Automation Direct Productivity2000 P2-08ND3-1 User Manual

Page 1
D3-1
12–
2000
1
Document Name Edition/Revision Date P2-08ND3-1-DS 1st Edition 9/21/2017
Input Specifications
Inputs per Module 8 (Sink/Source)
Voltage Rating 12–24 VDC
Input Voltage Range 10.2–26.4 VDC
Peak Voltage Range 30VDC
Input Current (typical)
3.5 mA @ 12VDC
7.5 mA @ 24VDC
Maximum Input Current 10mA @ 26.4 VDC
ON Voltage Level > 9.5 VDC
OFF Voltage Level < 7VDC
Minimum ON Current 2mA Maximum OFF Current 1.6 mA
OFF to ON Response 2ms Maximum, 1ms Typical
ON to OFF Response 2ms Maximum, 1ms Typical
Status Indicators Logic Side (8 Points)
Commons 2 (4 points/common) Isolated
Warranty: Thirty-day money-back guarantee. Two-year limited replacement. (See www.productivity2000.com for details).
Terminal Block sold separately, (see wiring options on page 2).
Input Specifications .................................................. 1
Module Installation ................................................... 2
Wiring Options .......................................................... 2
Wiring Diagram and Schematic ................................ 3
QR Code .................................................................. 3
Hot Swap Information ............................................... 3
Warning .................................................................... 4
Removable Terminal Block Specifications ............... 4
General Specifications ............................................. 4
P2-08ND3-1 DC Input
The P2-08ND3-1 DC Input Module provides eight 12–24 VDC sink/source inputs for use with the Productivity2000 system.
Page 2
www.productivity2000.com Tech Support 770-844-4200 Sales 800-633-0405 www.productivity2000.com
2
Wiring Options
1ZIPLink Connection System
Cable + ZIPLink Module = Complete System
ZIPLink pre-wired terminal block cables
0.5 m (1.6 ft) cable
1.0 m (3.3 ft) cable
2.0 m (6.6 ft) cable
ZIPLink Modules
Feed through
ZL-P2-CBL18 ZL-P2-CBL18-1 ZL-P2-CBL18-2
ZL-RTB20
ZL-RTB20-1
2
Terminal Block with pigtail cable
1.0 m (3.3 ft) cable
2.0 m (6.6 ft) cable
ZL-P2-CBL18-1P ZL-P2-CBL18-2P
3
Screw Terminal Block only
P2-RTB (Quantity 1)
4
Spring Clamp Terminal Block only
P2-RTB-1 (Quantity 1)
ZL-RTB20
1 Align
with slot
2 rotate
to seated
position
Module Installation
WARNING: Do not apply field power until
the following steps are completed. See hot-swapping procedure for exceptions.
WIRE STRIP
LENGTH
WIRE STRIP
LENGTH
Step One: Align module
catch with base slot and rotate module into connector.
Locked
Unlocked
Step Two: Pull top locking
tab toward module face. Click indicates lock is engaged.
Step Three: Attach field wiring using the removable
terminal block or ZIPLink wiring system.
ZL-RTB20-1
Page 3
QR CodeWiring Diagram and Schematic
12–24 VDC
+
12–24 VDC
+
C1
1
2
3
4
C2
5
6
7
8
12345678910 11 12 1813 14 15 16 17
+
+
3
INPUT
COM
Internal Module Circuitry
Optical Isolator
12–24 VDC
+
Equivalent Input Circuit
+
Important Hot-Swap Information
The Productivity2000 supports hot-swap! Individual
modules can be taken offline, removed, and replaced while the rest of the system continues controlling your process. Before attempting to use the hot-swap feature, be sure to read the hot-swap topic in the programming software’s help file or our online documentation at AutomationDirect.com for details on how to plan your installation for use of this powerful feature.
Use any QR Code reader application to display the module’s product insert.
Caution: If possible, remove field power prior to
proceeding. If not, then EXTREME care MUST be taken to prevent damage to the module, or even personal injury due to a short circuit from the live terminal block.
Page 4
www.productivity2000.com Tech Support 770-844-4200 Sales 800-633-0405 www.productivity2000.com
4
WARNING: To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call Technical Support at 770-844-4200.
This publication is based on information that was available at the time it was printed. At AutomationDirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product.
General Specifications
Operating Temperature 0° to 60°C (32° to 140°F) Storage Temperature -20° to 70°C (-4° to 158°F) Humidity 5 to 95% (non-condensing)
Environmental Air No corrosive gases permitted
Vibration IEC60068-2-6 (Test Fc)
Shock IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation 1800VAC applied for 1 second
Insulation Resistance >10MΩ @ 500VDC
Heat Dissipation 325mW Enclosure Type Open Equipment Module Keying to Backplane Electronic
Module Location Any I/O slot in a Productivity2000 System.
Field Wiring
Use ZIPLink Wiring System or removable terminal block (not included). See “Wiring Options” on page 2.
EU Directive
See the “EU Directive” topic in the Productivity2000 Help File. Information can also be obtained at: www.productivity2000.com
Connector Type (not included) 18-position removable terminal block
Weight 90g (3.2 oz)
Agency Approvals
UL 61010-2-201 file E139594, Canada & USA CE (EN61131-2 EMC and EN61010-2-201 Safety*)
*Meets EMC and Safety requirements. See the D.O.C. for details.
Removable Terminal Block Specifications
Part Number P2-RTB P2-RTB-1 Number of
Positions
18 Screw Terminals 18 Spring Clamp Terminals
Wire Range
30–16 AWG (0.051–1.31 mm2) Solid / Stranded Conductor 3/64 in (1.2 mm) Insulation Maximum
1/4 in (6–7 mm) Strip Length
28–16 AWG (0.081–1.31 mm2) Solid / Stranded Conductor 3/64 in (1.2 mm) Insulation Maximum
19/64 in (7–8 mm) Strip Length
Conductors “USE COPPER CONDUCTORS, 75°C” or Equivalent.
Screw Driver Width
1/8 inch (3.8 mm) Maximum
Screw Size M2 N/A
Screw Torque 2.5 lb·in (0.28 N·m) N/A
Loading...