Do-more H2 Series PLC System Specifications
General Specifications
General Specifications
Operating Temperature
Storage Temperature
Ambient Humidity
Environmental Air
Vibration
Shock
32°F to 131°F (0°C to 55°C)
–4°F to 158°F (–20°C to 70°C)
30% to 95% relative humidity (non–condensing)
No corrosive gases
MIL STD 810C, Method 514.2
IEC60068-2-6
JIS C60068-2-6 (Sine wave vibration test)
MIL STD 810C, Method 516.2
IEC60068-2-27
JIS C60068-2-27
Noise Immunity
Agency Approvals
NEMA ICS3-304
UL508 (File No. E157382, E316037)
CE (EN61131-2)
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-12
tDMH-12
1-800-633-0405
1-800-633-0405
CPU Modules
Specifications
Total Memory (bytes)
Ladder Memory (instruction words)
V-Memory (words)
Non-volatile V Memory (words)
D-memory (DWORDs)
Non-volatile D Memory (DWORDs)
R-memory (REAL DWORDs)
Non-volatile R Memory (REAL DWORDs)
Boolean execution/K
Stage Programming
Number of Stages
Handheld Programmer
Programming Software for Windows
Built-In communications ports
Program Memory
Total I/O points available
H2-DM1
$310.00
H2-DM1E
$415.00
Local I/O points available
Ethernet Remote I/O Discrete points
Ethernet Remote I/O Analog I/O Channels
Max Number of Ethernet slaves per Channel
I/O points per Remote Channel
Discrete I/O Module Point Density
Slots per Base
Number of instructions available
Control relays
Special relays (system defined)
Special registers (system defined)
Timers
Counters
System Date/Time structures
User Date/Time structures
ASCII String/Byte buffer structures
ASCII
PID Loop Control, Built In
Time of Day Clock/Calendar
Run Time Edits
Supports True Force
Internal Diagnostics
Password security
System error log
User error log
Battery backup
FeatureH2-DM1
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
128 per Program code-block; number of code-blocks configurable to memory limit
USB, RS-232
X, Y, each configurable up to 65536 (2048 default); WX, WY (analog in/out)
Yes, configurable up to memory limit, default 1024 input bits, 1024 coil bits,
>60 operators and functions: Integer, Floating Point, Trigonometric, Statistical,
CPU is forced into RUN Mode if no errors are encountered.
RUN, PROGRAM and DEBUG modes are available.
In this mode, the mode of operation can be changed
through the Programming Software.
CPU is forced into STOP Mode.
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-14
tDMH-14
1-800-633-0405
1-800-633-0405
CPU Modules
Communication Ports
USB Port
Used exclusively for programming and monitoring via a PC running
Do-more Designer.
USB Port Specifications
DescriptionStandard USB 2.0 Slave input for programming and online
Cables
(ADC part #)
monitoring, with built-in surge protection. Not compatible with
older full speed USB devices.
USB Type A to USB Type B:
USB-CBL-AB3 (3ft)
USB-CBL-AB6 (6ft)
USB-CBL-AB10 (10ft)
USB-CBL-AB15 (15ft)
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
RS-232 Port
RJ-12 style connector used for:
• Connection to a PC running Do-more
Designer
• Modbus RTU Master connections
• Modbus RTU Slave connections
• ASCII Incoming and Outgoing
communications
• Custom Protocol Incoming and Outgoing
communications
Pin Description
5V Bus Voltage Sense
1
D- Data -
2
D+ Data +
3
0V Ground
4
RS-232 Port Specifications
DescriptionNon-isolated, full duplex RS-232 DTE port used for programming, online moni-
Baud Rates1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
+5V Cable Power
Source
Maximum Output Load
(TXD/RTS)
Minimum Output
Voltage Swing
Output Short Circuit
Protection
Cable Options
(ADC part #)
toring or can connect the CPU as a Modbus RTU or ASCII master or slave to a
peripheral device. Includes ESD and built-in surge protection.
220mA maximum at 5V, ±5%. Reverse polarity and overload protected.
3kV, 1000pf
±5V
±15mA
D2-DSCBL
FA-CABKIT
FA-ISOCON for converting RS-232 to isolated RS-422/485
Pin Description
1
2
3
4
5
6
0V Power (-) connection (GND)
5V Power (+) connection (220mA max.)
RXDReceive Data (RS-232)
TXDTransmit Data (RS-232)
RTSRequest to Send (RS-232)
CTSClear to Send (RS-232)
For a list of protocols supported by each port, please refer to the Communications topic of the Do-more H2 Series PLC Overview in
this section.
Do-more H2 PLCs
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
tDMH-15
tDMH-15
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Ethernet Port
RJ-45 style connector used for:
• Connection to a PC running Do-more Designer
• Modbus TCP Client connections (Modbus
requests sent from the CPU)
• Modbus TCP Server connections (Modbus
requests received by the CPU)
• Ethernet Expansion I/O Master
Ethernet Port Specifications
Description Standard transformer isolated Ethernet port with built-in surge
protection for programming, online monitoring, Modbus/TCP
client/server connections (fixed IP or DHCP) and Ethernet
Expansion I/O capabilities.
Transfer Rate 10/100 Mbps; Auto-MDX (Crossover)
For a list of protocols supported by each port, please refer to the Communications topic of the Do-more H2 Series PLC Overview in this
section.
Do-more H2 PLCs
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
tDMH-16
tDMH-16
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Battery Specifications
A battery is included with the Do-more CPU
and is used to retain the Time and Date
along with any Tagname values that are set
up as retentive. It is recommended that the
battery be replaced once every five years or
when one year of cumulative OFF time has
been exceeded.
Up to two hours is allowed to change out a
battery without loss of data.
D0-MC-BAT is $3.00.
Battery
D0-MC-BAT
Coin type, 3.0 V Lithium
battery, number CR2032
H2-DM1 and H2-DM1E
Battery Replacement
Part # D0-MC-BAT.
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-17
tDMH-17
1-800-633-0405
1-800-633-0405
CPU Modules
For the latest prices, please check AutomationDirect.com.
For the latest prices, please check AutomationDirect.com.
Ethernet Expansion I/O
With Do-more Designer Software version V1.1 and newer, the
H2-DM1E CPU’s built-in Ethernet port can be configured as an
Ethernet Expansion I/O master. Much like the H2-ERM100 module,
the Ethernet Expansion I/O feature allows expansion beyond the local
chassis to slave I/O using the onboard high-speed Ethernet link.
The onboard Ethernet port can support up to 16 slave devices. The
slave I/O modules supported are:
• H2-EBC100
• T1H-EBC100 (Terminator I/O)
• GS-EDRV100 (GS Drives)
The Ethernet Expansion I/O network uses Category 5 UTP cables for
cable runs up to 100 meters (328 ft.) with extended distances achieved
through Ethernet switches.
It is highly recommended that a dedicated network be used with the
Ethernet Expansion I/O feature. Ethernet Expansion I/O networks and
ECOM/office networks should be isolated from one another to prevent
network delays.
Stride
Ethernet
Switch
Do-more H2-DM1E CPU
H2-DM1E
DirectLOGIC
DL205 I/O with
H2-EBC100
Module
C-more Operator
Interface
GS-EDRV100
Terminator I/O
with T1H-EBC100
Module
GS
Drive
www.automationdirect.com
www.automationdirect.com
Do-more H2 PLCs
Do-more H2 PLCs
tDMH-18
tDMH-18
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.