Autronica BS-100 DYFI Operator's Handbook Manual

P-BS100/FE - Rev.F / Doc/ 980114 Autronica Fire and Security AS
BS-100 DYFI
Program Version P1-BS100-3-20
P5-BS100-3E20
Protecting environment, life and property...
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 2 Autronica Fire and Security AS
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 3 Autronica Fire and Security AS
Contents
Please note!
This handbook contains instructions for operation of fire alarm system BS-100 DYFI ready designed and assembled from the factory. If the system is to be expanded on site, please see separate handbooks covering internal mounting and internal connections.
Page
1. Operating/control panel .......................................................................... 5
2. Prewarning ............................................................................................... 6
2.1 Indications on the control panel in the event of a "PREWARNING" 6
2.2 Actions to be taken in the event of a "PREWARNING"..................... 7
3. Fire alarm ................................................................................................. 8
3.1 Indications on the control panel in the event of a "FIRE" alarm ........ 8
3.2 Actions to be taken in the event of a "FIRE" alarm............................. 9
4. More alarms ........................................................................................... 11
4.1 Indications on the control panel in the event of “MORE ALARMS”11
4.2 Actions to be taken in the event of "MORE ALARMS" ................... 12
5. Fault ........................................................................................................ 14
5.1 Indications on the control panel in the event of “FAULT”............... 14
5.1.1 Indications at more (multiple) fault ............................................ 14
5.2 Actions to be taken at “FAULT” ....................................................... 15
6. Menu ....................................................................................................... 16
6.1 Menu structure ................................................................................... 16
6.2 Password protected functions ............................................................ 17
6.3 Menu operation .................................................................................. 18
6.4 "Main menu"...................................................................................... 19
7. Out / in - control..................................................................................... 20
7.1 Disable ............................................................................................... 20
7.1.1 Disable address ........................................................................... 21
7.1.2 Disable zone................................................................................ 22
7.1.3 Disable controls (password protected on operator level)............ 23
7.1.3.1 Disable BT-outputs (DHM, AUX) ...................................... 23
7.1.3.2 Disable controls (BSJ-100/101)........................................... 24
7.1.4 Disable sounders (AK) (can be password protected in different
countries) ............................................................................................. 24
7.1.5 Disable Fire Brigade (BMA, BMFO, BMF).............................. 25
7.2 Restore ............................................................................................... 25
7.2.1 Restore address ........................................................................... 25
7.2.2 Restore zone................................................................................ 26
7.2.3 Restore controls .......................................................................... 27
7.2.3.1 Restore BT-outputs (DHM, AUX) ...................................... 27
7.2.3.2 Restore controls (BSJ-100/101)........................................... 28
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 4 Autronica Fire and Security AS
7.2.4 Restore sounders (AK)................................................................ 28
7.2.5 Restore Fire Brigade/Fighters (BMA, BMFO, BMF)................. 28
8. Show status ............................................................................................. 29
9. Test .......................................................................................................... 31
9.1 Front panel ......................................................................................... 31
9.2 BMA/BMF/BMFO ............................................................................ 31
9.3 Fault ................................................................................................... 32
9.4 Sounders............................................................................................. 33
9.5 Buzzer ................................................................................................ 33
10. System ................................................................................................... 34
10.1 Sensitivity ........................................................................................ 35
10.1.1 Address ..................................................................................... 35
10.1.2 Beyond-limit ............................................................................. 37
10.1.3 Polluted ..................................................................................... 38
10.2 Internal ............................................................................................. 38
10.2.1 Program-version........................................................................ 38
10.2.2 Adjust-clock.............................................................................. 39
10.2.3 Show clock................................................................................ 39
10.3 Configuration ................................................................................... 39
10.4 System-Data (password protected) .................................................. 40
10.5 Change (site data) ............................................................................ 41
10.5.1 Display text - Change (Password protected on level 1)............ 41
10.5.2 Printer text - Changes (Password protected on level 1)............ 41
11. Feed paper ............................................................................................ 42
12. Service ................................................................................................... 42
Appendix A - Country variations................................................................ 43
Appendix B - Replacing the paper roll in the optional printer.................... 47
Appendix C - Multiple BS-100/-Control panels with common repeater
units (BU-100/101/70) ......................................................... 48
Appendix D - BS-100 master / Control unit with BS-60 slaves ................. 53
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 5 Autronica Fire and Security AS
1. Operating /control panel
The operating panel consists of text display (information window), indication lamps, operating buttons and a five elements key-pad. See below. By means of these control and indication devices, the entire fire alarm system is controlled
Fig. no. 1: BS-100 DYFI operating/control panel with indication lamps.
MORE ALARMS This black control button allows the second line of the text display to be scrolled. Revealing additional alarms on the system.
SOUNDER SILENCE When the red button is pressed, all alarm devices and the internal buzzer are muted.
RESET
When the green button is pressed, all events in the system are reset.
PRINTER
Optional printer
MORE ALARMS Red lamp lights when more alarms are present.
Textdisplay (Information window)
FIRE
Red lamp (sign) lights in alarm condition.*
These lamps will have custom designed text. (One is red and the lower two are amber (yellow). See app.A.
DEVICE(S) STILL IN ALARM COND.
Amber (yellow) lamp lights when an address (detector) is automatically disabled.
PREWARNING Amber (yellow) lamp lights with pulsating light when a prewarning situation has occured.*
FAULT Amber (yellow) lamp lights for any fault. Pulsating light. *
FUNCTION DISABLED
Amber (yellow) lamp lights when any part of the system is disabled (isolated).
MAINS Green lamp lights when the power is on.
Indication devices:
Operating buttons:
Five elements key-pad:
BS 100
DYFI
FIRE
MORE ALARMS
SOUNDER SILENCE
RESET
PREWARNING
FAULT
FUNCT. DISABL.
MAINS
A
utronica
NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
DEVICE(S) STILL IN ALARM COND.
The five elements key-pad
consists of four arrow keys and one “carry-out” (enter) key. The key-pad is used for information of the system. The four arrow keys control the cursor on the control panel text display.
The keys for scrolling in the menu and for moving the cursor up or down in the menu text on the text display. These arrow keys also scroll figures and letter values when they are to be entered in the menu functions.
Arrow keys for scrolling in the menu and for moving the cursor to the left or to the right in the menu on the text display.
“Carry-out” (enter) key. Select the menu part on which the cursor is pointed.
* Lamps go steady when “Sounder silence” button is operated.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 6 Autronica Fire and Security AS
All address related text indicated in the display together with the text
printed out on the optional printer may be custom designed. In this Operators handbook mainly default texts will be used.
2. Prewarning
2.1 Indications on the control panel in the event of a “PREWARNING”
Example of text in the display (and on the optional printer):
PV 01 ADDRESS NO. 0504 INVESTIGATE PREWARNING LOCATION
Print out on optional printer:
If more than one prewarning events is registered, the display will change to:
PW 01 ADDRESS NO: 0504 02 PREWARNINGS REGISTERED
All active prewarnings may be seen through the menu function “SHOW STATUS”, “PREWARNING”. Access to the menu is obtained by pressing
the
↵↵
key on the front panel.
2: The text display indicates the address(es) of the detector(s) in prewarning condition.
1:The amber (yellow) Prewarning - lamp lights
with pulsating lights.
3: The internal buzzer is activated.
Functions activated at “Prewarning”:
(BMFO) Common prewarning output.
****PREWARNING****
DATE: 15.08.91 T1.04.57 PW 01 ADDRESS NO. 0504
Prewarning
Indications
BS 100
DYFI
FIRE
MORE ALARMS
SOUNDER SILENCE
RESET
PREWARNING
FAULT
FUNCT. DISABL.
MAINS
A
utronica
NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
DEVICE(S) STILL IN ALARM COND.
!
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 7 Autronica Fire and Security AS
2.2 Actions to be taken in the event of a “PREWARNING”:
A. Always treat a “PREWARNING” condition as if it is a fire alarm.
B. Follow all precautions described in the local fire instructions step by
step.
C. Open the control panel door.
D. Press the “SOUNDER SILENCE” button.
(The built in buzzer will give a short signal approx. every fourth minute as long as the door remains open).
The “PREWARNING” indication lamp will now change to steady light.
E. Press the “RESET” button.
Wait for a while, while the following text appears in the display:
RESET PROCEDURE IN PROGRESS
WAIT ..............................
This text will remain for up to 60 seconds.
(The seconds are counted on the display with one point appearing every
sec. from 0 to 30 sec., and then removed the following 30 sec.)
The reset procedure is executed in this 60 seconds period.
If everything is in a normal condition the following text will appear in the
display:
RESET OK NORMAL CONDITION
F. Close the door.
In normal condition only the “MAINS” indication lamp should be illuminated when the door is closed.
Actions
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 8 Autronica Fire and Security AS
3. Fire alarm
3.1 Indications on the control panel in the event of a “FIRE” alarm:
Example of text in the display if detectors with address no. 345 has initiated the alarm.:
AL 01 ADDRESS NO. 0345
Print out on the optional printer:
3: The text in the display indicates the address of the detector which has initiated the first alarm. Possible disablements (isolations) of BMA, bells/sounders and control outputs are indicated in the lower line of the display.
