Autronica AutroSafe 4 Commissioning Handbook

116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01, Autronica Fire And Security AS
Commissioning Handbook
Release 4
COPYRIGHT ©
This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose.
Autronica Fire and Security AS and its subsidiaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security AS. The information in this publication may be updated without notice.
Product names mentioned in this publication may be trademarks. They are used only for identification.
Commissioning Handbook, AutroSafe Interactive Fire Detection System, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01, Autronica Fire and Security
E-1676
This product contains static-sensitive devices . Av oi d an y electrosta tic disc har ge.
The WEEE Directive
When the marking belo w is shown on the product and/or its liter ature, it means t hat the product should n ot be disposed with other household wastes at the en d of its life cycle. During waste treatment, disposal and collection, please separate the product from other types of wastes and recycle it responsi bly to promote the sustainable reuse of material resources. This product should not be mixed with other commercial wastes for disposal.
Introduction
Table of Contents
1. Introduction ...................................................................... 5
1.1 About the Handbook .......................................................................... 5
1.2 The Reader ....................................................................................... 5
1.3 Reference Documentation................................................................. 6
2. Quick Reference Guide ................................................... 7
2.1 Initial Commissioning ........................................................................ 7
2.2 Upgrading System Software and Configuration ................................ 7
3. Verifying the Loops ......................................................... 8
3.1 AS-2000 Loop Diagnostic Tool ......................................................... 8
3.2 Verification Procedure ....................................................................... 8
4. Consistency Check of Configur ati on Da t a ..................... 9
4.1 Introduction ........................................................................................ 9
4.2 Parameters Used for the Consistency Check ................................... 9
4.3 Importing Loop Data from the AS-2000 Tool .................................... 10
4.4 Consistency Check Using the AS-2000 / Config Mismatch Tool ..... 10
4.5 Generating Configuration Files ......................................................... 10
5. Power Commissioning .................................................... 11
5.1 Addressing Power Boards on the AutroFieldBus .............................. 11
5.1.1 Switch Settings on Power Board BSF-400 ............................. 11
5.1.2 Location of Switches ............................................................... 11
5.1.3 AutroFieldBus Addresses ....................................................... 13
5.1.4 Power Board Configuration Switches ..................................... 14
5.2 Calibration Procedure - Power Unit BPS-410 ................................... 15
6. Addressing Panels .......................................................... 16
6.1 Definitions .......................................................................................... 16
6.1.1 Network ID .............................................................................. 16
6.1.2 Panel ID .................................................................................. 16
6.2 Location of Switches ......................................................................... 17
6.3 Assigning Network IDs ...................................................................... 18
6.4 Assigning Panel IDs .......................................................................... 19
7. Verifying the System Bef ore Startup .............................. 21
8. Startup Procedure ........................................................... 22
8.1 Applying Power to the System .......................................................... 22
8.2 IP Number Structure .......................................................................... 24
8.3 Assigning IP Adresses ...................................................................... 24
8.3.1 Automatic Addressing Mode ................................................... 25
8.3.2 Manual Addressing Mode ....................................................... 27
Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 4
8.3.3 Configuration Missing.............................................................. 28
8.4 Configuration File .............................................................................. 29
8.4.1 Name, Format and Extension ................................................. 29
8.4.2 Copying the Zip File to a USB Stick ........................................ 29
8.5 Uploading Configuration Files to the System .................................... 30
8.6 Configuration Mismatch ..................................................................... 33
8.7 Entering Required Access Levels ..................................................... 34
9. Verifying the System after an Upload ............................. 36
9.1 General System Verification Procedure ............................................ 36
9.2 Verifying Detection Loops During Normal Operation ........................ 37
10. Upgrading the System ..................................................... 38
10.1 Introduction ........................................................................................ 38
10.2 Upgrading During Normal Operation (SW/Config) ............................ 38
10.2.1 Introduction ............................................................................. 38
10.2.2 Upgrading Software During Normal Operation ....................... 39
10.2.3 Upgrading Configuration During Normal Operation ................ 39
10.3 Upgrading when Panels are Added/Removed .................................. 40
10.4 Upgrading if IP Addresses are to be Changed.................................. 40
10.5 Upgrading a Single Panel.................................................................. 40
10.6 Upgrading by Remote Access to a Web site..................................... 41
10.7 Upgrading Software Version 4.0.1 to 4.1.1 ....................................... 42
10.7.1 General ................................................................................... 42
10.7.2 Preparing a System in Normal Operation ............................... 42
10.7.3 Preparing a System in System Fault Condition ...................... 43
10.8 Upgrading Software Version 4.0.1 or 4.1.1 to 4.3.1 .......................... 44
10.8.1 Example 1: Upgrading all Panels from SW Version 4.0.1
or 4.1.1 to 4.3.1 ...................................................................... 44
10.8.2 Example 2: Adding a BS-420/BS-430 panel with SW
Version 4.1.1 to a System Running on SW Version 4.3.1 ......
44
10.8.3 Example 3: Adding a BC-420 Controller with SW Version
4.1.1 to a System Running on SW Version 4.3.1 ................... 44
10.8.4 Example 4: Adding a Panel with SW Version 4.3.1 to a
System Running on SW Version 4.1.1.................................... 45
11. Startup Procedure for a Dua l S afe ty System ................. 46
11.1 Introduction ........................................................................................ 46
11.2 Guidelines – Startup Proce dur e ........................................................ 47
12. Fault Messages duri ng Uploading .................................. 49
12.1 Introduction ........................................................................................ 49
12.2 Invalid File on USB Stick ................................................................... 49
12.3 Data Transmission Timeout .............................................................. 49
12.4 Corrupt File ........................................................................................ 49
12.5 Fail to Unpack Files ........................................................................... 50
Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 5
1. Introduction
E-1676
This product contains static-sensitive devices . Always use an antistatic wrist strap / ground bracelet to avoid any electrostatic discharge.
1.1 About the Handbook
This handbook is intended to provide all necessary information for the commissioning of the AutroSafe Interactive Fire Detection System, Release 4.
The handbook covers the commissioning of a standalone system (Fire Alarm Control Panel), as well as the commissioning of a distributed system with several system units, operating on Autronica’s local area network; AutroNet, including:
Power Boards in Power Cabinet BP-405 and
Power Unit BPS-405/BPS-410 (AutroFieldBus addressing)
Fire Alarm Control Panel BS-420 Controller BC-420 / BC-440 Operating Panel BS-430 Repeater Panel BU-BV-420
1.2 The Reader
The handbook is intended to be used by Autronica Fire and Security trained service and technical personnel who are responsible for the installation of the AutroSafe Interactive Fire Detection System, Release 4.
