AutomationDirect SIO-MB16ND3 User Manual

3505 HUTCHINSON ROAD
®
CUMMING, GA 30040-5860, USA
Stride® Field i/O MOdules
discrete input MOdule: 16-pOint, 12-24Vdc (pn# siO-MB16nd3)
FEATURES
• Interface Ethernet 10/100 Base-T, Modbus TCP Server
• 16 digital inputs
• Integrated web server to acquire the status of the digital inputs via browser
Remotely congurable
• Connection by removable screw terminals
• LED signaling for Link/Act Ethernet, power supply
• LED signaling for digital input states
• Galvanic isolation
• UL listed / CE mark
• In compliance with EN-50022 DIN rail mounting
GENERAL DESCRIPTION
The SIO-MB16ND3 device is a Modbus TCP server with 16 digital input channels. For the digital inputs, up to four 32-bit counters are available with measurement frequency of up to 300Hz. The Ethernet interface allows reading and writing the values of the internal registers of the device in real time.
The built-in Web Server allows remote visualization, acquisition of the digital input states and access to the conguration parameters.
Signal LEDs for Ethernet activity, input state and power supply allow direct monitoring of the system. Connections are made by removable screw terminals (inputs and power supply) and RJ45 plug (Ethernet). The SIO-MB16ND3 is in compliance with Directive UL 61010-1 for the US market and with Directive CSA C22.2 No 61010-1 for the Canadian market. The device has full electrical isolation between the lines, providing protection against the effects of ground loops existing in industrial applications.
It is housed in a tough self-extinguishing plastic enclosure which, thanks to its thin 22.5 mm prole, allows high-density mounting on EN-50022 standard DIN rail.
USER INSTRUCTIONS
Before installing the device, please read the “Installation Instructions” section.
To congure the device in INIT mode, refer to the User Guide. Connect the INIT terminal to the V- terminal (refer to the User Guide). Connect power supply,
Ethernet and digital inputs as shown in the “Wiring” section. The LED states indicate the working condition of the device; see the “Front Panel LEDs” table to verify the device working state.
Instructions for conguration and calibration operations are contained in the User Guide.
To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
TECHNICAL SPECIFICATIONS (typical @ 25°C, nominal conditions)
NETWORK CONNECTIVITY
Standard Network Interface Protocol Max. Cable Length Number of Sockets
In compliance with IEEE 802.3
Ethernet 10/100Base-T
Modbus TCP 100m [328ft]
16 simultaneous Modbus TCP connections
Channels Input Voltage (Bipolar)
OFF State
ON State Impedance Sample Time Number of Counters Counters Register Bit Length Counters Frequency Minimum Pulse Width
Please refer to the User Guide for more information, including the
compete Modbus address list. Access the user guide by visiting
https://www.automationdirect.com/pn/doc/manual/SIO-MB16ND3
or scan the QR code below.
DIGITAL INPUTS
16
0–3V
10–30V
4.7 kΩ 5ms
4
32 bit
Up to 300Hz
1ms
Reverse Polarity Protection Current Consumption
Power Supply / Ethernet Inputs / Power Supply Inputs / Ethernet Input / Input
ENVIRONMENTAL CONDITIONS
Operating Temperature UL Operating Temperature Storage Temperature Humidity (non-condensing) Maximum Altitude Installation Pollution Degree
Ethernet Inputs / Power Supply
MECHANICAL SPECIFICATIONS
Material IP Code Wire diameter Tightening Torque Mounting Weight
EMC (for industrial environments)
Immunity Emission
US Standard Canadian Standard CCN UL Type Designation Classification File Number
POWER SUPPLY
To maintain a UL 508 panel listing use a
Class 2 power supply.