1: The red FIRE indication lamp lights with pulsating light.
2: If the address initially had given a prewarning, the amber (yellow) Prewarning lamp will light with steady light.
4: The internal buzzer is activated.
5: All sounders connected to the fire alarm are activated. (Control of sounder outputs can be custom designed).
Functions activated at alarm condition:
(BMA) Alarm message to the fire-fighters. (AUX) General control output. (DHM) Control output for door holders. Optional custom designed control outputs.
****FIRE****
DATE: 15.08.91 T1.05.02 AL 01 ADERESS NO.: 0345
Fire alarm
Indications
BS 100
DYFI
FIRE
MORE ALARMS
SOUNDER SILENCE
RESET
PREWARNING
FAULT
FUNCT. DISABL.
MAINS
A
utronica
NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
DEVICE(S) STILL IN ALARM COND.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 9 Autronica Fire and Security AS
3.2 Actions to be taken in the event of a “FIRE” alarm:
A: Follow all precautions described in the local fire instructions step by step.
When the scene of the fire is investigated and the necessary actions are carried out, the sounders may be switchedoff.
B: Open the control front door.
C: Press the”SOUNDER SILENCE” button.
All alarm devices (including the internal buzzer) will be muted.
The red “FIRE” indication lamp will switch to steady light.
All alarm outputs from the control panel will be turned of when the “SOUNDER SILENCE” button is pressed. However, the message to the Fire Fighters (BMA-) remains on.
If the silent alarm function (day/night) is in operation, the time delay (T1) will start. Alarm outputs and the BMA-output will not be ativated.
If the alarm is acknowledged within the delay period (T1) by operating the “SOUNDER SILENCE”-button, an additional delay period (T2) will be activated.
If the “SOUNDER SILENCE”-button not is operated within the delay period T1 or reset within the delay period T2, the alarm outputs and BMA will be activated.
The alarm delay of sounder outputs and the BMA-output applies only for alarm from detectors. Alarms from manual call points or 2 or more detectors, over-ride the alarm delays T1 + T2, and the sounder outputs and the BMA-output will operate immediately.
Silent alarm/alarm organisations (list L3.11) is controlled by external manual switch with time controlled relay or automatic from external clock.
If the “MORE ALARMS” indication lamp lights, please see section 4.1
D: Press “RESET”-button.
The following text will appear in the text display:
RESET PROCEDURE IN PROGRESS
WAIT..........................
Actions
!
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 10 Autronica Fire and Security AS
This text will remain in the display for up to 60 seconds. The reset procedure is as the one described in section 2.2. part E.
If everything is normal after the reset procedure is carried out, the following text will appear in the display:
RESET OK NORMAL CONDITION
This text remains in the display for 15 seconds, and then the menu selection will appear.
After resetting, an address may still be in an alarm condition. This can be due to mechanical demage, water damage, the presence of smoke still within the chamber or an electrical fault. The address still in the alarm condition, will automatically be disabled (isolated from the rest of the system). The amber (yellow) “DEVICE(S) STILL IN ALARM COND.” - indication lamp will light, and the following text will appear in the display:
01 ALARM ADDRESS(ES) DISABLED CONTROL PANEL IN ABNORMAL CONDITION
Contact technical personnel.
E: Close the door.
In normal condition only the “MAINS” indication lamp shall remain illuminated when the door is closed.
While an address is automatically disabled, the amber (yellow) “DEVICES STILL IN ALARM COND.” indication lamp also will be lit.
If the alarm condition disappears, the indication lamp will turn off and the address automatically restored to the system.
See also
special
functions
according to
SOLAS-
requirements,
described in
appendix A.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 11 Autronica Fire and Security AS
4. More alarms
4.1 Indications on the control panel in the event of “MORE ALARMS”:
Example of text in the display if more then two detector addresses (here we show 3) are in alarm condition:
AL 01 ADDRESS NO: 0007 AL 03 ADDRESS NO: 0002
Print-out on the optional printer:
1: The red FIRE indication lamp lights with pulsating light.
2: The amber (yellow) PREWARNING lamp lights with pulsating light. However, if the address initially had given a prewarning, the lamp will light with steady light.
5: The internal buzzer is activated.
6: All sounders connected to the fire alarm are activated. (Control of sounder outputs can be custom designed.)
Functions activated at alarm condition:
(BMA) Alarm message to the fire-fighters. (AUX) General control output. (DHM) Control output for door holders. Optinal custom designed control output.
****FIRE****
DATE: 21.10.91 T1.15.33
A
L 03 ADDRESS NO.: 0002
**** FIRE ****
DATE: 21.10.91 T1.15.28
A
L 02 ADDRESS NO: 0003
**** FIRE ****
DATE: 21.10.91 T1.15.24
A
L ADDRESS NO: 0007
3: The red MORE ALARMS indication lamp lights.
4:The upper line in the display indicates the first address in alarm condition. The lower indicates the last address in alarm condition.
More alarms
Indications
BS 100
DYFI
FIRE
MORE ALARMS
SOUNDER SILENCE
RESET
PREWARNING
FAULT
FUNCT. DISABL.
MAINS
A
utronica
NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
DEVICE(S) STILL IN ALARM COND.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 12 Autronica Fire and Security AS
4.2 Actions to be taken in the event of “MORE ALARMS”:
A: Follow all precautions described in the local fire instructions step by step.
B: Open the control panel front door.
C: Press the "MORE ALARMS"-button.
At the first time press on the button, the second alarm will normally be indicated on the lower line.
However, if the following functions - BMA, bells/sounders and control outputs are disabled (isolated) this will be indicated on the lower line for a short period before the second alarm is indicated.
Pressing the button a second time will show the 3rd alarm in the display.
Each new press of the button will show the next alarm in the queue.
If the button is pressed for 15 seconds, the last alarm will automatically show on the lower line.
D: Press “SOUNDER SILENCE”-button.
All alarm devices including the internal buzzer will be turned off.
See section 3.2 C for description of silent alarm function (day/night).
The ref “FIRE” indication lamp will switch to steady light.
All alarm outputs from the control panel will be turned off when the “SOUNDER SILENCE” button is pressed. However, the message to the Fire Fighters (BMA-) is not turned off.
E: Press “RESET”-button.
The following text will appear in the text display:
RESET PROCEDURE IN PROGRESS
WAIT.............................
This text will remain in the display for up to 60 seconds. The reset procedure is identical to the one described in section 2.2.
Actions
Special
SOLAS-
functions are
described in
appendix A.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 13 Autronica Fire and Security AS
If everything is in a normal condition the following text will appear in the display:
RESET OK NORMAL CONDITION
This text remains in the display for 15 seconds, and then the menu selection will appear.
After resetting, one or more addresses may still be in an alarm condition. This can be due to mecanical damage, water damage, the presence of smoke still within the chamber or an electrical fault. The addresses still in the alarm condition, will automatically be disabled (isolated from the rest of the system).
The following text will appear in the display:
01 ALARM ADDRESS(ES) DISABLED CONTROL PANEL IN ABNORMAL CONDITION
Contact technical personnel.
F: Close the door.
In normal condition only the “MAINS” indication lamp shall remain illuminated when the door is closed.
While an address is automatically disabled, the amber (yellow) “DEVICES STILL IN ALARM COND.” indication lamp also will be lit.
If the alarm condition disappears, the indicator lamp will turn off and the address automatically restored to the system.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 14 Autronica Fire and Security AS
5. Fault
5.1 Indications on the control panel in the event of “FAULT”:
5.1.1 Indications at more (multiple) fault
If more (multiple) faults (here we show two) the following indications can be shown in the display:
FA 01 ADERESS NO: 0123 LOOP/DET.FAULT: 1 SYSTEM FAULT: 1
Print out on optional printer:
This text means that there is one fault present on detector no. 0123, and that there is one system fault present (sounder circuit). The nature of the fault can be identified by using the menu.
Access to the menu is obtained by pressing the
↵↵↵↵-button on the five
elements key-pad.
1: The amber (yellow) FAULT lamp lights with pulsating light.
3: The internal buzzer is activated.
Functions activated at “Fault”:
BMF - Common fault warning output.
****SYSTEM FAULT****
DATE: 25.11.91 T1.09.52 SF 1 SOUNDER CIRCUIT 4 OPEN
****DETEKTOR FAULT****
DATE: 25.11.91 T1.09.50 FA 1 ADDRESS NO: 0123 (EO) NO OR SHORT ANSWER-PULSE
2: The text display indicates the nature of the fault. If the following letters are indicated at the start of the upper line: FA means loop / detector fault. SF means system fault.
Fault
Indications
More faults
BS 100
DYFI
FIRE
MORE ALARMS
SOUNDER SILENCE
RESET
PREWARNING
FAULT
FUNCT. DISABL.
MAINS
A
utronica
NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
DEVICE(S) STILL IN ALARM COND.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 15 Autronica Fire and Security AS
5.2 Actions to be taken at “FAULT”:
A. Press the “SOUNDER SILENCE”-button.
The internal buzzer is muted, and the amber (yellow) “FAULT”
indication lamp will switch to steady light.