Introduction
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 6
1.3 Reference Documentation
The table below shows an overview of the technical marketing documentation for AutroSafe Interactive Fire Detection System, Release 4.
Document Name
Part number
File name
System Description
116-P-ASAFE-SYSTEMD/EGB
asafesystemd_egb
Installation Handbook
116-P-ASAFE-INSTALL/DGB
asafeinstall_dgb
Commissioning Handbook
116-P-ASAFE-COMMISS/EGB
asafecommiss_egb
User Guide, Remote Access
116-P-ASAFE-REMOTEAC/EGB
asaferemoteac_egb
Connecting Loop Units
116-P-CONNECTLOOPUNIT/DGB
connectloopunit_dgb
Operator’s Handbook
116-P-ASAFE-OPERATE/FGB
asafeoperate_fgb
User Guide
116-P-ASAFE-USERGUI/LGB
asafeusergui_lgb
Wall Chart
116-P-ASAFE-WALLCHA/LGB
asafewallcha_lgb
Menu Structure
116-P-ASAFE-MENUSTR/MGB
asafemenustr_mgb
Datasheet; Fire Alarm Control Panel BS-420
116-P-BS420/CGB
bs420_cgb
Datasheet; Operator Panel BS-430
116-P-BS430/CGB
bs430_cgb
Datasheet; Repeater Panel BU-BV-420
116-P-BUBV420/CGB
bubv420_cgb
Datasheet; Fire Brigade Loop Panel BU-110
116-P-BU110/CGB
bu110_cgb
Datasheet; Information Loop Panel BV-110
116-P-BV110/CGB
bv110_cgb
Datasheet; Controller BC-420
116-P-BC420/CGB
bc420_cgb
Datasheet; Controller Unit Rack BC-440
116-P-BC440/CGB
bc440_cgb
Datasheet; Power Cabinet BP-405
116-P-BP405/CGB
bp405_cgb
Datasheet; Power Unit BPS-405
116-P-BPS405/CGB
bps405_cgb
Datasheet; Power Unit BPS-410
116-P-BPS410/CGB
bps410_cgb
Datasheet; AutroKeeper BN -180
116-P-BN180/CGB
bn180_cgb
Quick Reference Guide
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 7
2. Quick Reference Guide
This quick reference guide outlines all the necessary steps to successfully commission the AutroSafe Interactive Fire Detection System the very first time, assuming that the system software is already uploaded to the system, and no configuration files have been uploaded.
Configuration upgrade and system software upgrade are described in a separate chapter (Chapter 10).
2.1 Initial Commissioning
Step Action Chapter
1
Verify the detection loops by means of the AS-2000 tool.
Chapter 3
2
Perform a consistency check of the configuration data using the results from the AS-2000 verification and the data that has been configured by means of the AutroSafe Configuration Tool.
Chapter 4
3
Assign an AutroFieldBus address to each Power Board BSF-400 (rotary switches) / AutroFieldBus unit.
Chapter 5
4
Assign a Network ID to each panel by means of rotary switches (on BSA-400).
Chapter 6.3
5
Assign a Panel ID to each panel by means of switches (dip­switches and rotary switches on BSA-400).
Chapter 6.3
6
Verify the system before startup
Chapter 7
7
Apply power to the system
Chapter 8.1
8
Assign an IP Address to each panel
Chapter 8.3
9
Upload configuration data to all panels from one central point (a panel).
Chapter 8.5
10
Verify the system after an upload
Chapter 9
2.2 Upgrading System Software and Configuration
For information regarding configuration upgrade and system software upgrade, refer to Chapter 10.
Verifying the Loops
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 8
3. Verifying the Loops
3.1 AS-2000 Loop Diagnostic Tool
All loops should be verified with the AS-2000 Loop Diagnostic Tool before startup. Although this is presumably already done at an earlier stage (shortly after the installation), it is recommended that all loops are verified once again in case minor changes have been done. By doing this, you will eliminate possible pr ob lems which could occur during the startup procedure and upgrading of configuration data.
The AS-2000 allows you to find all points connected to the selected loop driver, and present them graphically.
AS-2000 can be connected directly to an AutroSafe operating panel, or directly to a detection loop by means of an external interface unit, WAS-2000.
3.2 Verification Procedure
Pressing the START button in the Topology window (AS-2000) tells AS-2000 to find all points connected to the selected loop driver, and present them graphically in a correct electrical sequence. Points will be presented with unique symbols for each type of Loop Unit, and wi th important information such as Production Number (PN), and the Loop Sequence Index (LSI). In case of illegal topologies, like multiple branch-offs and loop breaks, these will be presented with self­explaining symbols.
Use the AS-2000 to;
register all loop units on each loop, including:
the Loop Unit type (detector type, manual call point, electronic sounder, I/O unit)
Loop Sequence Indexes LSI (order/location)
register all branch offs and loop break positions locate any breaks on the loop wire (both positive and negative
wires)
measure the loops’ total resistance, current consumption and
voltage drop
earth fault
You will find detailed information on the installation and use of AS-2000 in the User Guide, AS-2000 Loop Diagnostic Tool.
Consistency Check
of Configuration Data
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 9
4. Consistency Check of Configuration Data
4.1 Introduction
4.2 Parameters Used for the Consistency Check
The table below provides a description of two of the parameters that are used for the consistency check. These parameters are shown in the Topology View in AS-2000, as well as in the topology view in the AutroSafe Configuration Tool.
Parameter
Abbreviation
Description
Illustration
Loop Unit
The loop unit can be a detector, a manual call point, a loop sounder or an I/O unit.
(Examples)
Heat detector (BD-200/300/500) Optical smoke detector (BH-200/300/500) MultiSensor detector (BH-220/320/520)
Manual callpoint (BF-200/300/500)
Electronic addressable sounder (BBR-200)
Input / Output unit (BN-300, BN-310, BN-320 etc.)
Loop Sequence Index
LSI
A loop specific index telling the exact Loop Unit order on the loop (sequencially numbered).
A branch-off is described by a decimal followed by a sequencial index.
NOTE: To ensure a problem-
free upload of configuration data, always
perform a consistency check, using the results from the AS-2000 verification and the data that has been configured by means of the AutroSafe Configuration Tool.
(Example)
Consistency Check of Configuration Data
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 10
4.3 Importing Loop Data from the AS-2000 Tool
The AutroSafe Configuration Tool features an Import command allowing you to import loop data directly from the AS-2000 Loo p Diagnostic tool. In this way, it is possible to ensure that the point types and sequence indexes in the configuration will be identical to the real loop. Tag Names and optional Detection Zones (DZs) will be assigned to the points during import.
For further information, refer to the Help System for AutroSafe Configuration Tool and the User Guide for the AS-2000 Loop Diagnostic Tool.
