Autarco MX3000, MX3000S, MX3600S, MX3600, MX4600 Installation And Operation Manual

...
© Autarco Group B.V. Version 2.2 2016-08-26
Installation and Operation Manual
Solar Inverters MX-series
2 MX-series Inverters
installation and operation manual
2016-08-26 3
Contact Information
Autarco Group B.V. Schansoord 60 5469 DT Erp The Netherlands
www.autarco.com info@autarco.com
Other Information
This manual is an integral part of the unit. Please read the manual carefully before installation, operation or maintenance. Keep this manual for future reference.
Product information is subject to change without notice. All trademarks are recognized as the property of their respective owners.
© Autarco Group B.V. All rights reserved.
4 MX-series Inverters
Table of Contents
1. Introduction ....................................................................................................................................... 5
1.1 Read this first ............................................................................................................................................... 5
1.2 Target Audience .......................................................................................................................................... 5
1.3 Product versions covered by this document ............................................................................................... 6
2. Preparation ........................................................................................................................................ 7
2.1 Safety instructions ....................................................................................................................................... 7
2.2 Package contents ......................................................................................................................................... 8
2.3 Internal DC switch ....................................................................................................................................... 8
2.4 Explanations of symbols on inverter ........................................................................................................... 8
3. Product information ........................................................................................................................... 9
3.1 Overview ...................................................................................................................................................... 9
3.2 Product identification .................................................................................................................................. 9
3.3 Product overview....................................................................................................................................... 10
4. Installation ....................................................................................................................................... 11
4.1 Safety ......................................................................................................................................................... 11
4.2 Mounting instructions ............................................................................................................................... 11
4.3 Safety clearance ........................................................................................................................................ 12
4.4 Mounting procedure ................................................................................................................................. 13
5. Electrical installation ........................................................................................................................ 14
5.1 AC connection ............................................................................................................................................ 14
5.2 DC connections .......................................................................................................................................... 17
5.3 Inverter commissioning sequence ............................................................................................................. 18
6. Operation......................................................................................................................................... 18
6.1 LED indicator lights .................................................................................................................................... 18
6.2 Inverter display .......................................................................................................................................... 18
6.3 Information ................................................................................................................................................ 19
6.4 Settings ...................................................................................................................................................... 19
6.5 Advanced info ............................................................................................................................................ 20
6.6 Advanced Settings ..................................................................................................................................... 20
7. Monitoring setup and system registration ......................................................................................... 21
8. Maintenance .................................................................................................................................... 21
9. Disposal ........................................................................................................................................... 22
10. Troubleshooting ............................................................................................................................... 22
10.1 General ...................................................................................................................................................... 22
10.2 Internal component fault .......................................................................................................................... 22
10.3 Grid errors ................................................................................................................................................. 23
10.4 System and design fault............................................................................................................................. 24
11. Product specifications: ...................................................................................................................... 25
installation and operation manual
2016-08-26 5
1. Introduction
1.1 Read this first
This manual contains important information for use during installation and maintenance of the MX-series Autarco inverter.
To reduce the risk of electrical shock, and to ensure the safe installation and operation of the MX-series Autarco inverters, the following safety symbols appear throughout this document to indicate dangerous conditions and important safety instructions.
WARNING! Indicates safety instruction, which if not correctly followed, can result in injury or property damages.
RISK OF ELECTRIC SHOCK! Indicates safety instructions, which if not correctly followed, could result in electric shock.
HOT SURFACE! Indicates safety instructions, which if not correctly followed, could result in burns.
1.2 Target Audience
This manual is intended for anyone who uses Autarco MX-series inverter. Before any further action, the operators must first read all safety regulations and be aware of the potential danger to operate high-voltage devices. Operators must also have a complete understanding of this device’s features and functions.
ATTENTION! Qualified personnel means a person with valid license from the local authority in:
Installing electrical equipment and PV power systems (up to 1000 V). Applying all applicable installation codes and using Personal Protective Equipment. Analyzing and reducing the hazards involved in performing electrical work.
