AutomationDirect H2 User Manual

For the latest prices, please check AutomationDirect.com.
1-800-633-0405
1-800-633-0405
For the latest prices, please check AutomationDirect.com.
Do-more H2 Series PLC System Specifications
General Specifications
General Specifications
Operating Temperature
Storage Temperature
Ambient Humidity
Environmental Air
Vibration
Shock
32°F to 131°F (0°C to 55°C)
–4°F to 158°F (–20°C to 70°C)
No corrosive gases
MIL STD 810C, Method 514.2 IEC60068-2-6 JIS C60068-2-6 (Sine wave vibration test)
MIL STD 810C, Method 516.2 IEC60068-2-27 JIS C60068-2-27
Noise Immunity
Agency Approvals
NEMA ICS3-304
UL508 (File No. E157382, E316037) CE (EN61131-2)
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-12
tDMH-12
1-800-633-0405
1-800-633-0405

CPU Modules

Specifications
Total Memory (bytes) Ladder Memory (instruction words) V-Memory (words) Non-volatile V Memory (words) D-memory (DWORDs) Non-volatile D Memory (DWORDs) R-memory (REAL DWORDs) Non-volatile R Memory (REAL DWORDs) Boolean execution/K Stage Programming
Number of Stages
Handheld Programmer Programming Software for Windows
Built-In communications ports
Program Memory
Total I/O points available
H2-DM1 $310.00
H2-DM1E $415.00
Local I/O points available Ethernet Remote I/O Discrete points
Ethernet Remote I/O Analog I/O Channels Max Number of Ethernet slaves per Channel I/O points per Remote Channel Discrete I/O Module Point Density Slots per Base
Number of instructions available
Control relays Special relays (system defined) Special registers (system defined) Timers Counters System Date/Time structures User Date/Time structures ASCII String/Byte buffer structures
Modbus Client memory
DL Classic Client memory Immediate I/O Interrupt input (hardware / timed) Subroutines Drum Timers Table Instructions Loops
Math
ASCII PID Loop Control, Built In Time of Day Clock/Calendar Run Time Edits Supports True Force Internal Diagnostics Password security System error log User error log Battery backup
Feature H2-DM1
Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default) Configurable up to 65536 (4096 default)
128 per Program code-block; number of code-blocks configurable to memory limit
USB, RS-232
X, Y, each configurable up to 65536 (2048 default); WX, WY (analog in/out)
Yes, configurable up to memory limit, default 1024 input bits, 1024 coil bits,
>60 operators and functions: Integer, Floating Point, Trigonometric, Statistical,
Yes, IN/OUT, Serial, Ethernet TCP and UDP; 11 output script commands
each configurable up to 65536 (256 default)
>160 >170
Configurable up to 65536 (2048 default)
Configurable up to 65536 (256 default) Configurable up to 65536 (256 default)
Configurable up to 65536 (32 default)
Configurable up to memory limit (192 default)
2048 input registers, 2048 holding registers
Up to memory limit, default 512 X, 512 Y, 512 C, 2048 V
Program and Task code-blocks, up to memory limit
FOR/NEXT, WHILE/WEND, REPEAT/UNTIL loops
Yes, configurable to memory limit (over 2000)
Multi-user, credentialed, session-based security
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
H2-DM1E
262144 bytes
65536 instruction words
50us
Yes
No
FREE Do-more Designer
USB, RS-232,
Ethernet (10/100 Base-T)
Flash ROM
256
131072
32768
16
32768
4/8/12/16/32
3/4/6/9
1024
512
8
No No
Yes, up to memory limit
Yes
Logical, Bitwise, Timing
Yes Yes Yes Yes
Yes Yes
Yes (Battery included)
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-13
tDMH-13
H
H2-DM1E
PWR
RUN
ROM
ERR
ETH
USB
TX
RX
-
PWR
N
T
H
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
H2-DM1
LED Status Indicators
PWR
RUN
ROM
ERR
H2-DM1
-
H2-DM1
PWR
PWR
RUN
N
ROM
ERR
H2-DM1E
-
USB
TX
RX
ETH
T
USB
TX
RX
LED Indicators
Indicator Status Description
PWR
RUN
ROM
ERR
ETH
USB
TX RX
Green Base Power ON
Yellow Low Battery
Green CPU is in RUN Mode
Yellow Forces are Active
Yellow
Red CPU Fatal Error
Green Ethernet Link Good
Yellow Ethernet Activity
Green USB Receive Activity
Yellow USB Transmit Activity
Green RS-232 Transmit Activity Green RS-232 Receive Activity
CPU is updating Non-volatile Memory
H2-DM1E
H2-DM1E
PLC Mode Switch
www.automationdirect.com
www.automationdirect.com
RUN
TERM
STOP
Mode Switch Functions
Mode Switch Position CPU Action
RUN (Run Program)
TERM (Terminal)
STOP (Stop Program)
CPU is forced into RUN Mode if no errors are encountered.
RUN, PROGRAM and DEBUG modes are available. In this mode, the mode of operation can be changed through the Programming Software.
CPU is forced into STOP Mode.
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-14
tDMH-14
