24V DC-Powered Relay
ZL-RRL16
COM NO NC COM NO NC
COM NO NC
GND 24V
NC
COM NO NC COM NO NC
11.76” [299.0mm]
4.81”
[122.2mm]
24VDC
Module Installation
Instructions
Heat Dissipation Mounting Requirements
ZL-RRL16F-24
D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 D15
F1
COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC
F3
F2
F4
+24V +24VGND GND
1
13
F5
TB5 TB6 TB7 TB8 TB13 TB14 TB15 TB16TB1 TB2 TB3 TB4 TB9 TB10 TB11 TB12
F7
F6
12
24
F9
F8
F11
F10
D16
F12
F13
F15
F14
Sinking ZL-RRL16F-24-1
Sourcing ZL-RRL16F-24-2
WARNING: We recommend installing
up to a 0.75 Amp fast-blow fuse such
as AGC-75 or similar in series with
the power supply as an extra safety
GND 24V
F16
measure.
2.5 mm
Te rminal Block Insertion
Point Opening Dimension
2.9 mm
0.114"
Airow
IMPORTANT! Mount Module horizontally to provide proper ventilation.
ZL-RRL16F-24-1 Sinking
DirectLOGIC Productivity3000 CLICK Productivity2000 BRX
+24V
J1
J2
J3
+24V
DirectLOGIC Productivity3000 CLICK Productivity2000 BRX
J1
J2
+24V
J3
Jumper Position Description
J1, J2, and J3
J1 +24V
J1 GND
J2 +24V
J2 GND
J3 +24V
J3 GND
+24V
J1
J2
GND GND
J3
+24V +24V
ZL-RRL16F-24-2 Sourcing
J1
GND
GND
J2
+24V
J3
GND
GND
Connects +24VDC to Connector Pins 1,7,13, & 19
Connects GND to Connector Pins 1,7,13, & 19
Connects +24VDC to Connector Pins 2, 8,14, & 20
Connects GND to Connector Pins 2, 8,14, & 20
Factory set On ZL-RRL16F-24-1
Connects +24VDC to Relay Coil Commons
Factory set On ZL-RRL16F-24-2
Connects GND to Relay Coil Common
J1
J2
+24V
J3
J1
+24V
J2
J3
GND
J1
J2
+24V
J3
+24V +24V
J1
J2
GND
+24V
J3
GND
J1
GND
J2
J3
J1
GND
+24V
J2
+24V
J3
GND GND
Jumpers referenced above and below
have this silkscreen on the PCB
GND
GND
2.23in
56.7mm
35mm
DIN RAIL
Typical Internal Circuit
2.30in
58.4mm
GND
24V
ZL-RRL16F-24 Pinouts
Connector Pin Relay
3 Relay 1 (TB1)
4 Relay 2 (TB2)
5 Relay 3 (TB3)
6 Relay 4 (TB4)
9 Relay 9 (TB9)
10 Relay 10 (TB10)
11 Relay 11 (TB11)
12 Relay 12 (TB12)
15 Relay 5 (TB5)
16 Relay 6 (TB6)
17 Relay 7 (TB7)
18 Relay 8 (TB8)
21 Relay 13 (TB13)
22 Relay 14 (TB14)
23 Relay 15 (TB15)
24 Relay 16 (TB16)
Jumper 1
ZL-RRL16F-24
D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 D15
F1
F3
F2
F4
+24V +24VGND GND
1
13
F5
TB5 TB6 TB7 TB8 TB13 TB14 TB15 TB16TB1 TB2 TB3 TB4 TB9 TB10 TB11 TB12
F7
F6
F8
ZL-RLL16F-24-2 Sourcing
Typical Internal Circuit
24V
GND
Note 1: See jumper notes.
