual
Installer: After installation give this manual to the home-
owner and explain operation of this heater.
Copyright 2008, T.I. $10.00 100-01193_003 4090807
4800 Harbour Pointe Blvd. SW
Mukilteo, WA 98275
2 Introduction
Overview
This manual details the installation requirements for the 1080 CF fireplace. For operating and maintenance instructions, refer to the 1080 CF Owner's Manual (part # 100-
01194).
Listing Details
This appliance was listed by OMNI Test Labs to ANSI Z21.88 - report # 028-F-81-5. The listing label is attached to the appliance near the gas control valve. A copy is shown to the right.
ICBO Approval
This appliance was listed by OMNI-Test Laboratories - ICBO # TL130.
Massachusetts Approval
This manual has been submitted to the Massachusetts Board of State Examiners of Plumbers and Gas Fitters
National Fireplace Institute
Figure 1
© Travis Industries 4090807 100-01193_003
Table of Contents 3
Introduction
Overview.................................................................2
Listing Details..........................................................2
Safety Precautions
Safety Precautions...................................................4
Features and Specifications
Installation Options...................................................6
Specifications..........................................................6
Dimensions.............................................................6
Installation
Packing List.............................................................7
Additional Items Required..........................................7
Installation Overview ................................................. 7
Recommended Installation Procedure .........................8
Massachusetts Requirements ..................................... 9
Preparing the Fireplace Stand-offs .............................. 10
Fireplace Placement Requirements.............................12
Clearances...........................................................12
Raised Fireplaces .................................................12
Minimum Framing Dimensions ................................13
Framing Dimensions - Corner Installations................14
Nailing Brackets....................................................15
Gas Line Requirements.............................................16
Gas Line Connection .............................................16
Gas Inlet Pressure ................................................16
Battery Pack – Wireless Wall Switch Installation ...........19
Battery Installation ................................................22
Remote Synchronization............................................23
Synchronizing the Remote and Wireless Wall Switch ......................24
Using the Reset Rod to Activate the Receiver Module ......................25
Installation (continued)
Vent Requirements .................................................. 26
Approved Vent...................................................... 26
Altitude Considerations..........................................26
Vent Clearances...................................................27
Vent Installation....................................................27
Approved Vent Configurations:
Horizontal Termination (1 90° Elbow) ........................29
Horizontal Termination (3 90° Elbows)....................... 30
Vertical Termination (0, 2, or 4 45° Elbows) ...............31
Vertical Termination (2 90° Elbows) .......................... 32
Termination Requirements......................................... 33
Hearth Requirements ............................................... 34
Hearth Requirements – Recessed Hearth ................35
Facing Requirements ............................................... 36
Non-Combustible Facing........................................37
Mantel Requirements................................................ 39
Finalizing the Installation
Air Shutter Adjustment.............................................. 41
Glass Frame Removal and Installation........................ 42
Log Set Installation .................................................. 43
LP Conversion Instructions ....................................... 51
Fireback Installation ................................................. 56
Andiron Installation................................................... 58
Power Heat Duct Installation...................................... 59
Index
Index...................................................................... 60
© Travis Industries 4090807 100-01193_003
4 Safety Precautions
Safety Warnings:
Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
This unit must be installed by a qualified installer to prevent the possibility of an explosion.
This appliance must be installed in accordance with all local codes, if any; if not, in U.S.A. follow ANSI
Z223.1 and NFPA 54(88).
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4. This appliance may be installed in Manufactured Housing only after the home is site located.
All exhaust gases must be vented outside the structure of the living-area. Combustion air is drawn from outside the living-area structure. The venting must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
Notify your insurance company before hooking up this fireplace.
The room heater should be inspected before use and at least annually by a qualified service person.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
The instructions in this manual must be strictly adhered to. Do not use makeshift methods or compromise in the installation. Improper installation will void the warranty and safety listing.
This heater is approved for use with natural gas (NG) or propane (LP). Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard. Direct questions about the type of fuel used to your dealer. Check the label and flame adjust knob on the gas control valve.
Contact your local building officials to obtain a permit and information on any installation restrictions or inspection requirements in your area.
