Autotrol Performa 440i Control, Performa 960F Control, Performa 940F Control Installation, Operation And Maintenance Manual

Page 1
®
TM
Autotrol Performa Filter Valve Series
440i Control 940F Control 960F Control
Water Conditioning Control System
Installation, Operation and Maintenance Manual
Page 2
Table of Contents
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location S election Water Line Connection Drain Line Connection
Placing Conditioner into Operation. . . . . . . . . 4
Electrical C o nnection
400 Series Control Settings. . . . . . . . . . . . . . . 5
440i Programming
900 ProSeries Control Settings . . . . . . . . . . . . 5
940F Programming Manual Regeneration 960F Programming Level I Parameters Level II Parameters
Regeneration . . . . . . . . . . . . . . . . . . . . . . . . . 11
Manual Regeneration Automati c Re ge ner a tio n
Removin g the Valve As s em bly or Servicing . 12
Removing 440i Contro l for Servicing. . . . . . . 12
Removin g the 940F and 96 0F Controls for
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Preventative Maintenance. . . . . . . . . . . . . . . 14
Water Meter Maintenance
Specifications . . . . . . . . . . . . . . . . . . . . . . . . 15
Control Valving Identification. . . . . . . . . . . . . 17
Valve Disc Principle of Operation . . . . . . . . . 17
Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . . 17
Replacement Parts . . . . . . . . . . . . . . . . . . . . 19
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . 22
Page 3
Installation
All plumbin g and electrical connections mus t co nfo r m to local codes.
Inspect unit carefully for carrier shortage or shipping damage.
Location Selection
1. The distance between the unit and a drain should be as short as possible.
2. If it is likely that supplementary water treatment equipment will be required, make certain adequate additional space is available.
3. Do not install any unit closer to a water heater than a total run of 10 feet (3 m) of piping between the outlet of the conditioner and the inlet to the heater. Water heaters can some times overheat to the extent they will tr ans mit heat back down the co l d pipe into the unit control valve.
Hot water can severely damage the conditioner. A 10-foot (3-m) total pipe run, including bends, elbows, etc. , is a reasona bl e di st an ce to hel p prevent this possibil ity. A positive way to preven t hot water flowing from heat source to the conditioner, in the event of a negative pressure situation, is to ins t all a check valve in the so ft water piping from the conditioner . If a ch eck valve
is installed, make cer tain th e wate r heati ng unit is equipped with a property rated temperature and pressure safety relief valve. Also, be certain that local codes are not violated.
4. Do not locate unit where it or its connections (including the drain) will ever be subjected to room temperatures under 34
o
(49
C).
5. Do not install unit near acid or acid fumes.
Water Line Connection
The installation of a bypass valve system is recommended to provide for occasions when the water conditioner must be bypassed for hard water or for servicing.
The most common bypass systems are the Autotrol Series 1265 bypass valve (Figure 1) and plumbed-in globe valves (Figure 2) . Though both are similar in function, the Autotrol Series 1265 bypass offers simplicity an d eas e of o pe r atio n.
o
F (1oC) or over 120oF
Not in Bypass
In
B
Y
P
A
S
S
Conditioner
Water
Out
B
Y
P
A
S
S
In
A
P
S
Y
S
B
In Bypass
Water
Conditioner
Out
A
S
S
P
Y
B
Figure 1
Not in Bypass In Bypass
Water
Conditioner
Water
Conditioner
Figure 2
Drain Line Connection
Note: Standard commercial practices are expressed
here. Local codes may require changes to the following suggestions.
1. Ideally located, the unit will be above and not mor e than 20 feet (6.1 m) from the drain. For such installations, using an appropriate ad apter fit ting , connect 1/2-inch (1.3-cm) plastic tubin g to the drain line connection of the control valve.
2. If the bac kw as h flo w rate exceeds 5 gpm (22.7 Lpm) or if the unit is located more than 20 feet (6.1 m) from drain, use 3/4 -inch (1.9-cm) tubing for runs up to 40 feet (12.2 m). Also, purchase appropriate fitting to connect the 3/4-inch tubing to the 3/4-inch NPT drain connection.
3. If the unit is located where the drain line must be elevated , yo u may elevate the line up to 6 feet (1.8 m) providin g th e ru n does not exceed 15 feet (4.6 m) and water pressure at conditioner is not less than 40 psi (2.76 bar). You may elevate an additional 2 feet (61 cm) for each additional 10 psi (0.69 bar).
4. Where the drain line is elevated but empties into a drain bel ow the lev el of the control valve, fo rm a
Page 4
7-inch (18-cm) loop at the far end of the line so that the bottom of the loop is level with the drain line connection . T his will prov id e an adequate sipho n trap.
5. Where the dr ain empties into an ov erh ea d s ew er line, a sink-t ype trap must be used.
IMPORTANT: Never insert drain line into a drain, sewer lin e o r tra p. Alway s allow an air g ap between the drain line and the wastewater to prevent the possibility of sewage bein g ba ck -s ip ho n ed into the co nditioner.
Right Wa y
Figure 3
Note: Standard commercia l prac tices have been expressed here. Loc al co d es may require changes to these suggestions.
c. When all of the air ha s been purged from the
tank (water begins to flow steadily from the
drain), open the main supply valv e all the way. d. Allow water to run to drain until clear. e. Turn off water supply and let the uni t stan d for
about five minutes. This will allow all trapped air
to escape from the tank.
4. Place the conditioner into operation. a. Advance t he indicato r knob or cycle indicator
COUNTERCLOCKWISE to the SERVICE position and run water from a nearby faucet until the water is clear.
Electrical Conne ction
100 VAC, 115 VAC, and 230 VAC units: Remove twist
tie from the powe r co rd and ex tend co rd to its fu ll length. Make sure the power source matches the rating printed on the control. Be certain a wall switch does not control the outlet.
12 VAC: Connect the plug of the transformer (supplied) secondar y cab le to t he ma tin g soc ke t at th e rear or bottom of the timer housing. Be certain the transformer is secure and is plugged int o a power sour ce of corr ect voltage that is n o t con trolle d b y a wall s wi tch .
Placing Conditioner into Operation
After all previous steps have been completed the unit is ready to be placed into operation. Follow these steps carefully.