B: Note the fault text indicated in the display and file the printout from the optional printer.
C: Contact technical /serice personnel.
Actions
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 16 Autronica Fire and Security AS
6. Menu
6.1 Menu structure
The whole menu structure is shown here, but “SYSTEM CONFIGURATION” and “SERVICE” is described in full detail within the “Commissioning handbook” - BS-100.
Select Main menu (Program P1-BS100-3-20 / P5-BS100-3E20)
Out/in- Disable Address control Zone
1) Controls BT-outputs (AUX,DHM)
3) Sounders Controls (1-240) Fire-brigade (BMA,BMFO,BMF)
Restore Address Zone Controls BT-outputs (AUX,DHM) Klokker Controls (1-240) Fire-brigade (BMA,BMFO,BMF)
Show-status Alarm Prewarning Addr./loop-fault System fault Disablements Alarm counter Stored events (last 150)
Test Front panel (lamp test) BMA,BMFO, BMF
Fault Sounders Buzzer
System Sensitivity Address Single address Beyond limit Loop Total Printer Polluted Printer Display Display Internal Program-version Adjust-clock Show-clock
2) Configuration Comm.channel Panel address Alarm info Silencealarm T1 (Alarm delay) T2 BU-units (display units) DYFI-changes Alarm Battery-voltage Prewarning Pocket pager Filter cont. on next page: System-Data
Menu
Menu structure
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 17 Autronica Fire and Security AS
1,2) Data Change 1) Changing of display and printer texts.
2) Changing of output controls, alarm outputs and disabling outputs. Add Print out Detector data Printer texts Feed paper
Service Report DYFI-factors Single address
Restart Main prc. (processor) Loops (processor) Clear Disable Loop Internal buzzer Internal printer
Restore Loop Internal buzzer Internal printer
Test Address-in-alarm Styringer Styringer BT-utganger Adress- Loop From detector control From front
Data control Transfer comm.port Yes No
Select “RET” to go 1 step back in the menu structure. Select “MM” to return to main menu.
1. Password protected on level 1. (Operator level).
2. Password protected on level 2. (Service level).
3. Can be password protected in different market and installations.
6.2 Password protected functions
Some of the functions in the BS-100 menu are password protected on two levels.
Following functions are password protected: Password level 1): "OPERATOR LEVEL". * Disable - Controls * System - Data * Disable - Sounders * Changing of display and printer texts
Password level 2): "SERVICE LEVEL" * System - Configuration * Service * Changing of output controls, alarm outputs and disabling groups.
Password
Menu cont...
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 18 Autronica Fire and Security AS
6.3 Menu operation
Information given in this section follows the MENU STRUCTURE given in section 6.1. That particular parts of the menu structure is shown prior to each section in order to ease the function overwiew.
When the control panel front door is opened, the following text will appear in the display:
AUTRONICA FIRE ALARM SYSTEM BS-100 USER MENU
Then the text changes to:
SELECT MAIN MENU PRESS
↵↵
USERS INSTRUCTION PRESS ßßßß
If the operator selects to read the short form users instruction by pressing the ß arrow key in the key-pad, the following text will appear in the display:
USER INSTRUCTION. PANEL IS OPERATED BY USING MENU FUNCTIONS. TO CONT. PRESS ßßßß
VARIOUS MENU FUNCTIONS ARE SELECTED BY
USE OF ßÝ
ßÝßÝ
ßÝ AND ßÝ
ßÝßÝ
ßÝ LAST PICT. NEXT PICT. ßÝ
ßÝßÝ
ßÝ
CHOSEN FUNCTION IN MENU IS MARKED AND
IS EXECUTED BY PRESSING ↵↵↵ ßßßß ÝÝÝÝ
IN ADDITION TO MENU FUNCTIONS THERE ARE
TWO FUNCTIONS WHICH CAN BE USED ßßßß ÝÝÝÝ
“RET” WHEN THIS FUNCTION IS CHOSEN, YOU TAKE ONE STEP BACK IN MENU ßßßß ÝÝÝÝ
WHEN SELECTING “MM” THAT TAKES YOU BACK TO MAIN MENU ßßßß ÝÝÝÝ
Operation
Short form
operators
instruction.
This appears on
the display on
the front panel
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 19 Autronica Fire and Security AS
“ARROWS” ARE USED IN ORDER TO BRING UP MORE SUB-MENUES WITHIN SAME MENU LEVEL ßÝ
ßÝßÝ
ßÝ
ßßßß ÝÝÝÝ ALSO TO BE USED WHEN SETTING REQUIR. VALUES OF DIFFERENT PARAMETERS ßßßß ÝÝÝÝ
ßÝ
ßÝßÝ
ßÝ SCROLLING FIGURES / VALUES /CHARACTERS
WHEN TO BE SET ßßßß ÝÝÝÝ
USERS INSTRUCTION FINISHED TO MAIN MENU: PRESS
↵↵
6.4 "Main menu"
If the “ MAIN MENU” is selected, part of main menu will appear in the display:
MAIN MENU: SELECT WITH
ÞÞÞÞ PRESS
↵↵↵
OUT/IN-CONTROL SHOW-STATUS TEST
ßßßß
The arrow pointing down next to the word TEST indicates more text in the line. By pressing the ß arrow key in the key-pad, the remaining text is shown in the lower line:
MAIN MENU: SELECT WITH
ÞÞÞÞ PRESS
↵↵
SYSTEM FEED-PAPER SERVICE RET ÝÝÝÝ
The required function is selected by moving the cursor by means of the arrow keys in the key-pad on the control panel front.
The function is selected, by pressing the
↵↵↵↵-key.
Out/in-control
Show-status
Test
System
Feed paper
Service
Main menu
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 20 Autronica Fire and Security AS
7. Out/in-control
Main menu
Out/in-control Disable Address Zone
1) Controls* BT-outputs(AUX,DHM)
3) Sounders* Controls (1-240) Fire-brigade (Fire fighters)
Restore Address Zone Controls BT-outputs Sounders Controls Fire-brigade (Fire fighters)
If the “OUT/IN-CONTROL” is selected in the main menu, the following text will appear in the display:
OUT/IN-CONTROL: SELECT WITH
ÞÞÞÞ
PRESS
↵↵
DISABLE RESTORE MM
7.1 Disable
When disabling parts of the system, the amber (yellow) lamp “FUNCTION DISABLED” on the front of the control panel will light as long as the disabling lasts.
All disablements must be allocated a time period. By selecting manually disable time of 99 hours, the function will be disabled until restored. The maximum automatic disable time is 24 hours. When disable time isout, those disabled functions will automatically be restored.
If “OUT/IN-CONTROL” is selected and then “DISABLE”, the following text will appear in the display:
DISABLE: SELECT WITH
ÞÞÞÞ PRESS ↵↵↵↵
ADDRESS ZONE CONTROLS SOUNDERS ßßßß
("FIRE BRIGADE" will appear when ß is pressed.)
Out/in-control
Disable
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 21 Autronica Fire and Security AS
7.1.1 Disable address
When disabling an address (detector, manual call point or an interface unit), the address will be isolated and not generate an alarm, prewarning or fault as long as the disabling lasts.
If “OUT/IN-CONTROL”, “DISABLE” and then “ADDRESS” are selected, the following text will appear in the display:
DISABLE ADDRESS(ES) SELECT ADDRESS 0000 RET MM
Select the address no. to be disabled and press
↵↵
↵.
The following text will appear in the display:
1 ADDRESS(ES) ENTERED FOR DISABLEMENT ADDRESS XXXX TIME RET MM
The selected address is ready to be disabled.
This address is not yet disabled, - only prepared for disablement!
The next address (XXXX) will automatically appear. Select this or another addres by pressing
↵↵
↵ .
If selected address is not present in the system, the following text will appear in the display:
THE ADDRESS DOES NOT EXIST IN PANEL LEGAL ADDRESSES xxxx TO XXXX
xxxx - lowest address in the system. XXXX - highest address in the system.
When all addresses to be disabled are selected, move the cursor to “TIME”
by means of the arrow key and press
↵↵↵↵.
The following text will appear in the display:
DISABLEMENT OF n ADDRESS(ES) DURATION 02 HOURS RET MM
n = number of addresses ready for disablement.
The time limit is automatically set to 2 hours (default value). Press ß Ý to select other values and press
↵↵
↵ .
Disable address
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 22 Autronica Fire and Security AS
The following text will appear in the display:
DISABLEMENT OF ADDRESS(ES) OK NUMBER: n TOTAL m RET MM
n = number of addresses disabled in this operation. m = number of addresses disabled total in the system.
7.1.2 Disable zone
It is only possible to disable zones if zones have been programmed in custom data. If not programmed the menu will not allow you to enter zone area.
When disabling zone(s) the addresses in the zone will be isolated and will not generate an alarm, prewarning or fault.
The total number of zones are 240. Zone addresses are 1-240.
If “OUT/IN-CONTROL”, “DISABLE” and then “ZONE” are selected, the following text will appear in the display:
DISABLE ZONE 001 NEXT PREVIOUS TIME ‘ZONE TEXT’ RET MM
Select the zone number for disablement by pressing the Ý ß -key.
