Automation Direct SL4848-RR, SL4848-CR, SL4848-VR, SL4848-RR-D, SL4848-LR Quick Start Manual

...
3505 HUTCHINSON ROAD CUMMING, GA 30040-5860
Quick Start Guide
Quick Start Guid
e
Quick Start Guid
e
SOLO
AutomationDirect’s SOLO is a single loop dual output temperature controller that can control both heating and cooling simultaneously. There are four types of control modes: PID, ON/OFF, Manual, and Ramp / Soak control. Depending upon the particular model of controller, the available outputs include relay, voltage pulse, current, and linear voltage. There are up to three alarm outputs available to allow seventeen alarm types in the initial setting mode. SOLO can accept various types of thermocouple, RTD, or analog inputs, and has a built in RS-485 interface using Modbus slave (ASCII or RTU) communication protocol.
Other features include:
• 1/16 DIN panel size
• 2 line x 4 character 7-segment LED display for Process Value (PV): Red color, and Set Point (SV): Green color
• Auto Tuning (AT) function with PID control
• Selectable between °C and °F for thermocouple or RTD inputs
• 0 to 50 °C (32 to 122 °F) operating temperature range
• UL, CUL and CE agency approvals
General Description
Specifications
Output Specifications
Part Number Input Voltage Output #1 Output #2 / Alarm #3* Alarm #1** Alarm #2**
SL4848-RR 100 - 240 VAC Relay - SPST Relay - SPST Relay - SPST Relay - SPST SL4848-VR 100 - 240 VAC Voltage Pulse Relay - SPST Relay - SPST Relay - SPST SL4848-CR 100 - 240 VAC Current Relay - SPST Relay - SPST Relay - SPST SL4848-LR 100 - 240 VAC Linear Voltage Relay - SPST Relay - SPST Relay - SPST SL4848-RR-D 24 VDC Relay - SPST Relay - SPST Relay - SPST Relay - SPST SL4848-VR-D 24 VDC Voltage Pulse Relay - SPST Relay - SPST Relay - SPST SL4848-CR-D 24 VDC Current Relay - SPST Relay - SPST Relay - SPST SL4848-VV 100 - 240 VAC Voltage Pulse Voltage Pulse Relay - SPST Relay - SPST SL4848-CV 100 - 240 VAC Current Voltage Pulse Relay - SPST Relay - SPST
SL4848-LV 100 - 240 VAC Linear Voltage Voltage Pulse Relay - SPST Relay - SPST
*Output #2 can be configured as control output #2 or as Alarm #3 **Alarm #1 and Alarm #2 have a shared common
Box Contents and Unpacking Instructions
• Unpack the SOLO temperature controller from its shipping carton. Included in the carton is the temperature controller, mounting brackets plus hardware and this Quick Start Guide.
• Inspect all equipment for completeness. If anything is missing or damaged, immediately call the AutomationDirect returns department @ 1-800-633-0405.
• Inspect the part number to ensure the model received matches the output type required.
1.76”
(44.75 mm)
3.15”
(80.0 mm)
0.37”
(9.5 mm)
1.89”
(48.0 mm)
1.89”
(48.0 mm)
4848
PV
SOLO
F
C
SV
OUT1
OUT2
ALM
AT
SET
1.76”
(44.75 mm)
Controller and Panel Cutout Dimensions
2.36”
[60.0 mm]
2.56"
[65.0 mm]
1.77"
[45.0 mm]
+0.02
-0 +0.6
-0
1.77"
[45.0 mm]
+0.02
-0 +0.6
-0
(Min.)
(Min.)
2
3
4
5
This Quick Start Guide provides basic information on setting up the SOLO temperature controller. For advanced setup and communication control as well as free configuration software visit the AutomationDirect web site at www.AutomationDirect.com.
Mounting Brackets and Hardware
SL4848 Temperature
Controller
SL4848
Quick Start Guide
*Note: The supplied 249 ohm resistor should be installed as shown in the terminal wiring diagrams
in section 7 for current input operation.
249 ohm resistor
Specifications
Input Power Requirements
100 to 240 VAC 50 / 60 Hz or 24 VDC
Operation Voltage Range
85 to 264 VAC or 21.6 to 26.4 VDC
Power Consumption
5 VA Max
Memory Protection
EEPROM 4K bit, number of writes 100,000
Control Mode
PID, ON/OFF, Ramp / Soak control or Manual
Input Accuracy
Less than ± 0.2% full scale (except thermocouple R, S, & B types) Max ± 3° (thermocouple R, S, & B types)
Vibration Resistance
10 to 55 Hz, 10 m/s2 for 10 min, each in X, Y and Z directions
Shock Resistance
Max. 300 m/s2, 3 times in each 3 axes, 6 directions
Ambient Temperature Range
32°F to 122°F (0°C to 50°C)
Storage Temperature Range
-4°F to 149°F (-20°C to 65°C)
Altitude
2000m or less
Relative Humidity
35% to 80% (non-condensing)
RS-485 Communication
Modbus slave ASCII / RTU protocol
Transmission Speed
2400, 4800, 9600, 19.2K, 38.4K bps
IP Rating
IP65: Complete protection against dust and low pressure spraying water from all directions.
