AUX AL-H12/4R1D, AL-H12/4R1DU, AL-H18/4R1D, AL-H18/4R1DU, ALCa-H12A4/R1C7-B7 Service Manual

...
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
1
Service Manual
(T1 , 50Hz , R410a , ON/OFF)
Version:01 2017/01
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
2
Content
Part 1. General information ............................................................ 3
Part 2. Indoor unit ............................................................................ 6
Part 3 Universal outdoor unit ....................................................... 83
Part 4 Trouble shooting ............................................................... 116
Part 5 Controller .......................................................................... 146
Part 6. Sensor resistance table .................................................. 155
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
3
Part 1. General information
1.Nomenclature .................................................................................... 4
2.Unit appearance ................................................................................ 5
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
4
1.Nomenclature
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
5
2.Unitappearance
Series
Picture of the indoor unit
Four-way
Cassette
12k Btu/h
18k Btu/h
24k Btu/h
36k Btu/h
48k Btu/h
60k Btu/h
Ceiling &Floor
18k Btu/h
24k Btu/h
36k Btu/h
48k Btu/h
60k Btu/h
Mid ESP
Duct
18k Btu/h
24k Btu/h
36k Btu/h
48k Btu/h
60k Btu/h
Series
Picture of the indoor unit
Universal
outdoor
unit
12k Btu/h
18k Btu/h
24k Btu/h
36k Btu/h
48k Btu/h
60 k Btu/h
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
6
Part 2. Indoor unit
Four-way cassette................................................................................. 7
Ceiling & floor type ............................................................................. 35
Middle static pressure duct type ....................................................... 61
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
7
Four-way cassette
1.Feature ............................................................................................................................ 8
2.Specfication .................................................................................................................... 9
3.Capacity Amendment .................................................................................................... 17
4.Demension .................................................................................................................... 19
5.Electrical wiring and connection .................................................................................... 20
6.Installation ..................................................................................................................... 25
7.Explode view ................................................................................................................. 31
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
8
1.Function introduction
Type
Item
ALCA-H**R1AA/AlCA-H**R1E
ALCA-H**R1AA
12/4
18/4
24/4
36/4
36/5
48/5
60/5
Protection
High pressure protection
- - -
Low pressure protection
- - -
Compressor overloading protection
High exh. temperate protection
- - -
Phase protection (Phase-loss, phase- reverse)
- - -
Over-heating protection
Anti-freezing protection
Sensor failure alarm
Failure code display
Comfort
Cooling
Heating
3-Speed
Auto-restart(Optional)
Anti-cold wind
Afterheat wind blowing
Timing ON/OFF
Operation
Time display
Operation mode display
Fan speed display
Defrost display