It is also possible to move the cursor to “NEXT” and “PREVIOUS” and press
↵↵↵↵ to select the zone numbers.
When correct zone number 1-240 is selected, move the cursor to “TIME”,
press
↵↵↵↵, and the following text will appear in the display:
DISABLE ZONE 001 NEXT PREVIOUS TIME TIME - DURATION 02 HOURS RET MM
Select duration for disablement and press
↵↵
↵.
The following text will appear in the display:
ZONE YYY DISABLE MORE ? YES NO
YYY is selected and that sone is disabled.
If more than one zone is to be disabled select “YES”, press
↵↵
and repeat the
disable procedure. Select “NO” to end the “DISABLE ZONE” procedure.
Disable zone
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 23 Autronica Fire and Security AS
7.1.3 Disable controls (password protected on operator level).
Disabling controls, ensures that output controls will not activate in the event of a alarm:
DISABLE OUTPUT CONTROLS BT-OUTPUTS CONTROLS RET MM
7.1.3.1 Disable BT-outputs (DHM, AUX)
If the BT-outputs are disabled, the outputs DHM (door holder magnets) and AUX (control-/alarm output) will not operate at alarm.
If “OUT/IN-CONTROL”, “DISABLE”, “CONTROLS” are selected and then the “BT-OUTPUTS”, the following text will appear in the display:
DISABLEMENT OF BT-OUTPUTS DUREATION 02 HOURS RET MM
Select theduration time fordisablement by means of the arrow keys and press
↵↵↵↵.
The following text will appear in the display:
DISABLEMENT OF BT-OUTPUTS DISABLEMENT EXECUTED
Press
↵↵
and the system will return to “DISABLE CONTROLS”-menu with
possibility to return to the main menu.
Disable controls
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 24 Autronica Fire and Security AS
7.1.3.2 Disable controls (BSJ-100/101)
When disabling the controls, the control-outputs from external control­output modules BSJ-100/BSJ-101 will not operate at alarm.
If “OUT/IN-CONTROL”, “DISABLE”, “CONTROLS” are selected and then the “CONTROLS”, the following text will appear in the display:
DISABLEMENT OF CONTROLS DURATION 02 HOURS RET MM
Select duration time for disablement by means of the arrow key and press
↵↵
↵.
The following text will appear in the display:
DISABLEMENT OF CONTROLS DISABLEMENT EXECUTED
Press
↵↵↵↵, and the system will return to “DISABLE CONTROLS”, with
possibility to return to the main menu.
Output controls can be disabled/restored from a superior computer through the communication line..
7.1.4 Disable sounders (AK) (can be password protected in different countries
- see Appendix A).
When disabling sounder output(s), the sounder(s) will not be activated at alarm. This is applicable for the 4 standard sounder outputs and the outputs from external sounder output board (BSB-100).
If “OUT/IN-CONTROL”, “DISABLE” and then “SOUDERS” are selected, the following text will appear in the display:
DISABLEMENT OF SOUNDERS DURATION 02 HOURS RET MM
Select the duration time for disablement by means of the arrow key and press
↵↵
↵.
The following text will appear in the display:
DISABLE SOUNDERS DISABLEMENT EXECUTED
Press
↵↵
, an the system will return to the “DISABLE”-menu with possibility
to return to the main menu.
Disable
sounders
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 25 Autronica Fire and Security AS
7.1.5 Disable Fire Brigade (BMA, BMFO, BMF)
When disabling the Fire Brigade output (BMA), prewarning (BMFO) and fault output (BMF) will also be disabled
If “OUT/IN-CONTROL”, “DISABLE” and then “FIRE BRIGADE” are selected, the following text will appear in the display:
DISABLEMENT OF FIRE BRIGADE OUTPUT DURATION 02 HOURS RET MM
Select duration time by means of the arrow key and press
↵↵
↵.
The following text will appear in the display:
DISABLEMENT OF FIRE BRIGADE OUTPUT DISABLEMENT EXECUTED
Press
↵↵
, and the system will return to the “DISABLE”-menu with
possibility to return to the main menu.
7.2 Restore
When disable parts of the system (functions) are restored, these will revert to their normal function.
The “FUNCTION DISABLED” lamp will turn off only when all disablements have been retsored.
If “OUT/IN-CONTROL” and then “RESTORE” are selected, the following text will appear in the display:
RESTORE: SELECT WITH
ÞÞÞÞ
PRESS
↵↵
ADDRESS ZONE CONTROLS SOUNDERS ßßßß
("RESTORE", "FIRE BRIGADE" will appear when ß is pressed.)
7.2.1 Restore address
Before restoring addresses it is always advisable to check the sensitivity to ensure that an alarm is not present.
By restoring the address(es), the addresses will revert to their normal function.
Disable
Fire Brigade
Restore
Restore
address
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 26 Autronica Fire and Security AS
If "OUT/IN-CONTROL", "RESTORE" and then "ADDRESS” are selected, the following text will appear in the display:
RESTORE ADDRESS(ES) ADDRESS 0000 RET MM
Select the address(es) to be restored by means of the arrow key and press ↵.
↵.↵.
↵.
The following text will appear in the display:
n ADDRESS(ES) RESTORED OK ADDRESS XXXX RET MM
n = number of restored address(es).
The next address (XXXX) will automatically appear. Select that or another address by means of the arrow key and press
↵↵
↵.
If selected address is not present in the system, the following text will appear in the display:
THE ADDRESS DOES NOT EXIST IN PANEL LEGAL ADDRESSES xxxx TO XXXX
xxxx - the lowest address in the system. XXXX - the highest address in the system.
7.2.2 Restore zone
It is possible to restore only if zones are programmed in custom data.
When restoring zones, addresses connected to the zones will revert to their normal function.
If “OUT/IN-CONTROL”, “RESTORE” and then “ZONE” are selected, the following text will appear in the display:
RESTORE OF ZONE 001 NEXT PREVIOUS OK ‘zonetext zone 1’ RET MM
Select zone number to be restored by means of the arrow keys and press ß Ý.
It is also possible to move he cursor to “NEXT” and “PREVIOUS” and press
↵↵
to select zone number.
Restore zone
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 27 Autronica Fire and Security AS
When correct zone number is selected, move the cursor to “OK” , press
↵↵
and the following text will appear in the display:
ZONE YYY RESTORED MORE ? YES NO
YYY is selected and restored zone.
If more than one zone is to be restored, select "YES", press
↵↵
and repeat the
restoring procedure. Select "NO" to end the "RESTORE ZONE"-menu.
7.2.3 Restore controls
By restoring the controls, these will activate at alarm.
If "OUT/IN-CONTROL", "RESTORE" and then "CONTROLS" are selected, the following text will appear in the display:
RESTORE OUTPUT CONTROLS BT-OUTPUTS CONTROLS RET MM
7.2.3.1 Restore BT-outputs (DHM, AUX)
By restoring BT-outputs, the outputs DHM (door holder magnets) and AUX (control-/alarm output) will activate at alarm.
If "OUT/IN-CONTROL", "RESTORE", "CONTROLS" and then "BT­OUTPUTS" are selected, the following text will appear in the display:
RESTORE OUTPUT CONTROLS RESTORE COMPLETED
Press
↵↵
, and the system will return to the "RESTORE CONTROLS" with
possibility to return to the main menu.
Restore controls
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 28 Autronica Fire and Security AS
7.2.3.2 Restore controls (BSJ-100/101)
By restoring the controls, the control outputs from external control output module(s) BSJ-100/BSJ-101 will activate at alarm.
If "OUT/IN-CONTROL", "RESTORE", "CONTROLS" and then “CONTROLS" are selected, the following text will appear in the display:
RESTORE OUTPUT CONTROLS RESTORE COMPLETED
Press
↵↵
, and the system will return to the "RESTORE CONTROLS"-menu
with possibility to return to the main menu.
7.2.4 Restore sounders (AK)
By restoring the sounder(s), the sounder(s) will revert to their normal function at fire alarm. This is applicable for the 4 standard sounder outputs and the outputs from external sounder output board (BSB-100).
If "OUT/IN-CONTROL", "RESTORE", and then "SOUNDERS" are selected, the following text will appear in the display:
RESTORE: SELECT WITH
ÞÞÞÞ PRESS
↵↵
RESTORE COMPLETED
Press
↵↵↵↵, and the system will return to the "RESTORE"-menu with
possibility to return to the main menu.
7.2.5 Restore Fire Brigade/Fighters (BMA, BMFO, BMF)
By restoring the Fire Brigade/Fighters output BMA (Alarm output), BMFO (Prewarning output) and BMF (Fault output), the output will revert to their normal function at alarm, prewarning or fault.
If "OUT/IN-CONTROL", "RESTORE" and then "FIRE BRIGADE" are selected, the following text will appear in the display:
RESTORE: SELECT WITH
ÞÞÞÞ PRESS
↵↵
RESTORE COMPLETED
Press
↵↵
, and the system will return to the "RESTORE"-menu with
possibility to return to the main menu.
