Automated Logic S6104 Technical Instructions

Technical Instructions
Using the S6104 2
Specifications 3
Mounting 3
Addressing 3
Power Wiring 4
Network Communications 4
Using the S6104 on an ARC156 Segment 5
Using the S6104 on a Legacy CMnet 5
Connecting the S6104 to the Network 5
Communicating with the Workstation Using SuperVision 6
Communicating Through the LogiStat Port Using SuperVision 6
Communicating Through the Access Port Using SuperVision 7
Inputs 8
LogiStat Wiring 10
Digital Outputs 11
Analog Outputs 12
Writing GFBs for the S6104 12
Point Identifiers 13
Point Identifiers in WebCTRL 13
Channel Numbers in SuperVision 13
Transferring Memory 14
Transferring Memory in WebCTRL 14
Transferring Memory in SuperVision 15
Troubleshooting 15
Formatting the Module 15
LEDs 15
Protection 16
Production Date 16
Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 • 770/429-3000 770/429-3001 Fax www.automatedlogic.com Copyright 2002 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, SuperVision, Eikon, Alert, InterOp, and WebCTRL are registered trademarks of Automated Logic Corporation. BACnet their respective companies.
®
is a registered trademark of ASHRAE. All other brand and product names are trademarked by

Using the S6104

The S6104 is part of the S-Line, designed specifically for controlling rooftop Air Handling Units (AHUs). The module can be mounted directly in or on the rooftop equipment.
The table below outlines the limitations and requirements depending on whether you are using WebCTRL or SuperVision to communicate with your S6104.
WebCTR L Super Vision
Module Driver DRV_S6104 SLM
Number of Function Blocks*
Number of BACnet Objects*
* depending on available memory
11
1000 1000
For more information, see the appropriate module driver document on the Automated Logic website at www.automatedlogic.com.
The S6104 has:
• 6 digital outputs
• 10 universal inputs
• 4 analog outputs
A single board provides the power circuitry, microprocessor, and non-volatile memory (stores data even during a power failure). The Access Port allows communication with WebCTRL or SuperVision. The 4-pin LogiStat Port provides the interface for a LogiStat room sensor. With certain restrictions, the LogiStat Port can also be used to communicate with WebCTRL or SuperVision
(see Figure 1).
11/4"
3.175 cm
LogiStat Port
Dual Rotary
Address Switches
87/8"
22.543 cm Manua l Format
Button
Digital O utput Mode
(H O A ) S witch e s
71/2"
19 cm
1/4"
.635 cm
Revised 7/30/02 • S6104 2 © 2002 Automated Logic Corporation
Access
Port
Figure 1. S6104 Dimensions and Layout
Power Switch
11/8"
2.858 cm
CAUTION
unit not expressly approved by the party responsible for compliance could void the user’s authority to operate equipment.
NOTE
found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
Changes or modifications to this
This equipment has been tested and

Specifications

Power
Inputs
NOTE
Input Resolution
Digital Outputs
Analog Outputs
24VAC ± 10%, 50-60Hz, 20VA (0.83A) maximum (single Class 2 source only, 100VA or less). (24VAC ± 10%, 60Hz when ordered for UUKL Smoke Control Systems.)
One LogiStat Port and 10 universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor/dry contact.
Universal inputs 9 and 10 are inaccessible if using a LogiStat or a LogiStat Plus. Temperature and setpoint adjust inputs replace universal inputs 9 and 10 in this situation.
10 bit A/D.
6 digital outputs (Form
A), 3A max.
4 analog outputs (0 to
10VDC), 20mA source capability.
For SuperVision, 156 kbps BACnet-over­ARCNET, 9600 bps or 38.4 kbps legacy Control Module network (CMnet). Access Port: 9600 bps or 38.4 kbps EIA-485.
Environmental Operating Range
to 150°F (-28.9° to 65.6°C); 10 to 90% relative humidity, non-condensing. When ordered for UUKL Smoke Control Systems, 32°-120.2°F (0°-49° C); 10 to 85% relative humidity, non-condensing.
Status Indication
communication, running, errors, and all outputs.
Memory
non-volatile battery-backed SRAM, and 128 bytes of serial EEPROM.
Real Time Clock
time clock that keeps track of time in the event of a power failure.
Protection
protection circuitry.
Bat t e ry
provides a minimum of 10,000 hours of data retention during power outages.
Listed by
No. 205-M1983 (PAZX7), FCC Part ­Subpart B - Class A.
512KB Flash memory and 512KB
Built-in surge and transient
Seven-year lithium BR2325 battery
UL 916 (PAZX), cUL C22.2
Visual (LED) status of
A battery-backed real
-20°

Mounting

Screw the S6104 into an enclosed panel using the mounting holes provided on the cover plate. Be sure to leave about 2 inches (5 centimeters) on each side for wiring.

