AutomationDirect ZL-RRL16-24-1, ZL-RRL16-24-2 Installation Instructions

ND
GN
+24V
+24V
24V DC-Powered Relay
+-
Module Installation Instructions
Heat Dissipation Mounting Requirements
Sinking ZL-RRL16-24-1
Sourcing ZL-RRL16-24-2
WARNING: We recommend installing up to a 0.5 Amp fast-blow fuse such as AGC-5 or similar in series with the power supply as an extra safety measure.
24VDC
Airow
IMPORTANT! Mount Module horizontally to provide proper ventilation.
ZL-RRL16-24 Pinouts
Connector Pin Relay
3 Relay 1 (TB1) 4 Relay 2 (TB2) 5 Relay 3 (TB3) 6 Relay 4 (TB4) 9 Relay 9 (TB9) 10 Relay 10 (TB10) 11 Relay 11 (TB11) 12 Relay 12 (TB12) 15 Relay 5 (TB5) 16 Relay 6 (TB6) 17 Relay 7 (TB7) 18 Relay 8 (TB8) 21 Relay 13 (TB13) 22 Relay 14 (TB14) 23 Relay 15 (TB15) 24 Relay 16 (TB16)
ZL-RRL16-24-1 Internal Circuitr y Details/
Use with Sinking Output Device
COM
COM
NO NC
NO NC
Cable Connector Pin
Cable Connector Pin
GND
ZL-RRL16-24-2 Internal Circuitr y Details/
GND
(Note 1)
24V
Note 1: See jumper notes.
Use with Sourcing Output Device
(Note 1)
24V
Note 1: See jumper notes.
2.7K
Terminal Block
2.7K
Terminal Block
11.77” [299.0mm]
2.14”
35mm DIN RAIL
0.098" [2.5 mm]
0.114" [2.9 mm]
Terminal Block Insertion Point Opening Dimension
3.42”
[86.8mm]
2.18”
[55.5mm]
General Module Specifications** Relay Contact Specifications
Description
Operating Frequency
Isolation Coil to Contact Isolation NC Contact to
NO Contact Same Relay Isolation Between Relays Red LED Indicator State Relay Operating Temperature Range
Humidity Range Terminal Block Contacts
Wire Range* Wire Strip Length Screw Torque Replacement Relay
Connector Type
Dimensions (LxWxH)
Approvals Cable/Wire Clearance Weight (lbs)
Relay Service Life
*Use conductors rated 60°/75°C for relay outputs. **Relay modules are reverse polarity protected and will not operate if reverse voltage is connected.
16 Output Relay module with LEDs, 24VDC coil
20 cycles per minute electrical 300 cycles per minute mechanical
2500 VAC for 1 minute
1000 VAC for 1 minute
1000 VAC for 1 minute ON = relay energized, OFF = relay de-energized 32 to 140°F (0 to 60°C)
45 to 85% RH
Copper alloy, tin-lead plated 12–24 AWG Solid or Stranded Conductor
0.24–0.27 in (6–7 mm)
4.4 in-lbs (0.5 Nm) ZL-RELAY-24X4
Molex Micro-Fit 3.0, 24 pin connector, example receptacle 43020-2400, Pins 43031 Series, Male
11.77 in x 3.42 in x 2.14 in (299mm x 86.8 mm x
54.3 mm)
File # E157382 UL, cUL 508, CE, EN 61131-2:2007
0.5 in (12.7 mm)
1.45
Mechanical: 10,000,000 Operations at no load condition; Electrical: 100,000 Operations at rated resistive load
Current Rating
Contact Type Contact Voltage (per point)* Maximum Power Inductive
Maximum Power Resistive Maximum Switching Voltage Minimum Load Contact Resistance Contact Material
Vibration Resistance Shock Resistances
Coil Specifications
Input Voltage Rating Maximum Continuous Coil Voltage Rated Current Per Coil Coil Resistance Power Consumption Per Coil Total Coil Supply Current Max. Pick Up Current Max. Per Coil Drop-Out Voltage Min. Pick-Up Voltage Max. Off to On/On to Off Response Time
30VDC @ 10A General Use 250VAC @ 8A General Use
1 Form C (SPDT) 250VAC/30VDC 2000 VA General Use
AC 2000 VA, DC 300W 250VAC, 110VDC 10mA @ 5VDC 100mΩ Max @ 1A, 6VDC AgNi (Silver Nickel Alloy)
10 to 55 Hz dual amplitude width 1.5mm
1000m/s² endurance, 100m/s² operation
24VDC (-20 / +30%)
31.2 VDC
16.7 mA (±10%) @ 24VDC 1440 Ω (±10%)
0.4W 293mA (All relays on) 15mA
1.2 VDC
19.2 VDC 12mS/8mS
GND
ND
+24V
24V DC-Powered Relay
+24V GND
Module Installation Instructions
Sinking ZL-RRL16-24-1
Sourcing ZL-RRL16-24-2
Remove or Install Relay
Rotate retaining clip away from relay.
1
Remove relay
2
from module.
Jumper 1 Jumper 3
DIN Rail Installation and Removal
To install ZIPLink module, insert upper tab into DIN rail.
Rotate until firmly seated
Click
Note: For cable/wire clearance requirements see specifications.
Jumper 2
and locked on DIN rail.
ZIPLink Cable Removal
Pull connector
2
from socket.
1
Push tab on raised tip and hold.
For Replacement Relay
To remove ZIPLink module, insert screwdriver between Tab 1 and module.
Use ZL-RELAY-24X4, Qty. 4/pkg.
Reverse procedure to replace relay.
Pry up to release clip from DIN rail.
WARNING: To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call Technical Support at 770-844-4200.
This publication is based on information that was available at the time it was printed. At AutomationDirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product.
Tab
1
Repeat for Tab 2.
Tab
2
ZL-RRL16-24-1 Sinking
DirectLOGIC Productivity3000 CLICK Productivity2000 BRX
+24V
J1 J2 J3
+24V
+24V
J1 J2 J3
+24V
J1
GNDGND +24V
J2 J3
+24V
GND
+24V
J1 J2 J3
+24V
GND
ZL-RRL16-24-2 Sourcing
DirectLOGIC Productivity3000 CLICK Productivity2000 BRX
J1 J2
+24V
J3
GND
GND
GND
GND
+24V
J1 J2 J3
J1 J2
+24V
GND
J3
GND GND
J1 J2
+24V
J3
GND
Jumper Position Description
J1, J2, and J3
J1 +24V
J1 GND
J2 +24V
J2 GND
J3 +24V
J3 GND
Connects +24VDC to Connector Pins 1,7,13, & 19
Connects GND to Connector Pins 1,7,13, & 19
Connects +24VDC to Connector Pins 2, 8,14, & 20
Connects GND to Connector Pins 2, 8,14, & 20
Factory set On ZL-RRL16-24-1 Connects +24VDC to Relay Coil Commons
Factory set On ZL-RRL16-24-2 Connects GND to Relay Coil Common
Jumpers referenced above and below have this silkscreen on the PCB
J1 J2 J3
+24V
+24V
J1 J2
+24V
J3
GND GND
GND
3505 Hutchinson Road, Cumming GA 30040
1-800-633-0405 www.automationdirect.com
Copyright 2018, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
Part Number Revision Date
ZL-RRL16-24 F 1/8/2020