Restore
sounders
Restore
Fire Brigade
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 29 Autronica Fire and Security AS
8. Show status
Main menu
Show status Alarm
Prewarning Addr./loop-fault System fault Disablements Alarmcounter Stored events (last 150)
When "SHOW STATUS” is selected, the following text will appear in the display:
SHOW STATUS SELECT WITH
ÞÞÞÞ PRESS
↵↵
ALARM PREWARNING ADDR./LOOP-FAULT ßßßß
By pressing the ß key the rest of the text will appear in the lower line.
Alarm: The last 20 stored alarms *)Prewarning: The last 20 active prewarnings. *)Addr./loop-fault: The last 20 active faults from detectors/detector-
loops.
*)System fault: The last 20 active system faults. Disablements: All stored disablements. Alarmcounter: Number of stored alarms. Stored-events: The last 150 stored events.
*) = These events are cleared when the "RESET"-button is pressed. Move the cursor to the required function and press the
↵↵
key.
For the function "SHOW STATUS", option "ALARM", the text in the display will be:
SHOW STATUS ALARM ADDRESS 0296 DATE: 11.02.91 TI. 16.25
Use the ß Ý arrow keys to scroll through the stored alarms. Use the
↵↵
arrow keys to return to "SHOW STATUS” menu.
"STORED EVENTS" is continually up-dated detailing the last 150 events in the system. The last event will always be shown first.
Feed-paper
Service*
Out/in-control
Show status
Test
System
Main Menu
Show status
Stored events
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 30 Autronica Fire and Security AS
All activities eg. alarms, prewarnings, faults, silence, reset, open and closing front door etc. are stored with date and time.
If the "STORED EVENTS" function is selected, the display will indicate as follows:
SHOW STORED EVENTS ON : PRINTER DISPLAY RET MM
As indicated in the above, the stored information can be shown in the display or on the optional printer. The printer will start with the latest events.
The optional printer may be stopped at any time simply by pressing one of the arrow keys in the key-pad located on the control panel front.
If display is selected, use the ß Ý arrow keys to scroll through "STORED EVENTS".
The "STORED EVENTS" function presents the events in a reduced format with date and time.
The content is:
* All alarms. * All prewarnings. * All faults (internal and external). * All button operations at event handling (SILENCE/RESET). * All automatic disablements at reset. * All disablements carried out by means of the menu and the arrow keys. * All disablements executed via data line. * All manually executed restorations. * All group disablements, externally controlled. * All group restorations, externally controlled. * All functions related to alarm organisation (time delay of external alarm). * All functions entered (carried out) via password. * Openings of the control panel front door. * Closing of the control panel front door. * "Cold-start", the system has been powered up. * "Warm-start", ("watch-dog" internal function).
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 31 Autronica Fire and Security AS
9. Test
Main menu
Test Front panel
BMA/BMF/BMFO Fault Sounders Buzzer
When entering the "TEST"-function in the main menu, the following text will appear in the display:
TEST FRONT PANEL BMA/BMF/BMFO FAULT ßßßß
In the lower line the ß arrow indicates more text.
Move the cursor to the required function and press the
↵↵
key.
9.1 Front panel
If the "FRONT PANEL" function is selected, the display is tested by showing all characters, and all lamps on the control panel front will light. The function is stopped by pressing any of the arrow keys. A special test sequence is also printed out on the optional printer, if this is installed. Repeater units may also be tested in this function by opening door (BU-100/101) or operating test button (BU-70).
9.2 BMA/BMF/BMFO
If the "BMA/BMF/BMFO" function is selected the following text will appear in the display:
TEST OF TRANSMISS. LINE TO FIRE BRIGADE WHEN COMPLETED PRESS
↵↵
This function will activate the corresponding outputs. Inform the fire brigade if connected!
Test
Front panel
BMA/BMF/BMFO
!
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 32 Autronica Fire and Security AS
9.3 Fault
If the "FAULT" function is selected the following text will appear in the display:
TEST EARTH-FAULT ACTIVE
. . . . .
The test process takes one minute. It is indicated by dots appearing in the display for the first half minute. Then the sequence is reversed the next half minute. This test process is a real one, and an genuine earth fault is introduced. The internal buzzer is activated. The test is terminated by
pressing the
↵↵
button.
Normal test function gives earth fault on the central panel.
When this earth fault test sequence is finished, the next sequence will automatically start. The following text will appear in the display:
TEST ADDRESS FAULT ACTIVE
. . . .
In this sequence the control panels ability to receive fault messages from the detectors/detector-loops is tested. This sequence also lasts for one minute. A fault message on address 0001 will be shown provided this address is not disabled. The fault will activate the internal buzzer.
When this address test sequence is finished, the next sequence will automatically start. The following text will appear in the display:
TEST BATTERY ACTIVE
. . . .
This sequence (which is a real battery capacity test) lasts for 10 seconds and normally should not give any fault message. (This test is automatically carried out by the BS-100 every day at 10:00 AM). Before continuing operate the "SOUNDER SILENCE" and "RESET" pushbuttons.
Fault
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 33 Autronica Fire and Security AS
9.4 Sounders
When the previous test sequence is completed, return to the "TEST" option and select the "SOUNDERS” sequence by moving the cursor with the arrow
keys and then press the
↵↵
key.
The following text will appear in the display:
SOUNDER TEST ACTIVE WHEN COMPLETED PRESS
↵↵
During this test sequence all alarm outputs will be activated (0,5 second ON every 8th second). The sequence is terminated by pressing the
↵↵
key.
9.5 Buzzer
When the sounder test sequence is finished, return to the "TEST" option and select the "BUZZER" sequence by moving the cursor with the arrow keys
and then press the
↵↵
key.
The following text will appear in the display:
BUZZER TEST ACTIVE WHEN COMPLETED PRESS
↵↵
The built-in buzzer will be activated until the buzzer test sequence is terminated by pressing the
↵↵
key.
Buzzers on all repeater units will also operate during this test sequence.
Sounders
Buzzer
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 34 Autronica Fire and Security AS
10. System
Main menu
System Sensitivity Address Single address Beyond-limit Loop Polluted Total Printer Display Internal Program-version Adjust-clock Show-clock
Configuration
*
Comm.channel Silence alarm (alarm delay) Standard (T1) BU-units Additional (T2) DYFI-changes Alarm Battery voltage Prewarning Pocket Pager Filter
1,2) Data* Change 1)Changing of display and printer texts.
2)Changing of output controls, alarm outputs and disabling groups. Add Print-out Detector data Transfer Printer texts
* See section 6.1 - "Menu structure".
Select "SYSTEM" in the main menu, and the following text will appear in the display:
SYSTEM SELECT WITH
ÞÞÞÞ PRESS
↵↵
SENSITIVITY INTERNAL CONFIG. DATA MM
The rest of the text will appear by pressing the ß key.
System
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 35 Autronica Fire and Security AS
10.1 Sensitivity
The "SENSITIVITY" function enables the user to read the analogue value of an individual detector(address), from a loop or from all addresses connected to the control panel. The analogue value is automatically updated every 5th second. To achieve all advantages available in this function, the optional printer must be fitted to the control panel. An analogue value may be seen even when the device is disabled.
If the "SENSITIVITY" function is selected by moving the cursor with the arrow- and enter-keys, the following text will appear in the display:
SENSITIVITY ADDRESS BEYOND-LIMIT POLLUTED RET MM
10.1.1 Address
By selecting "ADDRESS" the following text will appear in the display:
ADDRESS SENSITIVITY SINGLE ADDRESS LOOP TOTAL RET MM
If "SINGLE-ADDRESS" is selected, the following text will appear in the display:
ADDRESS SENSITIVITY ADDRESS: 0000 RET MM
Here it is necessary to select the address number by moving the cursor to the correct column and then set the number in question by using the ß or Ý
keys. When the correct address no. is set, operate the
↵↵↵↵ key.
If detector address 0001 is selected, the following text will appear in the display:
ADDRESS: 0001 SENSITIVITY: 074 WHEN COMPLETED PRESS
↵↵
The analogue value (sensitivity) is updated every 5th second. The value will alter slightly at each update due to minor environmental changes. (During the first few seconds of the sequence the display will show sensitivity = 000).
Sensitivity
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 36 Autronica Fire and Security AS
Normally the value shall be between 32 and 112 (standard range). Values below 32 indicate detector fault. Values between 112/128 indicate prewarning, and values above 128 indicate fire alarm.
The sequence is terminated by pressing the
↵↵
key. Another address may
now be selected.
If the sensitivity (analogue signal) from all detectors in a loop is to be checked, the loop number has to be selected from this text in the display:
ADDRESS SENSITIVITY LOOP 00 RET MM
When the loop number in question is selected with the arrow keys and the
↵↵↵↵ key, the following text will appear in the display:
(when selecting loop 01).
ADDRESS LOOP 01 PRINTER DISPLAY RET MM
In this sequence it is possible to select between a print-out from the optional printer, or an indication in the display. The selection is carried out by moving the cursor to "PRINTER" or "DISPLAY" with the arrow keys and
then press the
↵↵
key. The sensitivity value for one detector will remain in
the display for about 1 second before changing to the next detector.