Addressing

Before setting or changing the address, make sure the S6104’s power is off. The S6104 only reads the address when the module is turned on. After changing the address, you must transfer memory to the module. Refer to “Transferring Memory” on page 14.
Output resolution
Communication
BACnet-over-ARCNET and 9600 bps or
38.4 kbps EIA-485 BACnet MS/TP.
Revised 7/30/02 • S6104 3 © 2002 Automated Logic Corporation
8 bit D/A.
For WebCTRL, 156 kbps
The S6104 has two rotary switches for addressing:
• For WebCTRL systems, use the switches to assign the device’s MAC (medium access control) address on the BACnet­over-ARCNET network segment. The rotary switches define the MAC address portion of the device’s BACnet address which is composed of the network address and the MAC address.
• For SuperVision systems, use the switches to assign the device’s module number.
The S6104 has an operating range of 21.6VAC to 26.4VAC. If voltage measured at the module’s power input terminals is outside this range, the module may not work properly.
1. Turn the module’s power off. This prevents the module from being powered up before the proper voltage is verified.
2. Make sure the 24VAC power source is off.
3. Connect the power wires to the module’s power terminals labeled Gnd and 24VAC (see Figure 1 on page 2 for location).
4. Apply power to the transformer.
One switch corresponds to the tens digit and the other corresponds to the ones digit. For example, if the module’s address is three, set the tens switch to zero and the ones switch to three, as shown in Figure 2.
10s 1s
Figure 2. Setting the Module’s Address

Power Wiring

CAUTION
device (less than 30VAC, 100VA maximum). Take appropriate isolation measures when mounting the S6104 module in a control panel where non-Class 2 devices (for example, 120VAC) or wiring are present.
You can power several modules from the same transformer if you maintain the same polarity.
The S6104 module is a Class 2
5. Make sure that 24VAC is present at the module’s power input terminals.
6. Set the module’s address. Refer to “Addressing” on page 3 for details about setting the address.
7. Turn the S6104’s power switch on.
When the module turns on, the Run and Power LEDs turn on. The Run LED begins blinking and the Error LED turns off. See Table 9 on page 16 to troubleshoot the LEDs. If the module does not respond, call Technical Support at (770) 429-3002.

Network Communications

The S6104 module supports several communications options through its CMnet port.
On a SuperVision system, the S6104 module can connect to a legacy CMnet at 9600 bps or
38.4 kbps, or to a BACnet-over-ARCNET
network segment at 156 kbps.
Revised 7/30/02 • S6104 4 © 2002 Automated Logic Corporation

Using the S6104 on an ARC156 Segment

When communicating at 156 kbps, the network segment uses a unique implementation of the industry standard BACnet-over-ARCNET protocol called ARC156. For a summary of the differences between ARCNET and ARC156, please refer to
ARC156 CMnet Wiring Technical Instructions
.
Use the appropriate wire for network communications. When using an ARC156 network, use an A3ARC156 wire available from:
Magnum Cable Corporation Cleveland, OH 44110-0500 (800) 421-0820
When the CMnet Select jumper is set to ARC156, the CMnet port is connected to an ARCNET processor, enabling the S6104 to communicate on an ARC156 network segment. Communication speed is 156 kbps regardless of the Baud Select jumper setting (see Table 1).
Table 1. Jumper positions
CMnet Type CMnet Select Port Select Baud Select
ARC156 ARC156 Access or
LogiStat
Legacy CMnet Legacy Access
Not Applicable
9600 bps or
38.4 kbps

Using the S6104 on a Legacy CMnet

Use a dedicated 22AWG to 18AWG twisted pair wire for legacy CMnet (EIA-485) wiring. For more information about CMnet wiring, refer to the
When the CMnet Select jumper is set to Legacy, the module communicates on a legacy CMnet at the baud rate set by the Baud Select jumper (see Table 1). The Port Select jumper must also be set to Access.
Technical Handbook
.
NOTE
Setting the CMnet jumper to Legacy disables the industry standard BACnet-over­ARCNET (ARC156) protocol for the network segment and enables the proprietary ALC CMnet protocol.

Connecting the S6104 to the Network

Before connecting the S6104 to the CMnet, be sure the S6104’s power is off.
1. Set the CMnet mode (ARC156 or legacy
CMnet) using the CMnet Select jumper.
2. If communicating on a legacy CMnet, set
the Baud Select jumper for either 9600 bps or 38.4 kbps.
NOTE
use the same baud rate.
3. Set the Port Select jumper:
• On a legacy CMnet, set the Port Select jumper for Access.
• On an ARC156 CMnet on a WebcTRL system, set the Port Select jumper for LogiStat.
• On an ARC156 CMnet on a SuperVision system, set the Port Select jumper for either Access or LogiStat depending on which port will be used for serial communications (see “Communicating with the Workstation Using SuperVision” on page 6).
4. Check the network communication wiring for shorts and grounds.
5. Connect the CMnet wires to the module’s screw terminals as shown in Figure 3 on page 6. Be sure to follow the same polarity as the rest of the CMnet.
All modules on the CMnet must
Revised 7/30/02 • S6104 5 © 2002 Automated Logic Corporation
Loading...
+ 11 hidden pages