WARNING! Do not use this product unless it has been successfully installed by qualified personnel in accordance with the instructions in chapter 4 “Installation”.
6 MX-series Inverters
1.3 Product versions covered by this document
The main purpose of this user manual is to provide instructions and detailed procedures for installing, operating, maintaining, and troubleshooting the MX-series of Autarco inverters which includes the following models:
MX3000(S) MX3600(S) MX4600(S)
The product code will be “S2.<product version>”, e.g. S2.MX2500.
Please keep this user manual available at all times in case of emergency.
installation and operation manual
2016-08-26 7
2. Preparation
2.1 Safety instructions
DANGER! Do not touch any internal components whilst the inverter is in operation.
DANGER! Do not stand close to the inverter during severe weather conditions such as lighting, etc.
Make sure you completely cover the surface of all PV arrays with opaque (dark) material before wiring them or make sure the DC circuit breaker or equivalent DC isolator is disconnected. This is because photovoltaic (PV) arrays create electrical energy when exposed to light, and could cause a hazardous condition.
The MX series inverter must only be operated with PV arrays of protection class II, in accordance with IEC 61730, class A.
WARNING! The PV inverter will become hot during operation; please don’t touch the heat sink or peripheral surface during or shortly after operation.
NOTICE! Do not directly connect AC output of the inverter to any private AC equipment. The PV inverter is designed to feed AC power directly into the public utility power grid.
WARNING! The installation, service, recycling and disposal of the inverters must be performed by qualified personnel in compliance with national and local standards and regulations. Please contact your dealer to get the information of authorized repair facility for any maintenance or repairmen.
Any unauthorized actions including modification of product functionality of any form will affect the validation of warranty service; Autarco may deny the obligation of warranty service accordingly.
8 MX-series Inverters
2.2 Package contents
Autarco MX-series
inverter
AC plug
Mounting bracket
DC connectors
Instruction manual
2.3 Internal DC switch
Please verify whether your Autarco MX-series inverter is equipped with an internal DC switch. This switch can be found on the bottom of the inverter (see 3.3). If there isn’t an internal DC switch it is important to apply an external DC disconnector in order to completely disconnect the solar PV module strings from the inverter.
2.4 Explanations of symbols on inverter
10 min.
DANGER - HIGH ELECTRIC VOLTAGE
This device is directly connected to the public grid. All work on the inverter should be carried out by qualified personnel only. There might be residual currents in the inverter for up to 10 minutes because of large capacitors.
ATTENTION
This device is directly connected to electricity DC generators and the public AC grid.
DANGER – HOT SURFACES
The components inside the inverter will get hot during operation, DO NOT touch aluminum housing during operating.
ATTENTION
In the case of any work on the inverter, always refer to this manual for detailed product information.
ATTENTION
This device SHALL NOT be disposed of in residential waste. Please go to Chapter 9 “Recycling and Disposal” for proper treatments.
CE MARK
This equipment conforms to the basic requirements of the EU guideline governing low voltage and electromagnetic compatibility.
installation and operation manual
2016-08-26 9
3. Product information
3.1 Overview
Autarco MX-series grid tied inverters are state of the art, high efficiency, robust and reliable grid tied inverters at the best price quality ratio available. They are easy to install and carry a standard 10 year product warranty. Our rigorous quality control and testing facilities guarantee Autarco inverters meet the highest quality standards possible. These inverters are the key to our international track record of delivering extremely reliable solar power solutions.
Key features:
Maximum efficiency of 97.6% Wide MPPT voltage range Low turn off voltage High enclosure protection class IP65
Silent design using convection cooling
principle
Standard ten year product warranty Compatible with WiFi, GPRS, 3G, Smart Home
and LAN cable
Optional integrated DC switch
For full specifications please see chapter 11 “Product specifications”.
3.2 Product identification
You can identify the inverter by the serial number (S/N) sticker on the side of the inverter. Important electrical specification can also be found on the label on the right side of the inverter housing. Do not remove the label or the serial number as this voids the product warranty.