This sensitivity sequence can be terminated by pressing the
↵↵
key. The
sequence is automatically terminated when the sensitivity of all detectors has been indicated in the display:
If a total sensitivity check is to be carried out, select the "TOTAL" menu option under the "ADDRESS" sequence by moving the cursor to "TOTAL"
with the arrow keys and press the
↵↵
key. The sequence is carried out the
same way as described above and a selection between printer or display can be made.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 37 Autronica Fire and Security AS
10.1.2 Beyond-limit
If "SENSITIVITY" and then "BEYOND-LIMIT" are selected from the menu, only detectors beyond limits are listed out in the display or on the optional printer. The following text will appear in the display:
ADDRESSES SENSITIVITY BEYOND LIMITS HIGH LEVEL: 100 LOW LEVEL: 045
The limits appearing in the display are preset at the factory. Detectors having a sensitivity beyond these limits should be serviced.
The preset limits can be changed by means of the arrow keys. The
↵↵
key
must be pressed to activate the function.
Also in this sequence it is necessary to select if the result shall be presented in the display or printed out on the optional printer. If the display is selected, each detector address beyond the preset limits will be indicated for approx. 5 seconds. The following text appears in the display:
SENSITIVITY BEYOND LIMITS TESTING ADDRESS: 001 XXX PRESS
↵↵
TO STOP
This sequence will be automatically completed when all detector addresses beyond limits have been listed, or when the
↵↵
key is pressed.
The following text will appear in the display:
SENSITIVITY BEYOND LIMITS TESTING ALL EXAMINED. XXXX BEYOND LIMIT
A smoke detector exposed to air pollution, dust or similar environment will slowly be polluted and may approach the alarm limit. This can lead to an unwanted alarm. When an address reaches the monitoring level (Between 96 - 103 answer pulse), the BS-100 DYFI function will automatically raise the alarm limit so that the quiescent value and alarm level threshold is maintained.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 38 Autronica Fire and Security AS
10.1.3 Polluted
If "SENSITIVITY" and then "POLLUTED" are selected, the following text will appear in the display:
ADDRESSES POLLUTED (LIMIT 9:00) PRINTER DISPLAY RET MM
As indicated above, a selection has to be taken if the information is to be given in the display or printed out on the optional printer. When this selection has been made, only those detectors which have had their alarm level raised will be shown.
All indicated detectors should be serviced.
10.2 Internal
Main menu
System Sensitivity Internal Program-version Configuration Adjust-clock Data Show-clock
10.2.1 Program-version
If "SYSTEM", "INTERNAL" and then "PROGRAM-VERSION" are selected by means of the arrow keys, it is possible to see the programme version present in the system. The following text will appear in the display:
INTERNAL PROGRAM VERSION PROGRAM: X-XX SYSTEM-TEXT: X-XX
"SYSTEM TEXT" indicates the menu program version.
Internal
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 39 Autronica Fire and Security AS
10.2.2 Adjust-clock
If "SYSTEM", "INTERNAL" and then "ADJUST-CLOCK" are selected by means of the arrow keys, it is possible to adjust the built-in clock. The following text will appear in the display:
ADJUST DATE AND TIME DATE: dd.mm.yy TI: hh.mm RET
Adjustment of date and time will be stored in "STORED EVENTS" described in section 8.
10.2.3 Show clock
If "SYSTEM", "INTERNAL" and then "SHOW-CLOCK" are selected by means of the arrow keys, it is possible to check that the clock shows the correct time. The following text will appear in the display:
SHOW DATE AND TIME DATE: dd.mm.yy TI: hh.mm RET MM
10.3 Configuration
See "Commissioning Handbook" - BS-100.
Configuration
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 40 Autronica Fire and Security AS
10.4 System-Data (password protected)
Changing of display and printer texts are password protected on operators level (1). Changing of output controls, alarm outputs and disabling groups are password protected on service level (2).
Main menu
System Sensitivity Internal Configuration 1,2) Data Change 1) Changing of display and printer texts.
2) Changing of output controls, sounder outputs and disabling groups. Add Printout Detector data Printer texts
All changes and additions to custom designed text, controls, alarm outputs, groupings and printer texts can be implemented in this function. A print-out of all custom text data/site data can also be made by using this function. The function is password protected.
Note! Changing of addresses between programmed zones is not possible through the key-pad.
By selecting “SYSTEM” and then “DATA” after having input the password, the following text will appear in the display:
DATA CHANGE ADD PRINTOUT RET MM
Select the required function by means of the arrow keys and press the
↵↵↵↵ key.
Data
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 41 Autronica Fire and Security AS
10.4.1 Change (site data)
The “CHANGE” function gives possibilities for changing the existing data. Password level 1 only for changing display and printer texts. Password level 2 gives possibilities to change all custom data.
The function has limited capacity. Max. 30 addresses can be changed or added. When selecting "SYSTEM", "DATA" and "CHANGE" the following text will appear in the display:
CHANGE SITE DATA ADDRESS: 0000 RET MM
When the address in question is selected by means of the arrow key, press
the
↵↵↵↵ key.
10.4.1.1 Display text - Change (Password protected on level 1)
The customised designed text will appear in the display eg.:
SITE DATA ADDRESS 0001 0001 LABORATORY 1. FLOOR . ROOM 3. ßßßß
By means of the two arrow keys Þ the cursor is moved to left or right. The changes are carried out by moving the cursor to the letter or figure to be changed and pressing the ß Ý arrow keys. Letters in alphabetic order, figures and special signs scroll every time one of the two keys is pressed.
After changing the display text, move the cursor to the end of the line and then the reference number for the printer text will appear in the display ( password level 1).
10.4.1.2 Printer text - Changes (Password protected on level 1)
On password level 2, the output control data will appear on the display when moving the cursor to the end of the line.
SITE DATA ADDRESS 0001 PRINTER TEXT 0001 ßßßß ÝÝÝÝ
Change the ref. number for the printer text and move the cursor to the end of the line.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 42 Autronica Fire and Security AS
The following text will appear in the display:
SITE DATA ADDRESS 0001 SAVE-NEW-DATA ? RET MM
Keep the cursor in position "SAVE-NEW-DATA" and press
↵↵
key.
Changing of output controls and alarm outputs require password level 2 (service level).
11. Feed paper
Main menu
Feed paper
When "FEED PAPER" is selected from the main menu a fixed length of paper is fed from the optional printer each time the
↵↵
key is pressed.
If the
↵↵
key is kept constantly pressed, the paper feed continues until the
pressure on the key is released.
12. Service
Main menu
Service
See "Commissioning Handbook" - BS-100.
Feed paper
Service
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 43 Autronica Fire and Security AS
Appendix A - Country variations
A.1 Strapping
Within the menu / system text EPROM’s there is a country code that must correspond to the code set with the function code straps (jumpers) W14, W15, W16 and W17 located on the main board BSA-100. The function code is used inside the system program to perform the required functions for that particular country or market, (e.g. SOLAS and Offshore etc.).
Country Program code Function code Menu program 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Norway P5-BS100-3N20 X X X Sweden P5-BS100-3S20 X X X X Denmark P5-BS100-3D20 X X X England P5-BS100-3E20 X X X X Finland P5-BS100-3F20 X X X Holland P5-BS100-3H20 X X X Italy P5-BS100-3I20 X X X X Hungary P5-BS100-3U20 X X X X Germany P5-BS100-3T20 X X X X France P5-BS100-3A20 X X X X Spain P5-BS100-3P20 X X X X Poland P5-BS100-3L20 X X X
Strapping W14 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 field W15 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 ref. fig. 2.6 in W16 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 Comm. handbook W17 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
*) Function code 8 is SOLAS version **) Function code 15 is OFFSHORE version I = Installed strap 0 = Open strap
Function codes and belonging functions
Function code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Function no.
Function number 0 7 2 1 1 5 0 0 16 7 0 1 0 0 0 16 See description 12 3 4 3 11 22 12 4 22 15 14 8 6 15 23 15 10 24 18 15 9 13 18 21 25 19 17 10 15 20 23 20 23 16 21 23
Menu Program P5
- BS100 - XNXX
Version no.
Language (N = Norwegian) Program no. Control panel type Menu program
System Program P1
- BS100 - XXX
Version no.