Timing ON/OFF display
Wind angle display
Sleeping mode display
Running
Auto start
Dehumidifying
Auto defrost
Ventilation function
Low ambient temperature cooling
Health Washable air filter
Fresh air interface
Installation
Left/right drainage(optional)
Left/right pipe connection(optional)
Down/back air suction(optional)
Installation indicating board
Remarks: Stands for “YES” Stands for “NO”
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
9
2.Specfication
Model Indoor Unit
ALCA-H12/4R1AA
ALCA-H18/4R1AA
Panel
MB13
MB13
Outdoor Unit
AL-H12/4R1D(U)
AL-H18/4R1D(U)
Factory Model Indoor Unit
ALCa-H12A4/R1C7-B7
ALCa-H18A4/R1C7-B7
Panel
MB13
MB13
Outdoor Unit
AL-H12A4/R1(T)-B7
AL-H18A4/R1(T)-B7
Code Indoor Unit
16106022000055
16106022000054
Panel
16108004000004
16108004000004
Outdoor Unit
16107022000017
16107022000019
Power Supply
V~,Hz,Ph
220~240,50,1
220~240,50,1
Capacity Cooling
Btu/h
12000
18000
kW
3.60
5.30
Heating Btu/h
13500
20000
kW
3.90
5.80
Electric Data
Rated Cooling Power Input
kW
1.19
1.76
Rated Heating Power Input
kW
1.20
1.80
Rated Cooling Current
A
5.49
8.08
Rated Heating Current
A
5.63
8.27
Performance EER
W/W
3.03
3.01
COP
W/W
3.25
3.22
Indoor Fan Motor
Model
YDK25-6E1
YDK30-6E1
Brand
WELLING/Sinjun
WELLING/Sinjun
Output Power x Fan Quantity
W
25*1
30*1
Capacitor
uF
1.5
2.5
Speed (Hi/Mi/Lo)
r/min
850/750/650
920/850/750
Indoor Coil
Number Of Rows
2
2
Tube Pitch(a)x Row Pitch(b)
mm
20.5×12.7
20.5×12.7
Fin Pitch
mm
1.5
1.5
Fin Material
Hydrophilic aluminum fin
Tube Outside Dia.and Type
mm
φ7 Inner grooved
φ7 Inner grooved
Coil Length x Height x Width
mm
1160×184.5×25.4
1160×184.5×25.4
Heat Exchanging Area
m2
4.32
5.76
Indoor Unit Indoor Air Flow
(Hi/Mi/Lo)
m3/h
620/496/434
900/720/630
Noise Level(Hi/Mi/Lo)
dB(A)
41/38/32
41/38/32
Net Dimension
mm
615×615×263
615×615×263
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
10
(W*H*D)
Packing Dimension (W*H*D)
mm
700×700×330
700×700×330
Net Weight
kg
17.5
18
Gross Weight
kg
21.5
22
Panel
Net Dimension (W*H*D)
mm
650×650×55
650×650×55
Packing Dimension (W*H*D)
mm
700×700×330
700×700×330
Net weight
kg
3
3
Gross weight
kg
5
5
Refrigerant Pipe
Liquid Side
mm
6.35
6.35
Gas Side
mm
12.7
12.7
Max. Refrigerant Pipe Length
m
15
20
Max. Level Difference
m
10
15
Setting Temperature Range
°C
16~32
16~32
Operation Ambient Temperature Range
Cooling
°C
-15~49
-15~49
Heating
°C
-15~24
-15~24
Application Area
m2
13-21
21-35
Connection Wiring Power Wiring( Indoor)
mm2
3×2.5mm2
3×4mm2
Power Wiring( Outdoor)
mm2
/
/
Signal Wiring
mm2
3×2.5mm2+2×1mm2
3×2.5mm2+2×1mm2
Wireless Remote Controller Model Type
YKR-K/001E
YKR-K/001E
Stufing Quantity
20/40/40H
Set
66/137/161
66/137/161
Note:
1. Working condition of the cooling capacity measured: Indoor temperature 27°C DB, 19°C WB;Outdoor 35°C DB, 24°C WB;
2. Working condition of the heating capacity measured: Indoor temperature 20°C DB, 19°C WB;Outdoor 7°C DB, 6°C WB;
3. Parameters above are all measured when the connecting pipe is 5 meters.
4. Parameters above may be modified as product improvement. We keep the right to change the product
specifications without prior notice, please take the parameters listed on the nameplate as criterion.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
11
Model Indoor Unit
ALCA-H24/4R1AA
ALCA-H36/5R1AA
Panel
MB12
MB12
Outdoor Unit
AL-H24/4R1D(U)
AL-H36/5R1D(U)
Factory Model Indoor Unit
ALCa-H24B4/R1EB-B7
ALCa-H36A5/R1EB-B7
Panel
MB12
MB12
Outdoor Unit
AL-H24A4/R1(T)-B7
AL-H36A5/R1(T)-B7
Code Indoor Unit
16106022000053
16106022000056
Panel
16108002000007
16108002000007
Outdoor Unit
16107022000018
16107022000020
Power Supply
V~,Hz,Ph