(inside suitable enclosure)
Agency Approvals
UL, CUL, CE (UL file number E311366)
Pollution Degree
Degree 2 - Normally, only non-conductive pollution occurs.
Temporary conductivity caused by condensation is to be expected.
Input Types
• Thermocouple*
K, J, T, E, N, R, S, B, L, U, TXK (Sampling Rate: 400 ms / per scan)
• Platinum RTD
3-wire Pt100, JPt100 (Sampling Rate: 400 ms / per scan)
• Analog
0-50 mV, 0-5V, 0-10V, 0-20 mA, 4-20 mA (sinking) (150 ms per scan)**
Control Output Options
• Relay (R)
SPST max. resistive load 5A @ 250 VAC
• Voltage Pulse (V)
DC 14V Max, output current 40mA Max
• Current (C)
DC 4-20 mA output (sourcing) (Load resistance: Max 600Ω)
• Linear Voltage (L)
DC 0-10V (Load resistance Min 1KΩ)
*Note: Use only ungrounded thermocouples. ** Analog input impedance: 1.8MΩ
Safety Information
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equip­ment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call us at 1-800-633-0405 or 770-844-4200.
This publication is based on information that was available at the time it was printed. At Automationdirect. com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without obligation. This publication may also discuss features that may not be available in certain revisions of the product.
WARNING! Electric shock danger
1. To prevent electric shock, do not touch the AC terminals while the power is supplied to the controller.
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with insolation (M3 screw, width is 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 Nm (4kgfcm). Applicable wire: Solid/twisted wire of 2 mm, 12AWG to 24AWG. Choose AutomationDirect part numbers BM-00120, BM-00220 or BM-00320 depending on wire size. Be sure to tighten them properly.
2. Protect the controller from dust or foreign objects to prevent controller malfunction.
3. Do not modify or disassemble the controller.
4. Do not connect anything to the “Not used” terminals.
5. Make sure all wires are connected correctly.
6. Do not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid (b) High humidity (c) Vibration and shock (d) EMI / RFI (e) high temperature.
7. Turn power off when wiring or changing a temperature sensor.
8. Be sure to use wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Use wires with correct resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and
route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity,
dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Make sure power cables and signals from instruments are all installed properly before energizing the controller,
otherwise serious damage may occur.
13. To prevent electric shock, do not touch the terminals in the controller or try to repair the controller when power
is applied.
14. Use a soft, dry cloth to clean the controller. Do not use acid or alkaline liquids for cleaning.
15. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required,
install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
16. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcur -
rent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
5
1
Product Support and Configuration Software
• For product support, specifications, and installation troubleshooting, a complete User Manual can be downloaded from the On-line Documentation area of the AutomationDirect web site.
• For additional technical support and questions, call our Technical Support team @ 1-800-633-0405 or 770-844-4200.
• Configuration software for the SOLO controller is available for free down­load at www.AutomationDirect.com. The software allows communication and programming for up to four controllers at the same time. Parameters, process values, set points and temperature changes can be monitored with the software. The setup data can be uploaded to the user’s PC via RS-485 communication. The user can monitor the temperature changes of the controllers from the “PV Monitor” Display.
Reset to Factory Default Instructions
Mounting Instructions
SOLO temperature controllers can be mounted through a cutout in an enclosure or panel by using the dimen­sions shown in Section 5. The directions for mounting the controller through a cutout are:
1. Insert the temperature controller through the panel cutout.
2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm mounting screw in the mounting bracket.
3. Insert the mounting bracket into the mounting groove at the top and bottom of the controller, and push the mounting bracket forward until the bracket stops.
4. Tighten top and bottom screws evenly to secure temperature controller in place.
1
4
3
2
4848
PV
SOLO
F
C
SV
OUT1
OUT2
ALM
AT
SET
6
SL4848-LV SL4848-VV
SL4848-CV
WARNING! Electric shock danger
To prevent electric shock, do not connect AC power to your device until all input and output connections are completed.
SL4848-RR
SL4848-VR
SL4848-CR
Terminal Identification
SL4848-LR
7
Display, LED and Key Pad
4848
PV
SOLO
F
C
SV
OUT1
OUT2
ALM
AT
SET
PV Display: To display the process value or parameter type.
SV Display: To display the set point, parameter operation read value
manipulated variable or set value of the parameter.
AT: Auto-tuning LED, flashes when the Auto-tuning operation is ON.
OUT1 / OUT2: Output LED, lights when the output is ON.
ALM: Alarm output LED, lights when one of the alarms is on.
°C, °F: Temperature unit LED. °C: Celsius °F: Fahrenheit
Set Button: Press this key to select the desired function mode and confirm the setting value.
Rotate Button: Press this key to select parameters within the function mode.
Down Button: Press this key to decrease values displayed on the SV display. Hold down this key to speed up the decrement.