System program
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 44 Autronica Fire and Security AS
Functions:
Function Description of function
no. 0 Standard function 1 LED no. 2, Lights up when alarm sounders are disabled 2 LED no. 2, Lights up when address control is activated 3 LED no. 3, Lights up when front door is open 4 LED no. 3, Lights up when BMA is disabled 5 Mains LED, Lights when the central panel has working voltage 220V AC or 24V DC. 6 Mains LED, Lights when the central panel is in normal condition 7 LED, “More alarms” is pulsating when more alarms is active, and switched off at the first registrated alarm in the scrolling function 8 Internal buzzer gives signal when detectors are disabled. Silence by pressing silence sounder button. 9 Internal buzzer gives signal when BMA and AK are disabled. Can not be silenced by silence sounder button. 10 Internal buzzer gives signal after pressing silence sounder button in alarm condition. 11 Internal buzzer gives signal every 4th minute when the front door is closed and the central panel is in abnormal condition 12 Disabling of internal buzzer when the front door is open 13 Disabling of BMA, BMFO and BMF when the front door is open 14 Disabling of BMA, BMFO, BMF and output control when the front door is open 15 Output no. 10 (SP) is active when the front door is open 16 System message is given 1 minute after interrupt of 220 VAC 17 System message is given 30 minutes after interrupt of 220 VAC 18 Silence sounders and reset buttons have to be operated for more than 2 seconds 19 Only 4 digit of text on the first line, additional text on the second line 20 BMF is active in normal condition and “OPEN” in fault condition. Resets to active at silence sounders. 21 Disabling of detectors and alarm sounders can be password protected on operator level in different countries 22 Alarm delay for marine installations (SOLAS). See special description. 23 Automatic disabling of detectors in alarm condition after reset has to be accepted within 10 seconds. 24 No automatic disabling of detector in alarm condition after reset 25 Reset time is programmed to be a minimum, also after alarm
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 45 Autronica Fire and Security AS
Appendix A.2 - Functions
A.2.1 SOLAS (Safety of life at sea)
SOLAS program version can be chosen for any language.
Verification before automatic disablement, see section 3.2 and 4.2 in the "Operators Handbook"- BS-100.
If one or more addresses are still in an alarm condition after the "RESET" procedure, an operator acknowledge is required to have these addresses disabled. At the end of the "RESET" procedure the following text will appear in the display:
ADDRESS(ES) STILL IN ALARM TO DISABLE PRESS
↵↵
WITHIN 10 SECONDS
If the
↵↵
key is not acknowledged within the limit of 10 seconds, new alarms
will be given for these addresses.
By pressing the
↵↵
key within the time limit, the address will automatically
be disabled. To find the addresses concerned, the menu function "SHOW­STATUS", "DISABLEMENTS" should be used.
Alarm delay (T1, T2), see section 3.2 and 4.2.
If the silent alarm input is active the alarm outputs will be delayed by period T1 at alarm from an automatic detector. In the standard version the additional alarm delay period T2 will be started when the "SILENCE SOUNDERS" button is pressed.
For the SOLAS version the alarm delay T2 will not be activated by operate "SILENCE SOUNDERS" and the alarm outputs will be blocked.
This means that there will be no automatic alarm after ended alarm delay T1. If "SILENCE SOUNDERS" is not operated, there will be an automatic alarm at the end of T1.
If more than one alarm is present within time limit of alarm delay (T1), the alarm delay will proceed unchanged from the first alarm and to the end of the selected alarm delay. If "SOUNDER SILENCE" is operated within selected alarm delay, the AK/BMA-outputs will be blocked. If new alarms are registered after operating the "SOUNDER SILENCE", a new delay period will start from the time the new alarm is registered. If the AK/BMA-outputs are required to be activated the silent alarm input must be removed or a manual call-point operated.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 46 Autronica Fire and Security AS
A.2.2 - LPC (England)
Disablement of loop (under service-menu) activates the internal buzzer.
If one or more addresses are still in alarm condition after the "RESET" procedure, an operator acknowledge is required to have these addresses
disabled by pressing the
↵↵
key on the front panel (as SOLAS).
Disablement of internal buzzer is not allowed.
Disabling the sounders through the menu will illuminate the "SOUNDERS DISABLED" lamp.
Disablement of the fire brigade output will illuminate the "FIRE BRIG. DISABLED" lamp.
A.2.3 - Denmark
If one or more addresses are still in alarm condition after the "RESET" procedure, an operators acknowledge is required to have these addresses
disabled by pressing the
↵↵
key on the front panel (as SOLAS).
BMA, BMFO, BMF and output controls are disabled when the front door is open. System fault is given after 30 minutes interrupt of 220V AC.
A.2.4 - Sweden
Inverted BMF-output (active when there is voltage on the control panel).
Internal buzzer is disabled when front door is open.
Sounder silence and reset button must be pressed for more than 2 seconds to activate the function.
Custom specified address text is presented on line 2.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 47 Autronica Fire and Security AS
Appendix B - Replacing the paper roll in the optional printer
If a printer is fitted, it is located on the inside of the control panel inner door.
A: Open the control panel inner door. B: Remove the empty roll by releasing the locking clip on the right-
hand side of the paper roll shaft, and pull the shaft out to the other side (See fig. A). C: Let the free end of the new paper roll point downwards. Bend it and guide it into the printer paper slot in the lower end of the printer. (See fig. A). D: Bend the end of the paper in an arrow shape to simplify the import into the printer paper slot. E: Put the new paper roll in its correct place, insert the paper roll shaft again and secure it by means of the locking clip.
Fig. A: Side view of the optional printer located at the rear side of the inner door.
Fig. B: Location of the finger screw on the optional printer (front view).
F: Feed the paper manually through the printer by turning the finger screw. (See fig. B) G: Close the control panel inner door.
Paper slot
Paper roll
Paper roll shaft
Locking clip (left hand)
Control panel inner door
Printer paper
Ribbon container
Finger screw
Paper roll
Slot for ribbon
Adjusting wheel for ribbon
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 48 Autronica Fire and Security AS
Appendix C - Multiple BS-100/-Control panels with common repeater units (BU-100/101/70)
There is no communication between the individual BS-100 control panel. Each individual BS-100 control panel gives warning about its own condition and relays this to the common BU-units.
(BU-units, common name for repeater units BU-100, BU-101 and BU-70).
- Custom designed texts within each BS-100 control panel is presented to all BU-units.
- The EA-computer has to contain a special system program for comm. with BU-units.
- Digital in-/outputs can be used as supplement function from EA-.
The table below shows which operator buttons. Indication lamps are fitted to the various BU-units.
Indication lamps BU-100 BU-101 BU-70
H1 Indicator lamp X X H2 Indicator lamp X X H3 Indicator lamp X X Device(s) still in alarm cond. X X Prewarning X X X Fault X X X Function disabled X X Mains X X X More alarms X X X
Operation buttons
More alarms X X X Sounder silence X Sounder silence (buzzer) X X Reset X
A
BS-100
Fire alarm control
panel
BS-100
Fire alarm control
panel
BS-100
Fire alarm control
panel
EA-
Protocol
Interfacer
Display-unit
(BU-unit)
Display-unit
(BU-unit)
A
B
C
CL
CL
CL
Programversion in EA-: P1-EAC4/A1-22
* Program variant 1XX (ex. 103) promises that the program is communicating with BU-units.
Digital inputs
Digital outputs
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 49 Autronica Fire and Security AS
C.1 Alarm /Prewarning / Fault /More alarms
BU-units can be programmed to present fire alarm, prewarning and fault with text on the display.
C.1.1 Fire alarm from a BS-100
Fire alarm message (panel address, loop, detector no. or custom text) will only appear in the display of the BS-100 control panel which has registered the incident and on the BU-units.
BU-100 will present alarm from all detectors, BU-70 and BU-101 can be programmed into presentation zones.
Fire alarm message will only appear in the display of the BS-100 control panel even if the door is open.
Internal buzzer and FIRE indication lamps will be activated on the BS-100 control panel which registered the fire alarm and on the BU-units.
Only the BMA-output on the control panel which registered the fire alarm will be activated.
Only the control outputs on the BS-100 control panel which registered the fire alarm will be activated.
Only the sounders connected to the control panel which registered the fire alarm will be activated.
Alarm output on the EA- will be activated (output L57).
C.1.2 Prewarning
Prewarning message (panel address, loop, detector no. or custom text) will only appear in the display of the BS-100 control panel which registered the prewarning and on the BU-units.
If the front door is open on the BS-100 control panel, there will be no message in the display or transmitted to the BU-units. The message will appear when the door is closed.
Internal buzzer and PREWARNING indication lamps will be activated on the BS-100 control panel which registered the prewarning and on the BU­units. Only the BMFO-output on the control panel which registered the prewarning will be activated. Prewarning output on the EA- will be activated (output L58).
!
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 50 Autronica Fire and Security AS
C.1.3 Fault
Detector-/System faults registered on a BS-100 control panel will only give message to that control panel and on the BU-units. On the BS-100 control panel the fault message will appear in the display. Internal buzzer and FAULT indication lamp will also be activated.
If the door is open on the BS-100 control panel, there will be no fault message in the display. The message will appear when the door is closed.
On the BU-units the internal buzzer and the FAULT indication lamp will be activated. (No text in the display)
Fault output (not comm.fault) on the EA- will be activated (output L59).
Only the BMA-output on the control panel which registered the fault will be activated.
If a communication failure between the BS-100 control panel and the EA occurs, the fault message will be printed out on the printer on the BU-units. Comm.fault output BS-/EA- will be activated (output L61).
When there is a communication failure between the EA and the BU-units the comm.fault output EA-/BU- will be activated (output L62).
C.1.4 More alarms
The "MORE ALARMS" indication lamp will light on the BS-100 control panel which is registering more than one alarm. When there are two alarms on different BS-100 control panels, the "MORE ALARMS" indication lamp will not light.
