Autonics PR Series Catalog Page

PR Series
PR Series
Cylindrical Type Proximity Sensor
Features
Improved the noise immunity with dedicated IC
● Built-in reverse polarity protection circuit (DC 3-wire type)
● Built-in surge protection circuit
● Built-in output short over current protection circuit (DC type)
● Long life cycle and high reliability, and simple operation
● IP67 protection structure (IEC standard)
● Replaceable for micro switches and limit switches
Please read “Safety Considerations” in the instruction manual before using.
Specifications
● DC 2-wire type
PRT08-1.5DO
Model
Diameter of sensing side
Sensing distance 1.5mm 2mm 2mm 4mm 5mm 8mm 10mm 15mm
Installation Shield (ush)
Hysteresis Max. 10% of sensing distance
Standard sensing target
Setting distance 0 to 1.05mm 0 to 1.4mm 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm
Power supply (operating voltage)
Leakage current Max. 0.6mA
Response frequency
Residual voltage
A󰀨ection by Temp.
Control output 2 to 100mA
Insulation resistance Over 50MΩ (at 500VDC megger)
Dielectric strength 1,500VAC 50/60Hz for 1 min
Vibration 1mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Shock 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times
Indicator Operation indicator: Red LED
Environ-
ment
Protection circuit Surge protection circuit Surge protection circuit, output short over current protection circuit
Protection structure IP67 (IEC standard)
Cable
Material
Approval
Weight
※ ※ ※ ※
1
Ambient temperature
Ambient humidity
3
1: The response frequency is the average value. The standard sensing target is used and the width is set as 2 times of the standard
sensing target, 1/2 of the sensing distance for the distance.
2: Before using non-polarity type, check the condition of connected device because residual voltage is 5V. 3: The weight includes packaging. The weight in parenthesis in for unit only. The ' ' of model name is for power type. 'D' is 12-24VDC, 'X' is non-polarity 12-24VDC. Environment resistance is rated at no freezing or condensation.
PRT08-1.5DC PRT08-1.5DO-V
8mm 12mm 18mm 30mm
8×8×1mm
(iron)
12- 24VDC (10 -30VDCᜡ)
1.5kHz 1kHz 1.5kHz 500Hz 350Hz 400Hz 200Hz
2
Max. 3.5V (non-polarity type is max. 5V)
Max. ±10% for sensing distance at ambient temperature 20 (for PRT08 Series: ±20% max.)
-25 to 70℃, storage: -30 to 80
35 to 95% RH, storage: 35 to 95% RH
Ø3.5mm, 2-wire, 2m
(AWG24, Core diameter:
0.08mm, Number of cores: 40, Insulator diameter: Ø1mm)
Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate, Standard cable (black): Polyvinyl chloride (PVC), Oil resistant cable (gray): Oil resistant polyvinyl chloride (PVC)
Approx. 64g (approx. 52g) Approx.84g (approx. 72g) Approx.122g (approx. 110g) Approx.207g (approx. 170g)
PRT08-2DO PRT08-2DC
Non-shield
(non-ush)
PRT12-2DO PRT12-2DC
Shield (ush)
12×12×1mm
(iron)
Ø4mm, 2-wire, 2m Ø5mm, 2-wire, 2m
AWG22, Core diameter: 0.08mm, Number of cores: 60, Insulator diameter: Ø1.25mm
PRT12-4DO PRT12-4DC
Non-shield
(non-ush)
When the model name is X, it is non-polarity model.
