Stride® Field i/O MOdules
discrete input MOdule: 16-pOint, 12-24Vdc (pn# siO-MB16nd3)
FEATURES
• Interface Ethernet 10/100 Base-T, Modbus TCP Server
• 16 digital inputs
• Integrated web server to acquire the status of the digital inputs via browser
• Remotely congurable
• Connection by removable screw terminals
• LED signaling for Link/Act Ethernet, power supply
• LED signaling for digital input states
• Galvanic isolation
• UL listed / CE mark
• In compliance with EN-50022 DIN rail mounting
GENERAL DESCRIPTION
The SIO-MB16ND3 device is a Modbus TCP server with 16 digital input channels.
For the digital inputs, up to four 32-bit counters are available with measurement frequency of up to 300Hz.
The Ethernet interface allows reading and writing the values of the internal registers of the device in real time.
The built-in Web Server allows remote visualization, acquisition of the digital input states and access to the conguration parameters.
Signal LEDs for Ethernet activity, input state and power supply allow direct monitoring of the system.
Connections are made by removable screw terminals (inputs and power supply) and RJ45 plug (Ethernet).
The SIO-MB16ND3 is in compliance with Directive UL 61010-1 for the US market and with Directive CSA C22.2 No 61010-1 for the Canadian market.
The device has full electrical isolation between the lines, providing protection against the effects of ground loops existing in industrial applications.
It is housed in a tough self-extinguishing plastic enclosure which, thanks to its thin 22.5 mm prole, allows high-density mounting on EN-50022 standard DIN rail.
USER INSTRUCTIONS
Before installing the device, please read the “Installation Instructions” section.
To congure the device in INIT mode, refer to the User Guide. Connect the INIT terminal to the V- terminal (refer to the User Guide). Connect power supply,
Ethernet and digital inputs as shown in the “Wiring” section. The LED states indicate the working condition of the device; see the “Front Panel LEDs” table to
verify the device working state.
Instructions for conguration and calibration operations are contained in the User Guide.
To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
TECHNICAL SPECIFICATIONS (typical @ 25°C, nominal conditions)
NETWORK CONNECTIVITY
Standard
Network Interface
Protocol
Max. Cable Length
Number of Sockets
In compliance with IEEE 802.3
Ethernet 10/100Base-T
Modbus TCP
100m [328ft]
16 simultaneous Modbus TCP connections
Channels
Input Voltage (Bipolar)
OFF State
ON State
Impedance
Sample Time
Number of Counters
Counters Register Bit Length
Counters Frequency
Minimum Pulse Width
Please refer to the User Guide for more information, including the
compete Modbus address list. Access the user guide by visiting
https://www.automationdirect.com/pn/doc/manual/SIO-MB16ND3
or scan the QR code below.
DIGITAL INPUTS
16
0–3V
10–30V
4.7 kΩ
5ms
4
32 bit
Up to 300Hz
1ms
Power Supply Voltage
Reverse Polarity Protection
Current Consumption
Power Supply / Ethernet
Inputs / Power Supply
Inputs / Ethernet
Input / Input
ENVIRONMENTAL CONDITIONS
Operating Temperature
UL Operating Temperature
Storage Temperature
Humidity (non-condensing)
Maximum Altitude
Installation
Pollution Degree
Ethernet
Inputs / Power Supply
MECHANICAL SPECIFICATIONS
Material
IP Code
Wire diameter
Tightening Torque
Mounting
Weight
EMC (for industrial environments)
Immunity
Emission
US Standard
Canadian Standard
CCN
UL Type Designation
Classification
File Number
POWER SUPPLY
To maintain a UL 508 panel listing use a
Class 2 power supply.