The "MORE ALARMS" indication lamp on the BU-units will light if there are more than one alarm registered in the system. Two alarm from two different BS-100 control panels will activate the "MORE ALARMS" indication lamp on the BU-units.
C.1.5 Device(s) still in alarm cond.
After "RESET" the "DEVICE(S) STILL IN ALARM COND." indication lamp may light on the BS-100 control panels which still has addresses in alarm condition. If this lamp lights on one of the BS-100 control panels, it will also light on the BU-units.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 51 Autronica Fire and Security AS
C.1.6 Function disabled
The "FUNCTION DISABLED" indication lamp will only light on the control panel which is partly disabled. If this lamp is illuminated on one of the BS-100 control panels, it will also light on the BU-units.
C.1.7 Indication lamps H1, H2, H3
The indication lamps H1, H2 and H3 on the BS-100 control panel are controlled separately.
The indication lamps H1, H2 and H3 on the BU-units are controlled from the control outputs on the EA 2/3 (input L51, 52, 53).
C.2 Operation
C.2.1 SOUNDER SILENCE
C.2.1.1 From fire alarm control panel
When "SOUNDER SILENCE" button on the BS-100 control panel which has registered the alarm is operated, all alarm devices connected to this control panel and the internal buzzer on the BU- units are switched off. If another BS-100 control panel also is in alarm condition, "SOUNDER SILENCE" also must be operated at that control unit.
C.2.1.2 From EA- or BU-100
If the "SOUNDER SILENCE" is operated from the EA 1/2/3 (separate input) or the BU-100, all alarm devices and internal buzzers on all BS-100 control panels will be silenced.
C.2.2 Reset
C.2.2.1 From fire alarm control panel
When operating the "RESET" on a control panel in abnormal condition (all other control panels are in normal condition), this will reset the entire system. If another BS-100 control panel is in abnormal condition, operating of the "RESET" will only reset the control panel which is operated. To reset the entire system (BS-100 and BU-units) operate the last control panel in abnormal condition.
C.2.2.2 From EA- or BU-100
Operating of the "RESET" from EA 1/2/3 or BU-100 will reset the entire system.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 52 Autronica Fire and Security AS
C.2.3 More alarms
When operating the "MORE ALARMS" on the individual BS-100 control panels, it is only possible to scroll alarms registered in that particular BS­100 control panel which has been operated.
When operating the "MORE ALARMS" on BU-units, it is possible to scroll alarms registered in the entire system.
C.3 Disable / Restore
Disablements on a BS-100 control panel will activate "FUNCTION DISABLED" only on this control panel and on the BU-units.
Disablements will be stored in "STORED-EVENTS" and only showed in the menu "SHOW-STATUS DISABLEMENTS" on the control panel where the disablement was carried out.
Disablements / restorations of address, zone, controls, sounders and Fire brigade can only be carried out on the individual BS-100 control panel.
C.4 System
C.4.1 Sensitivity
Sensitivity control must be carried out at each individual BS-100 control panel.
C.4.2 Internal
The real-time clock in BS-100 control panels has to be set manually via menu. The EA- clock will be set equal to the clock in control panel with address A.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 53 Autronica Fire and Security AS
Appendix D - BS-100 master / Control unit with BS-60 slaves
When a condition (fire, fault, prewarning) is registered on a control panel (BS-100/BS-60), the indication lamps on the panel front will light, the outputs will be activated etc. in the normal way.
The custom texts presented in the display on both BS-100 and BS-60 have to be manually programmed in both control panels.
There is no communication between the BS-60 control panels.
D.1 Alarm /Prewarning / Fault/ More alarms
D.1.1 Fire alarm
Fire alarm from the BS-100 control panel is only registered on the BS-100 control panel. There will be no display of info. on the BS-60 control panel(s).
Fire alarm from a BS-60 control panel is registered on the relevant BS-60 control panel and on the BS-100 control panel.
There will be no display of info. on any other BS-60 control panel.
BS-60 Fire alarm control panel 1 loop
BS-60 Fire alarm control panel 1 loop
BS-60 Fire alarm control panel 1 loop
BS-60 Fire alarm control panel 1 loop
BS-100 Main fire alarm control panel
KDL-26 Comm. line splitter
CL
CL
CL
CL
CL
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 54 Autronica Fire and Security AS
D.1.2 Prewarning
Prewarning from the BS-100 control panel is only registered on the BS-100 control panel. There will be no display on the BS-60 control panel(s).
Prewarning from a BS-60 control panel is registered on the relevant BS-60 control panel and on the BS-100 control panel.
There will be no display of info. on any other BS-60 control panel.
D.1.3 Fault
(The BS-100 control panel will look at the BS-60 control panels as ordinary loops).
Fault from the BS-100 control panel is registered on the BS-100 control panel. There will be no display of info. on BS-60 control panel(s).
Fault from a BS-60 control panel is registered on the relevant BS-60 control panel and on the BS-100 control panel.
D.1.4 More alarms
More alarms from the BS-100 control panel will only be registered on the BS-100 control panel. There will be no display of info. on the BS-60 control panel(s).
More alarms from a BS-60 control panel will also be registered as more alarms on the BS-100 control panel. There will be no display of info. on other BS-60 control panels.
2 alarms from 2 different BS-60 control panels will be registered as more alarms on the BS-100 control panel.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 55 Autronica Fire and Security AS
D.2 Operating
D.2.1 Sounder Silence
The "SOUNDER SILENCE" function will be dependent upon how it is configured within each of the BS-60 control panels.
When operating the "SOUNDER SILENCE" on the BS-100 control panel, all alarm devices will be switched off (also devices connected to the BS-60 control panels).
If the "SOUNDER SILENCE" function is set to "OFF", the "SOUNDER SILENCE" can only be operated from the BS-100 control panel.
If the "SOUNDER SILENCE" function is set to "ON", the "SOUNDER SILENCE" can be operated from both the BS-60 and the BS-100 control panel.
If the "SOUNDER SILENCE" is operated from a BS-60, alarm devices connected to the BS-60 control panel which is operated, will be switched off.
D.2.2 Reset
The "RESET" function will also be dependent upon how it is configured within each of the BS-60 control panels.
When operating the "RESET" from the BS-100 control panel, the entire system will be reset.
If the "RESET" function is set to "OFF", the "RESET" can only be operated from the BS-100 control panel.
If the "RESET" function is set to "ON", the "RESET" can be operated from both the BS-100 and the BS-60 control panel.
When operating the "RESET" from the BS-60 control panel, only the BS-60 which is operated will be reset.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 56 Autronica Fire and Security AS
D.3 Disable / Restore
When disabling on a BS-60 control panel, the "FUNCTION DISABLED" indication lamp will light only on this control panel.
This will be logged in "SHOW-STATUS DISABLEMENTS" and in "STORED-EVENTS" only on the current control panel.
It is advisable to disable / restore BS-60 addresses from the BS-100.
D.3.1 Address
The BS-100 can disable/restore all addresses in the system. The BS-60 can only disable/restore addresses connected to it.
D.3.2 Zone
Only zones defined in the BS-100 control panel can be disabled/restored from the BS-100 control panel. Zones defined in a BS-60 control panel can be disabled/restored only at the relevant BS-60 control panel.
D.3.3 Controls
Controls connected to the BS-100 control panel can only be disabled/restored from the BS-100 control panel.
Controls connected to the BS-60 control panel can only be disabled/restored at the relevant BS-60 control panel.
D.3.4 Sounders
Sounders connected to the BS-100 control panel can only be disabled/restored from the BS-100 control panel.
Sounders connected to a BS-60 control panel can only be disabled/restored at the relevant BS-60 control panel
D.3.5 Fire brigade / fighters
BMA, BMF, BMFO outputs from the BS-100 control panel can only be disabled/restored from the BS-100 control panel.
BMA, BMF, BMFO outputs from the BS-60 control panel can only be disabled/restored at the relevant BS-60 control panel.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 57 Autronica Fire and Security AS
D.4 System
D.4.1 Sensitivity
All addresses in the system (including those connected to the BS-60 control panel(s)) can be interrogated from the BS-100 control panel.
From the BS-60 control panel it is only possible to interrogate the addresses connected to it.
D.4.2 Internal
In all control panels the internal clock has to be set manually.
The internal clocks of all control panels are independent and must be set individually.
BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 58 Autronica Fire and Security AS
Autronica Fire and Security AS is an international company, based in Trondheim,
Norway and has a world-wide sales and service network. For more than 40 years Autronica’s monitoring systems have been saving lives and preventing catastrophes on land and at sea. Autronica Fire and Security’s most important business area is fire detection & security. Autronica Fire and Security stands for preservation of environment, life and property.
Quality Assurance
Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our quality system conforms to the Quality System Standard NS-EN ISO 9001, and is valid for the following product and service ranges: marketing, sales, design, development, manufacturing, installation and servicing of:
fire alarm and security systems
petrochemical, oil and gas instrumentation systems for monitoring and control
In the interest of product improvement, Autronica Fire and Security reserves the right to alter specifications according to current rules and regulations.
Autronica Fire and Security AS Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68
fax: 1923 22 55 77.
Loading...