AUX DC Inverter Free Match 50HZ R410A
1
SERVICE MANUAL
(DC Inverter Free Match R410a)
AUX DC Inverter Free Match 50HZ R410A General description
2
Table of Contents
Part 1 General information ..................................................................................................3
Part 2 Indoor unit .................................................................................................................7
Part 3 Free Match outdoor unit ......................................................................................... 68
Part 4 Trouble shooting ..................................................................................................... 96
Part 5 Controller .............................................................................................................. 124
Part 6 Sensor resistance table ....................................................................................... 135
AUX DC Inverter Free Match 50HZ R410A General description
3
Part 1General information
1. Nomenclature
Outdoor Unit
Indoor Unit
AUX DC Inverter Free Match 50HZ R410A General description
4
2. Unit Appearance
Picture of the indoor unit
AUX DC Inverter Free Match 50HZ R410A General description
5
Picture of the outdoor unit
AUX DC Inverter Free Match 50HZ R410A General description
6
*Note:
① All of the above indoor unit can be freely matched and combined,but must be installed strictly
according to the above table.Orthe cooling capacity and stability would be decreased.
② The wall mounted indoor unit(F series) cannot be matched with the 36/42K outdoor unit.
AUX DC Inverter Free Match 50HZ R410A Indoor unit
7
Part 2 Indoor unit
Four-way cassette ...............................................................................................................5
Ceiling & floor type ............................................................................................................ 22
Low ESP Ducted Type ....................................................................................................... 35
Wall Mounted Type ............................................................................................................ 49
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
8
Four-way cassette
1. Function Introduction .....................................................................................................9
2. Specification .................................................................................................................. 10
3. Capacity Amendment .................................................................................................... 11
4. Dimension ...................................................................................................................... 14
5. Electrical Diagram ......................................................................................................... 14
6. Installation ..................................................................................................................... 15
7. Explode view .................................................................................................................. 20
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
9
1. Function Introduction
Error code display function
Fresh air function preserved
Installation instruction plate is available
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
10
2. Specification
Electric Data
Power Supply
Tube Outside Dia.&Material
Coil Length x Height x Width
Performance
Air Flow Volume
Note:
1. Cooling capacity test Condition:(27℃DB,19℃WB Indoor/35℃DB,24℃WB Outdoor);
Heating capacity test Condition:(20℃DB Indoor/7℃DB,6℃WB Outdoor);
connecting pipe length: 5M.
2. Datas may be changed withunit improvement. We keep the right to change the datas or specifications
withoutprior notice, please follow the datas listed on the nameplate.
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
11
3. Capacity Amendment
3.1 Running range
3.2Amendment coefficient of cooling capacity under different indoor/outdoor
temperature(K1)
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.3 Amendment coefficient of heating capacity under different indoor/outdoor DB/WB
temperature K2
Actualheatingcapacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
12
3.4 Amendment coefficients of heating and cooling capacity under different height
drop K3
Different Cooling Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit - Height of Indoor Unit
Different Heating Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit - Height of Indoor Unit
3.5 Correction capability
Cooling capacity = nominal cooling capacity xK1xK3
Heating capacity = nominal heating capacity xK2xK3
3.6 Equivalent Pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate the pressure
loss.
Equivalent pipe length EL (m)
Equivalent pipe lengthEL(m)
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
13
Bend and Oil Loop Conversion tablet
Equivalent Pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
AMCA-H09/4R1AActual Pipe length is 25 meters, Gas pipe diameter is 9.52mm. If there’s 5 bends and 2
oil loops during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
◇Specification of Connection Pipe for Indoor Unit and Outdoor Unit
Extra R410a per meter when the pipe length is
more than 5 meter (kg)
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is
necessary. If the pipe length is more than this then you should charge more refrigerant into the system
according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased. And the more
bend quantity, the resistance in the piping system would be bigger, then the cooling and heating
capacity would be decreased even lead to compressor broken. We suggest you to use the shortest
connection pipe according to the pipe length parameter in this manual.If the height difference between
outdoor and indoor unit is more than 5m, an oil trap should be installed in the gas pipe for every 10
meters.