1-800-633-0405
1-800-633-0405
CPU Modules
Communication Ports
USB Port
Used exclusively for programming and monitoring via a PC running Do-more Designer.
USB Port Specifications
Description Standard USB 2.0 Slave input for programming and online
Cables
(ADC part #)
monitoring, with built-in surge protection. Not compatible with older full speed USB devices.
USB Type A to USB Type B:
USB-CBL-AB3 (3ft)
USB-CBL-AB6 (6ft)
USB-CBL-AB10 (10ft)
USB-CBL-AB15 (15ft)
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
RS-232 Port
RJ-12 style connector used for:
• Connection to a PC running Do-more Designer
• Modbus RTU Master connections
• Modbus RTU Slave connections
• ASCII Incoming and Outgoing communications
• Custom Protocol Incoming and Outgoing communications
Pin Description
5V Bus Voltage Sense
1
D- Data -
2
D+ Data +
3
0V Ground
4
RS-232 Port Specifications
Description Non-isolated, full duplex RS-232 DTE port used for programming, online moni-
Baud Rates 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
+5V Cable Power Source
Maximum Output Load (TXD/RTS)
Minimum Output Voltage Swing
Output Short Circuit Protection
Cable Options
(ADC part #)
toring or can connect the CPU as a Modbus RTU or ASCII master or slave to a peripheral device. Includes ESD and built-in surge protection.
220mA maximum at 5V, ±5%. Reverse polarity and overload protected.
3kV, 1000pf
±5V
±15mA
D2-DSCBL
FA-CABKIT
FA-ISOCON for converting RS-232 to isolated RS-422/485
Pin Description
1 2 3 4 5 6
0V Power (-) connection (GND) 5V Power (+) connection (220mA max.)
RXD Receive Data (RS-232) TXD Transmit Data (RS-232) RTS Request to Send (RS-232) CTS Clear to Send (RS-232)
For a list of protocols supported by each port, please refer to the Communications topic of the Do-more H2 Series PLC Overview in this section.
Do-more H2 PLCs
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
tDMH-15
tDMH-15
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Ethernet Port
RJ-45 style connector used for:
• Connection to a PC running Do-more Designer
• Modbus TCP Client connections (Modbus requests sent from the CPU)
• Modbus TCP Server connections (Modbus requests received by the CPU)
• Ethernet Expansion I/O Master
Ethernet Port Specifications
Description Standard transformer isolated Ethernet port with built-in surge
protection for programming, online monitoring, Modbus/TCP client/server connections (fixed IP or DHCP) and Ethernet Expansion I/O capabilities.
Transfer Rate 10/100 Mbps; Auto-MDX (Crossover)
For a list of protocols supported by each port, please refer to the Communications topic of the Do-more H2 Series PLC Overview in this section.
Do-more H2 PLCs
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
tDMH-16
tDMH-16
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Battery Specifications
A battery is included with the Do-more CPU and is used to retain the Time and Date along with any Tagname values that are set up as retentive. It is recommended that the battery be replaced once every five years or when one year of cumulative OFF time has been exceeded.
Up to two hours is allowed to change out a battery without loss of data.
D0-MC-BAT is $3.00.
Battery
D0-MC-BAT
Coin type, 3.0 V Lithium battery, number CR2032
H2-DM1 and H2-DM1E Battery Replacement Part # D0-MC-BAT.
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-17
tDMH-17
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Ethernet Expansion I/O
With Do-more Designer Software version V1.1 and newer, the H2-DM1E CPU’s built-in Ethernet port can be configured as an Ethernet Expansion I/O master. Much like the H2-ERM100 module, the Ethernet Expansion I/O feature allows expansion beyond the local chassis to slave I/O using the onboard high-speed Ethernet link.
The onboard Ethernet port can support up to 16 slave devices. The slave I/O modules supported are:
• H2-EBC100
• T1H-EBC100 (Terminator I/O)
• GS-EDRV100 (GS Drives)
The Ethernet Expansion I/O network uses Category 5 UTP cables for cable runs up to 100 meters (328 ft.) with extended distances achieved through Ethernet switches.
It is highly recommended that a dedicated network be used with the Ethernet Expansion I/O feature. Ethernet Expansion I/O networks and ECOM/office networks should be isolated from one another to prevent network delays.
Stride Ethernet Switch
Do-more H2-DM1E CPU
H2-DM1E
DirectLOGIC DL205 I/O with H2-EBC100 Module
C-more Operator Interface
GS-EDRV100
Terminator I/O with T1H-EBC100 Module
GS Drive
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-18
tDMH-18