220~240,50,1
380~415,50,3
Capacity Cooling
Btu/h
24000
36000
kW
7.20
10.60
Heating Btu/h
27500
40000
kW
8.08
11.70
Electric Data
Rated Cooling Power Input
kW
2.39
3.77
Rated Heating Power Input
kW
2.50
3.50
Rated Cooling Current
A
11.06
6.76
Rated Heating Current
A
11.59
6.28
Performance EER
W/W
3.01
2.81
COP
W/W
3.23
3.34
Indoor Fan Motor
Model
XD30A
YDK45-6Q
Brand
WELLING/Sinjun
WELLING/Sinjun
Output Power x Fan Quantity
W
30*1
45*1
Capacitor
uF
2.5
3
Speed (Hi/Mi/Lo)
r/min
500/430/320
650/520/450
Indoor Coil
Number Of Rows
2
2
Tube Pitch(a)x Row Pitch(b)
mm
20.5×12.7
20.5×12.7
Fin Pitch
mm
1.4
1.4
Fin Material
Hydrophilic aluminum fin
Tube Outside Dia.and Type
mm
φ7 Inner grooved
φ7 Inner grooved
Coil Length x Height x Width
mm
2142×205×25.4
2142×205×25.4
Heat Exchanging Area
m2
11.34
12.76
Indoor Unit Indoor Air Flow
(Hi/Mi/Lo)
m3/h
1300/1040/910
1500/1200/1050
Noise Level(Hi/Mi/Lo)
dB(A)
45/42/36
48/45/39
Net Dimension
mm
835×835×250
835×835×250
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
12
(W*H*D)
Packing Dimension (W*H*D)
mm
910×910×310
910×910×310
Net Weight
kg
24
24
Gross Weight
kg
27.5
27.5
Panel
Net Dimension (W*H*D)
mm
950×950×55
950×950×55
Packing Dimension (W*H*D)
mm
1000x1000x100
1000x1000x100
Net weight
kg
5
5
Gross weight
kg
7
7
Refrigerant Pipe
Liquid Side
mm
9.52
9.52
Gas Side
mm
15.88
15.88
Max. Refrigerant Pipe Length
m
30
50
Max. Level Difference
m
15
30
Setting Temperature Range
°C
16~32
16~32
Operation Ambient Temperature Range
Cooling
°C
-15~49
-15~49
Heating
°C
-15~24
-15~24
Application Area
m2
28-47
42-70
Connection Wiring Power Wiring( Indoor)
mm2 / 3×1mm2
Power Wiring( Outdoor)
mm2
3×6mm2
5×4mm2
Signal Wiring
mm2
3×2.5mm2+3×1mm2
2×1mm2
Wireless Remote Controller Model Type
YKR-K/001E
YKR-K/001E
Stufing Quantity
20/40/40H
Set
42/82/92
30/70/79
Note:
1. Working condition of the cooling capacity measured: Indoor temperature 27°C DB, 19°C WB;Outdoor 35°C DB, 24°C WB;
2. Working condition of the heating capacity measured: Indoor temperature 20°C DB, 19°C WB;Outdoor 7°C DB, 6°C WB;
3. Parameters above are all measured when the connecting pipe is 5 meters.
4. Parameters above may be modified as product improvement. We keep the right to change the product
specifications without prior notice, please take the parameters listed on the nameplate as criterion.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
13
Model Indoor Unit
ALCA-H48/5R1AA
ALCA-H60/5R1AA
Panel
MB12
MB12
Outdoor Unit
AL-H48/5R1D(U)
AL-H60/5R1D(U)
Factory Model Indoor Unit
ALCa-H48A5/R1EB-B7
ALCa-H60A5/R1EB-B7
Panel
MB12
MB12
Outdoor Unit
AL-H48A5/R1(T)-B7
AL-H60A5/R1(T)-B7
Code Indoor Unit
16106022000057
16106022000058
Panel
16108002000007
16108002000007
Outdoor Unit
16107022000022
16107022000023
Power Supply
V~,Hz,Ph
380~415,50,3
380~415,50,3
Capacity Cooling
Btu/h
48000
60000
kW
14.00
17.60
Heating Btu/h
53000
63500
kW
15.50
18.50
Electric Data
Rated Cooling Power Input
kW
4.87
5.71
Rated Heating Power Input
kW
5.13
6.00
Rated Cooling Current
A
8.88
10.42
Rated Heating Current
A
9.33
10.88
Performance EER
W/W
2.87
3.08
COP
W/W
3.02
3.08
Indoor Fan Motor
Model
XD80A
XD80A
Brand
WELLING/Sinjun
WELLING/Sinjun
Output Power x Fan Quantity
W
80*1
80*1
Capacitor
uF
3
4
Speed (Hi/Mi/Lo)
r/min
695/585/495
695/585/495
Indoor Coil
Number Of Rows
2
3
Tube Pitch(a)x Row Pitch(b)
mm
20.5×12.7
20.5×12.7
Fin Pitch
mm
1.4
1.4
Fin Material
Hydrophilic aluminum fin
Tube Outside Dia.and Type
mm
φ7 Inner grooved
φ7 Inner grooved
Coil Length x Height x Width
mm
2142×246×25.4
2142×246×25.4
Heat Exchanging Area
m2
15.60
15.60
Indoor Unit Indoor Air Flow (Hi/Mi/Lo)
m3/h
1800/1440/1260