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
14
4. Dimension
AMCA-H09/4R1A, AMCA-H12/4R1A, AMCA-H18/4R1A
5. Electrical Diagram
AMCA-H09/4R1A, AMCA-H12/4R1A, AMCA-H18/4R1A
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
15
6. Installation
6.1 Preparation before installation
6.1.1Please buy following spare parts from your local market before installation
Adhesive belt (big size) 5 pcs, (small size) 5 pcs
Heat insulation material used to connect copper pipe (PE foam material, its thickness is more than 8mm)
Power cable, electrical wire between indoor and outdoor unit(Must be in accordance with the wire diameter
in the wiring diagram)
Acetylene cylinders, oxygen cylinders (when longer pipe used it should be welded)
One set pipe cut machine. (cut copper pipe)
Refrigerant cans, electronic balance (when longer pipe used additional gas should be charged)
Pressure gauges, pipe clamp, welding torch, 2B silver electrode
Wrench 2 pcs, one of them is with adjustable torque wrench(42N.m,65N.m,100N.mm)
Nitrogen cylinder (in order to prevent oxidation when welding, using Nitrogen to replace the air)
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
16
6.3 Installation precaution
◇ Hanging location should be able to support the unit’s weight, there should be no increasement in
noiseand vibration. If the hanging location needs reinforcement, it should be reinforced before
installation;
◇ Choose the space above the ceiling that can put the indoor unit inside;
◇ The location should be easy for drainage;
◇ The unit should not be installed in the heat source, steam or oil mist source (such as machine room,
kitchen, laundry room, mechanical workshop, etc.)
◇ Choose the location at least 1 meter away from TV and radio, in order to avoid interference to them
◇ There should be certain distance between indoor unit and obstaclesfor maintenance;
◇ In case of leakage of refrigerant, units should immediately stop running, and contact with maintenance
personnel in time. There must be no fire at the site, because the refrigerant will turn to harmful gas
when get to the fire.
6.4 The distance between indoor unit and obstacle
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
17
6.5 Indoor unit suspension
◇ Select the suspension foundation:
The suspension foundation is a structure of either wooden frame or reinforced concrete. It must be
firm and reliable to bear at least 4 times weight of itself and capable of bearing vibration for long
periods.
◇ Fixing of suspension foundation:
◇ Fix the suspension bolts either as shown in the picture or by a steel or wooden bracket.
◇ If this unit is installed on a sloping ceiling, a cushion block should be installed between the ceiling and
the air outlet panel, in order to ensure that the unit is installed on a level surface.
This is as shown in the drawing as follows:
◇ Adjust the relative position of the suspension hook on the suspension bolt so that the unit can be in
level position in all directions. Check with a level gauge after installation to ensure that the indoor unit
is horizontal, otherwise it will cause water leakage, air leakage etc.
◇ Tighten the bolt and ensure that four hooks are in close contact with the nuts and washers,to fix the
indoor unitunder the ceiling.
◇ After the unit is installed ensure it is secure and does not shake or sway.
◇ Ensure that the centre of the indoor unit is in alignment with the centre of the opening in the ceiling.
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
18
6.6 Drainage pipe installation
The drainage pipe should be properly insulated to prevent the generation of condensation.Heat insulation
material: the thickness of rubber insulation pipe should be more than 8mm
◇ Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
◇ The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water left in
the pipe will drain back and may overflow the drain tray causing water leakage. For this reason please
install the drain pipe as shown
◇ When draining multiple units into a common drain line, this common drain should be installed about
100mm below each units drain outlet, as shown in the drawing.
◇ When finish installation please carry out the drainage test to ensure that the water flow through the
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
19
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage. If the unit
is installed in the newly built house, strongly recommend that this test taken before the ceiling
installation. Even it is the heating only unit, this test is unavoidable.
6.7 Panel installation
As to the MB13 panel please refer to the following picture, the panel has four hooks which attach to
corresponding hangers on the unit and the panel should be positioned using these first. The panel is then
fixed into position by four bolts which are accessed through the four corner panels on the grille.
