Automated Logic LGC Technical Instructions

Page 1
Technical Instructions
Using the LGC 2
Specifications 3
Mounting 3
Wiring 3
Power 3
Communications Wiring 4
Addressing 4
Transferring Memory 4
Troubleshooting 5
Communicating with the Workstation 5
Formatting the Module 6
LEDs 7
Protection 7
Production Date 7
Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 • 770/429-3000 770/429-3001 Fax www.automatedlogic.com Copyright 2000 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, SuperVision, Eikon, Alert and InterOp are registered trademarks of Automated Logic Corporation. BACnet their respective companies.
®
is a registered trademark of ASHRAE. All other brand and product names are trademarked by
Page 2

Using the LGC

The LGC is part of the LANgate family and provides communication between a workstation and a control module network (CMnet) consisting of fewer than 100 modules.
The LGC communicates with the CMnet using an EIA-485 connection. The CMnet is a peer­to-peer network that allows all control modules to communicate with equal authority using a token-passing protocol.
EIA-232 ConsolePort 1
EIA-232 ConsolePort 2
A workstation can communicate with the LGC directly or through a modem. The LGC provides two EIA-232 Console Ports and an Access Port that can be connected to a workstation, portable computer, or a modem.
The LGC must use v6.00g or later of the LGM module driver. For more information, see the
LGM Module Driver
document on the Automated Logic website at www.automatedlogic.com.
Power Switch
71/8"
Auxiliary Device Port
CMnet Baud Rate Jumper
Access Port
LEDs
61/4"
Figure 1. Module dimensions and layout
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed
Manual Format Button
Addressing DIP Sw itch
CMn et Connection
1"
15/8"
and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Revised 6/16/00 • LGC 2 © 2000 Automated Logic Corporation
Page 3

Specifications

Power

Communications
Environmental Operating Range
Status Indication
Memory
Protection
Bat t e ry
Listed By
24VAC ±10%, 0.3A [(7.2VA), 50­60Hz, power consumption] (single Class 2 source only, 100VA or less).
CMnet Port with EIA-485, twisted pair, selectable for 156 kbps, 38.4 kbps, or 9600 bps. Two Console Ports, selectable for 38.4 kbps or 9600 bps, for direct connect or modem. One Access Port for direct network using an APT. One Auxiliary Device Port for a keypad/ display.
0 to 130°F (-17.8 to 54.4°C); 10 to 90% relative humidity, non-condensing.
Visual (LED) status of Console Port 1 and CMnet communications, errors, running, and power.
1MB Flash, 1MB RAM.
Built-in surge and transient
protection circuitry.
7-year lithium BR2325 battery provides a minimum of 10,000 hours of data retention during power outages.
UL 916 (PAZX), cUL C22.2 No.205 - M1983 (PAZX7), FCC Part 15 ­Subpart B - Class A.

Mounting

Screw the LGC into an enclosed panel using the mounting holes provided on the cover plate. Be sure to leave about 2 inches (5 centimeters) on each side for wiring.
BACview the auxiliary device port.
You must use SuperVision to transfer memory to the LGC. You can connect a portable computer running SuperVision to the LGC using the module’s Access port. For more information about connecting to a workstation, refer to “Formatting the Module” on page 6.
1
or BACview2 keypad display unit to
Power
CAUTION
device (less than 30VAC, 100VA maximum). Take appropriate isolation measures when mounting the LGC module in a control panel where non-class 2 devices or wiring are present.
You can power several modules from the same transformer if you maintain the same polarity.
The LGC has an operating range of 21.6VAC to 26.4VAC. If voltage measured at the module’s power input terminals is outside this range, the module may not work properly.
Since the module’s address is factory-set as #1, you do not need to set the address.
1. Turn the module’s power off. This prevents the module from being powered up before the proper voltage is verified.
2. Make sure the 24VAC power source is off.
The LGC module is a Class 2
CAUTION
unit not expressly approved by the party responsible for compliance could void the user’s authority to operate equipment.
Changes or modifications to this

Wiring

The LGC connects to the CMnet through a CMnet Connection port. The LGC also provides an EIA-232 port for diagnostic purposes. You can connect an optional
Revised 6/16/00 • LGC 3 © 2000 Automated Logic Corporation
3. Connect the power wires to the module’s power terminals labeled Ground and 24VAC (see Figure 1 on page 2 for location).
4. Apply power to the transformer.
5. Make sure that 24VAC is present at the module’s power input terminals.
When the module turns on, the Run and Error LEDs turn on and the Run LED begins blinking. See Table 2 on page 7 to
Page 4
troubleshoot the LEDs. If the module does not respond, call Technical Support at (770) 429-3002.