1. Remove control valve cover. Note: The following step s will require turning the
indicator knob (Figure 4 and Figure 5) or the cycle indicator (Figu re 7) to various positions. Manuall y rotate the camshaft COUNTERCLOCKWISE only until indicator kn ob an d cy cle indi cato r p oi nts to des i re d posi tion . ( See manua l re gene ratio n sections for each control’s manual operatio n. )
2. Rotate indicator knob or cycle indicator COUNTERCLOCKWISE until it points directly to the word BACKWASH.
3. Fill med ia tan k with water. a. With wate r supply off , place the by pass valve(s )
into the “service” position.
b. Op en wa ter su pp ly va lv e v er y slow ly to
approximately the 1/4 open position.
IMPORTANT: If opened t oo rapidly or too far, media may be lost. In the 1/4 open positi on , you sh ould hear air escaping slowly from the drain line.
Page 5
400 Series Control Settings
440i Control
Day Arro w
Skipper Pins
Skipper Wheels
extra regeneration can be achieved. Depress the indicator knob on the 440i (Figure 4) with a wide-blade screwdriver and turn COUNTERCLOCKWISE to START to initiate a regener atio n. It will tak e a few minutes for regeneration to start. A normal regeneration will take approximately two hours.
Manual Regeneration
Electrici ty is used only to run the control an d to rotate the camshaft. All other functions are operated by water pressure. Therefore, in the event of a power outage, all the regeneration p o si tion s may be dia led ma nually by depressin g the indicator knob and turning COUNTERCLOCKWISE (Figure 4). The foll o wing cycle times should be used for proper regeneration :
BACKWASH - 20 minutes FAST RINSE - 10 minutes
900 ProSeries Control Settings
940F Control
Indicator Knob
Timer Knob
Time Arrow
Timer Locking Pin
Figure 4
Programming
1. Set days of regeneration on skipper wheel (Figure 4).
• Pull all skipper pins outward (away from
control).
• Rotate skipper wheel until day arrow points to
current day or number 1.
• Depress skipper pin ( s) at da y(s) fo r which
regeneration i s desired.
2. Set the time of day.
• Grasp timer k n ob and pull outward.
• Rotate in either direction until the timer arrow
points to the actual time of day.
• Release timer knob.
Note: with the time of day properly set, the conditioner will regenerate at about 2:30 a.m. If you prefer to have the unit regenerate at an earlier or later time, simply set current time-of-d ay ac co rding ly (e.g. , to h ave th e unit regenerate at 4:30 a.m. - two hours later - set the clock two hours earlier than the actual time of day.)
Note: The timer locking pin should always be horizontal (Figure 4) during operation.
Guest Cycle
When abnormally high water usage exhausts your water cond ition e r ’s capacity ahea d of s ch ed ule, an
Indicator Knob
TM
Performa Filter
FOR MANUAL BACKWASH ROTATE POINTER COUNTER CLOCKWISE TO START POSITION
TO ADJUST BACKWASH MINUTES, ROTATE SMALL DIAL COUNTER CLOCKWISE. DO NOT ADJUST DURING BACKWASH
N
I
R
T
S
A
F
S
E
R
V
I
C
E
BACKWASH COMPLETE
Clock Dial
E
S
B
A
C
K
W
A
S
H
TO SET REGENERATION DAYS PRESS PINS IN
Day Pins
Figure 5
Programming
1. Set da ys of regenera tion (Figure 5).
• Pull all day p ins outward (away from cont rol ).
• Depress day pin(s) for whi ch regener ation is
desired.
Note: The NEXT DAY day pin is n oted on the timer face. Depressing this pin will insure a regeneration the next day at approximately 2:00 a.m. Since the calendar cap progre sses CLOCKWISE, depr essing the day pin immediately COUNTERCLOCKWISE will insure a regeneration the following day at 2:00 a.m. This progression is noted on the timer face as “FUTURE DAYS”.
Page 6
2. Set the time of day.
Time of Day Time of Regen Fact or A Fact or B Capacity Regen Time
Remaining
R
E
G
E
N
E
R
A
T
IO
N
C
O
M
P
L
E
T
E
F
A
S
T
R
I
N
S
E
B
A
C
K
W
A
S
H
P
M
Performa
Filter
TM
• Rotate Clock Dial CLOCKWISE until the pointer
is directed at the curre nt time .
Note: With the time of day properly set, the conditioner will regenerate at about 2:00 a.m. If you prefer to have the unit regenerate at an earlier or later time, simply set the current time-of-da y ac co rdingly (e. g., to have the unit REGENERATE at 4:00 a.m. - two hours later - set the clock two hours earlier than the actual current time).
Note: Do not rotate the Calendar Cap by hand; the clock dial indexes it daily. To man ually index the Calendar Cap, rotate the Cl ock Dial CLOCKWISE one complete turn for e very day to be indexed.
Backwash Dial
Indicator Knob
Figure 6
How to Adjust the Backwash Time
With the indicator knob in the BACKWASH COMPLETE position (Figure 6), rotate the Backwash Dial COUNTERCLOCKWISE at least one full turn to cancel the previous setting. A light clicking will be replaced by a heavier clicking when the previous setting is cancelled. T hen, rotate the Backwash Dial to the desired backwash time. The numb ers are minutes of backwash per regeneration.
Manual Regeneration
Electricity is use d only to run the control and to rotate the camshaft. All other functions are operated by water pressure. Therefore, in the event of a power outage, all regeneration positions may be dialed manually. Grasp the indicator knob and turn COUNTERCLOCKWISE to each regener ation cycle (rotation is muc h eas ier if you grasp the camshaft with your free hand and turn it at the same tim e). T he fo ll ow in g cy cle times shoul d be used for proper regeneration.
BACKWASH - 20 minutes FA ST R INSE - 10 minutes
960F Control
Cycle Indicator
Figure 7
Programming
This sec tio n co v ers all as pects of programm in g t he control. The cont rol is shipp ed fr om the fa ctory with default values for most parameters. These default values will result in a system capacity of 100 gallons (1 cubic meter). While the control may operate with these values, the following parameters mu st b e change d to meet the actual ope rating condition s :
Refill Controller Value, Brine Draw Rate, and Slow Rinse Time parameters are not required for 960F operation, but should be ad justed as instruc ted to ac hiev e the shortest possi bl e backwash cycle ti me.