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
20
7. Explode view
AMCA-H09/4R1A, AMCA-H12/4R1A, AMCA-H18/4R1A
AUX DC Inverter Free Match 50HZ R410A Four-way cassette
21
Return-air grille assembly
Cover for electric components
QRD-SN3F(18-60)K(485)-SYE1(SY)
Evap outlet tube assembly
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
22
Ceiling & floor type
1. Function Introduction ......................................................... Error! Bookmark not defined.
2. Specfication ................................................................................................................... 24
3. Capacity amendment .................................................................................................... 25
4. Dimension ...................................................................................................................... 28
5. Electrical Diagram ......................................................................................................... 29
6. Installation ..................................................................................................................... 30
7. Explode view .................................................................................................................. 33
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
23
1. Function Introduction
Error code display function
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
24
2. Specfication
Tube Outside Dia.&
Material
Note:
1.Cooling capacity test Condition:(27℃DB,19℃WB Indoor/35℃DB,24℃WB Outdoor);
Heating capacity test Condition:(20℃DB Indoor/7℃DB,6℃WB Outdoor);
connecting pipe length: 5M.
2.Datas may be changed with unit improvement. We keep the right to change the datas or specifications
withoutprior notice, please follow the datas listed on the nameplate.
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
25
3. Capacity amendment
3.1 Running range
3.2 Amendment coefficient of cooling capacity under different indoor/outdoor
temperature(K1)
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.3 Amendment coefficient of heating capacity under different indoor/outdoor
temperature K2
Actualheatingcapacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
26
3.4 Amendment coefficients of heating and cooling capacity under different height
dropK3
Different Cooling Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit - Height of Indoor Unit
Different Heating Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit - Height of Indoor Unit
3.5 Correction capability
Cooling capacity = nominal cooling capacity xK1xK3
Heating capacity = nominal heating capacity xK2xK3
3.6 Equivalent Pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate the
pressure loss.
Equivalent pipe length EL (m)
Equivalent pipe lengthEL(m)
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
27
Bend and Oil Loop Conversion tablet
Equivalent Pipe length L=Actual Pipe length L+ Bend Qty× Equivalent pipe bend length+ Oil Loop
Qty × Equivalent Oil Loop length
Sample:
AMCF-H09/4R1Actual Pipe length is 25 meters, Gas pipe diameter is 9.52mm. If there’s 5 bends and
2 oil loops during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
◇Specification of Connection Pipe for Indoor Unit and Outdoor Unit
Extra R410a per meter when the pipe
length is more than 5 meter (kg)
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is
necessary. If the pipe length is more than this then you should charge more refrigerant into the system
according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased. And the
more bend quantity, the resistance in the piping system would be bigger, then the cooling and heating
capacity would be decreased even lead to compressor broken. We suggest you to use the shortest
connection pipe according to the pipe length parameter in this manual.If the height difference between
outdoor and indoor unit is more than 5m, an oil trap should be installed in the gas pipe for every 10
meters.
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
28
4. Dimension
AMCF-H09/4R1, AMCF-H12/4R1, AMCF-H18/4R1
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
29
5. Electrical Diagram
AMCF-H09/4R1, AMCF-H12/4R1, AMCF-H18/4R1
AUX DC Inverter Free Match 50HZ R410A Ceiling & Floor Type
30
6. Installation
6.1 Preparation and equipments before installation
6.1.1Please buy following spare parts from your local market before installation
Adhesive belt (big size) 5 pcs, (small size) 5 pcs
Heat insulation material used to connect copper pipe (PE foam material, its thickness is more than 8mm)
Power cable, electrical wire between indoor and outdoor unit(Must be in accordance with the wire diameter
in the wiring diagram)
Acetylene cylinders, oxygen cylinders (when longer pipe used it should be welded)
One set pipe cut machine. (cut copper pipe)
Refrigerant cans, electronic balance (when longer pipe used additional gas should be charged)
Pressure gauges, pipe clamp, welding torch, 2B silver electrode
Wrench 2 pcs, one of them is with adjustable torque wrench(42N.m,65N.m,100N.mm)
Nitrogen cylinder (in order to prevent oxidation when welding, using Nitrogen to replace the air)