10 MX-series Inverters
3.3 Product overview
A: Inverter cover B: LED light – POWER C: LED light – OPERATION D: LED light – ALARM E: LCD display 2x16 characters F: Escape key G: Up key H: Down key I: Enter key J: DC input MPPT 1 K: DC input MPPT 2 (optional) L: DC switch (optional) M: Communication port N: AC output
A
B C D E F G H I J K L M N
installation and operation manual
2016-08-26 11
4. Installation
4.1 Safety
DANGER! Do not install the inverter near flammable or explosive items.
WARNING! The installation must be performed by qualified personnel and in compliance with national and local standards and regulations. This inverter will be connected to a high voltage DC power generator and AC grid. Inappropriate installation may jeopardize the life span of the inverter.
The installation site must have good ventilation conditions. Direct exposure to intense sunshine is not recommended.
4.2 Mounting instructions
The inverter is suitable for outdoor and indoor installation. Vertical installation is recommended, with a maximum inclination of 15° backwards. Make sure the mounting wall is strong enough to hold the weight of the inverter. The ambient temperature of installation site should be between -20 °C and +60 °C. It is not recommended that the inverter is exposed to the direct sunshine. Make sure of ample ventilation at installation site, insufficient ventilation may reduce the performance
of the electronic components inside the inverter and shorten the life span of the inverter.
Max. 15°
12 MX-series Inverters
4.3 Safety clearance
Caution! Make sure heat sinks are out of reach of children.
Observe the following minimum clearances to walls:
Min. 100mm
Min. 100mm
Min. 300mm
Min. 300mm
installation and operation manual
2016-08-26 13
4.4 Mounting procedure
Step 1 Mount the wall bracket onto the mounting wall with appropriate screws plugs Step 2 Lower the inverter onto the bracket
290 ± 2 mm
104 ± 2 mm
14 MX-series Inverters
5. Electrical installation
DANGER! This inverter will be connected to a high voltage DC power generator and AC grid. The installation must be performed by qualified personnel and in compliance with national and local standards and regulations
5.1 AC connection
DANGER! Never connect or disconnect the connectors under load.
NOTICE! The AC connection to the electrical distribution grid must be performed only after receiving authorization from the utility that operates the grid.
The Autarco inverter is equipped with an integrated Residual Current Protective Device (RCPD) and Residual Current Operated Monitor (RCOM). The RCOM will detect the volume of the leakage current and compare it with the expected value, if the leakage current exceeds the permitted range, the RCPD will disconnect the inverter from the AC load.
If regulations in the country of installation stipulate an external Residual Current Device (RCD), you must use a device with a tripping threshold of 100 mA or more. A type “A” RCD can be used in accordance with our
Manufacturer’s declaration for usage of residual current devices with Autarco SX, MX and LX grid-tied inverters.
The AC cable used must be dimensioned in accordance with any local and national directives on cable dimensions which specify requirements for the minimum conductor cross-section. Cable dimensioning factors are e.g.: nominal AC current, type of cable, type of routing, cable bundling, ambient temperature and maximum specified line losses.
We recommend 4mm 105 cable with resistance lower than 1.5 ohm.
Cable gland cap
Cable gland body
Connector
installation and operation manual
2016-08-26 15
Step 1 Slide the cable gland cap, cable gland body and adapter to the cable.
Step 2 Strip outer jacket 60mm and strip each cable insulation about 12±1mm.
Step 3 Insert cable strands into connector socket, and lock the screws. Make sure to fit the ground wire
into the PE hole.
Step 4 Fit the connector, cable gland body and cable gland cap to the connector as per below.
16 MX-series Inverters
NOTICE! It is important that the AC wires are connected to the right terminals as indicated by the “L”, “N” and “Earthing” symbols on each AC connector. In some countries a second protective conductor is required as a matter of principle. In each case, observe the applicable regulations for the site.
Always use separate fuses for consumer load. Use dedicated circuit breakers with load switch functionality for load switching.
