C2-14AR
Installation Instructions
C2-14AR OPTION SLOT MODULE
8 discrete AC inputs
6 discrete relay outputs
General Specifications*
Operating Temperature
Storage Temperature
Ambient Humidity
Altitude
Environmental Air
Environment
Vibration
Shock
Weight
Bus Power Required
Agency Approvals
Other
* Isolate from shock, vibration and electric or ferromagnetic eld.
Keep out iron powder, moisture, oil or chemicals.
Indoor use only. Keep out of direct sunlight.
32°F to 131°F [0°C to 55°C]
–4°F to 158°F [–20°C to 70°C]
30% to 95% relative humidity
(non–condensing)
Up to 2,000m
No corrosive gases
Pollution Degree 2 (UL840)
For Indoor Use Only
5–9Hz: 3.5 mm amplitude; 9–150Hz: 1.0 G
10 sweep cycles per axis on each of
3 mutually perpendicular axes.
15G peak, 11ms duration,
3 shocks in each direction per axis,
on 3 mutually perpendicular axes.
63g
Max 75mA (all points ON)
UL61010 (File No. E157382);
CE (EN61131-2);
CUL Canadian C22.2
RoHS 2011/65/EU Amendment (EU)2015/863
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
1-800-633-0405
Please read and understand the information in these
installation instructions prior to installation, operation, or
servicing this equipment. This module is intended to be used
with a CLICK PLUS CPU. Ensure the CPU is installed in
accordance with its installation and safety instructions.
PLEASE REVIEW SAFETY WARNINGS ON PAGE 2!
Input Specifications
Inputs per Module
Operating Voltage Range
Input Voltage Range
AC Frequency
Input Current
Max. Input Current
Input Impedance
ON Voltage Level
OFF Voltage Level
Minimum ON Current
Maximum OFF Current
OFF to ON Response
ON to OFF Response
Input Filter
Status Indicators
Commons
* Set from CLICK Tool.
Outputs per Module
Operating Voltage Range
Output Voltage Range
Output Type
Max. Output Current
Min. Load Current
Max. Inrush Current
OFF to ON Response
ON to OFF Response
Status Indicators
Commons
8
100–120VAC
80–144VAC
47–63Hz
8.5 mA @ 100VAC (50Hz), typical
10mA @ 100VAC (60Hz), typical
16mA @ 144VAC
15kΩ @ 50Hz, 12kΩ @ 60Hz
> 60VAC
< 20VAC
5mA
2mA
< 40ms
< 40ms
1ms unit (set from 1 to 99 ms)*
8 Green LEDs
2 (4 points/common) Isolated
Output Specifications
6
6–27VDC, 6–240VAC (47–63Hz)
5–30VDC, 5–264VAC (47–63Hz)
Relay, Form A(SPST)
1A/point,
C3: 4A/common; C4: 2A/common
5mA @ 5VDC
3A for 10ms
< 15ms
< 15ms
6 Red LEDs
2 (4 points or 2 points/common)
Copyright© 2020, Automationdirect.com Incorporated/All Rights Reserved Worldwide
www.automationdirect.com/click-plc
1
C2-14AR Option Slot Module
3 Push the top and bottom locking clips
backward until they click into place.
1 Remove the Option Slot Cover (#C2-FILL)
if it was installed in the CPU, by grasping its
top and bottom front corners, squeezing and
pulling it forward.
3 Push the top and bottom locking clips
backward until they click into place.
Lift slightly on the locking clips until they
release, then slide each clip forward.
Reverse the procedure.
To install an Option Slot Module To install an Option Slot Module
To remove an Option Slot Module
To remove an Option Slot Module
3 Push the top and bottom locking clips
backward until they click into place.
Installation Instructions
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
1-800-633-0405
Safety Warnings
Please follow these instructions for personal and operational safety.
WARNING
CAUTION
Don’t use this equipment in a flammable or explosive
environment in order to avoid accidental injury or fire.
You should use external electromechanical devices that are
independent of the PLC (Programmable Logic Controller)
system to provide protection for any part of the system;
otherwise malfunction or output failures may result in a
hazardous accident.
24VDC power is required from a secondary circuit or a specific
power supply unit only.
Ensure the Ground Terminal of the Power Supply (C0-00AC/
C0-01AC) for the CLICK PLUS CPU is connected to Earth
Ground to avoid electric shock or equipment damage during a
short circuit.
Don’t operate the equipment with a nonconforming external
power supply to avoid electric shock, equipment damage or fire.
Don’t intentionally fault the wiring; this may cause equipment
damage or fire.
To avoid electric shock or malfunctions which might result in an
accident, don’t touch any terminal while the PLC power is on.
Don’t put metals (e.g. screwdriver) into vent holes, or drop trash
or foreign objects (e.g. wire cut-offs) into the device, in order to
avoid electric shock or equipment damage.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
invalidated.
Assumes that incorrect handling may cause hazardous
conditions, resulting in severe injury or death.
Assumes that incorrect handling may cause hazardous
conditions, resulting in medium or slight injury, or
may cause equipment damage.
WARNING
Hardware Installation
CAUTION
CAUTION
INSTALL OR REMOVE THE OPTION SLOT MODULE
Discharge static electricity before installation or
wiring to avoid electric equipment damage.
Cut off all phases of the power source externally
and wait 5 seconds before installing or removing
the Option Slot Module of a running system.
To install an Option Slot Module To install an Option Slot Module
1 Remove the Option Slot Cover (#C2-FILL)
if it was installed in the CPU, by grasping its
top and bottom front corners, squeezing and
pulling it forward.
2 Hold the
Option Slot
Module by the
top and bottom front
corners, align the PCB card
edge with the guide slots in the
CPU, and slide the module into
its slot. Press the module into place until it is
fully seated
CAUTION
For use in Pollution Degree 2 Environment. Use and store the
equipment in an environment described in the specifications
(regarding temperature, humidity, vibrations, shock, etc.) in
order to avoid equipment damage or fire.
Ensure all wiring has strain reliefs in order to avoid damage to
insulation that might result in electric shock or fire.
Ensure secondary external power circuits are only live after PLC
control program is started; otherwise a malfunction or output
failure may result in a hazardous accident.
Don’t block the vent holes. This may cause an increase of inter-
nal temperature resulting in equipment damage or fire.
Don’t disassemble or modify equipment so as to avoid electric
shock, equipment damage, or fire.
Cut off all phases of the external power source before mainte-
nance work, thus avoiding electric shock or equipment damage.
Copyright© 2020, Automationdirect.com Incorporated/All Rights Reserved Worldwide
3 Push the top and bottom locking clips
backward until they click into place.
To remove an Option Slot Module
To remove an Option Slot Module
Lift slightly on the locking clips until they
release, then slide each clip forward.
Reverse the procedure.
www.automationdirect.com/click-plc
2