Note that some p arameters have a single unit of measure option . Ot her pa ra me ter s have dual units such as Ca pa city wh i ch ca n be entered in gallons or cubic meters. To select which units are active, look for a comment in the N O T ES colu m n of Tables 1 and 2. It will reference another parameter that selects which units are active. For example, parameter P12 (Table 2) selects U.S. units if it is set to “0” and metric if it is set to “1”.
Page 7
Level I Parameters (Table 1)
Level I parameters are identified as those that have an LED indicator on the front p an el . Th e gree n in di cator illuminates next to the name of the active control settings. The end user has access to all of these parameters. I n general, pressi n g the down arrow (↓) button displays the Level I Parameters in the following order:
• Time of Day
• Time of Regen
• Factor A
• Factor B
• Capacity
If you continue to pr ess the dow n arrow (↓) button, the parameters start over with Time of Day. Pressing the up arrow (↑) button displays the parameters in reverse order. Refer to Table 1 for a desc r ip tio n of th es e parameters and the available ran ges for each parameter.
Press the SET button and the far right digit of the display starts fl ashi n g. If you want to change this number, press the up arrow (↑) button to increa se th e number or the do wn arrow ( ↓) button to de creas e the number. To skip the number without changing, press the left arrow (←) button. When you reach the far left digit, pressing the left arrow (←) button will return you to the far right digit.
Note: If you press and hold either the u p arrow (↑) button or the down arrow (↓) button for more than one second, the flashing number will increment or decrement at the rate of 10 counts per second.
When the num be r is correc t, p ress th e lef t ar row (←) button. The far right digit sto ps fla shing and the nex t digit to the left starts flashing. You can only change the flashing number. Continue changing numbers until you reach the desired setting. Press the SET button. The numbers stop flashing and the control accepts the new setting. After approximately 30 seconds, the control starts alternating the display between Time of Day and Capacity .
Note: If the new setting is not accepted because it was outside the allowable range, the old value will be displayed.
Time of Day
Press the SET button. The display will show the Time of Day with the minu tes digi t blinking. If you want to change this number, press the up arrow (↑) button to increase the num b er or th e d o wn arrow (↓) button to decrease the number. To skip the number without changing, press th e lef t ar row (←) button. The first number stops flashing and the next number starts
flashing. You can only change the flashing number. When you have reached the far left digit, pressing the left arrow (←) button returns you to the far right digit. Continue changing numbers until you each the desired setting. Pres s the SET button again to enter the valu e .
Time of Backwash
The next value displ ayed is t he Time of Bac kwash. It is similar to Time of Day programming. It has a default value of 2:00 a.m. If 2:00 a.m. is acceptable, press the down arro w (↓) b utto n. If this is no t acce pt ab le, press the SET button and ch an ge th e num b ers . Press the
SET button again to enter the v alue.
Factor A
Factor A is the next value displayed. The 960F control uses this val ue to calcula te the system ca pacity . Factor
A must be set to 10 (100 for metric units) for the 960F control to accurately calculate system capacity. The default value is 10 (100 for metric units).
If the Factor A setting is not cor rect, press th e SET button and change the value. Press th e SET b utto n again to enter the new v alue .
Factor B
Factor B is the next value displayed. This value is used by the control to calculate the pause for the refill cycle. Becaus e the re fill cyc le is no t requ ired fo r 960 F operation, Factor B should be set to 0 .2 (0.1 for metric units). This is the minimum setting and will cause the control to skip the refill cycle, thereby shortening the backwash cycle ti me. The default va lue for Factor B is
0.2 (0.1 for metric units). To change Factor B, press the
SET button and change to the correct value. Press the SET button again to enter the new va lue .
Capacity
Capacity is the next value displayed and is used by the 960F control in combination with Factor A to determine the capacity of the filter. The Capacity value should be set to the actual capacity of the filter expressed as gallons/100 (cubic meters/10 for metric units).
Example: If the actual filter capacity is 950 gallons, enter 9.5 for the Capacity setting. The default value for Capacity is 1.0 (0.1 for metric units). To change the Capacity setting, press the SET button and adjust the correct valu e. Press the SET bu tton again to enter the new value.
At this time, all of the Lev el I par ame ter s are programed. The display will alternate between the Time of Day and Capacity if no keys are pressed for 30 seconds. The Capacity value displayed i s the volume remaining in g allons (cubic me te r s for me tr ic) be fo re a backwas h is n eed ed .
Page 8
Note: The 960F control uses Factor A and Capacity settings to calculate the actual system capacity. If the actual syst em capacity is in exc es s of 99 99 ga llo n s (99.99 cubic meters) the control will display 9999 (99.99) until the water usage has dropped the remaining capacity below that number. When water is
Table 1 - Level I Programming Parameters
flowing through the system, the colon in the Time of Day disp lay wi ll blink.
To complete the initial programming of the 960F, proceed to the Level II Para met e rs.
Parameter
Name Description
Time of day
P1
P2
P3 Factor A
P4 Factor B
P5
AM or PM
Time of d ay of
backwash
Capacity of
unit
Range of
Values
1:00 to 12:59
00:00 to 23:59
1:00 to 12:59
AM or PM
00:00 to 23:59
3 to 250
30 to 2500
0.2 to 51.0
0.1 to 25.5
0.1 to 140.0
0.01 to 14.00
Minimum
Increments
1 None Hour: minute
1 2:00 AM Hour: minute
1
10
0.2
0.1
0.1
0.01
Default
10
100
0.2
0.1
1.0
0.1
Cubic Meters/
Units of
Measure
U.S.
Metric
U.S.
Metric
Gallons/100
10
Notes
Range depends on value selected for
P13. Enter the current time.
Range depends on value selected for
P13. Skip this parameter to accept the
default or enter a new time.
Unit of measure depends on value
selected for P12. Set to 10 (10 0 for
metric units) for proper operation.
Unit of measure and default depends
on value selected for P12. Set to .5
(.1 for metric units ) for proper 960i
operation.