The selection of the mains circuit breaker rating depends on the wiring design (wire cross- section area), cable type, wiring method, ambient temperature, inverter current rating etc. Derating of the circuit breaker rating may be necessary due to self-heating or if exposed to heat.
MX3000(S)
MX3600(S)
MX4600(S)
Max. AC current (A)
15.7
16
23.8
Recommended fuse type gL/gG
or comparable automatic
circuit breaker rating (A)
25
25
32
DANGER! No consumer load should be applied between the mains circuit breaker and the inverter.
installation and operation manual
2016-08-26 17
5.2 DC connections
DANGER! Never connect or disconnect the connectors under load.
MX-series inverters have two MPP trackers. The DC characteristics of each model is shown in the table below:
Inverter
MPP tracker
Max DC power
Max DC voltage
Max. DC current per MPPT
MX3000(S)
2
3500W
600W
10A
MX3600(S)
4200W
MX4600(S)
5300W
15A
DANGER! Do not connect strings with an open circuit voltage greater than the max DC voltage of the inverter.
Use 4mm² or 6mm² PV cable and MC4 connectors to connect the PV generator to the inverters.
DANGER! For protection against electric shock, MC4 connectors must be isolated from the PV array while being assembled or disassembled.
DC connections must not be unplugged while under load. They can be placed in a no-load state by switching off the inverter or breaking the DC circuit interrupter. Plugging and unplugging while under voltage is permitted.
CAUTION! MC4 connectors are watertight IP67 but cannot be used permanently under water. Do not lay the MC4 connectors on the roof surface.
CAUTION! If any tools or parts are used in the MC4 connector assembly other than those listed in the MC4 connector manual, neither safety nor compliance with the technical data can be guaranteed.
CAUTION! Every string connected to a MPPT must be identical, i.e. share the module type, module quantity, azimuth and pitch.
18 MX-series Inverters
5.3 Inverter commissioning sequence
Turn ON
Turn OFF
1. Connect AC side (if not connected yet)
2. Connect DC side (if not connected yet)
3. Switch ON the DC switch
4. Switch ON the AC switch
1. Switch OFF the DC switch
2. Switch OFF the AC switch
6. Operation
6.1 LED indicator lights
There are three LED status indicator lights in the front panel of MX series inverters. The left POWER light (red) indicates power status of the inverter. The middle OPERATION light (green) indicates the operation status. The right ALARM light (yellow) indicates the alarm status. Table 3.1 explains their meanings.
Light
Status
Description
POWER (red)
ON
The PV array provides power to the inverter
OFF
The PV array does not provide power to the inverter
OPERATION (green)
ON
The inverter is feeding AC power to the grid
OFF
The inverter is not feeding AC power to the grid
FLASHING
The inverter is initializing
ALARM (yellow)
ON
There is a fault. Refer to the inverter display and chapter 10 of this manual for details
OFF
The inverter is operation normally
When inverter DC switch and AC switch have been turned on the inverter will start initializing. After approx. 3 minutes the inverter will start normal operation with the inverter display showing GENERATING.
6.2 Inverter display
NOTICE! During normal operation, make sure the optional integrated DC switch is switched “on”.
The display content consists of 2 lines. During regular operation the display shows the current power and operation status alternatively for 10 seconds. Pressing the UP or DOWN buttons will manually cycle through these two displays. Pressing the ENTER button gives access to the main menu which has four sub menus:
Information, described in detail in chapter 6.3. Settings, described in detail in chapter 6.4. Advanced information, described in detail in chapter 6.5. Advanced settings, described in details in chapter 6.6.
By pressing UP or DOWN keys you can cycle through these sub menus and click ENTER to go into the submenu.
installation and operation manual
2016-08-26 19
6.3 Information
The MX series inverters main menu provides access to operational data and information. The information is displayed by selecting "Information" from the main menu. By default the inverter display will scroll through the information states below. Pressing the ENTER key will lock or unlock the current display. You can also press UP or DOWN keys to manually scroll through. By pressing the ESC key returns to the main menu.