If the flame becomes sooty, dark orange in color, or extremely tall, do not operate the heater. Call your dealer and arrange for proper servicing.
It is imperative that control compartments, screens, or circulating air passageways of the heater be kept clean and free of obstructions. These areas provide the air necessary for safe operation.
Do not operate the heater if it is not operating properly in any fashion or if you are uncertain. Call your dealer for a full explanation of your heater and what to expect.
Do not store or use gasoline or other flammable liquids in the vicinity of this heater.
Do not operate if any portion of the heater was submerged in water or if any corrosion occurs.
Do not place clothing or other flammable items on or near the heater. Because this heater can be
controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
Light the heater using the built-in piezo igniter. Do not use matches or any other external device to light your heater.
Never remove, replace, modify or substitute any part of the heater unless instructions are given in this manual. All other work must be done by a trained technician. Don't modify or replace orifices.
The viewing glass should be opened only for lighting the pilot or conducting service.
Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
© Travis Industries 4090807 100-01193_003
Safety Precautions 5
Safety Warnings (continued):
Allow the heater to cool before carrying out any maintenance or cleaning.
Operate the heater according to the instructions included in this manual.
If the main burners do not start correctly turn the gas off at the gas control valve and call your dealer for
service.
The pilot flame must contact the thermopile and thermocouple. If it does not, turn the gas control valve to "OFF" and call your dealer.
This unit is not for use with solid fuel.
Do not place anything inside the firebox (except the included fiber logs).
If the fiber logs become damaged, replace with Travis Industries log set.
Do not throw this manual away. This manual has important operating and maintenance instructions
that you will need at a later time. Always follow the instructions in this manual.
Do not touch the hot surfaces of the heater. Educate all children of the danger of a high-temperature heater. Young children should be supervised when they are in the same room as the heater.
Due to the high temperature, the heater should be located out of traffic and away from furniture and draperies.
Instruct everyone in the house how to shut gas off to the appliance and at the gas main shutoff valve. The gas main shutoff valve is usually next to the gas meter or propane tank and requires a wrench to shut off.
Travis Industries, Inc. grants no warranty, implied or stated, for the installation or maintenance of your heater, and assumes no responsibility of any consequential damage(s).
© Travis Industries 4090807 100-01193_003
6 Features and Specifications
Installation Options
Residential or Mobile Home
Straight or Corner Placement
Flush or Recessed Face
Raised or Floor Placement
Internal or External Chase
Horizontal or Vertical Vent
Bedroom Approved
Specifications
Natural Gas Propane
Maximum BTU Input Per Hour 36,000 36,000 Minimum BTU Input on Low 20,800 23,500
Dimensions
8-5/8" Outside Diameter
27" ***
43" **
41-1/2" **
12-1/4"*
2"
56-3/4" **
NOTE: 2" Clearance to the Back of the Fireplace
NOTE: 4" Clearance to the Sides of the Fireplace
Tabs for lifting handles (sku 98500711)
25"*
49-1/2" **
32-3/4" **
37.5"
1-1/2" **
Weight: 250 Lbs.
49.5"
* Includes the required 2" clearance.
5"
** Includes the 1-1/2" standoff below the baseplate. *** Does not include the required 4" clearance to each side.
Base of Fireplace (bottom of standoffs)
Figure 2
© Travis Industries 4090807 100-01193_003
Packing List
AAAAAAAAA
AAAAAAAAA
AAAAAAAAA
AAAAAAAAA
Installation (for qualified installers only) 7
Propane Conversion Kit (orifice, rate screw)
Log Set
Remote Control and Wireless Wall Switch
Reset Rod
Battery Box with 12’ Wire Lead
Door Latch Tool
Andiron Brackets
Additional Items Required
1080/36 CF Direct Vent (available only from Travis Industries – see page 26 for part numbers)
Gas Line Equipment (shutoff valve, pipe, etc.)
Installation Overview
All requirements below must be met.
See the section "Mantel Requirements"
See the section See the section "Control Panel Installation"
NOTE: Control wire is 12' long.