Unit of measure depends on value
selected for P12. Enter the unit
capacity in gallons/100 (cubic meters/
10 if metric units).
Page 9
Table 2 - Le ve l II Programming Par a me ters
Parameter
Name Description
Refill Con t rol
P6
P7 P8 Not used NA NA NA NA NA P9
P10
P11
P12
P13 Clock mode 0 to 1 1 0
P14
P15 Reserve type 0 to 3 1 0
P16
P17
P18
P19
Value
Brine draw
value
Backwash
time
Slow Rinse
time
Fast Rins e
time
Units of
measure
Calendar
override
Fixed r ese rv e
capacity or
initial average
value
Operation
type
Factor B/ Capacity
Factory
defaults
Range of
Values
1 to 99 1 99
1 to 99 1 99 Set to 99 for 960F operation.
3 to 30 1 14 Minutes
8 to 125 1 8 Minutes Set to 8 minutes for 960F operation.
2 to 19 1 9 Minutes
0 to1 1 0
0 to 30 1 0 Days
0 to 70 1 30
0 to 1 1 4 Set to 4 for 960F operation.
0 to 1 change
lock out
0 to 3 1 99
Minimum
Increments
10
Default
Units of
Measure
Percent of
capacity
Set to 99 for 960F operation. Skip for
Enter the desired backwash time in
minutes. Skip for default.
Enter the desired fast rinse time in
minutes. Skip for default.
0=U.S., 1=Metric. Skip thi s p ara me te r
to accept U.S. or enter 1 for Metric.
0=12-hour cloc k, 1=24-hour clock. Skip
this parameter for a 12-hour clock or
enter 1 for a 24-hour clock.
0=no calendar override. Skip this
parameter for no calendar override or
enter a value.
0=va ri able rese rve, 1= f i xed rese r ve ,
2=variable reserve with immediate
backwash, 3=fixed reserve with
immediate backwash. Skip this
parameter to accept th e default or ente r
a different reserve type.
Description depends on the value
entered for P 15. Skip this par a mete r to
accept the default or enter a different
0=none, 1=Factor B/Capacity change
locked out. Skip this parameter to
accept the default or enter 1 to lock out
Factor B/capacity change.
Loads in factory default values.
Do not change this parameter.
Notes
default.
value.
Level II Parameters
The Level II parameters are P6 through P19 in Table 2. The Home Owners Manual for this product does not
mention these parameters, so the end user does not normally have access to these values. T o access Level II Parameters, simultaneously press and hold the down arrow (↓) and up ar row (↑) button for three seconds.
If th e c on trol was alt ern at in g b et we en T ime o f Da y a nd Capacity when the above button sequence is entered, the display shows P1. If a diff e rent Level I Parameter was displayed, t h e di spl ay, shows the “P” number for
that parameter . Refer to T able 2 to find the “P” number associated with each parameter.
Use the up arrow (↑) button or the down arrow (↓) button to move from one para met er to the next. Th e display cycles through the “P” numbers shown in T ables 1 and 2. When you reach P19, the display will go back to P1.
When the parameter number you want to change is displayed, pres s the l eft arr ow (←) button to display the data assigned to that parameter . Press the SET button
Page 10
and the far right digit on the display star ts flashi ng. If you want to change this number , press the up arrow (↑) button or the down arrow (↓) butto n. To skip the number without cha ng ing, press the le ft arrow (←) button. When the numb er is correct, press the SET button. The numbers stop flashing and the control accepts the new setting. If the new setting was not accepted, the dis p la y wi ll s ho w the previous setting. Refer to Table 2 for allowable values for that parameter .
To change or view other parameters, press the left arrow (←) button to have the display show “P” numbers. Now use the up arrow (↑) button or the down arrow (↓) button to move to the parameter number you wish to change.
To exit the Level II programming mode, simultaneously press a n d hold the do wn arrow (↓) and up arrow (↑) buttons for three seconds, or wait 30 seconds without pressing a button . The co ntrol starts alternating the display between Time of Day and Capacity.
Refill Control
The Performa Valve with the 960F control is designed for use as a three cycle filter valve and does not include a refill control. However, the software program used in the 960F control is also used for the five cycle softener control, and requires a refill controller value to calculate how long to pause the cam shaft in the refill position. In general, a small refill control value results in a long pause, and a larg e refill control value results in a s hort pause. For 960F operation, the refill Control Value should be set to 99 to avoid delays during backwash. The default value for Refill Control Value is 99.
Brine Draw Value
Brine Draw V alue P7 is used to calculate the amount of time required for the b ri ne draw cycle. Becau s e the 960F does not require a brine draw cycle, the Brine Draw Value should be set to 99 to avoid delays during backwash.
• This control does not use parameter P8. No entry is
needed for this parameter.
Backwash Time
Parameter P9 is used to set the b ack wash time in minutes. The default in P9 is 14 minutes. If a different backwash time is desired, press the SET button and enter a new value.
Slow Rinse Time
Parame ter P 10 Slo w Ri n s e Time is used to calculate how long to pause the cam s haf t fo r the slow rinse cycle. For 960F operation, t he Sl ow Rinse t ime should be set to 8 minutes to avoid de la ys du r i n g backwash. The default value for Slow Rinse Time is 8 minutes.
Fast Rinse Time
Parameter P11 determines the fast rinse time. The default value is 9 minutes. If a different fast rinse time is desired, press the SET button and enter a n ew val ue.
• Parameter P12 selects the units of measure. Be
sure that this is set to the corre ct value before entering any data for parameters P3, P4, or P5.
• Parameter P13 selects the clock display mode. If
the 12 hour m ode is selected, a PM ind icator is used. If the 24 hour mode is selected, the indicator is not used.
• Parameter P14 is used to set the calendar override
feature. The default value is zero. If set to zero, the feature is disabled. Refer to Calendar Override for more inform ati on on the calendar overr id e feature.
• Parameter P15 selects a varia ble r ese rve type , 0 to
3. For more information on r eserve options, re fer to Reserve Options.
• Par ame ter P 16 is used to calculate the in it ial
average d aily water usage valu es . T he co ntr ol multiplies the to tal cap acity by the percentage entered for Parameter P16 and uses that value as the initial average daily usage for each day of the week until water usage establishes new averages. The default is set for 30% of the capa city. In most installatio n s this is acce ptable.