4.4 Consistency Check Using the AS-2000 / Config Mismatch Tool
4.5 Generating Configuration Files
System configuration is done from a computer by the means of the AutroSafe Configuration Tool. This tool allows you to generate configuration files, which then can be uploaded to target after the system has been verified.
The AutroSafe Configuration Tool allows you to do a consistency check of configuration data by means of a menu called AS-2000 / Config Mismatch Tool (in the Tool menu).
This feature allows you to easily compare the actual configuration data downloaded from a detection loop and imported to the AutroSafe Configuration Tool (using the AS-2000) with the configuratio n d ata you have entered in the AutroSafe Configuration Tool.
Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 11
5. Power Commissioning
5.1 Addressing Power Boards on the AutroFieldBus
5.1.1 Switch Settings on Power Board BSF-400
The board is configured by means of two switches:
Rotary switches X10 and X11 - AutroFieldBus address switch.
Each Power Board is given a unique address.
Dipswitch S5/S6 – configuration (refer to dipswitch table, chapter
5.1.4)
5.1.2 Location of Switches
The location of the dipswitch S5 and S6, plus the rotary switches X10 and X11 are shown on the drawing.
Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 12
1 2 3
AFB A AFB A"
AFB CT A 4 5 6
AFB Earth Fault Sense
AFB B
AFB B" 7 8
AFB CT B
AFB Earth Fault Sense
J2
1
6 1 2 3
A A
R 4 5 6
F
F
F
F1 F2
J19
S1 Reset
High Low
8 7 6 5 4 3 2 1
J24
J23
J22
0V
C2
J21
F2AL
F3 B1
F2AL
F4 B2
F2AL
F5 C1
F2AL
F6 C2
A
1 2 3
Earth Fa Battery AFB pre
4 5 6
Battery
61
S6
ON
OFF
15
5 4 3 2 1
Therm.+ Therm.­PSF
-V Vcon
+
-
BATT
J20
J17
F7 Battery
F8 Charger
1
Charger +24V
J18
+
0V
+
C1
0V
+
B2
0V
+
B1
0V
+
A2
0V
+
A1
X11
X10
BP-410/01 BP-405/01
T10T5T10
T5
F7 F8 AH AH AH AH
S5 AFB Earth Fault Off AFB Earth Fault On
1
OFF
ON
2
OFF
ON
Dipswitch S6
AutroFieldBus
Address Switch
X10, X11
Dipswitch S5
S1 Reset button
Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 13
5.1.3 AutroFieldBus Addresses
Each AutroFieldBus unit/Power Board BSF-400 on an AutroFieldBus must be assigned a unique address by means of an rotary switch (see previous page). The drawing below shows the AutroFieldBus connections on the main terminal block, list L1 mounted on a DIN rail inside the cabinet (BS-420/BC-420). The first AutroFieldBus unit is connected to the terminals L1.9 / L1.11 (AFB A). The last unit is connected to L1.3 / L1.5 (AFB B).
CT (CenterTap) of transformer shall not be connected (terminal 3 and
11). Shield is connected to earth at one end only.
L1.3
L1.5 L1.7
L1.15
L1.9 L1.11 L1.13
Last AFB unit
First AFB unit
SA 400 with shielded AF cable
A maximum of 31 AutroFieldBus units can be connected to one AutroFieldBus, giving the number range 01 to 31. The physical addresses are set by means of the rotary switches on the board. The illustration below shows an example of the system topology window. 4 AutroFieldBus units are added to the AutroFieldBus interface.
The sequence of the units in the topology window determines the switch settings on each unit, i.e. the first unit (the uppermost unit in
the topology window) is to be given switch address 01, the next is to be given switch address 02, and so on. Note that the physical sequence of AutroFieldBus units on the AutroFieldBus must not necessarily corres p ond to the s equence shown in the topology window, however this is recommended.
Addressing AutroFieldBus units on the AutroFieldBus
Fire Alarm Control
Panel BS-420
BSA-400
BSF-400
BSD-321
BSF-400
AutroFieldBus
Switch Address 01
BSF-400
Switch Address 02
Switch Address 03
Switch Address 04
Always address 00
The first AutroFieldBus unit
Example: System topology window in the AutroSafe Configuration Tool
Switch address 01
Switch address 02 Switch address 03 Switch address 04
Main terminal block, list L1
inside the BS-420/BC-420
AFB
AFB
Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 14
5.1.4 Power Board Configuration Switches
The settings of the dipswitches are read during startup. If the switches are changed for any reason, the changes will not take affect until the Power Board is restarted (pressing the reset button S1 on the Power Board).
Dipswitch table – S5
S5.1
S5.2
Function
OFF
OFF
AutroFieldBus earth fault OFF
ON
ON
AutroFieldBus earth fault ON
Dipswitch table – S6
Switch
Name
Comment
S6-1 Earth Fault
ON: Earth fault monitoring
activated OFF: Earth fault monitoring
deactivated
S6-2 NA
Must always be set to OFF
(default).
S6-3 AutroFieldBus
ON: AutroFieldBus connected
OFF: AutroFieldBus not
connected
S6-4
NA
-
S6-5
Battery
ON: Battery connected OFF: Battery not connected
S6-6
Power Unit Type
ON: BPS-405 OFF: BPS-410
Power Commissioning
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 15
5.2 Calibration Procedure - Power Unit BPS-410
When using Power Unit BPS-410 (including a 24V/10A power supply), a calibration procedure must be performed. This is necessary in order to obtain a correct temperature compensated charging voltage to the batteries. The procedure is as follows:
Before applying power to the system, the power supply’s
temperature sensor (thermistor delivered with the power unit) must be temporarily replaced with a fixed 2,2kresistor (terminal point 2 and 6 from the left, marked with a stippled line from terminal point 2 to the thermistor symbol at point 6).
Apply power to the system by connecting the mains cable to the
mains socket or by switching the power ON from an external main fuse box.
Measure the voltage on the BSF-400’s battery terminals (BATT +/-)
while adjusting the voltage with a small screw driver to 27,4V on the power supply (OUT ADJ).
Disconnect mains power from the power supply and remove
charger fuse F8.
Remove the resistor and reinsert the thermistor. Insert the charger fuse F8 and re-connect mains power to the
power supply.
15
5 4 3 2 1
Therm.+ Therm.­PSF
-V Vcon
+
-
BATT
J20
J17
arger
1
+24V
BP-405/01 T5 T5
AH AH AH AH
0V
C2
15
5 4 3 2 1
Therm.+ Therm.­PSF
-V Vcon
+
-
BATT
J20
J17
F7 Battery
F8 Charger
1
Charger +24V
BP-410/01 BP-405/01
T10T5T10
T5
F7 F8 AH AH AH AH
Measure
Adjust
Charger fuse F8
Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 16
6. Addressing Panels
6.1 Definitions
6.1.1 Network ID
A panel’s Network ID indicates which system and unique configuration a panel belongs to. All panels communicating on the same AutroNet network must have the same Network ID, usually set to 01 (switch setting; rotary switches X5 and X3).