1800/1440/1260
Noise Level(Hi/Mi/Lo)
dB(A)
50/47/41
50/47/41
Net Dimension (W*H*D)
mm
835×835×290
835×835×290
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
14
Packing Dimension (W*H*D)
mm
910×910×350
910×910×350
Net Weight
kg
26.5
26.5
Gross Weight
kg
30.5
30.5
Panel
Net Dimension (W*H*D)
mm
950×950×55
950×950×55
Packing Dimension (W*H*D)
mm
1000x1000x100
1000x1000x100
Net weight
kg
5
5
Gross weight
kg
7
7
Refrigerant Pipe
Liquid Side
mm
9.52
9.52
Gas Side
mm
19.05
19.05
Max. Refrigerant Pipe Length
m
50
50
Max. Level Difference
m
30
30
Setting Temperature Range
°C
16~32
16~32
Operation Ambient Temperature Range
Cooling
°C
-15~49
-15~49
Heating
°C
-15~24
-15~24
Application Area
m2
56-93
64-107
Connection Wiring Power Wiring( Indoor)
mm2
3×1mm2
3×1mm2
Power Wiring( Outdoor)
mm2
5×4mm2
5×4mm2
Signal Wiring
mm2
2×1mm2
2×1mm2
Wireless Remote Controller Model Type
YKR-K/001E
YKR-K/001E
Stufing Quantity
20/40/40H
Set
22/50/55
22/50/55
Note:
1. Working condition of the cooling capacity measured: Inside the room DB temperature 27°C,WB
temperature19°C;Outside of the room DB temperature 35°C,WB temperature 24°C;Working condition of the heating capacity measured:Inside the room DB temperature 20°C,Outside of the room DB temperature 7°C,WB temperature 6°C.
2. Parameters above are all measured when the connecting pipe is 5 meters.
3. Parameters above may be modified as product improvement. We keep the right to change the product
specifications without prior notice, please take the parameters listed on the nameplate as criterion.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
15
Model Indoor
ALCA-H36/4R1E
Panel
MB12
Outdoor
AL-H36/4R1(U)
Factory Model Indoor
ALCa-H36A4/R1-EA
Panel
MB12
Outdoor
AL-H36A4/R1(T)
Code Indoor
16106021000005
Panel
16108002000007
Outdoor
16107022000001
Power Supply
V~,Hz,Ph
220~240,50,1
Capacity Cooling
Btu/h
36000
KW
10.60
Heating Btu/h
40000
KW
11.70
Electric Data
Rated Cooling Power Input
KW
3.77
Rated Heating Power Input
KW
3.50
Rated Cooling Current
A
17.3
Rated Heating Current
A
16.6
Performance EER
W/W
2.81
COP
W/W
3.34
Indoor Fan Motor
Model
YDK45-6Q
Brand
WELLING/Sinjun
Output Power x Fan quantity
W
45*1
Capacitor
uF 3 Speed (Hi/Mi/Lo)
r/min
650/520/450
Indoor Coil
Number Of Row
2
Tube Pitch(a)x Row Pitch(b)
mm
20.5×12.7
Fin Pitch
mm
1.4
Fin Material
louver
Tube Outside Dia.and Material
mm
φ7, Inner grooved
Coil Length x Height x Width
mm
2014×205×25.4
Heat Exchanging Area
m2
12.18
Indoor Unit Indoor Air Flow
(Hi/Mi/Lo)
m3/h
1500/1200/1050
Noise Level(Hi/Mi/Lo)
dB(A)
48/45/39
Net Dimension
mm
835×835×250
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
16
(W*H*D)
Packing Dimension (W*H*D)
mm
910×910×310
Net Weight
Kg
24
Gross Weight
Kg
27.5
Panel
Net Dimension (W*H*D)
mm
950×950×55
Packing Dimension (W*H*D)
mm
1000x1000x100
Net weight
Kg
5
Gross weight
Kg
7
Refrigerant Pipe
Liquid Side
mm
9.52
Gas Side
mm
15.88
Max. Refrigerant Pipe Length
m
50
Max. Difference In Level
m
30
Operation Temperature Range
°C
16~32
Ambient Temperature Range(Cooling/Heating)
°C
-5~49/-15~24
Application Area
m2
42-70
Connection Wiring Power Wiring( Indoor)
3×4mm2
3×4mm2
Power Wiring( Outdoor)
5×4mm2
5×4mm2
Signal Wiring
2×1mm2
2×1mm2
Wireless Remote Controller
YKR-K/001E
Qty’per 20’& 40’&40HQ (Only For Reference)
Set
30/70/79
Note:
1. Working condition of the cooling capacity measured: Inside the room DB temperature 27°C,WB
temperature19°C;Outside of the room DB temperature 35°C,WB temperature 24°C;Working condition of the heating capacity measured:Inside the room DB temperature 20°C,Outside of the room DB temperature 7°C,WB temperature 6°C.
