Product and component descriptions
AutroSense Micra 10 Aspirating Smoke Detector Installers Handbook 3
Specifications
Caution: This equipment is only to be used in accordance with these
specifications. Failure to operate the equipment as specified may cause damage
to the unit, injury, or property damage.
Table 1: Specifications
Specification Value
SELV rating EN 60950 Class III
Supply voltage 21.60 to 26.40 VDC
PSU Type: conforming to EN 54-4
Electrical safety complies with BS EN 610190-1
Size 145 W × 220 H × 90 D mm
(5.7 W × 8.6 H × 3.5 D in.)
Weight 1.7 kg (3.75 lbs.) with docking station
Operating temperature range −10 to +60ºC (EN 54-20)
32 to 100°F (0 to 38°C) (UL 268, CAN/ULC-S529,
FM3230)
Operating humidity range 0 to 90% Noncondensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation category II
Sensitivity range
(%obs/ft.)
(%obs/m)
Min. = 7.62%, Max. = 0.00914% FSD
Min. = 25%, Max. = 0.03% FSD
Maximum sensitivity resolution 0.0015% obs/m (0.00046% obs/ft.)
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003 µm to 10 µm
Current consumption 250 mA
Relay contact rating 500 mA at 30 VDC
Optional relay input card contact rating 1 A at 24 VDC
Maximum sampling pipe length 50 m (165 ft.) total
Sampling pipe inlets 1
Sampling pipe internal diameter 3/4 in. (ID) or 27 mm (OD)
Alarm levels 4 (Fire 2, Fire 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals Greater than 8 years (depending on environment)
Dust separator (filter) replacement
intervals
Greater than 5 years (depending on environment)
Laser lifetime (MTTF) Greater than 50 years
Programming PC via RS-232
IP rating IP50