WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered trademarks, and Alert is a trademark of Automated Logic Corporation.
®
BACnet
is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies.
Page 3
NOTE
NOTE
NOTE
What is the SE6166 controller?
Driver and control
program
Specifications
The SE6166 controller controls rooftop Air Handling Units (AHUs) or other large single
pieces of equipment. You can mount the SE6166 on or inside the rooftop equipment.
Driver DRV_SE
Maximum number of control programs 1
Maximum number of BACnet objects* 300**
* Depends on available memory.
** Any points that exceed this number will not be network visible.
Power 24 Vac ±10%, 50–60 Hz, 20 VA power consumption (38.4
VA with BACview6 attached) single Class 2 source only, 100
VA or less
BACnet port
(This port may be labeled
For communication with the controller network using
ARC156 or MS/TP (9600 bps–76.8 kbps)
CMnet.)
Local Access port For system start-up and troubleshooting
LogiStat port For LogiStat and LogiStat Plus room sensors. The LogiStat
port uses two universal inputs.
The SE6166 does not support the LogiStat Pro. Use
an RS Pro on the Rnet port instead.
Rnet port Supports up to four RS Standard sensors and one RS Plus,
RS Pro, or RS Pro-F sensor for averaging or high/low select
control. The sensors can share the Rnet port with a BACview
6
or BACview
.
If you use the Rnet port, you cannot connect a
LogiStat sensor to the LogiStat port.
Inputs 16 inputs, configurable for 0–10 Vdc, 0–20 mA, RTD,
thermistor, or dry contact, and one LogiStat port. Inputs 1
and 2 are also configurable for pulse counter or timed local
override (TLO).
If using a LogiStat or LogiStat Plus, temperature and
setpoint adjust inputs replace inputs 9 and 10, making 9
and 10 unavailable.
Input resolution 12 bit A/D
Input pulse frequency 40 pulses per second. Minimum pulse width (on or off time)
Real-time clock Battery-backed real-time clock keeps track of time in event
of power failure
Battery 10-year Lithium CR2032 battery provides a minimum of
10,000 hours of data retention during power outages
Protection Incoming power and network connections are protected by
non-replaceable internal solid-state polyswitches that reset
themselves when the condition that causes a fault returns to
normal. The power, network, input, and output connections
are also protected against voltage transient and surge
events.
BT485 connector You attach a BT485 (not included) to a controller at the
beginning and end of a network segment to add bias and to
terminate a network segment.
Status indicators LED's indicate status of communications, running, errors,
power, and digital outputs
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, noncondensing
The SE6166 has 16 inputs that accept the signal types described below.
All Thermistor1 Precon type 2 (10 kOhm at 77°F). Input voltages should
be from 0.489 Vdc to 3.825 Vdc for thermistors.
All Dry contact A 5 Vdc wetting voltage detects contact position, resulting
in a 1 mA maximum sense current when the contacts are
closed.
All 0–5 Vdc
0–10 Vdc
The output impedance of a 0–5 Vdc or a 0–10 Vdc source
must not exceed 200 Ohms. The input impedance of the
SE6166 is approximately 20 kOhm.
All 0–20 mA The input resistance on the positive (+) terminal is 250
Ohms. The
connector is capable of
supplying 24 Vdc to multiple 4–20 mA transducers, but
the total current demanded must not exceed 200 mA. If
the voltage measured from the
to
is less than 18 Vdc, you need to use an external
connector
power supply.
All RTD1 Platinum - 1 kOhm at 32°F (0°C)
Nickel/Iron - 1 kOhm at 70°F (21°C)
Balco TS8000 - 1 kOhm at 70°F (21°C)
Input voltages should be from 0.6–1.2 V.
ALC recommends use of an external current
transducer between an RTD and the SE6166.
IN-1, IN-2 Pulse
counter
2
Pulse counting up to 40 pulses per second.
Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
IN-1, IN-2 Timed local
override
A momentary contact switch that overrides a schedule and
turns equipment on for a defined period of time. The
override time added for each push of the button and the
maximum allowable On time are software adjustable.
IN-9, IN-10 LogiStat
LogiStat Plus
IN-9–See Thermistor.
3
IN-10–Setpoint adjust. Input voltages should be from 1.4–
3.4 Vdc.
1
To use a thermistor or RTD not listed above, you can set up a custom translation table (page 19)
for your sensor.
2
The SE6166 can perform pulse counting for dry contact or voltage inputs if you assign the input to
a Pulse to Analog Input microblock. See To assign inputs or outputs to points (page 13).
3
A LogiStat or LogiStat Plus connected to the SE6166 uses IN-9 and IN-10. A LogiStat Pro or an RS
room sensor does not use these inputs.
Digital outputs
The SE6166 has 6 digital outputs. You can connect each output to a maximum of 24 Vac.
Each output is a dry contact rated at 3 A maximum and is normally open.
The SE6166 has 6 analog outputs that support voltage or current devices. The controlled
device must share the same ground as the controller and have the following resistance to
ground:
Room sensors
0–10 Vdc
0–20 mA
min 500 Ohms
max 800 Ohms
NOTE The SE6166 supervises all outputs.
RS sensors
You can wire RS sensors to the SE6166's Rnet port. An Rnet can consist of any of the
following combinations of devices wired in a daisy-chain or star configuration:
• 1 RS Plus, RS Pro, or RS Pro-F
• 1–4 RS Standards
• 1–4 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
• Any of the above combinations, plus up to 2 BACviews, but no more than 6 devices
total. See BACviews below.
LogiStats
You can wire a LogiStat or LogiStat Plus to the SE6166's LogiStat port.
NOTES
• The SE6166 does not support the LogiStat Pro.
• A LogiStat or LogiStat Plus wired to the SE6166 cannot be used for local access.
• If you use the Rnet port, you cannot connect a LogiStat sensor to the LogiStat port.
BACviews
You can wire a BACview5 or BACview6 keypad/display unit to the Rnet port of the SE6166
to view or edit some of its property values or its real time clock. See Room sensors above
5
for Rnet configurations. See the BACview
(http://accounts.automatedlogic.com) or BACview
Hardware Setup Guide
6
Hardware Setup Guide
(http://accounts.automatedlogic.com) for installation instructions.
To start up and troubleshoot the SE6166, you can temporarily connect the following items
to its Local Access port:
6
•The BACview
Handheld. See its Technical Instructions
(http://accounts.automatedlogic.com).
•A laptop running the Virtual BACview software. Virtual BACview software simulates the
6
BACview
and is included with WebCTRL v4 or later.
NOTE Before you can use the BACview5, BACview6, BACview6 Handheld, or Virtual
BACview with the SE6166, you must create a BACview screen file in ViewBuilder, enter
the screen file name in the controller's