Up Button: Press this key to increase values displayed on the SV display. Hold down this key to speed up the increment.
8
10
All of the following set up instructions are for setting up a controller from the factory defaults. If the application for a controller needs to be changed, reset the controller to factory default using the following steps.
1. Press the • button until the parameter
loC
appears. Use the
.
button to select
loC1
. Press the
;
button.
2. Press and hold the , and . buttons simultaneously for one second and release.
3. Press the • button repeatedly until the PV display shows
pass
. Use the , button to change the value
on the SV display to
1357
. Press the ; button.
4. Cycle power on the Controller to reset to factory default mode. All user set values are erased.
Key Pad Operation
Operation Mode
SET
Hold for 3 sec.
SET
Initial Setting
Mode
Regulation
Mode
SET
Press for less
than 3 sec.
Initial Setting
Parameters
Operation
Parameters
Regulation Parameters
SET
The SOLO temperature controller has three function modes: Initial Setting mode, Operation mode and Regulation mode. When power is first applied to the temperature controller, the module information splash screen appears. This screen shows the firmware version on the PV display and the two output types for that particular model on the SV display. After three seconds, the controller will automatically proceed to the Operation mode main screen. Press and hold the ; button for three seconds to go into the Initial Setting mode. Press the ; button for less than three seconds to access the Regulation mode. Press the • button while inside any of the three function modes to access the individual parameters for each function mode. Use the . and , buttons to change the individual parameter values. Pressing the ; button saves the parameter values. Press the ; button again to return the controller to the Operation mode.
1. Access the Initial Setup mode by pressing and holding the ; button for three seconds. In the parameter
inpt
, use the , and . buttons to select the value that corresponds to the thermocouple or RTD type that will be attached to the controller. See the table below for specifications. Press the ; button to save the selected value. The controller will display the module information splash screen for three seconds and then return to the main screen.
2. Press the
;
button for three seconds again. Press the
button to access the
tpun
parameter. Use the , and . buttons to select either C for Centigrade or f for Fahrenheit display. Press the ; button to save the selected value. The controller will display the module information splash screen for three seconds and then return to the main screen.
3. Press the
;
button for three seconds again. Press the
button repeatedly until the
tp-H
parameter appears. Use the , and . buttons to set the maximum value of the operational temperature range. In operation, if the PV value is higher than the TP-H value, the PV display flashes to indicate an error and the controller outputs shut off. The SV value cannot exceed the TP-H value. Press the ; button to save the selected value. Press the • button to access the
tp-l
parameter. Use the , and . buttons to set the minimum value of the operational temperature range. In operation, if the PV value is lower than the TP-L value, the PV display flashes to indicate an error and the controller outputs shut off. The SV value cannot be set lower than the TP-L value. Press the ; button twice to save the selected value and return to the controller main screen.
4. Press the • button repeatedly until the parameter
sp
appears. Use the
,
and
.
buttons to select
either
0
for a whole degree or
1
for a tenth degree temperature display.* Press the ; button twice to save
the selected value and return to the controller main screen.
5. If the input temperature from the thermocouple or RTD needs to be adjusted, press the ; button for less than 3 seconds. Press the • button repeatedly until the parameter
tpof
appears. Use the , and
.
buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the ; button twice to save the selected value and return to the controller main screen.
*Note: The decimal point display cannot be adjusted for B, S, and R type thermocouples.
Thermocouple or RTD Input
Thermocouple* Type and Temperature Range
Input Temperature Sensor Type LED Display Temperature Range Thermocouple TXK type
txk
-328 ~ 1472°F (-200 ~ 800°C)
Thermocouple U type
u
-328 ~ 932°F (-200 ~ 500°C)
Thermocouple L type
l
-328 ~ 1562°F (-200 ~ 850°C)
Thermocouple B type
b
-212 ~ 3272°F (100 ~ 1800°C)
Thermocouple S type
s
32 ~ 3092°F (0 ~ 1700°C)
Thermocouple R type
r
32 ~ 3092°F (0 ~ 1700°C)
Thermocouple N type
n
-328 ~ 2372°F (-200 ~ 1300°C)
Thermocouple E type
e
32 ~ 1112°F (0 ~ 600°C)
Thermocouple T type
t
-328 ~ 752°F (-200 ~ 400°C)
Thermocouple J type
j
-148 ~ 2192°F (-100 ~ 1200°C)
Thermocouple K type
k
-328 ~ 2372°F (-200 ~ 1300°C)
RTD Type and Temperature Range
Input Temperature Sensor Type LED Display Temperature Range Platinum Resistance (Pt100)
pt
-328 ~ 1112°F (-200 ~ 600°C)
Platinum Resistance (JPt100)
jpt
-4 ~ 752°F (-20 ~ 400°C)
*Note: Use only ungrounded thermocouples.
11-1
Sensor Input Power Input
9
0 – 10 VDC 4 – 20 mA
2-wire RTD
Thermocouple 3-wire RTD
AC Powered
Models
DC Powered
Models
24 VDC power for models with –D suffix only
Loading...