State
Description
V_DC1 %VALUE% I_DC1 %VALUE% A
Shows the input voltage (V) of the MPPT1 Shows the input current (A) of the MPPT1
V_DC2 %VALUE% I_DC2 %VALUE% A
Shows the input voltage (V) of the MPPT2 Shows the input current (A) of the MPPT2
V_AC %VALUE% I_AC %VALUE% A
Shows the voltage (V) of the grid Shows the current (A) of the grid
Status: %VALUE% Power: %VALUE% W
Shows the status of the inverter Shows current output power (W) of the inverter
For any status other than “Generating” and “Initializing” please refer to
chapter 10 for troubleshooting
Grid frequency F_Grid %VALUE% Hz
Shows current frequency (Hz) of the grid
Total Energy %VALUE% kWh
Shows total energy output (kWh)
This Month: %VALUE% kWh Last Month: %VALUE% kWh
Total energy output in this month (kWh) Total energy output of last month (kWh)
This day: %VALUE% kWh Last day: %VALUE% kWh
Total energy output in this day (kWh) Total energy output of yesterday (kWh)
6.4 Settings
The following options are available under the Settings submenu:
Set Time and Date
Press UP/DOWN keys to set change element Press ENTER key to move to next element Press ESC key to save date and return
Set Address
Assign a number (##) to the inverter to distinguish between multiple inverters on a single monitoring device. Not necessary for installations of single inverters.
Press UP/DOWN keys to set change number Press ENTER key to save the setting Press ESC key to return
Restore Settings
Delete alarm messages that have been generated
20 MX-series Inverters
6.5 Advanced info
WARNING! Access to this section of the menu is for Autarco qualified and accredited technicians only. Unauthorized access will void the product and system warranty.
The default password is “0010". Press “DOWN” to move the cursor, press “UP” to select the number. After you
enter the correct password, you will be able to access the information as shown in the table below. Press the UP/DOWN keys to scroll through the information. Press ENTER key to enter a submenu. Press ESC key to go back to the main menu.
Alarm Messages
Scroll through the last ten alarm messages for trouble shooting purposes.
Press UP/DOWN keys to cycle through alarm messages Press ESC key to return
Temperature
The screen shows the temperature of the inverter in degrees Celcius.
Standard NO.
The screen shows the current grid standard
Version
The screen shows the operating software version of the inverter
Communication data
The screen shows information interpretable to qualified technicians only
6.6 Advanced Settings
WARNING! Access to this section of the menu is for Autarco qualified and accredited technicians only. Unauthorized access will void the product and system warranty.
Refer to 6.5 for the password to access this menu.
Select grid standard
WARNING! Set GRID OFF (see below) before changing this setting.
Press UP/DOWN keys to cycle through available standards
AS4777 VDE0126 UL1741 G83 User defined
Press ENTER key to save the setting Press ESC key to cancel and return
When selecting User defined the following upper and lower values have to be set for voltage and frequency: OV-V: 240-270V UV-V: 180-210V
installation and operation manual
2016-08-26 21
OV-G-F: 50.3-52.0Hz (60.3-62.0Hz) UV-G-F: 47.0-49.5Hz (57.0-59.5Hz) Press UP/DOWN keys to scroll through these values Presss ENTER key to edit the selected value Press UP/DOWN keys to change the selected value Presss ENTER key to save and return Press ESC key to cancel and return
WARNING! Set GRID ON (see below) before new standard is activated.
WARNING! Please note that the User-Def standard is not to be used without the agreement of the local grid authority.
Grid ON/OFF
Press UP/DOWN keys to cycle through grid ON/OFF options Press ENTER key to save Press ESC key to return
Clear Energy
Reset the inverters total kWh output to zero.
New Password
Change the password to enter Advanced Info and Advanced Settings.
7. Monitoring setup and system registration
The instructions about monitoring setup and system registration can be found in separate manuals enclosed in the documentation that came with this Autarco system. For more information, please contact your Autarco installer or refer to the downloads page of our website www.autarco.com.