The Network ID also determines the specific number series of the IP Addresses (which are set during commissioning by operating the AutroSafe menu).
6.1.2 Panel ID
Each panel in the system must be assigned a unique Panel ID (switch setting; rotary switches X6 and X4, plus the settings of dip-switch S2). For each different panel type (i.e. BS-420 or BU-420) the addressing on the rotary switches always starts on 0-1.
The Configuration Tool generates a catalogue structure with the following number series of Panel IDs for the different panel types. (Note that the physical adressing on the rotary switches does not follow the numbering series generated by the Configuration Tool).
Panel Panel IDs
Number Series
Panel IDs
Hexadecimal
values
BS-420
1-31
01-1F
BC-420
33-63
21–3F
BC-440
33-63
21–3F
BS-430
65-95
41-5F
BU-420
97-159
61-9F
BV-420
161-223
A1-DF
Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 17
6.2 Location of Switches
The switches are located on the lower left hand side of the BSA-400 circuit board, easily access ible throu gh the hol e in the metal cover.
The BSA-400 circuit board
X3
X5
X6
X4
S2
Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 18
6.3 Assigning Network IDs
The settings of the rotary switches X5 and X3 determine the panel’s Network ID, i.e. which system and unique configuration the panel belongs to.
All panels communicating on the same AutroNet network must have the same Network ID, usually set to 01.
X5 is set to 0 X3 is set to 1
If there is a second network, this network can be set to 02, a third can be set to 03, etc.
Switch X5 corresponds to the most significant digit in the address.
X3
X5
Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 19
6.4 Assigning Panel IDs
Each panel in the system must be assigned a unique Panel ID (switch setting; rotary switches X6 and X4, plus the settings of dip-switch S2). For each different panel type (i.e. BS-420 or BU-420) the addressing on the rotary switches always starts on 0-1.
Note that a standalone Fire Alarm Control Panel BS-420 always has Panel ID=00.
Switch X6 corresponds to the most significant digit in the address. Note that the correct switch settings for the panel type in question is
preset at the factory (dipswitch S2) - except for the BU-BV-420 panel, as this panel can be defined both as a Information Panel and Fire Brigade Panel.
The following table deals with the Panel IDs when several panels communicate on the AutroNet (local area network).
Panel
Panel ID
Panel ID
Hex.
values Rotary
switch X6
Rotary
switch X4
Panel Type
Dip-switch S2
0=OFF, 1=ON
Switch 1 2 3 4
BS-420
1-31
01-1F
0-3
0-9
0 0 0 0
BC-420
33-63
21–3F
0-3
0-9
1 0 0 0
BC-440
33-63
21–3F
0-3
0-9
1 0 0 1
BS-430
65-95
41-5F
0-3
0-9
0 1 0 0
BU-420
97-159
61-9F
0-6
0-9
1 1 0 0
BV-420
161-223
A1-DF
0-6
0-9
1 0 1 0
X6
X4
S2
Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 20
Example:
A network configuration consists of two BS-420 panels, one BS-430 panel and one BU-BV-420 panel (a BU-BV-420 panel defined as a Fire Brigade Panel).
In this example, the following addressing applies:
Panel
Panel ID
Rotary
switch X6
Rotary
switch X4
Panel Type
Dip-switch S2
0=OFF, 1=ON
Switch 1 2 3 4
BS-420
1 0 1
0 0 0 0
BS-420
2 0 2
0 0 0 0
BS-430
65 0 1
0 1 0 0
BU-BV-420
97 0 1
1 1 0 0
Verifying the System Before Startup
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 21
7. Verifying the System Before Startup
Before verifying the system, all parts in all system units must be installed and properly connected, and all panels and AutroFieldBus units must be addressed correctly. Installation, cabling and connections
Verify all internal cabling in all system units (all panels) Verify that all IO modules in the Fire Alarm Control Panel and
Controller are installed in the cabinet
Verify all external connections in the Fire Alarm Control Panel and
Controller (to detector loops, other input / output connections)
Verify all network connections Addressing Verify that all AutroFieldBus units (Power Boards BSF-400) are
addressed correctly
Verify that all panels are assigned correct Panel IDs Verfiy that all panels are assigned Network IDs Check power for correct mains voltage
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 22
8. Startup Procedure
When the AutroFieldBus units (Power Boards BSF-400, BSD-321 and all panels) have been addressed, and the configuration files have been generated by means of the AutroSafe Configuration Tool, power is to be applied to the system.
The commissioning can take place from any Fire Alarm Control Panel BS-420 or Operator Panel BS-430 in the system (freely selected panel).
During uploading of configuration files (or system software), the system may report possible faults. If such fault messages occur, the panel in question should be rebooted (Service Menu/Upgrade/Reboot). For detailed information on possible errors, refer to chapter 12, Fault Messages during Uploading.
8.1 Applying Power to the System
Always connect the cables to the batteries first, then power up the system by connecting the mains cable to a mains socket (230V/115V AC) or by switching the power ON from an external main fuse box. When power is applied to the system the very first time, an initialization of the system will automatically take place.
Apply power to the system.
The display will show the following information (example):
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. ??
Detecting network structure…
5. Update panel list
The system will automatically detect the network structure that is used, either Star Topology or Ring Topology. If both topologies are detected, the message: “Conflicting Network Structure” will appear, and it will not be possible to proceed.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 23
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2 of 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
IP not set, select addressing mode:
1. Automatic 2. Manual
(Note that, to prepare the system for later reconfigurations or software upgrades, a hardware reset must be performed. Refer to Upgrading the System, chapter 10.)
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 24
8.2 IP Number Structure
Example:
172.16.101.21
172.17.101.117
172.16.101.21
8.3 Assigning IP Adresses
When the initialization is completed, the display will show the following:
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2 of 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
IP not set, select addressing mode:
1. Automatic 2. Manual
If Automatic Mode is selected, default IP Adresses will be assigned to each panel. The number series which is used depends on the switch settings for the panel’s Network ID.
Note: Use automatic addressing mode if you are not absolutely sure how to set IP addresses.
Panel ID (+20), unique ID assigned to each panel. Network ID (+100), identifies the unique network the
panel belongs to.
Subnet ID, common number for all panels. 172.16.x.x
for primary and 172.16.x.x for secondary network.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 25
8.3.1 Automatic Addressing Mode
Selecting Automatic Addres s ing Mode wi ll ass ign default IP Addresses to all panels.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2 of 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
IP not set, select addressing mode:
1. Automatic 2. Manual
Press 1 to select Automatic Addressing.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
NETWORK ADDRESS: 172.16/172.17
BS-420 01.01: 101.21
BU-420 01.01: 101.117
Do you want to save or set manually?