Communications Wiring

The LGC can connect to the CMnet at 9600 bps, 38.4 kbps, or 156 kbps. When communicating at 156 kbps, the CMnet uses a unique implementation of the industry standard ARCNET protocol called ARC156. For a summary of the differences between ARCNET and ARC156, please refer to
CMnet Wiring Technical Instructions
ARC156
.
Baud 156K
Bau d 156K Baud 9 600/38.4K
Consolebaud 9600
address
(Module)
CMnetbaud 9600
LGnet
38.4K
38.4K
On
Off
4 2 1
Figure 2. Using an ARC156 CMnet
Use the appropriate wire for CMnet communications. When using the ARC156 protocol, use an A3ARC156 wire available from:
Magnum Cable Corporation Cleveland, OH 44110-0500 (800) 421-0820
Use a dedicated 22AWG to 18AWG twisted pair EIA-485) for legacy CMnet wiring. For more information about CMnet wiring, refer to the
Technical Handbook
CMnet Wiring Technical Instructions
or to
ARC156
.
1. Turn off the power.
2. Attach the two CMnet EIA-485 communications wires to the CMnet Connection port labeled Net - and Net + on the LGC (see Figure 1 on page 2). On an ARC156 CMnet, you must also connect the Shield.
Be sure to follow the same polarity as used throughout the rest of the CMnet.
3. Make sure the LGC is configured for the correct baud rate. All modules on the CMnet must use the same baud rate.
On an ARC156 CMnet, set the CMnet Baud Rate jumper to Baud 156K. Refer to Figure 2 for the jumper’s location.
If you are using a legacy CMnet, set the CMnet Baud Rate jumper to Baud 9600/
38.4K and select the proper speed with the first switch on the Addressing DIP switch. Refer to Figure 3 for the switch’s location.
CMnet Baud 9600
Baud 9600/38.4 K
Bau d 156K Baud 9 600/38.4K
Console 1 Baud 9600 Console 2 Baud 9600
CMnetbaud 9600
Consolebaud 9600
LGnet
Off
address
4 2
(Module)
1
Figure 3. Using a Legacy CMnet
38.4K
38.4K
38.4K
38.4K
38.4K
On

Addressing

The LGC’s address is factory-set as control module #1 and cannot be changed.

Transferring Memory

The LGC module stores the LGM module driver. To transfer the module driver to the LGC, you must use SuperVision v2.6 or later software, and you must use FBLINK version
2.7a or later. For more information about using SuperVision, refer to the
User’s Guide
.
SuperVision
Revised 6/16/00 • LGC 4 © 2000 Automated Logic Corporation
Page 5
The first memory transfer to the LGC takes
9
Rx
6
1 2-Tx out 3-Rx in 5-Gnd 1,6,8-+10V or floating
Tx +5V
APT
5
Exec. 4 relay
Isolate Network
Mode Select
TTL
485
ACCESS
PORT
EIA-232
Port
Mode Select
Switch
Exec. 4 relay
Switch
Access
Port
Ground 24Vac
Optiona
l
She
i
l
d
Net-
Net+
longer than subsequent memory transfers.
1. Log in to SuperVision on a workstation connected to the CMnet. You can also connect directly to the gateway using the Access Port; see “Communicating with the Workstation” .
2. Navigate to the module driver and look at the module status page in SuperVision to make sure the gateway type and number agree with the module.
• To view the module status page in SuperVision v3.0, click Tools ­Troubleshooting - Module Status.
• To view the module status page in SuperVision v2.6, press the Esc key, type
MO ,,module address,15
and press Enter.
3. Transfer memory to the module.
• In SuperVision v3.0, click Tools ­Troubleshooting - Transfer Memory to Module.
• In SuperVision v2.6, choose Download Memory for This Module.
When the memory transfer is finished, check the module status page again. Make sure the FB List shows all the FBs you intended to transfer.
Figure 4. Using the Access Port
speed for each Console Port is set individually using the eight-position DIP switch. DIP switch 1 sets the baud rate for Console Port 1 and switch 2 set the baud rate for Console Port 2 (see Figure 3 on page 4). Use the wiring diagrams in Figure 5 on page 6 to connect a Console Port to a workstation or a modem.
Use the following procedure to connect the Access Port to a workstation.
1. Connect the computer’s serial port to the EIA-232 port of the APT using a standard straight-through cable (see Figure 4).
2. Set the APT’s Mode Select switch.
• On an ARC156 CMnet, use the TTL setting.
• On a legacy CMnet, use the 485 setting.
3. Connect the Access Port of the APT to the Access Port of the module.