8. Maintenance
The MX-series inverters do not require regular maintenance. However, impurities such as dust and dirt
accumulation on the heat sink may negatively affect the inverter’s ability to dissipate heat. Any dirt or dust can
be removed with a cloth or soft brush.
CAUTION! Do not touch the heat sink when the inverter is in operation. Turn OFF the inverter (see section 0) and allow for cooling down before cleaning.
CAUTION! Never use any solvents, abrasives or corrosive materials to clean the inverter.
22 MX-series Inverters
9. Disposal
To comply with European Directive 2002/96/EC on waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility. Ignoring this EU Directive may have severe effects on the environment and your health.
10. Troubleshooting
10.1 General
Display
message
Action
Blank screen
Check that all switches are in the ON position (including internal DC switch if present) Check AC and DC power supply. If DC power is greater than 10W and string voltage
greater than 100V the inverter should start.
If switches are on and AC and DC power supplies are available please contact installer.
10.2 Internal component fault
Error type
Display
message
Error code
Error
description
Action
Over BUS DC voltage
OV-BUS
1021
Internal fault
1. Restart inverter (up to three times).
2. If error persists contact installer for
replacement inverter.
Under BUS DC voltage
UN_BUS
1012
Internal fault
BUS pressure fault
UNB2_BUS
1024
Internal fault
System initial fault
INI-PRO
1031
Internal fault
Relay fault
Relay_PRO
1035
Internal fault
DSP_B fault
DSP_B_PRO
1036
Internal fault
DC injection
DCInj_PRO
1037
Internal fault
12V under voltage fault
12Power_PRO
1038
Internal fault
installation and operation manual
2016-08-26 23
Error type
Display
message
Error
code
Error description Action
Over
voltage
OV-G-V
1010
Grid voltage exceeds the
standard set in the inverter
1. Wait to see if the grid voltage returns within limits.
2. If problem persists, check whether the grid standard is set correctly in Advanced
Settings (see 6.6).
3. Check V_AC, grid voltage, in Information display of inverter (see 6.3) and
perform independent measurement of grid voltage to confirm that the inverter
reading is correct. If the measured voltage is outside the local grid standard
limits, please contact your local utility as it may require monitoring and
adjustment
4. With agreement from utility it is possible to set a user defined voltage range (see
6.6).
Under
voltage
UN-G-V
1011
Grid voltage is below the
standard set in the inverter
Over
frequency
OV-G-F
1012
Grid frequency exceeds the
standard set in the inverter.
1. Wait to see if the grid frequency returns within limits.
2. If a problem persists, check whether the grid standard is set correct in Advanced
Settings (see 6.6).
3. Check grid frequency, in Information display of inverter (see 6.3) and perform
independent measurement of grid frequency to confirm that the inverter
reading is correct. If the measured frequency is outside the local grid standard
limits, please contact your local utility as it may require monitoring and
adjustment.
4. With agreement from utility it is possible to set a user defined frequency range
(see 6.6).
Under
frequency
UN-G-V
1013
Grid frequency is below the
standard set in the inverter.
Grid
impedance
G-IMP
1014
High grid impedance
1. Wait to see if the grid returns within limits.
2. If problem persists please contact your local utility as it may require monitoring
and adjustment.
No Grid NO Grid
1015
The inverter cannot detect a
grid.
1. Check your AC power connections and switches.
2. Restart the inverter.
3. Call your local grid to resolve the black out.
10.3 Grid errors
24 MX-series Inverters
Error type
Display
message
Error
code
Error description Action
Over DC
voltage
OV-DC
1020
The DC input of the solar
strings exceeds the
inverters limits.
1. Restart inverter (up to three times).
2. Contact installer to:
a. Perform independent measurement of string voltage to confirm that the
inverter reading is correct.
3. Rewire strings so that string voltage is within accepted range.
Over
temperature
TEM-PRO
1032
The internal
temperature of inverter
exceeds limits.