• Parameter P17 has be en preset to 4. Do no t
change this setting. P17 must be set to 4 for
proper 960F operation. Improper backwashes will occur if P1 7 is set to som ething other than 4.
• Parameter P18 allows the ins tall er to lock the
Factor B and Ca pa city values so they cannot be changed. When Parameter 18 is set to 1, those two settings can only be viewed when the control is in the Level II mode. The settings will b e sk ip p ed when the control is in the Level I mode. When Parameter 18 is set to zero, the Fa ctor B and Capacit y ca n be view ed and changed in ei th er Level I or Level II.
• Parameter P19 is used at the facto r y t o en ter
default va lues. T his parameter does not need to be changed. Using this parameter will erase the
values for all other pa ram eters and replace them with default values. P19 should be set at 99 and should not be changed.
10
Page 11
Regeneration
When the control begins a regeneration, the display will alternate b etween Time of Day and Regen Time Remaining . The Regen Time Remaining is sh ow n in minutes. The control will sta r t and stop an int ernal moto r which drives t h e cam gear through the vario us backwash positions. The control uses the information entered in the parameters sh own in Table 2 to determine how long each part of the cycle should last.
If power fails d ur ing a regene r atio n cy cle, the cycle completes normally when the power is restored.
Note: The REGEN button is only activ e when the display is alt ernating between Time of Day and Capacity. When programming Level I or II param eters, the REGEN button is not active.
The Regen Time Remaining will continue to count down until the cam gear r eaches the Ser v ice positi o n.
Manual Regeneration
To initiate a manual regeneration, press the REGEN button. This button is located on the front of the control. When you press the REGEN button, the control performs a full regeneration of the filter.
If you press thi s button again more than one minu te afte r rege neration begins, but bef ore the regeneration is complete, a second regeneration will start when the first r egeneratio n is finished. The
display will freeze and only show the Regen Time Remaining as an indication that the sec on d regeneration wil l be performed. When the first regeneration is com pl ete, th e s econ d o ne wi ll begin and the display will alternate between Time of Day and Regen Time Remaining.
Automatic Regeneration
There are two ways to have the control automatic ally initiate a regeneration: calendar override or normal metered water usag e.
Calendar Override
This feature is set in parameter P14. It can be set for 1 to 30 days. If it is set to zero, this feature is disabled. When this feature is active, the control keeps track of the number of days since the last backwash and when that number equals the value set in P14, a backwash is automatically started at the Time of Backwash set in P2.
Normal M etere d Wat er U sa ge
The control compares the water usage to the calculated volume capacity of the system. The control uses the Capa city p ar am eter P5 and the Factor A paramet er P3 to calcu la te th e volu m e capacity of the system. It also uses a reserve value to determine if a backwash is necess ar y. If t he water usage s ince the last backwas h is g reater than the s yste m capacity minus the rese rve , a b ack wash is needed.
Note: If the water usage exceeds 150% of the syste m capacity between backwashes, the control will automatically call for a second backwash the next day even if no water used.
Reserve Options
There are two type s of reserve option s for this control: fixed reserve and historical water usage pattern. They are selected with parameter P1 5.
Fixed Rese rv e
When the fixed reserve is selected, the control multiplies the maxi mum system capacity by the percent value set in parameter P16 and uses the result as a reserve.
Water Usage Pattern
The other reserve op tion allows the contr ol to adjust the reserve based upon the historical water usage pattern of the system. The control k eeps track of the water usage for each day of the week and uses that day’s avera g e usage mult iplied by 1.2 as the r eserve for that day. Every day at the Time of Backwash, the control recalculates the day’s average water usage. If less than 10% of a day’s average water u s age is u sed, the control will not change the day’s average. If more than twice the da y’s average is used , the control uses the actual usage in the reserve calculation.
Since a new installation has no history of water usage, the control multiplies the percent of capacity value set in parameter P16 by the total system capacity to determin e st ar ting av erage for each day of the wee k. The factory set default value for P16 is 30 which means that 30% of the tota l sys tem capacity is used for t he starting average for each day.
Program parameter P15 is also used to select whether the control wa its unt il the Time o f Backwash set in paramet er P2 to start a backwash, or if the co nt rol should beg in a ba ckwash immed iate ly when the capacity rema ining is les s than th e rese rve.
11
Page 12
Removing the Valve Assembly for Servicing
1. Unplug t he p owe r c ord.
2. Shut off water supply or put bypass valves into bypass position.
3. Remove cover and with screwdriver, relieve tank pressur e by pushing ope n valve No. 7 (r ear flapper ) on control as shown (Figure 8).
Figure 8
Indicator Arrow
Figure 9
Yellow Camshaft
Clip
4. When used with a globe valve bypass, loosen and detach the inlet, outlet, brine an d drain lines from the valve. If using the 1265 bypass, loosen and remove valve fr om bypass as well as loosening and removing the brine and drain lines.
5. Unscrew ( co un terclockwise) and remov e valve from tank.
6. To replac e th e con trol valve , reve rse th e ab ove procedure.
Removing 440i for Servicing
1. Unplug t he p owe r c ord.
2. Remov e the co v e r.
3. Align the indic ator arrow on the rea r of the camshaft with the top of the rear hoo p of the top plate (Figure 9).
Figure 10
4. Remove the yellow camshaft clip, located at the rear of the camsh af t (Fig ure 10) to remove the camshaft. Push the two end s of the clip togeth er (Figure 1 1) to remove the clip from the bac k.
Figure 11
12
Page 13
5. Remove the yellow camshaft clip from the rear top plate hoop (Figure 12).
Figure 12
6. Diseng ag e the front of the camshaft from the output gear of the control.
7. Remov e the timer locking pi n an d lift the co nt ro l straight up and off of the valve.
8. Reverse the above procedures to reinstall the camshaft and control.
Figure 14
5. To remove the camshaft or to reinstall it, the arrow on the shaft must be pointing at the line on the rear “hoop” of the top plate. This occurs when the indicator knob is rotated to the refill position. Press down on the b ack o f the camshaft to disengag e it from the rear “hoop” of the top plate, (Figure 15). Slide the cam s h af t bac k to dise n g age it from the timer, (Figure 16).