"Vent Requirements"
Drywall (or other combustible)
Side Wall
Non-combustible facing ­(included) see the section "Facing Requirements"
See the section "Hearth Requirements"
11"
Min.
See the section "Minimum Framing Dimensions"
Nailing Brackets
© Travis Industries 4090807 100-01193_003
Figure 3
8 Installation (for qualified installers only)
Recommended Installation Procedure
1. Frame the opening for the fireplace. We suggest omitting the framing above the header to allow for easier vent installation.
2. Place the fireplace in place, making sure it is level and plumb. Attach using the nailing brackets.
3. Install the vent, gas line, electrical connection, and battery box.
4. Install the framing above the header.
5. Install the hearth (if applicable).
6. Install the included non-combustible facing.
7. Install the facing.
8. Install the mantel (if applicable).
9. Finalize the installation (see page 40).
© Travis Industries 4090807 100-01193_003
Installation (for qualified installers only) 9
Massachusetts Requirements
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
© Travis Industries 4090807 100-01193_003
10 Installation (for qualified installers only)
Preparing the Fireplace Stand-offs
This appliance is shipped with the header and side stand-offs in the retracted position. These stand­offs must be placed in their upright position prior to installing the fireplace
WARNING: Failure to correctly erect the stand-offs may lead to a serious fire-hazard and will void the listing and warranty of this fireplace.
Side Stand-Offs
Bend the side stand-off until it is flat.
a
Remove the two screws behind the side stand-off and place them aside.
Bend the stand-off return back until
b
the holes in the stand-off line up with the holes on the side of the fireplace.
Secure the stand-off with two
c
screws removed earlier.
Repeat steps "a", "b", and "c"
d
for the opposite side.
Figure 4
© Travis Industries 4090807 100-01193_003
Header Stand-Off
Installation (for qualified installers only) 11
Rotate the header standoff until
a
the side braces lock into place.
The notch in the side brace slides over this screw.
d
Remove the screw below the center header standoff. Rotate the lower standoff upwards and attach using the same screw.
Rotate the header brackets up
b
Un-fold the side of the header
c
standoff until it is flat (both sides).
Figure 5
© Travis Industries 4090807 100-01193_003
12 Installation (for qualified installers only)
Fireplace Placement Requirements
The fireplace requires a 4" clearance from the sides and 2” from the back of the fireplace to the
framing members. No material (insulation, framing, etc.) may be placed into this area.
Fireplace must be placed in a room with a minimum 96” ceiling.
Fireplace must be placed directly on the sub-floor or wood platform (not on linoleum or carpet).
Fireplace must be installed on a level surface capable of supporting the fireplace and vent.
This heater may be placed in a bedroom. Please be aware of the large amount of heat this
appliance produces when determining a location.
Clearances
When installed, walls in front of the fireplace must be a minimum 11” from the glass (5" from
the side stand-offs - see Figure 3).
Due to the high temperature, the heater should be located out of traffic and away from furniture
and draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
The fireplace (and hearth, if desired) may be placed on a platform designed to support the
fireplace 250 Lbs.) and vent.
Minimum 60 Fireplace
Enclosure Height.
Enclosure must also
meet 6 vent clearance.
Optional Raised Hearth
(see Hearth Requirements” for details)
Platform
Figure 6
© Travis Industries 4090807 100-01193_003
Installation (for qualified installers only) 13
Minimum Framing Dimensions
NOTE: Do not build into this area - it must be left clear to provide adequate clearance for the vent. A maximum 3-1/2
depth is allowed in this 14 wide area centered along the front of the fireplace.
Minimum 60 Fireplace
Enclosure Height.
Enclosure must also meet
6 vent clearance.
14” Min.
3.5 Max.
25
56-3/4
50
Figure 7
© Travis Industries 4090807 100-01193_003
14 Installation (for qualified installers only)
Framing Dimensions - Corner Installations
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all
clearances still apply).
Minimum 2"
21.25"
(approximate)
Clearance
(approximate)
59"
Figure 8
© Travis Industries 4090807 100-01193_003
Nailing Brackets
Use screws or nails to secure the fireplace to the
framing with the six nailing brackets.