Troubleshooting

4. In SuperVision, define the connection type using Table 1

Communicating with the Workstation

The LGC can connect to a workstation through the Access port using an APT (see Figure 4) or through the Console Ports. A Console Port can connect directly to the workstation’s serial port or to a modem,
through which you can dial the workstation.
The LGC’s Console Ports can communicate at 9600 bps or 38.4 kbps. The communication
Revised 6/16/00 • LGC 5 © 2000 Automated Logic Corporation
Table 1. Connection Types
SuperVision
Vers i o n
3.0 any n/a Access Port
2.6 ARC156 yes Direct Connect
2.6 ARC156 no Direct Network
2.6 legacy n/a Direct Network
Typ e o f
CMnet
Gateway Present?
Use Connection
Type
Page 6
Console Po rt
(9 pin )
*DCD 1
RX 2
TX 3
*DTR 4
GND 5
Console Port 1
Workstation
(9 pin)
4DTR* 3TX
2RX 1 DCD*
5GND
Console P ort 2
Console Port
(5 pin)
TX 1 RX 2
GND 5
Workstation
(9 pin)
2RX 3TX
5GND
Console Port
(9 pin )
*DCD 1
RX 2
TX 3
*DT R 4
GND 5
Console Port
(9 pin)
*DCD 1
RX 2
TX 3
*DT R 4
GND 5
*DS R 6
**RTS 7
**CT S 8
*RI 9
W orkstation
(25 pin)
20 DTR* 2TX 3RX 8 DCD* 7GND
Modem (25 pin )
8 DCD* 3RX 2TX
20 DTR* 7GND 6DSR* 4RTS** 5CTS** 22 RI*
Console P ort
GND 5
Console Port
(5 pin)
TX 1
RX 2 *D TR 3 *DCD 4
GND 5
* W ire connection usually not needed ** N eeded only if hardware handshaking is used † DCD can be hooked up to the DTR signal for
self-handshaking
Figure 5. Wir ing Diagrams
(5 pin)
TX 1 RX 2
Workstation
(25 pin)
3RX 2TX 7GND
Modem (25 pin )
2 TX (receive input)
3 RX (transmit output) 20 DTR*†
8 DCD*† 7GND
The baud rate of the Access Port is determined by the CMnet Baud Rate DIP switch on the module.
2. Press and hold the Format button (see Figure 1 on page 2 for location). While continuing to hold the Format button, turn the module’s power on.

Formatting the Module

When you are unable to communicate with a module, you can, as a last resort, manually format the module to try to restore communication. Formatting the module erases all memory, so you need to transfer memory back to the module once it is
3. Continue to hold the button until the Error LED flashes three times in sync with the Run LED.
4. Release the Format button.
5. Transfer memory to the module. Refer to “Addressing” on page 4.
formatted.
1. Turn the module’s power off.
Revised 6/16/00 • LGC 6 © 2000 Automated Logic Corporation
Page 7

LEDs

The LGC has several LED indicators to show the status of certain functions. Table 2 explains the Run and Error LED signals in detail to assist troubleshooting. See Figure 1 on page 2 for location of LED signals.
Table 2. LED Signals
Run LED Error LED Condition
5 flashes per second
7 flashes per second
Off Firmware transfer in
progress
7 flashes per second
Ten second recovery period after brownout
Power - indicates power is being supplied to the module.
CMnet receive -indicates when the LGC receives data from the CMnet.
CMnet transmit - indicates when the LGC transmits data over the CMnet.
Console receive - indicates when the Console Port receives data.
Console transmit - indicates when the Console Port transmits data.
An - blinks to indicate network activity.
Table 2. LED Signals
Run LED Error LED Condition
2 flashes per second
2 flashes per second
2 flashes per second
Off Normal
1 flash per second
2 flashes alternating per second
Normal, but module is alone on the CMnet
Five minute auto-restart delay after system error
14 flashes per second
14 flashes per second
Brownout

Protection

The LGC is protected by internal solid state Polyswitches on the incoming power and network lines. These Polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.

Production Date

To determine when a module was manufactured, check the Module Status report in SuperVision. Refer to the
User’s Guide
for more information about the
Module Status report.
A sticker on the back of the module also shows the date the module was manufactured. The first three characters on the sticker indicate the type of module. The next three characters show the year, month, and week of manufacture. (The month digit is in hexadecimal.)
SuperVision
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
Revised 6/16/00 • LGC 7 © 2000 Automated Logic Corporation
2 flashes in sync per second
3 flashes per second
4 flashes per second
On Exec halted after frequent
On Exec start-up aborted, Boot
Module is configured for a different baud rate than the rest of the CMnet
Module has just been formatted
Two or more items in the database have the same ARC156 CMnet address
system errors
is running
Loading...