Removing the 940F and 960F Controls For Servicing
Complete the following steps to remove the 940F and 960F control for servicing:
1. Unplug the wa ll -mount transfo rmer.
2. Shut of f the water supply o r put the bypass valve (s) into bypass position.
3. Remove the rear cover by depressing the two tabs provided on the cover, (Figure 1 3). Lift the front of the cover and remo ve to exp ose the valve body.
Tab
Figure 15
Figure 16
Figure 13
4. Relieve syst em pressur e by opening t he Backwash Drain Valve (the seventh valve back from the control) with a screwdriver, (Figure 14).
6. Disconne ct the turb ine probe from the turbine assembly.
7. Lift the control off the valves, Figure 17. To r eplace the control, reverse the above procedure. Note that the camshaft needs to be positioned correctly before it can be inserted into the back of the
13
Page 14
control. There is a loca tin g rib on the camshaft. Position the rib on the top of the shaft and slide the camshaft into the control. Push up on the end of the camshaft, furthest from the timer, snapping it into place.
Figure 17
Preventive Maintenance
Injector Screen
Turbine
instances, the turbine wheel of the water meter can collect small particle s of o xid ized iron, eventually preventing the wheel from turning .
1. Shut off the water supply or put the bypass valve(s) into the bypass posit ion .
2. Reli eve pressure by opening the Back wash Drain Valve (the seventh back from the control) with a screwdriver (Figure 14).
3. Loosen and remove the pipe/ tub e adapters or 1265 bypass from the inl et and ou tlet o f the valv e body.
4. Using a needle-nose pliers, remove the turbine from the outlet housing. Grasp one of the four vanes of the outer gland and pull straight out to remove turbine asse mb ly from the outlet of the valve (Figure 18).
5. Caref ully rem o ve the tu rbine wheel from the housing. Use a toothbrush to lightly scrub the iron off the magnet. Iron buildup on the surfaces can be removed by s oa ki ng the wh e el in a mi ld s o di um hydrosulfite (such as RoVer*) solution for a few minutes. Flush thoroughly with water.
6. Carefully reinstall the turbine wheel into the turbine cage housing. Make sure that the shaft of the wheel seats into t he be arin g of th e cage . Rea sse mble the turbine cag e an d check that the wheel rotates freely.
Injector
Cap
Figure 18
Water Meter Maintenance
Note: A water meter is used only with the 960F control. If you are using the 440i or 940F control, this section does not pertain to your conditioner.
The metering device used with the 960 dema nd controls may requ ire simp le maintenance. In rare
7. Reinst all the turbine cage into the outlet o f the valve.
8. Reinstall the pipe/tube adapters or 1265 bypass to the inlet and outlet of the valve.
9. T urn on the water supply or put the bypa ss valve(s) into the service position and purge the air out of the system.
To ch eck for proper meter op eration, open a downst ream faucet and observe the water flow indic ation on the co nt rol display.
14
Page 15
Specifications
263/440i Drawings
1
6
2
5
3
4
Inlet
2.5 inch (63 mm)
Drain
2.5 inch (63 mm)
Outlet
11.59 inch (294 mm)
8.74 inch (222mm)
2.88 inch (73 mm)
1.356 inch (34 mm)
3.37-inch (86 mm)
3.66-inch (93 mm)
5.76 inch (146 mm)
5.82 inch (148 mm)
Hydrostatic Test Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 p si (20 .6 9 bar )
Working Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-125 psi (1.38 - 8.62 bar)
Standard Electrical Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115V 60 Hz
Optional Electrica l Rating . . . . . . . . . . . . . . . . . . . . . . 115V 50 Hz, 230V 50 Hz, 200V 60 Hz, 24V 60 Hz, 24V 50 Hz,
100V 60 Hz, 100V 50 Hz, 12V 50 Hz/transformer, 12V 60 Hz/transformer
Electrical Cord (standard rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 inch (1.5 m) 3-wire with plug
Pressure Tank Thread . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1/2 inch-8 male
Riser Pipe Diameter Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.050 inch OD (26.7 mm)
Riser Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . .1-1/8
± 1/8 inches (31.8 mm) highe r than the top of mineral tank
Standard Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-inch (25.4-mm) copper tube adapters
Optional Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3/4-inch, 22-mm, and 28-mm copper tube adapters
3/4-inch BSPT , 1-inch BSPT , 1-inch NPT brass pipe adapters
3/4-inch, 1-i nch, 25-mm CPVC tube adapters
Drain Line Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4-inch NPT male
Optional Bypass Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Rotating handles, full 1-inch porting, reinforced Noryl
Control Module, Tank Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Reinforced Noryl
Rubber Goods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compounded for co ld wa t er service
Program Clock (Timer). . . . . . . . 440i: Available in 6 - or 7-day English, Ge rman, French, Italian, Spanish, Japanese
940F: Availa ble in 7 - or 12-day English, Ger man , French, Italian, Spanish, Japane se
960F: Available in English, German, French, Italian, Spanish, Japanese
Internal Backwash Controllers. . . . . . . . . . . . . . . . 7- through 14-inch (17.8- though 35.6-cm) diameter media tanks
All sizes to flow 4.5 gpm/sq ft (183 L/m/m
2
) of bed area. For tank sizes above 14 inches in diameter ,
use an external flow control.