Installation (for qualified installers only) 15
1
2
4
3
5
6
7
Figure 9
© Travis Industries 4090807 100-01193_003
16 Installation (for qualified installers only)
Gas Line Requirements
MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a “T” handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas
log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the
requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure
testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of
the gas control valve to make sure the correct fuel is used (see illustration on page 4).
An additional shut-off valve is required. It must be accessible and within 6’ of the fireplace.
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts
a licensed plumber/gasfitter).
A shutoff valve is built into the fireplace. It is located on the left side of the fireplace and acts as the gas
inlet connection. After installing the gas line (and testing), remove the cover plate shown below and turn the gas shutoff valve to “ON”.
The gas inlet is located
5.5" above the base of the fireplace.
Gas Line
(1/2" M.P.T.)
Gas Inlet Pressure
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should
Built-In Shut-off Valve
7"
4"
Standard Input Pressure
Natural Gas 7" W.C. (1.74 kPA) Propane 13" W.C. (2.73 kPA)
adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
LEFT SIDE OF
FIREPLACE
Gas Inlet
Figure 10
Shutoff Valve
© Travis Industries 4090807 100-01193_003
Installation (for qualified installers only) 17
Required Electrical Connection
Make sure power to the heater has been turned off prior to installation (disable the breaker).
Do not connect 110-120 VAC to the gas control valve or the on/off circuit on this fireplace.
This fireplace utilizes 110 VAC to power the receiver module and intermittent pilot system. A separate battery box is included to provide power for the adjustable flame height and in case of power outages (see “Battery Pack – Wireless Wall Switch Installation” on page 19 for details).
The electrical line to the grounded receptacle inside the fireplace must be installed by a
qualified installer and must meet all local codes. The fireplace must be properly grounded in accordance with local codes (or ANSI/NFPA 70-1987).
Make sure the household breaker is shut off prior to working on any electrical lines.
The fireplace must be properly grounded in accordance with local codes (or ANSI/NFPA 70-1987)
The electrical line must be a min. 14 gauge, and supply 120 Volts at 60 Hz (2 Amps)
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Attach an electrical line to the receptacle inside the control box (see the illustration below).
Make sure to connect the ground wire to the grounding tab on the receptacle (this grounds the fireplace).
These wires are for the
optional accent light.
Control Box
Cover Plate
Romex Connector
Grounded 110V
Attacfh the electrical line,
including the grounding wire,
to this receptacle.
Power Supply
© Travis Industries 4090807 100-01193_003
18 Installation (for qualified installers only)
Accent Light Electrical Connection
Make sure power to the heater has been turned off prior to installation (disable the breaker).
Do not connect 110-120 VAC to the gas control valve or the on/off circuit on this fireplace.
The electrical line must be installed by a qualified installer and must meet all local codes.
The optional accent light requires a 110v circuit wired through a junction box to the fireplace.
See the illustration below for details.
The wiring for the accent light is best installed prior to drywall installation around the fireplace. All electrical connections must be made by a qualified installer and must meet all local codes.
Do not route the wires over the top
of the fireplace.
Power Supply
(110v ac)
Junction Box
(not supplied)
Rheostat (included)
Cover Plate (included)
Insulated Wire (Romex)
Cover Plate on Control Box
(see instructions below)
Power Supply
Knob (included)
Remove one of the knock-outs on the cover
plate and pass the wiring through the cover
plate (use the romex connector included with
the accent light). Attach the hot and common
wire from the accent light switched power
supply to the black and white wire leading from
the molex connector. Attach the ground wire to
the grounding tab on the receptacle.
Common
(white)
Hot
(black)
Ground (green)
Wiring Schematic
Rheostat Junction Box
Common
(white)
(black)
Ground (green)
Control Box
Romex
Connectors
Fireplace Junction Box
Hot
Accent Lights
Accent
Light
Molex
Connector
Cover Plate
Fireplace Power Supply
(attached to receptacle)
Accent Light Switched
Power Supply
© Travis Industries 4090807 100-01193_003
Loading...
+ 42 hidden pages