1. Save 2. Set Address Manually
When the automatic addressing is completed, you can either save the automatic addressing (proceed to next step), or set addresses manually (refer to chapter 8.3.2, Manual Addressing Mode).
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 26
To save the addressing, press 1.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2 of 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
Config missing
Verify config on switch settings
3. Upgrade software 4. Upgrade config
6. Reboot panels
When the IP addressing is completed, proceed to chapter 8.5, Uploading Configuration Files.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 27
8.3.2 Manual Addressing Mode
If you have to take into consideration IP Addresses that are already assigned to other existing components on the network, IP Addresses can be set manually. In this way, you can freely select IP Addresses within the given ranges of 3 different number series, each representing a specific class (Class A, B or C).
Note that the standard IP version 4 addressing is applied. This means that once a specific class is selected (A, B or C), only numbers within the range of this class can be selected.
Class A: number series 1-127 Class B: number series 128-191 Class C: number series 192-223
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
IP ADDRESS: 172.16/172.17
BS-420 01.01: 101.21
BU-420 01.01: 101.117
Please set the SUB A network address:
<10 . . . >
<11 . . . >
Set the network addresses If necessary, press 1 to change host address Press 2 to save the manual addressing
When the manual IP addressing is completed, proceed to chapter 8.5, Uploading Configuration Files.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 28
8.3.3 Configuration Missing
If no configuration has been uploaded to the system previously, the message “Config Missing” will be shown.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
Config missing
1. Import config from USB stick
2. Reboot all panels
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 29
8.4 Configuration File
8.4.1 Name, Format and Extension
The AutroSafe Configuration Tool generates the following compressed file:
AC_Vnn_mm_filename.tar.bz2
AC
AutroSafeConfiguration
Vnn
Main interface model number
mm
Sub interface model number
filename
The AutroSafe configuration file name, valid characters are [0-9a-zA-Z] and underscore '_'. If the filename contains non-valid characters the file name will be replaced with the name "Configuration".
The zip file cannot contain more than 127 characters, if so the filename will be truncated.
8.4.2 Copying the Zip File to a USB Stick
Make sure to copy and paste the files in the root directory of the USB stick. Also make sure to remove all other files from the memory stick.
When the configuration zip file is generated by means of the
AutroSafe Configuration Tool, copy the file to a USB memory stick (root catalogue).
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 30
8.5 Uploading Configuration Files to the System
When the IP addressing is completed, configuration files can be uploaded to the system from one central point (any BS-420/BS-430 panel in the system).
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
Config missing
Verify config on switch settings
3. Upgrade software 4. Upgrade config
6. Reboot panels
Press 4 (Upgrade config).
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
Insert USB stick in USB port
Insert the USB memory stick into one of the USB host ports on the
BSA-400 Controller Board.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 31
The following will appear on the display:
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
Transfering to panels (1 of 2)
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
Unpacking to panel (1 of 2)
Please wait, upgrade in progress
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
Upgrading config…
Finished
3. Upgrade software 4. Upgrade config
6. Reboot panels
Remove the USB stick when the uploading is completed, then
press 6 to reboot the system.
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 32
Selection 3. “Upgrade Software” is shown only if the software is not already upgraded.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
Rebooting the system
Please wait, upgrade in progress
When the system is rebooted, the system will enter normal operation mode.
To run initialization, press 1 or wait (countdown).
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 33
8.6 Configuration Mismatch
If the system has an existing configuration, and the new configuration you have uploaded does not match the installation in question, the message “Config Mismatch” will appear.
If the software to be used is not supported by the config model, the message “Config Mod el Mismatch” will appear (see screenshot below).
The “Config Faulty” message will appear if the configuration files for some reason are corrupt.
The “Config Market Mismatch” message will appear if the panel does not match the market that has been selected in the configuration.
Autrosafe software version 4.5.0
Config model 4.5
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1 Commiss. Star
BU-420 01.01: 4.3.1 Commiss. Star
Config model mismatch
Verify Config
3. Upgrade software 4. Upgrade config
6. Reboot panels
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 34
8.7 Entering Required Access Levels
All user interface controls are classified as belonging to one of the different access levels described below:
Access Level
Access Remedy
Description
1 No key or password
required.
Accessible by members of the general public. A ll mand atory indications are visible at access level 1 without prior manual intervention.
2 Access by key.
Accessible by persons having a specified responsibility for safety.
3 Password restricted. Accessible by persons trained and authorized to do
reconfiguration of site specific data and maint en anc e according to the manufacturer’s published instruction.
To be able to verify the system after an upgrade, Access Level 2 must be entered. Access Level 2 is accessed by the key (turn the key counter-clockwise).
Access level 3 is entered as described in the procedure below.
Step
Actions to be taken
Display Indication
1
To enter the Main Menu from normal Operation Mode, press
2
To select SYSTEM, press 4.
19:23
MAIN MENU
1 SHOW STATUS 2 DISABLE 3 ENABLE 4 SYSTEM 5 SERVICE 6 OUTPUT CONTROL
19:23
MAIN MENU
1 SHOW STATUS 2 DISABLE 3 ENABLE 4 SYSTEM 5 SERVICE 6 OUTPUT CONTROL
SYSTEM
1 DATE AND TIME 2 INFORMATION 3 ACCESS LEVEL 3 4 PRINTER 5 CHANGE LANGUAGE 6 INITIALIZE 7 DAY/NIGHT TIMERS
19:23
SYSTEM
1 DATE AND TIME 2 INFORMATION 3 ACCESS LEVEL 3 4 PRINTER 5 CHANGE LANGUAGE 6 INITIALIZE 7 DAY/NIGHT TIMERS
19:23
Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 35
Step
Actions to be taken
Display Indication
3
To select ACCESS LEVEL 3, press 3.
4
To enter ACCESS LEVEL 3, press 1.
5
Enter the password, then press
twice.
SYSTEM
ACCESS LEVEL 3
1 ENTER ACCESS LEVEL 3 2 LEAVE ACCESS LEVEL 3 3 SET PASSWORD
19:23
SYSTEM
ACCESS LEVEL 3
1 ENTER ACCESS LEVEL 3 2 LEAVE ACCESS LEVEL 3 3 SET PASSWORD
19:23
SYSTEM
ACCESS LEVEL 3/ENTER ACCESS LEVEL 3
Enter password:
19:23
SYSTEM
ACCESS LEVEL 3/ENTER ACCESS LEVEL 3
Enter password:
19:23
SYSTEM
ACCESS LEVEL 3/ENTER ACCESS LEVEL 3
Enter password: ****
Successfully Completed
19:23
SYSTEM
ACCESS LEVEL 3/ENTER ACCESS LEVEL 3
Enter password: ****
Successfully Completed
19:23
Verifying the System after an Upload
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 36
9. Verifying the System after an Upload
9.1 General System Verification Procedure
To ensure that the system works properly during normal operation after an upload, the whole system (control panel, detectors, control functions) should be verified after an upload.