1. Check location of inverter. Ensure it has adequate ventilation and is not
exposed to direct sunlight.
2. Contact your installer to replace inverter if problem persists.
Short circuit
fault
SHORT-PRO
1030
A short circuit has been
detected in the system.
1. Restart inverter (up to three times).
2. Call installer to:
a. Check for pinched, crimped or otherwise damaged cables and
connections.
b. Check all switches for short circuit.
3. If error persists contact your installer for a replacement inverter.
Ground fault
GROUND-PRO
1033
Current flow detected
through ground
conductor.
1. Restart inverter (up to three times).
2. Call installer to:
a. Check if there is any current on the ground conductor using a clamp
meter.
b. Check for pinched, crimped or otherwise damaged cables and
connections.
3. If error persists contact your installer for a replacement inverter.
Current
leakage
ILeak_PRO
1034
A current leak has been
detected.
1. Restart inverter (up to three times).
2. Call installer to:
a. Check if there is any current on the ground conductor using a clamp
meter.
b. Check for pinched, crimped or otherwise damaged cables and
connections.
3. If error persists contact your installer for a replacement inverter.
10.4 System and design fault
installation and operation manual
2016-08-26 25
11. Product specifications
MX2500(S)
MX3000(S)
MX3600(S)
MX4600(S)
Input
Max. DC voltage (V)
600
MPPT voltage range (V)
100-500
Turn on voltage (V)
120
Turn off voltage (V)
120
Number of MPP trackers
2
Max. DC current per MPPT (A)
10
15
Number of DC connections per MPPT
1
Total number of strings
2
DC connection type
MC4
Output
Nominal AC power (W)
2500
3000
3600
4600
Max. AC power (W)
2800
3300
4000
5000
Nominal AC current (A)
10.9
13
15.7
20
Max. AC current (A)
13.3
15.7
16
23.8
Power connection
Single phase
Grid voltage range
According to VDE 0126-1-1, UL1741, G83/2, AS4777
Grid frequency range
According to VDE 0126-1-1, UL1741, G83/2, AS4777
Power factor
>0.99
Harmonic distortion at nominal output
<3%
AC connector
Plug in connector
Overvoltage category
OVC III (MAINS), OVC II (PV)
Power consumption
Nighttime power consumption (W)
< 1
Standby power consumption (W)
6
Efficiencies
Max. efficiency
97.5%
97.8%
Euro efficiency
96.8%
97.0%
MPPT efficiency
>99%
26 MX-series Inverters
MX2500(S)
MX3000(S)
MX3600(S)
MX4600(S)
Safety protection
Internal overvoltage protection
Yes
DC Insulation monitoring
Yes
Earth fault protection
Yes
Grid monitoring
According to VDE 0126-1-1, UL1741, G83/2, AS4777
Earth fault current monitoring
According to VDE 0126-1-1, UL1741, G83/2, AS4777
DC current monitoring
According to VDE 0126-1-1, UL1741, G83/2, AS4777
Islanding protection
According to VDE 0126-1-1, UL1741, G83/2, AS4777
CE- compliant
According to EN 62109, EN 61000-6-1, EN 61000-6-3, EN 61000-6-2, EN
61000-6-4, EN61000-3-2, EN61000-3-3, EN61000-3-12, EN61000-3-11
General data
Dimensions (W x H x D) (mm)
339 x 565 x 172.5
Weight
12kg
13.8kg
15.8kg
Installation environment
Indoor or outdoor
Mounting
Wall bracket
Operating temperature range (°C)
-25 to 60
Max. relative humidity
100% (without condensation)
Maximum altitude
4000m
IP protection rating
IP65 according to EN60529
Isolation type
Transformerless
Cooling concept
Convection
Noise level (dB)
< 30
LED indicators
3
LCD display
16 x 2 character
Communication interfaces
RS485
Optional interfaces
Wi-Fi 802.11, RS232, RJ45, GPRS
Standard warranty
5-10 years
Integrated DC switch
Optional