15
Page 16
263/900 Series Drawings
16
Page 17
Control Valving Identifications
7 Backwash Drain Valves
3 Inlet Valve
6 Rinse Drain Valve
4 Outlet Valve
2 Bypass Valve
Flow Diagrams
Valve Disc Operation
1 Treate d Water Posit i on
Untreated Water
Treated Water
Plug
3
5
6
Valve No. 1 - Closed 2 - Closed 3 - Open 4 - Open 5 - Closed 6 - Closed 7 - Closed
Inlet
Outlet
2
4
Drain
Mineral Tank
2 Backwash Pos i t ion
Untreated Water
Treated Water
1
1
Plug
Inlet
7
Outlet
Drain
3
2
4
Valve No. 1 - Open 2 - Open 3 - Closed 4 - Open 5 - Open 6 - Closed 7 - Open
Mineral Tank
1
Plug
5
6
Plug
7
Backwash Flow Control
17
Page 18
3 Fast Rinse Position
Untreated Water
Treated Water
Valve No. 1 - Closed 2 - Open 3 - Open 4 - Closed 5 - Closed 6 - Open 7 - Closed
Inlet
Outlet
Drain
3
2
4
Mineral Tank
1
Plug
5
6
Plug
7
18
Page 19
Performa Valve Replacement Parts
Performa Valve
5
6
7
12
18
15
15
17
16
11
8
1
14
10
13
9
4
3
2
19
Page 20
Parts List
Part
Code
No. Description Qty. Code
10 1030334 Plugged Brine Refill Control 1 1 1035807 Valve Assy, w/o Flow Controls (940F, 960F) 1 11 1002449 Drain Fitting Elbow (3/4” hose barbed) 1 2 1035606 Valve Assembly, w/o Flow Controls (4 40i) 1 12 1000226 Cap Assembly 1 3 1031391 Timer Locking Pin 1 13 1010429 O-Ring 1 4 1035624 440i Filter Camshaft (Grey) 1 14 1035622 T ank Ring 1 5 103038 0 940F, 960F Fil ter Camshaft 15 Plumbing Adapter Kit s: 1 6 Drain Control Assembly: 1 1001606 3/4-inch Copper Tube Adapter Kit
100020 9 No. 7 (1.2 gpm; 4.5 Lpm) 1001670 1-inch Copper Tube Adapter Kit 100021 0 No. 8 (1.6 gpm; 6.1 Lpm) 1041210 1-1/4-inch copper Tube Adapter Kit 1000211 No. 9 (2.0 gpm; 7.6 Lpm) 1001608 22-m m Copp er Tube Adapter Kit 1000212 No. 10 (2.5 gpm; 9.5 Lpm) 1001609 28-mm copper Tube Adapter Kit 100021 3 No. 12 (3 .5 gpm; 13.2 Lpm) 1001613 3/4-inch CP VC Tube Adapt er Kit 1000214 No. 13 (4.1 gpm; 15.5 Lpm) 1001614 1-inch CPVC Tube A dapter Kit
100021 5 No. 14 (4.8 gpm; 18.2 Lpm) 1001769 3/4-inch NPT Plastic Pipe A dapter Kit 7 103050 2 Ball, Flow Cont rol 2 1001603 1-inch NPT Plastic Pipe Adapter Kit 8 1032978 Plugged Injector Assembly 1 1001604 3/4-inch BSPT Plastic Pipe Adapter Kit 9 1000218 Inje c tor Cap Assembl y 1 1001605 1-inc h BSPT Plastic Pipe Adapt er Kit
16 1 0 33 444 Turbine As se mb ly (9 60 F on ly) 1 17 1001580 Spring, Flapper Valve
*Valve Disc Kit:
* 10000 62 I-Lid Cover 1
Part
No. Description Qty.
1001611 3/4-inch BSPT Brass Pipe Adapter Kit 1001610 1-inch NPT Brass Pipe Adapter Kit 1001612 1-inch BSPT Brass Pipe Adapter Kit
1041174 Standard 1041175 Severe Service
20
Page 21
Tim
e of Day
Tim
e of Regen Factor A Factor B Capacity Regen Tim
e
Remaining
REGENERATION COMPLETE
F
A
S
T
R
I
N
S
E
B
A
C
K
W
A
S
H
PM
Perform
a
Filter
T
M
440i Control 940F Control
TM
Performa Filter
FOR MANUAL BACKWASH ROTATE POINTER COUNTER CLOCKWISE TO START POSITION
BACKWASH COMPLETE
TO ADJUST BACKWASH MINUTES, ROTATE SMALL DIAL COUNTER CLOCKWISE. DO NOT ADJUST DURING BACKWASH
12
960F Control 1265 Bypass
A
P
Y
B
E
S
N
I
R
T
S
A
F
S
E
R
V
I
C
E
S
S
B
A
C
K
W
A
S
H
TO SET REGENERATION DAYS PRESS PINS IN
S
S
A
P
Y
B
34
Part
Code
1 2 3 4 1040930
* 1000811
*
*
*Not Shown
No. Description Qty.
440i Control (6 day or 7 day) 940F Cont rol (7 day or 12 day) 960F Control 1265 Bypass Transformer (440i, 460i, 960):
1000907
1034264
Transformer Extension Cord 15 feet (4.6 m)
Y-Splitter (run 2 units from 1 tran s­former)
1 1 1 1 1
1
1
21
Page 22
Troubleshooting
The technology upon which the Autotrol Perf orma control valve is based is well established and proven in service over many years. However , should a pr oblem or question aris e re gard ing the o pe r atio n o f the s y st em, the control can v ery eas ily be se rviced. For parts mentione d, refer to ex pl od ed v iew s in the
Replacement Parts section of this manual.
Valve Troubleshooting
Problem Possible Cause Solution
1. Control backwashes at excess ively low or high rate.
2. Untreated water leakage during service.
a. Incorrect backwash controller used. b. Foreign matter affecting co ntroller
operation !
a. Improper regeneration. b. Leaki ng of bypass valve ! c. O-ring around riser tube damaged !
440i and 940F Control Troubleshooting
IMPORTANT: Serv ice procedures that r equire the
water pressur e to be rem oved from the system are marked with a ! after the possible caus e. To remove water pressure from the system, put the bypass valve or three-valve bypa s s into the bypa s s po sitio n and open the backwash drain valve (the seventh valve back from the control) with a screwdriver. Restore system water pressure when the service work is completed.
a. Replace with correct size controller. b. Remove controller and ball. Flush with water.
a. Repeat regeneration making certain that the
correct salt dosage i s set.
b. Replace O-rin g. c. Replace O-ring.
Problem Possible Cause Solution
1. Control will not regenerate automatically.
2. Control regenerates at wrong time of day.
a. Transformer or motor not connected. b. Defecti ve timer motor. c. Skipper pins not down on timer skipper
wheel.
d. Binding in gear train of timer. a. Time set incorrectly. a. Correct time setting according to inst ructions.
a. Connect power. b. Replace motor. c. Depress pins for days regeneration required. d. Replace timer.