Step
Description
1
To test the panel indicator lights and internal buzzer, press and hold the Reset button for at least 5 seconds. All indicators are lit and the buzzer is turned on. The test will automatically stop. The lamp test can be performed in access level 1 (no use of key).
2
Test all operating keys by pressing each key (refer also to Operator’s Handbook): All buttons will give a short "Beep" when pressed except Mute button, Menu button and
Reset System button (plus the ones that are not supported, see below).
Note that the left/right arrow buttons and the two buttons in the lowermost right hand corner (indicated with a white line) are not yet supported:
3
Perform a visual and functional inspection of manual call-points and automatic detectors.
4
Disable any alarm transference to the Fire Alarm Routing Equipment -FARE output.
5
Activate the alarm system. Test all sounders by activating an alarm from a corresponding manual call-point.
6
Test all control functions.
7
Activate alarms from at least one detector/manu al call-point in each zone and a check that
Mute Panel button
Silence Alarms button Reset System button
Menu button Close Window button
Alphanumeric keyboard
Manoeuvre buttons
Verifying the System after
an Upload
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 37
Step
Description
all respective outputs are activated.
8
Test the action of any auxiliary operating functions (disabling, cancelling and resetting buttons).
9
Check the alarm transference outputs by connecting from outgoing outputs (potential free relay and 24V output) activated by alarm in a zone.
10
Check the fault warning function from detector zones by removing a detector in each zone. Activate a fault (remove battery fuse) and observe:
- the Fault indicator starts to blink
- a fault warning is displayed
- the internal buzzer is turned ON
- the Fault Warning Routing Equipment (FWRE) output i s activated (if any)
11
Verify all conditions, i.e.:
- Fire Alarm condition
- Fire Warning condition
- Fault Warning condition
- Disablement condition
- Test condition
12
On completion of checks, ensure that only the green "Power" indicator is ON when the panel is in its idle state (normal operation).
13
Enable alarm transference to the Fire Alarm Routing Equipment -FARE output.
9.2 Verifying Detection Loops During Normal Operation
It may be necessary to verify the detection loops (checking the loop topology, the types of loop units, the location of loop units, the Loop Sequence Indexes, etc.) during normal operation using the AS-2000 Loop Diagnostic Tool. Before applying the tool, prepare the system for the verification as follows:
Enter the Service Menu (5), select Upgrade (5), then Reboot
System (6).
The system will now enter system fault condition.
Remove fuse A1 and A2 from the Power Board BSF-400. Connect and apply the tool, and do the necessary verifications.
Alternative 1:
Disconnect a detection loop. Use the AS-2000 Was-box to verify
the loop. Perform a verification for each loop in turn.
Alternative 2:
Disconnect the ribbon cable to BSL-310. Connect the AS-2000.
Run an initialization.
When the verificat ion is co mpleted, disconnect the tool/PC, re-
connect the cables, then re-place the fuses.
Reboot the system again.
1 2 3
AFB A AFB A"
AFB CT A 4 5 6
AFB Earth Fault Sens
AFB B
AFB B" 7 8
AFB CT B
AFB Earth Fault Sens
J2
J19
S
High Low
J24
J18
+
B
0V
+
A2
0V
+
A1
X11 X10
S5 AFB Earth Fault Off AFB Earth Fault On
1
OFF
ON
2
OFF
ON
Power Board BSF-400
Fuse A1 and A2
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 38
10. Upgrading the System
10.1 Introduction
After the very first startup of a system, a running system can be upgraded at any time using the service menu commands (shown in the next chapter). The upgrading can be performed from any Fire Alarm Control Panel BS-420 or Operator Panel BS-430 in the system (a freely selected panel).
Note that once you have selected a “master” panel for upgrading, the system will temporarily block all other panels during the upgrade procedure, preventing the system from being upgraded from other panels.
This chapter deals with upgrading by means of a USB memory stick. Upgrading can also be performed by using a computer remotely connected to a web site (refer to separate handbook).
10.2 Upgrading During Normal Operation (SW/Config)
10.2.1 Introduction
The Service Menu includes submenus which allows you to upgrade both the system software and the configuration (or either of them) during normal operation (see following chapters).
Note that if both the software and the configuration are to be upgraded, the system software and configuration have to be supported by the same config model. As a general rule, if both the software and the configuration are to be upgraded, always upgrade the software version first, then the configuration.
To use the Service Commands, access level 3 is required (refer to Operator’s Handbook).
Upgrade
Upgrade SW
Upgrade Config
Export Config
Export Log
View Upgrade Status
Reboot System
After an upgrade, a reboot must always be executed for changes
to take effect (software and/or configuration ugrade).
Note that it is possible to upgrade both software and the
configuration in turn bef ore r eboot in g, i.e. it is not nece s s ar y to reboot after each single upgrade.
NOTE:
When upgrading the system by means of a USB memory stick, do not remove the USB stick from the USB port until you are sure that the upgrade procedure is completed.
Enter the menu “View Upgrade Status” to follow the progress and verify that the procedure is completed.
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 39
10.2.2 Upgrading Software During Normal Operation
Note that before executing this command, insert the USB memory
stick with the correct and valid file into one of the USB ports on the BSA-400 Controller Board.
After the stick is inserted, wait at least 5 seconds before executing
the command.
From the panel front, press 5 to enter the Service Menu (Access
Level 3).
To select Upgrade, press 5. To Upgrade SW press 1. To view the upgrade status, the View Upgrade Status command
can be used.
If you do not intend to upgrade the configuration at this point, the
panel has to be rebooted for changes to take effect.
If you also intend to upgrade the configuration, do not reboot at this
point, but go to Upgrade Config (see next chapter).
When the upgrade is completed, press 6 to run the Reboot System
command.
10.2.3 Upgrading Configuration During Normal Operation
Note that before executing this command, insert the USB memory
stick with the correct and valid file into one of the USB ports on the BSA-400 Controller Board.
After the stick is inserted, wait at least 5 seconds before executing
the command.
From the panel front, press 5 to enter the Service Menu (Access
Level 3).
To select Upgrade, press 5. To Upgrade Config press 2. To view the upgrade status, the View Upgrade Status command
can be used.
If you do not intend to upgrade the software at this point (if not
already done), the panel has to be rebooted for changes to take effect.