2. Parameters above are all measured when the connecting pipe is 5 meters.
3. Parameters above may be modified as product improvement. We keep the right to change the product
specifications without prior notice, please take the parameters listed on the nameplate as criterion.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
17
3.CapacityAmendment
3.1 Amendment coefficient of cooling capacity under different indoor/outdoor temperature
Indoor temperature°C
Outdoor temperature°C(DB)
DB
WB
25
30
35
40
43
45
47
49
23
16
0.98
0.94
0.89
0.85
0.82
0.79
0.74
0.71
25
18
1.05 1 0.95
0.90
0.87
0.82
0.77
0.72
27
19
1.1
1.05 1 0.95
0.91
0.87
0.84
0.79
28
20
1.12
1.07
1.02
0.96
0.93
0.90
0.86
0.81
30
22
1.19
1.13
1.08
1.02
0.99
0.96
0.91
0.88
32
24
1.26
1.20
1.15
1.08
1.05
1.02
0.97
0.92
Actual cooling capacity calculation: Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list ——amendment coefficient of cooling capacity could be found from table above.
Amendment coefficient of heating capacity under different indoor/outdoor temperature
Actual heating capacity calculation: Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list ——amendment coefficient of heating capacity could be found from table above.
Indoor DB
temperature °C
Outdoor temperature °C(WB)
-15
-10
-5 0 6
10
15
16
0.45
0.53
0.65
0.80
1.02
1.13 - 18
0.47
0.55
0.61
0.76
1.02
1.12 - 20
0.46
0.54
0.6
0.75 1 1.11
1.25
21
0.42
0.49
0.59
0.72
0.99
1.1
1.24
22
0.41
0.49
0.58
0.71
0.97
1.09
1.23
24
0.39
0.45
0.56
0.7
0.96
1.08
1.22
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
18
3.2 Amendment coefficients of heating and cooling capacity under different height drop
Different Cooling Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit Height of Indoor Unit
Different Heating Capacity modified coefficients at different height:
Note:
H = Height of Outdoor Unit Height of Indoor Unit
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
19
4.Demension
ALCA-H12/4R1AA, ALCA-H18/4R1AA
ALCA-H24/4R1AAALCA-H36/4R1E ,ALCA-H36/5R1AA
ALCA-H48/5R1AAALCA-H60/5R1AA
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
20
5.Electrical wiring and connection
ALCA-H12/4R1AA, ALCA-H18/4R1AA
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
21
ALCA-H24/4R1AA
ALCA-H36/4R1E ,ALCA-H36/5R1AA ,ALCA-H48/5R1AAALCA-H60/5R1AA
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
22
Electrical connection
ALCA-H12/4R1AA ALCA-H18/4R1AA
ALCA-H24/4R1AA,
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
23
ALCA-H36/4R1E
ALCA-H36/5R1AAALCA-H48/5R1AAALCA-H60/5R1AA
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
24
Introduction of Control Board QRDL-3F(2S)-SYE1 (indoor unit) (match with the outdoor unit which the Power supply is 220V-240V, 1PH)
Introduction of control board QRD-SN3F(EX)-SYE1 sockets (Indoor unit) (match with the outdoor unit which the Power supply is 380V-415V, 3PH)
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
25
6.Installation
6.1 Preparation before installation
1. Please buy following spare parts from your local market before installation
Hung bolts M12, 4 pcs
Drainage pipe PVC
Copper pipe
Adhesive belt (big size) 5 pcs, (small size) 5 pcs
Heat insulation material used to connect copper pipe (PE foam material, its thickness is more
than 8mm)
Power cable, electrical wire between indoor and outdoor unit(Must be in accordance with the
wire diameter in the wiring diagram)
2. Beside general implements, other implements are needed when connecting the pipe
Acetylene cylinders, oxygen cylinders (when longer pipe used it should be welded)
One set pipe cut machine. (cut copper pipe)
Refrigerant cans, electronic balance (when longer pipe used additional gas should be charged)
Pressure gauges, pipe clamp, welding torch, 2B silver electrode
Wrench 2 pcs, one of them is with adjustable torque wrench(42N.m,65N.m,100N.mm)
Nitrogen cylinder (in order to prevent oxidation when welding, using Nitrogen to replace the
air)
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
26
6.2 Installation diagram
6.3 Installation precaution
Hanging location should be able to support the unit’s weight, there should be no increasement in