PRT18-5DO PRT18-5DC
Shield (ush)
18×18×1mm
(iron)
PRT18-8DO PRT18-8DC
Non-shield
(non-ush)
25×25×1mm
(iron)
PRT30-10DO PRT30-10DC PRT30-10DO-V
Shield (ush)
30×30×1mm
(iron)
PRT30-15DO PRT30-15DC
Non-shield
(non-ush)
45×45×1mm
(iron)
F-70 F-71
Cylindrical Type
Specifications
● DC 3-wire type
PR12-4DN PR12-4DP PR12-4DN2 PR12-4DP2 PRS12-4DN PRS12-4DP PRS12-4DN2 PRS12-4DP2 PRL12-4DN PRL12-4DP
Non-shield
(non-ush)
PR18-5DN PR18-5DP PR18-5DN2 PR18-5DP2 PR18-5DN-V PRL18-5DN PRL18-5DP PRL18-5DN2 PRL18-5DP2
Shield (ush)
18×18×1mm
(iron)
PR18-8DN PR18-8DP PR18-8DN2 PR18-8DP2 PRL18-8DN PRL18-8DP PRL18-8DN2 PRL18-8DP2
Non-shield
(non-ush)
25×25×1mm
(iron)
PR: Approx. 122g (approx. 110g) PRL: Approx. 142g (approx. 130g)
PR30-10DN PR30-10DP PR30-10DN2 PR30-10DP2 PRL30-10DN PRL30-10DP PRL30-10DN2 PRL30-10DP2
Shield (ush)
30×30×1mm
(iron)
PR30-15DN PR30-15DP PR30-15DN2 PR30-15DP2 PRL30-15DN PRL30-15DP PRL30-15DN2 PRL30-15DP2
Non-shield
(non-ush)
45×45×1mm
(iron)
PR: Approx. 207g (approx. 170g) PRL: Approx. 247g (approx. 210g)
Model
Diameter of sensing side
PR08-1.5DN PR08-1.5DP PR08-1.5DN2 PR08-1.5DP2 PRL08-1.5DN PRL08-1.5DP PRL08-1.5DN2 PRL08-1.5DP2
8mm 12mm 18mm 30mm
PR08-2DN PR08-2DP PR08-2DN2 PR08-2DP2 PRL08-2DN PRL08-2DP PRL08-2DN2 PRL08-2DP2
PR12-2DN PR12-2DP PR12-2DN2 PR12-2DP2 PRS12-2DN PRS12-2DP PRS12-2DN2 PRS12-2DP2
Sensing distance 1.5mm 2mm 2mm 4mm 5mm 8mm 10mm 15mm
Installation Shield (ush)
Non-shield
(non-ush)
Shield (ush)
Hysteresis Max. 10% of sensing distance
Standard sensing target
8×8×1mm (iron) 12×12×1mm (iron)
Setting distance 0 to 1.05mm 0 to 1.4mm 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm
Power supply (operation voltage)
Current consumption
Response frequency
1
12 -24VDC (10- 30VDCᜡ)
Max. 10mA
1.5kHz 1kHz 1.5kHz 500Hz 350Hz 400Hz 200Hz
Residual voltage Max. 2.0V Max. 1.5V
A󰀨ection by Temp.
Max. ±10% for sensing distance at ambient temperature 20, PR08 Series: max. ±20%
Control output Max. 200mA
Insulation resistance Over 50MΩ (at 500VDC megger)
Dielectric strength 1,500VAC 50/60Hz for 1 min
Vibration 1mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Shock 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times
Indicator Operation indicator: Red LED
Environ-
ment
Ambient temperature
Ambient humidity
-25 to 70℃, storage: -30 to 80
35 to 95%RH, storage: 35 to 95%RH
Protection circuit Surge protection circuit, Reverse polarity protection circuit, output short over current protection circuit
Protection structure IP67 (IEC standard)
Material
Cable
Approval
2
Weight
1: The response frequency is the average value. The standard sensing target is used and the width is set as 2 times of the standard
sensing target, 1/2 of the sensing distance for the distance.
2: The weight includes packaging. The weight in parenthesis in for unit only.
Environment resistance is rated at no freezing or condensation.
Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate, Standard cable (black): Polyvinyl chloride (PVC), Oil resistant cable (gray): Oil resistant polyvinyl chloride (PVC)
Ø3.5mm, 3-wire, 2m
(AWG24, Core diameter: 0.08mm, Number of cores: 40, Insulator diameter: Ø1mm)
Ø4mm, 3-wire, 2m Ø5mm, 3-wire, 2m
AWG22, Core diameter: 0.08mm, Number of cores: 60, Insulator diameter: Ø1.25mm
PR: Approx. 64g (approx. 52g) PRL: Approx. 66g (approx. 54g)
PR: Approx. 84g (approx. 72g) PRS: Approx. 82g (approx. 70g) PRL: Approx. 88g (approx. 76g)
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(A) Photoelectric Sensors
(B) Fiber Optic Sensors
(C) LiDAR
(D) Door/Area Sensors
(E) Vision Sensors
(F) Proximity Sensors
(G) Pressure Sensors
(H) Rotary Encoders
(I) Connectors/ Connector Cables/ Sensor Distribution Boxes/ Sockets
PR Series
Specifications
● AC 2-wire type
Model
Diameter of sensing side
Sensing distance 2mm 4mm 5mm 8mm 10mm 15mm
Installation Shield (ush)
Hysteresis Max. 10% of sensing distance
Standard sensing target
Setting distance 0 to 1.4mm 0 to 2.8mm 0 to 3.5mm 0 to 5.6mm 0 to 7mm 0 to 10.5mm
Power supply (operation voltage)
Leakage current Max. 2.5mA
Response frequency
Residual voltage Max. 10V
A󰀨ection by Temp.
Control output 5 to 150mA 5 to 200mA
Insulation resistance Over 50MΩ (at 500VDC megger)
Dielectric strength 2,500VAC 50/60Hz for 1 min
Vibration 1mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Shock 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times
Indicator Operation indicator: Red LED
Ambient
Environ-
ment
Protection circuit Surge protection circuit
Protection structure IP67 (IEC standard)
Cable
Insulation type
Material
Approval
Weight
※ ※
temperature Ambient
humidity
2
1: The response frequency is the average value. The standard sensing target is used and the width is set as 2 times of the standard
sensing target, 1/2 of the sensing distance for the distance.
2: The weight includes packaging. The weight in parenthesis in for unit only. Environment resistance is rated at no freezing or condensation.
PR12-2AO PR12-2AC
12mm 18mm 30mm
12×12×1mm (iron) 18×18×1mm (iron) 25×25×1mm (iron) 30×30×1mm (iron) 45×45×1mm (iron)
100- 240VAC (85- 264VACᜠ)
1
20Hz
Max. ±10% for sensing distance at ambient temperature 20
-25 to 70℃, storage: -30 to 80
35 to 95%RH, storage: 35 to 95%RH
Ø4mm, 2-wire, 2m Ø5mm, 2-wire, 2m
AWG22, Core diameter: 0.08mm, Number of cores: 60, Insulator diameter: Ø1.25mm
Double insulation or reinforced insulation (Mark: , dielectric strength between the measuring input part and the power part: 1kV)
Case/Nut: Nickel plated brass, Washer: Nickel plated iron, Sensing surface: Polybutylene terephthalate, Standard cable (black): Polyvinyl chloride (PVC)
Approx. 84g (approx. 66g)
PR12-4AO PR12-4AC
Non-shield
(non-ush)
PR18-5AO PR18-5AC PRL18-5AO PRL18-5AC
Shield (ush)
PR: Approx. 130g (approx. 118g) PRL: Approx. 142g (approx. 130g)
PR18-8AO PR18-8AC PRL18-8AO PRL18-8AC
Non-shield
(non-ush)
PR30-10AO PR30-10AC PRL30-10AO PRL30-10AC
Shield (ush)
PR: Approx. 207g (approx. 170g) PRL: Approx. 245g (approx. 208g)
PR30-15AO PR30-15AC PRL30-15AO PRL30-15AC
Non-shield
(non-ush)
F-72 F-73
Loading...