22
Page 23
960F Control Troubleshooting
Alarms
The Model 960 continuously monitors itself and sounds an alarm if it detects something wrong. The alarm is a beep that is on for o ne s eco nd an d th en o ff for nine seconds. When the alarm sounds, the display shows the letters “Err” wi th a numb er from 1 to 4. The tab le
Model 960 Alarms
Indication Description
Err 1 Electronics Failu re
Improper start of
Err 2
regeneration (limit switch closed when it should be
open).
Improper finish of
Err 3
regeneration (limit switch
open when it should be
closed).
Improper control settings
Err 4
(one or more setti ngs out of
the allowable range).
Control settings need
reprogramming.
Valve camshaft has been manually rotated during a
regeneration.
Valve camshaft has been
manually rotated out of
“regeneration complete”
Faulty motor.
Faulty motor drive.
Faulty s witch.
Valve camshaft has been
manually rotated out of
“regeneration complete”
Faulty motor.
Faulty motor drive.
faulty switch.
One or more se ttings out of
the allowable range.
below lists the Err numbers, a description of each error, the cause of the error, and the solutions. T o silence the alarm, press any button o n the co ntrol. If the error still exists, th e con trol w ill g o bac k to the alarm condition after 30 seconds.
Cause
Press any key to load defaul t valu es. Refe r
to “Programming the Model 960 Control”.
Press any key to silence the alarm. (Note:
Alarm automatically clears at “TIME OF
The control will turn the motor on and drive
the camshaft to the proper location.
position.
The control will turn the motor on and drive
the camshaft to the proper location.
position.
Hardness: Adjust range: 3 to 250.
Capacity: Adju st range: 0.1 to 140.0.
Refill c on t rol: Ad ju s t ran g e : 1 to 99.
Brine draw value: Adjust range per Table 2.
Solution
REGEN”.)
Replace the control. Replace the control. Replace the control.
Replace the control. Replace the control. Replace the control.
Problem Possible Cause Solution
1. Capacity Display stays at 9999 even though there is water usage.
2. Timer beeps when left arrow button is pressed.
3. Timer does not respond to REGEN button.
4. Timer d oes not di splay ti me of day.
5. Timer does not display correct time of day.
a. Total system capacity was cal culated to
a. Button is only active in the programming
a. Button is not active in the programming
a. Transformer is unplug ged. b. No electric pow er at outlet. c. Defective transformer. d. Defecti ve circuit board. a. Outlet operated by a switch. b. Power outages.
be a value greater than 9999.
mode.
mode.
23
a. As the water usage continues, the remaining
capacity will dr op below 9999 and then other values will be shown.
a. Refer to the Programming section.
a. Refer to the Regeneration section.
a. Connect power. b. Repair outlet or us e working outlet. c. Replace transformer. d. Replace control. a. Use outlet not controlled by switch. b. Reset Time of Day.
Page 24
6. No water flow display when water is flowing (colon does not blink).
7. Control display is frozen at Regen Time Remain ing.
8. Control regenerates at wrong time of day.
9. Timer stalled in regeneration cycle.
10. Continuous regeneration. Camshaft does not stop at the end of regeneration.
11. Control does not regenerate automatically or when R EGEN button is depressed.
a. Bypass valve in bypass position. b. Meter probe disconnected or not fully
connected to meter housing.
c. Restricted meter turbine rotation due to
foreign material in meter ! d. Defecti ve meter probe. e. Defective circuit board.
a. Back to back regenerations were
requested. a. Power outages. b. Time of day set incorrectly. c. Time of regeneration set incorrectly. a. Motor not operating. b. Motor runs backwards. c. No electric power at outlet. d. Incorrect voltage or frequency (Hz). e. Broken gear. f. Defective switch. g. Air leak in brine connecti o ns ( pr essure
locked flapper). h. Binding of camshaft. i. Water pressure greater th an 125 psi
during regeneration. j. Defective circuit board .
a. Broken projecti o n on drive gear. b. Defective switch.
a. Transformer unplugged. b. No electric pow er at outlet. c. Defective motor. d. Broken gear. e. Binding in gear train. f. Defective switch.
a. Shift bypass valve into service position. b. Fully insert probe into meter housing. c. Remove meter housing, free up turbine and
flush with clean water. Turbine should spin freely, if not, refer to the Water Meter
Maintenance section. d. Replace control. e. Replace control. a. Refer to the Manual Regeneration section.
a. Reset time of day to correct time of day. b. Reset time of day to correct time of day. c. Reset time of regeneration. a. Replace control. b. Replace control. c. Repair outlet or use working outlet. d. Replace timer and/or transformer with one of
correct voltage and frequency (Hz). e. Replace control. f. Replace control. g. Check all junction points and m ake
appropriate corrections. h. Remove foreign object obstruction from valve
discs or camshaft. i. Install pressure regulator to reduce pressure. j. Replace control. a. Replace control. b. Replace control.
a. Connect power. b. Repair outlet or us e working outlet. c. Replace control. d. Replace control. e. Replace control. f. Replace control.
12. Control does not regenerate
a. If water flow display is not operative, refer automatically but do es regenerate when REGEN button is depressed.
13. Run out of treated water between regenerations
b. Incorrect program settings. c. Defective circuit board. a. Improper regeneration. b. Fouled resin bed. c. Incorrect factor 1 or capacity settings. d. Restricted meter turbine rotation due to
e. Excessive water usage below 1/5 gallon
to item 5 in this table.
foreign material in meter housing !
per minute.
a. Refer to item 5 in this table. b. Set new control v alu es. Refer to the
Programming section. c. Replace control. a. Repeat regeneration making certain that
correct salt dosage is used. b. Use resin cleaner. c. Set to correct values. Refer to the
Programming section in this manual. d. Remove meter housin g, fr ee up turbine, and
flush with clean water. Turbine should spin
freely, if not, replace meter. e. Repair leaky plumbing and/or fix tures.
© Copyright 2007 GE Water & Process Technologies
Printed in USA P/N 1227982 Rev. D
Loading...