If you also intend to upgrade the software (supported by the sam e
config model), do not reboot at this point, but go to Upgrade Software (see previous chapter).
When the upgrade is completed, press 6 to run the Reboot System
command,.
NOTE:
Do not remove the USB stick from the USB port until you are sure that the upgrade procedure is completed.
NOTE:
Do not remove the USB stick from the USB port until you are sure that the upgrade procedure is completed.
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 40
10.3 Upgrading when Panels are Added/Remo ved
If panels are added or removed, or it is necessary to change IP addresses, a reboot must be executed. The continuing procedure is similar to the startup procedure, chapter 8.
Go to chapter 8 and follow the procedure.
10.4 Upgrading if IP Addresses are to be Changed
If it is necessary to change IP addresses, a reboot must be executed. The continuing procedur e i s desc r ibed in the startup procedure, chapter 8.
Go to chapter 8 and follow the procedure.
10.5 Upgrading a Single Panel
If a single panel in a network system for some reason has a wrong software and/or configuration version, the process of upgrading the entire system could be both unnecessarily time-consuming, or even impossible if the software versions are incompatible. To simplify the version correction in such a case, the system features an upgrade procedure of a single panel. Before the upgrade procedure is carried out, the file name of the software and/or configuration file has to be changed.
Locate the software/configuration file(s) in question on your
computer.
Change the name of the software file:
Add the text _Recovery to the name of the software file as follows: Example: The file name AS_V4_3_0_0_C4_34.tar.bz2 is changed to AS_V4_3_0_0_C4_34_Recovery.tar.bz2
Change the name of the configuration file:
Remove the text representing the “file name” (in this example, Tiller) and replace it with the text Recovery: Example; AC_4_34_Tiller.tar.bz2 is changed to AC_4_34_Recovery.tar.bz2
Copy the file(s) onto your USB memory stick. Insert the USB memory stick into one of the USB ports on the
BSA-400 Controller Board, then reboot the panel.
The panel will automatically be upgraded.
If the panel has a display, the process similar to the startup
procedure will be shown (chapter 8).
If the panel does not ha ve a display, the process will be indicated
by means of the yellow LED indicator D2 on the BSA-400 board as follows (see illustration, chapter 10.7.3):
- Slow blink: upgrade in progress
-
Fast blink: upgrade failed
-
Steady yellow light: Upgrade completed, remove stick to reboot the panel
NOTE:
Do not remove the USB stick from the USB port until you are sure that the upgrade procedure is completed.
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 41
10.6 Upgrading b y Remo te Access to a Web site
Upgrading can be performed by means of a computer with remote access to a web site providing several service functions.
From the Service menu, press 6 to select Remote Access.
For further information, refer to separate handbook.
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 42
10.7 Upgrading Software Version 4.0.1 to 4.1.1
10.7.1 General
This chapter deals with the upgrade from software version 4.0.1 to
4.1.1.
Before reconfiguring the system or upgrading the system software, a hardware reset must be executed. All panels belonging to the same system will be reset and upgrading can then take place.
If the system is in normal operation, go to chapter 10.7.2. If the system is in system fault condition, go to chapter 10.7.3.
10.7.2 Preparing a System in Normal Operation
Push the reset button S5 less than 1 second to shut down the
panel in a controlled manner.
Wait until the blue LED indicator D22 (see illustration on next page)
goes off.
The panel has now entered system fault condition.
Go to chapter 10.7.3.
IMPORTANT:
Follow the upgrade procedure as described in detail below.
During the upgrade to software version 4.1.1, the system will enter system fault condition.
Do NOT disconnect the mains power or press the front panel’s
Reset System button.
Press the front panel’s Mute button to silence the buzzer.
Note that a panel that has been upgraded to software version
4.1.1 cannot be downgraded to software version 4.0.1.
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 43
10.7.3 Preparing a System in System Fault Condition
To perform a hard reset, push and hold down the reset button S5
until the red LED indicator D20 and D21 are lit for a short moment and you hear a click from the relay.
The system will now detect all running panels, and prompt you to
reboot the entire system (all running panels).
Verify that all panels in the system are detected. Press 2 to select Reboot running panels.
When all panels are rebooted, four selections will appear.
Press 3 (“Upgrade Software”). Insert the USB memory stick with the valid file into one of the USB
host ports on the BSA-400 Controller Board.
The display will indicate when the uploading is completed. Remove the USB stick.
The system will automatically reboot. After a short while, the panel will indicate system fault condition.
Do NOT disconnect the mains power or press the front panel’s
Reset System button.
Press the front panel’s Mute button to silence the buzzer.
When the system is rebooted, the system will be upgraded (the new system software version) and the system will enter normal operation mode.
Proceed with the upgrading procedure.
Reset button S5
LEDs
LEDs
Controller Board BSA-400
D20
D21
D13
D17
D23
D2
D22
D1
D19
D16
D18
D15
D3
Upgrading the System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 44
10.8 Upgrading Software Version 4.0.1 or 4.1.1 to 4.3.1
This chapter shows examples of how to upgrade from software version 4.0.1 or 4.1.1 to 4.3.1.
10.8.1 Example 1: Upgrading all Panels from SW Version 4.0.1 or
4.1.1 to 4.3.1
All panels have software version 4.0.1 or 4.1.1 ins ta lle d.
Upgrade all panels simultaneously by using a USB stick including
program version 4.3.1 (or later when available).
10.8.2 Example 2: Adding a BS-420/BS-430 panel with SW Version 4.1.1 to a System Running on SW Version 4.3.1
A system is running on software version 4.3.1. A new BS-420/BS-430 panel with software version 4.1.1 installed is going to be added.
Start the new panel without connecting it to the AutroNet. Install version 4.3.1 by using an USB stick . Connect the new panel to the system AutroNet. Restart the system and upgrade the new system configuration data
by using an USB stick.
10.8.3 Example 3: Adding a BC-420 Controller with SW Version 4.1.1 to a System Running on SW Version 4.3.1
A system is running with software version 4.3.1. A new BC-420 Controller with software version 4.1.1 installed is going to be added.
Disconnect a BS-420 panel from the system AutroNet. Restart and downgrade the BS-420 panel to run version 4.1.1 by
using a USB stick.
Temporarily, connect the downgraded panel and the new BC-420
Controller together by using an AutroNet connection.
Start the two system units and upgrade them to run version 4.3.1
by using an USB stick.
Connect the two system units to the original system AutroNet. Restart the system and upgrade the new system configuration data
by using an USB stick.
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 45
10.8.4 Example 4: Adding a Panel with SW Version 4.3.1 to a System Running on SW Version 4.1.1
A system is running on software version 4.1.1. A new panel with software version 4.3.1 installed is going to be added.