60VDC max
220mA max (2)
10–30VDC
ISOLATION
1500VAC, 50Hz, 1 min 1500VAC, 50Hz, 1 min 1500VAC, 50Hz, 1 min 1500VAC, 50Hz, 1 min
-10°C to +60°C [+14°F to +140°F]
-10°C to +40°C [+14°F to +104°F]
-40°C to +85°C [-40°F to +185°F] 0 to 90%
2000m [6500ft]
Indoor
2
CONNECTIONS
RJ-45
Removable screw terminals
Self-extinguishing plastic
IP20
0.8 to 2.1 mm2 / AWG 14–18
0.5 N·m [4.4 in·lb]
In compliance with DIN rail standard EN-50022
About 160g [5.6 oz]
EN 61000-6-2 EN 61000-6-4
UL
UL 61010-1
CSA C22.2 No 61010-1
NRAQ/NRAQ7
Open Type device
Industrial Control Equipment
E157382
INSTALLATION INSTRUCTIONS
49.3
1.94
50.8
2.00
120.0
4.72
12-WIRE CONNECTOR
9-WIRE CONNECTOR
22.5
0.89
RESET BUTTON
POWER
GREEN LED
STATUS
YELLOW LED
DIGITAL INPUTS
( 16X )
The device shall be mounted on DIN rail in a vertical and upright orientation. For optimum operation and long life follow these instructions: When the devices are installed side by side it is necessary to separate them by the following minimum distances:
10 mm if UL certication is required.
5 mm if UL certication is not required.
Make sure that sufcient air ow is provided for the device. Avoid placing
raceways or other objects where they could obstruct the ventilation slits. Avoid mounting the devices above appliances generating heat; ideally locate them in the lower part of the panel. Install the device in a place without vibrations. Avoid routing conductors near power signal cables (motors, induction ovens, inverters, etc.). Use shielded cable for connecting signals; ground shield at one end only.
DEFAULT CONFIGURATION
• IP Address: 192.168.1.100
• Modbus Address: 1
• Default user name: admin
• Default password: password
Register Description Access
MODBUS REGISTERS
40002 Firmware [0] RO 40003 Firmware [1] RO 40004 -Reserved- RO 40005 -Reserved- RO 40007 Node ID R/W 40011 System Flags R/W 40013 Watchdog timer R/W 40032 Digital Inputs RO 40033 Digital Inputs Rise Latch R/W 40034 Digital Inputs Fall Latch R/W 40035 Frequency, Digital Input 0 RO 40036 Frequency, Digital Input 1 RO 40037 Frequency, Digital Input 2 RO 40038 Frequency, Digital Input 3 RO 40039 32-bit Counter, Digital Input 0 R/W 40041 32-bit Counter, Digital Input 1 R/W 40043 32-bit Counter, Digital Input 2 R/W 40045 32-bit Counter, Digital Input 3 R/W
BOTTOM INPUT PINOUT
Pin Description
1 COM1 2 IN8 3 IN9 4 IN10 5 IN11 6 IN12 7 IN13 8 IN14 9 IN15
TOP INPUT PINOUT
Pin Description
E COM F IN0 G IN1 H IN2 I IN3 J IN4 L IN5
M IN6
N IN7
FRONT PANEL LEDS
LED COLOR STATE DESCRIPTION
PWR GREEN
STS YELLOW
In RED
ON Device powered
OFF Device not powered
BLINK Watchdog alarm
OFF Device in RUN mode
BLINK Device in INIT mode
ON Digital Input High Level (1)
OFF Digital Input Low Level (0)
POWER SUPPLY (1)
+VS
O
P
-VS
+
10–30 VDC
-
INIT FUNCTION (2)
INIT
Q
P
-VS
NOTE: (1) To maintain the UL listing use a Class 2 or SELV and
limited energy power supply. See User Guide for instructions on using the INIT feature.(2)
DIGITAL INPUTS
GROUP DIGITAL INPUTS 0–7
E
COM
E
DI0
F
J
DI1
G
L
DI2
H
M
DI3
I
N
GROUP DIGITAL INPUTS 8–15
1
COM1
1
DI8
2
6
DI9
3
7
DI10
4
8
DI11
5
9
NOTES: “COM” (E) and “COM1” (1) are each isolated commons. Input channels 0–7 share common “COM” (E). Input channels 8–15 share common “COM1” (1). Input channels 0–7 are isolated from input channels 8–15.
ON: Short INIT to -VS
COM
DI4
DI5
DI6
DI7
COM1
DI12
DI13
DI14
DI15
MECHANICAL DIMENSIONS
MM [IN]
WEEE compliance ­These devices comply with the WEEE directive. Dispose of properly.