Setting Conflict Message
(P89) (16) Stat exerciser cannot be used with sequencing.
Stat exerciser should be used for test purposes and cannot be used with sequencing.
Check option 16 and parameter 89.
(P99) (P100) Graceful shutdown and assured low fire shut off not allowed.
If graceful shutdown is set, then assured low fire shut off cannot be used.
Check parameters 99 and 100.
(E1) (1) Water level control requires a boiler pressure sensor.
Water level control cannot be used with a hot water boiler (load/external temperature detector).
Check expansion option 1 and option 1.
(E1) (E3, E4) At least one analogue level sensor required.
If water level is enabled with one capacitance probe, then an external level sensor is required.
Check expansion options 1, 3 and 4.
(E1) (E3, E4, E5, E6) Sensor enabled but water level control disabled.
Water level control enabled must be enabled if capacitance probes, external level sensor, 2
nd
low
probe or auxiliary water level alarm inputs are set.
Check expansion options 1, 3, 4, 5 and 6.
(E3, E4, E5, E6) At least two level sensing elements are required.
A minimum of two of the following level sensing elements is required: capacitance probe, external
level sensor, auxiliary water level alarm input or second low probe.
Check expansion options 3, 4, 5 and 6.
(E4) (57) External level sensor cannot be optioned with fuel flow feedback
External level sensor cannot be used with fuel flow feedback, as they use same terminals.
Check expansion option 4 and option 57.
(E11) (E12) Pump turn off point must be above pump turn on point.
Pump turn off point cannot be set lower than pump turn on point.
Check expansion options 11 and 12.
(E17) (E40) Bypass valve cannot be optioned with solenoid top blowdown.
Bypass and solenoid top blowdown cannot be used together, as they use same terminals.
Check expansion options 17 and 40.
(E28) (E3) External level sensor without scaling requires a capacitance probe.
If external level sensor does not have a scale to indicate what level the 4-20mA signal represents,
a capacitance probe is required.
Check expansion options 3 and 38.
(E40) (1) Top blowdown requires a boiler pressure sensor.
Top blowdown cannot be used with a hot water boiler (load/external temperature detector).
Check expansion option 40 and option 1.
(E42) (E46) TDS warning level less than TDS target.
TDS warning level cannot be set lower than the TDS target value.
Check expansion options 42 and 46.
(E60) (1) Bottom blowdown requires a boiler pressure sensor.
Bottom blowdown cannot be used with a hot water boiler (load/external temperature detector).
(E62) (E64) Bottom blowdown reduction boiler steam production rating not set.
If bottom blowdown reduction is enabled, than steam production rating must be set.
Check expansion options 62 and 64.
(E62) (E120) Bottom blowdown reduction requires steam flow to be enabled.
If bottom blowdown reduction is enabled, then steam flow metering must be enabled.
Check expansion options 62 and 120.
Page 59 Mk8 MM End User Guide 22.05.2017
4 Errors and Lockouts