Start the system without connecting the new panel to the AutroNet. Upgrade the system to run version 4.3.1 by using a USB stick. Connect the new panel to the system AutroNet. Restart the system and upgrade the new system configuration data
by using an USB stick.
Startup Procedure for a Dual Safety System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 46
11. Startup Procedure for a Dual
Safety System
11.1 Introduction
This chapter describes the initial startup procedure of a system consisting of a Primary System and a Secondary System (AutroSafe Dual Safety concept).
In principle, the startup procedure is identical to the startup procedure of a normal system, however, the startup procedure must be carried out for each system in turn (both the Primary System and the Secondary System).
The startup of the Primary System can take place from any selected Fire Alarm Control Panel BS-420 or Operator Panel BS-430 belonging to the Primary System. Likewise, the startup of a Secondary System can take place from any panel belonging to the Secondary System.
There are two AutroKeepers BN-180 for each detection loop in a Dual Safety System. One must be assigned to the Primary System and the other to the Secondary System (dipswitch settings). Furthermore, the type of protocol for the AutroFieldBus Protocol Converter BSD-321 (if used) must be set to Al_Com+ (rotary switch setting).
In the following guidelines, a startup of the Secondary System is carried out first, then the Primary System. When the startup of both systems is completed, the Primary System will be in Active Mode (it controls the detecton loops), and the Secondary System will be in Standby Mode (ready to take over control of the detection loops).
Startup Procedure for a Dual Safety System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 47
11.2 Guidelines – Startup Procedure
The following guidelines apply:
Step Action Chapter
1
Perform the following actions for both the Primary and the Secondary System:
Verify the detection loops by means of the AS-2000 tool. Perform a consistency check of the configuration data using the
results from the AS-2000 verification and the data that has been configured by means of the AutroSafe Configuration Tool.
Assign an AutroFieldBus address to each AutroFieldBus unit. Assign a Panel ID to each panel by means of switches (dip-switches
and rotary switches on BSA-400).
Assign a Network ID to each panel by means of rotary switches (on
BSA-400).
Verify the system before startup (chapter 7).
3, 4, 5,
6 and 7.
2
Define the type of protocol and assign an Au troFieldBus address on the AutroFieldBus Protocol Converte r BSD-321
The BSD-321’s default protocol by delivery is Al_Com+. If needed, the procedure for selecting the protocol type is described below.
Set the actual AutroFieldBus address in the range of 1-31 according
to the specific configuration.
The type of protocol is defined by on-board rotary switches.
To select protocol type:
Apply power to the converter. Set the switches to 70 (Al_Com+), then press the reset button.
The indicators will start flashing.
When the indicators stop flashing after a short while. Set the actual AutroFieldBus address, then press reset.
3
Set switches for Primary or Secondary on the AutroKeepers (BN-180)
Set dipswitch 1 in postion OFF for the BN-180 that belongs to the
Primary System
Set dipswitch 1 in postion ON for the BN-180 that belongs to the
Secondary System
Apply power to BN-180 (24V DV external power).
Startup Procedure for a Dual Safety System
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 48
Step Action Chapter
4
Apply power to the panel belonging to the S eco n d ary System, then:
Select Automatic addressing mode to assign an IP Address to each
panel.
Upload configuration data to all panels from the panel in question. Start system, perform an initialization.
8.1, 8.3,
8.5
5
Apply power to the panel belonging to the P rimary System, then:
Select Automatic addressing mode to assign an IP Address to each
panel.
Upload configuration data to all panels from the panel in question. Start system, perform an initialization.
8.1, 8.3,
8.5
6
Verify the Dual Safety functionality: The Primary System is now in Active Mode. The Secondary System is
in Standby Mode (the indicator Dual Safety Stdby on this panel has a steady yellow light).
Perform a manual transfer of control from the Primary System to the Secondary System.
From the Primary System, enter the Service Menu, and select Dual
Safety, then Transfer to Secondary
As soon as the loop control is transferred to the Secondary System,
the indicator Dual Safety Stdby will be lit on the Prim ary S ystem’s panel and will go off on the Secondary System’s panel.
7
Transfer the control back to the Primary System
From the Primary System, enter the Service Menu, and select Dual
Safety, then Transfer to Primary
As soon as the loop control is transferred to the Primary System, the
indicator Dual Safety Stdby will be lit on the Secondary System’s panel.
8
Verify the entire system after an upload.
9
Dual Safety Stdby
Applicable to systems using the Dual Safety concept; a system with redundant loop control consisting of a Primary and Secondary System.
Steady yellow light:
The panel is in Standby Mode, i.e. this panel does not control the detection loops. The panel(s) in the other system controls the detection loops and is in Active Mode.
Blinking light: the panel does not control all detection loops/loop units,
and/or loop control is being transferred. Actions must be taken.
Fault Messages during Uploading
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 49
12. Fault Messages during
Uploading
12.1 Introduction
During uploading, the system may report possible faults. If such fault messages occur, the panel in question should be rebooted by means of the reset button S5 on the Controller Board BSA-400 inside the panel.
To perform a hard reset, push and hold down the reset button S5
(approximately 6 to10 seconds) until the red LED indicators D20 and D21 are lit for a short moment and you hear a click from the relay.
12.2 Invalid File on USB Stick
Invalid file is found on the USB stick Example: Software: "Software Upgrade, File with syntax AS_V*_*_*_*_C*_*.tar.bz2 not found in root folder" Config: "Config Upgrade, File with syntax AC_V4_5_*.tar.bz2 not found in root folder"
12.3 Data Transmission Timeout
The transmission of data to a panel takes too long (timer) due to a possible network failure: "Transfer to panel <NN> timed out"
12.4 Corrupt File
File found, but it is corrupt (crc). Example: "Corrupt file AS_V4_0_0_1_C4_5.tar.bz2"
Fault Messages during Uploading
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.F, 2014-04-01,
Autronica Fire and Security AS
Page 50
12.5 Fail to Unpack Files
If the unpacking of files on a panel is not successful, one of the following error messages may occur: "Failed to unpack, file system error on panel <NN>" "Failed to unpack, panel error on panel <NN>"
Autronica is a leading innovator, manufacturer and supplier of fire safety equipment. Our products ensure safety in applications on land and sea worldwide. The company is owned by United Technologies Corporation (UTC) and employs more than 380 people with great skill and experience in the developing, manufacturing and marketing of fire safety equipment. Autronica Fire and Security AS is an international company based in Trondheim, a dynamic city known as the technological hotspot of Norway.
Protecting life, environment and property
Autronica Fire and Security AS
Haakon VIIS gt. 4, NO-7041 Trondheim, Norway | Tel: +47 90 90 55 00 | Fax: +47 73 58 25 01
E-mail: info@autronicafire.no | www.autronicafire.com
Loading...