60VDC max
220mA max (2)
10–30VDC
ISOLATION
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
1500VAC, 50Hz, 1 min
-10°C to +60°C [+14°F to +140°F]
-10°C to +40°C [+14°F to +104°F]
-40°C to +85°C [-40°F to +185°F]
0 to 90%
2000m [6500ft]
Indoor
2
CONNECTIONS
RJ-45
Removable screw terminals
Self-extinguishing plastic
IP20
0.8 to 2.1 mm2 / AWG 14–18
0.5 N·m [4.4 in·lb]
In compliance with DIN rail standard EN-50022
About 160g [5.6 oz]
EN 61000-6-2
EN 61000-6-4
UL
UL 61010-1
CSA C22.2 No 61010-1
NRAQ/NRAQ7
Open Type device
Industrial Control Equipment
E157382

INSTALLATION INSTRUCTIONS
49.3
1.94
50.8
2.00
120.0
4.72
12-WIRE
CONNECTOR
9-WIRE
CONNECTOR
22.5
0.89
RESET BUTTON
POWER
GREEN LED
STATUS
YELLOW LED
DIGITAL INPUTS
( 16X )
The device shall be mounted on DIN rail in a vertical and upright orientation.
For optimum operation and long life follow these instructions:
When the devices are installed side by side it is necessary to separate them by
the following minimum distances:
• 10 mm if UL certication is required.
• 5 mm if UL certication is not required.
Make sure that sufcient air ow is provided for the device. Avoid placing
raceways or other objects where they could obstruct the ventilation slits.
Avoid mounting the devices above appliances generating heat; ideally locate
them in the lower part of the panel.
Install the device in a place without vibrations.
Avoid routing conductors near power signal cables (motors, induction ovens,
inverters, etc.). Use shielded cable for connecting signals; ground shield at one
end only.
DEFAULT CONFIGURATION
• IP Address: 192.168.1.100
• Modbus Address: 1
• Default user name: admin
• Default password: password
Register Description Access
MODBUS REGISTERS
40002 Firmware [0] RO
40003 Firmware [1] RO
40004 -Reserved- RO
40005 -Reserved- RO
40007 Node ID R/W
40011 System Flags R/W
40013 Watchdog timer R/W
40032 Digital Inputs RO
40033 Digital Inputs Rise Latch R/W
40034 Digital Inputs Fall Latch R/W
40035 Frequency, Digital Input 0 RO
40036 Frequency, Digital Input 1 RO
40037 Frequency, Digital Input 2 RO
40038 Frequency, Digital Input 3 RO
40039 32-bit Counter, Digital Input 0 R/W
40041 32-bit Counter, Digital Input 1 R/W
40043 32-bit Counter, Digital Input 2 R/W
40045 32-bit Counter, Digital Input 3 R/W
BOTTOM INPUT PINOUT
Pin Description
1 COM1
2 IN8
3 IN9
4 IN10
5 IN11
6 IN12
7 IN13
8 IN14
9 IN15
TOP INPUT PINOUT
Pin Description
E COM
F IN0
G IN1
H IN2
I IN3
J IN4
L IN5
M IN6
N IN7
FRONT PANEL LEDS
LED COLOR STATE DESCRIPTION
PWR GREEN
STS YELLOW
In RED
ON Device powered
OFF Device not powered
BLINK Watchdog alarm
OFF Device in RUN mode
BLINK Device in INIT mode
ON Digital Input High Level (1)
OFF Digital Input Low Level (0)
POWER SUPPLY (1)
+VS
O
P
-VS
+
10–30 VDC
-
INIT FUNCTION (2)
INIT
Q
P
-VS
NOTE: (1) To maintain the UL listing use a Class 2 or SELV and
limited energy power supply.
See User Guide for instructions on using the INIT feature.(2)
DIGITAL INPUTS
GROUP DIGITAL INPUTS 0–7
E
COM
E
DI0
F
J
DI1
G
L
DI2
H
M
DI3
I
N
GROUP DIGITAL INPUTS 8–15
1
COM1
1
DI8
2
6
DI9
3
7
DI10
4
8
DI11
5
9
NOTES:
“COM” (E) and “COM1” (1) are each isolated commons.
Input channels 0–7 share common “COM” (E).
Input channels 8–15 share common “COM1” (1).
Input channels 0–7 are isolated from input channels 8–15.
ON: Short INIT
to -VS
COM
DI4
DI5
DI6
DI7
COM1
DI12
DI13
DI14
DI15
MECHANICAL DIMENSIONS
MM [IN]
WEEE compliance These devices comply with the WEEE directive.
Dispose of properly.