Jumper 2
12
24
F9
F11
F10
COM
COM
(Note 1)
NO NC
(Note 1)
NO NC
F12
Cable Connector Pin
Terminal
Block
Optional External
Transient
Supression
Cable Connector Pin
Terminal
Block
Optional External
Transient
Suppresion
Jumper 3
D16
F13
F14
2.7K
2.7K
GND 24V
F15
F16
1
Description
Mechanical Life
Electrical Life
Operating Frequency
Isolation Coil to Contact
Isolation NC Contact to NO Contact
Isolation Between Relays
Red LED Indicator State Relay
Operating Temperature Range
Shock Resistance
Terminal Block Contacts
Wire Range*
Wire Strip Length
Screw Torque
Connector Type
Replacement Relays
Fuses (Sold Separately)
Replacement Fuses
Cable/Wire Clearance
Weight
Approvals
COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC
General Module Specifications Relay Contact Specifications
16 Fused Output Relay module with LEDs, 24 VDC Coil
100,000,000 Operations no load condition
1,000,000 Operations at rated resistive load
6 cycles per minute electrical
300 cycles per minute mechanical
2500VAC for 1 minute
1000VAC for 1 minute
1000VAC for 1 minute
ON = relay energized, OFF = relay de-energized
32 to 140°F (0 to 60°C)
1000m/s² endurance, 100m/s² operation
Copper alloy, tin-lead plated
12–24 AWG Solid or Stranded Conductor
0.24–0.27 in (6–7 mm)
4.4 in-lbs (0.5 Nm)
Molex Micro-Fit 3.0, 24 pin connector,
example receptacle 43020-2400, Pins 43031 Series, Male
ZL-RELAY-F24X4, Qty. 4/pkg
Sixteen 5X20mm, 250V
See Edison 5X20mm Glass Fuse section range up to Max. 10
0.5in (12.7mm)
930g (32.8 oz)
File # E139594 UL, cUL 508, CE, EN 61131-2:2007
Current Rating
Contact Type
Contact Voltage*
Maximum Power Inductive
Maximum Power Resistive
Maximum Switching Voltage
Minimum Load
Contact Resistance
Contact Capacity
Contact Material
Input Voltage Rating**
Maximum Continuous Coil Voltage
Rated Current Per Coil
Coil Specifications
Coil Resistance
Power Consumption Per Coil
Total Coil Supply Current Max.
Pick Up Current Max. Per Coil
Drop-Out Voltage Min.
Pick-Up Voltage Max.
Off to On/On to Off Response Time
30VDC @ 8A General Use
250VAC @ 8A General Use
1 Form C (SPDT)
250VAC/30VDC
2000VA General Use
AC 2000VA, DC 240W
250VAC, 300VDC
10mA @ 5VDC
100mΩ Max @ 1A, 6VDC
5FLA/30LRA, 250VAC
1/2 HP, 250VAC
Pilot Duty B300-C300
AgNi (Silver Nickel Alloy)
24VDC (-20 / +30%)
31.2VDC
16.7 mA (±10%) @ 24VDC
1440Ω (±10%)
0.4 W
400mA (Total 16 relays)
15mA
1.2 VDC
19.2 VDC
12mS/8mS
*Use conductors rated 60°/75°C for relay outputs. **Relay modules are reverse polarity protected and will not operate if reverse voltage is connected.
![](/html/c3/c3fb/c3fb1004342758cd3c93426199abe11402bbd1cf51a53b7bdf6e6a5f6e95fae2/bg2.png)
Click
DIN Rail Installation
and Removal
Repeat for Tab 2.
Tab
1
Tab
2
To remove
ZIPLink
module, insert
screwdriver
between Tab 1
and module.
Pry up
to release
clip from DIN rail.
To install ZIPLink module, insert upper tab
into DIN rail.
Rotate
until
firmly seated
and locked
on DIN rail
Note: For
cable/wire
clearance
.5” (12.7mm)
1
Rotate retaining clip away from relay.
2
Remove relay
from module.
Reverse procedure
to replace relay.
Remove or Install Relay
24V DC-Powered Relay
Module Installation
Sinking ZL-RRL16F-24-1
Instructions
Sourcing ZL-RRL16F-24-2
WARNING: To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate the
installation and operation of your equipment. These codes vary from
area to area and it is your responsibility to determine which codes
should be followed, and to verify that the equipment, installation, and
operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from
the failure to follow all applicable codes and standards. We do not
guarantee the products described in this publication are suitable for
your particular application, nor do we assume any responsibility for
your product design, installation, or operation.
If you have any questions concerning the installation or operation
of this equipment, or if you need additional information, please call
Technical Support at 770-844-4200.
This publication is based on information that was available at the
time it was printed. At AutomationDirect.com® we constantly strive to
improve our products and services, so we reserve the right to make
changes to the products and/or publications at any time without notice
and without any obligation. This publication may also discuss features
that may not be available in certain revisions of the product.
3505 Hutchinson Road, Cumming GA, USA 30040
1-800-633-0405 www.automationdirect.com
Copyright 2018, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
ZIPLink Cable Removal
Pull connector
2
from socket.
1
Push tab on
raised tip
and hold.
For Replacement Relay
Use ZL-RELAY-F24X4, Qty. 4/pkg.
Part Number Revision Date
ZL-RRL16F-24 6th Ed. 1/20/2021
2