• 1-channel or 2-channel connection
• LED indication for operation
• Output: 5 N.O. and 1 N.C. contacts
Safety Relays Selection Chart
Part Number Price Marking Type Voltage Outputs
LG5929-60-100-61
$102.00 Safety relay extension module 24 VAC/VDC 5 N.O./1 N.C.
Safety Relay Extenson Module Specification Table
General Specifications
Temperature Altitude
Vibration Resistance Degree of Protection Housing Weight Agency Approvals and Standards
Terminal Designation per EN 50 005 Wire Connections
Wire Fixing
Nominal Voltage
Voltage Range
Maximum Consumption Nominal Frequency Control Current Overvoltage Protection
Electrical Contact Life Mechanical Life
Contact Type Operate/Release Time Nominal Output Voltage Thermal Current (I
th)
Short Circuit Strength
Switching Capacity IEC/EN 60 947-5-1
Switching Frequency
1x4 mm
Input Specifications
Output Specifications
Storage: -25°C to 85°C (-13°F to 185°F) Operating: -15°C to 55°C (5°F to 131°F)
2
solid or 1 x 2.5 mm2 stranded ferruled (isolated) or 2 x 1.5 mm2 stranded ferruled (isolated) DIN 46 228-1/-2/-3/-4
Plus-minus terminal screws M3.5 box terminals with wire protection or cage clamp terminals.
At 10% residual ripple: 0.9 to 1.1 U
5 N.O. positively driven and 1 N.C. relay contacts (N.O. contacts are safety contacts)
Max. 5A per contact. See continuous current limit curve in installation manual.
DC 13: N.O. contacts: 4A/24V; N.C. contacts: 4A/24VDC; N.O. contact: 8A/24V >25x103
Safety Data – Values per EN ISO 13849-1
Category 4 according to EN 954-1 Performance level PLe according to EN 13849-1 MTTF
d
DC
avg
Safety Data – Values per IEC/EN 62061 /IEC/EN 61508
SIL CL SIL HFT (Hardware Failure Tolerance) DC
avg SFF PFH
D
< 2,000 meters
Amplitude: 0.35mm, Frequency: 10 to 55 Hz (IEC/EN 60-068-2-6)
Per IEC/EN 60 529. Housing: IP40; Terminals IP20
UL 94V-0 Thermoplastic; Din mount 35 mm x 7.5 mm
205g (7.23 oz.)
CSA, cULus file E107778, CE, RoHS, TUV
or 2 x 2.5 mm2 solid per DIN 46 228-1/-2/-3 /-4
24V AC/DC
AC: 0.85 to 1.1 U
24VAC/DC: 1.8VA
50 to 60 Hz
Control current typ. at 24V over 2 relays: 75 mA
Internal VDR (Voltage Dependent Resistor)
To AC15 at 2 A,230V: 105 switching cycles IEC/EN 60 947-5-1
20 x 106 switching cycles
Operate typ at UN: 20 m.; Release typ at U
250VAC
Max fuse rating:10A gl (IEC/EN 60 9470-5-1); Line circuit breaker: B6A
AC 15: N.O. contacts: 3A/230V; N.C. contacts: 2A/230VAC
ON: 0.4s, OFF: 9.6s
Max. 1,200 switching cycles/hr
N
; At 48% residual ripple: 0.85 to 1.1 U
N
: 35 ms.
N
>100 years
99%
3 per IEC/EN 62061 3 per IEC/EN 61508 1
99%
99.7%
-1
4.68E-10 h
N
www.automationdirect.com
Safety Electrical Components
tESC-310
1-800-633-0405
Dold LG5929 Extension Module
For the latest prices, please check AutomationDirect.com.
Wiring
LG5929 Block Diagram
A1(+) A2(-)
A3(+) A4(-)
Applications
L1
24V
24V
Dimensions mm [in]
13 23 33 43 53 Y1
K1
K2
14 24 34 44 54 Y2
Emergency Stop
A1(+)
A2(-)
S21S33 S34141424
S12S22 131323
S11
LG5925
..
..
On
Y1 Y2
N
A1(+) A3(+)
LG5929/100
A2(-) A4(-)
23 33 43
24 34 44
53
54
Contact multiplication with LG 5929/100
Note: This is a representative drawing. Depending on the LG5925 safety relay you select, different voltage sources may be required.
www.automationdirect.com
*Note: When switching inductive loads, surge suppressors are recommended.