noise and vibration. If the hanging location needs reinforcement, it should be reinforced before installation;
Choose the space above the ceiling that can put the indoor unit inside; The location should be easy for drainage; The unit should not be installed beside the heat source, steam or oil mist source (such as machine
room, kitchen, laundry room, mechanical workshop, etc.)
Choose the location at least 1 meter away from TV and radio, in order to avoid interference to them There should be certain distance between indoor unit and obstacles for maintence; In case of leakage of refrigerant, units should immediately stop running, and contact with
maintenance personnel in time. There must be no fire at the site, because the refrigerant will turn to harmful gas when get to the fire.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
27
6.4 The distance between indoor unit and obstacle
6.5 Indoor unit suspension
Select the suspension foundation: The suspension foundation is a structure of either wooden frame or reinforced concrete. It must be
firm and reliable to bear at least 4 times weight of itself and capable of bearing vibration for long periods.
Fixing of suspension foundation: Fix the suspension bolts either as shown in the picture or by a steel or wooden bracket.
If this unit is installed on a sloping ceiling, a cushion block should be installed between the ceiling and
the air outlet panel, in order to ensure that the unit is installed on a level surface.
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
28
This is as shown in the drawing as follows:
Adjust the relative position of the suspension hook on the suspension bolt so that the unit can be in
level position in all directions. Check with a level gauge after installation to ensure that the indoor unit is horizontal, otherwise it will cause water leakage, air leakage etc.
Tighten the bolt and ensure that four hooks are in close contact with the nuts and washers, to fix the
indoor unit under the ceiling.
After the unit is installed ensure it is secure and does not shake or sway. Ensure that the centre of the indoor unit is in alignment with the centre of the opening in the ceiling.
6.6 Drainage pipe installation
The drainage pipe should be properly insulated to prevent the generation of condensation. Heat
insulation material: the thickness of rubber insulation pipe should be more than 8mm
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water left in
the pipe will drain back and may overflow the drain tray causing water leakage. For this reason please install the drain pipe as shown.
More than 1:100
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
29
When draining multiple units into a common drain line, this common drain should be installed about
100mm below each units drain outlet, as shown in the drawing.
When finish installation please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage. If the unit is installed in the newly built house, strongly recommend that this test taken before the ceiling installation. Even it is the heating only unit, this test is unavoidable.
6.7 Panel installation
As to the MB12 panel please refer to the following picture, the panel has four hooks which attach to
corresponding hangers on the unit and the panel should be positioned using these first. The panel is then fixed into position by four bolts which are accessed through the four corner panels on the grille.
6.8 Connect duct, fresh air ventilation
In order to meet different customers’ requirements and their different usage environment, indoor unit reserves one fresh air ventilation hole and four duct connection holes. The fresh air can be introduced from outside or through duct.
Less than 300mm
Less than 600mm
(Unit: mm)
Less than 800mm
More
than
1 00
mm
AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
30
Fresh air ventilation: In the corner of the unit there is a circular fresh air connection hole, if users want
this feature, please cut down the circular metal sheet and connect it to the duct. Fresh air hole is connected to the return air inlet of the indoor unit, when operation, the fresh air can be introduced from outside due to the negative pressure.