A.1. EC declaration of conformity 3
A.2. General instructions 3
A.3. Explanation of symbols 3
A.4. Changes to the unit 4
A.5. Warranty and liability 4
B. Description of controller 5
B.1. Specications 5
B.2. Temperature resistance table
for Pt100 0 sensors 5
B.3. About the controller 6
B.4. Scope of supply 6
B.5. Disposal and pollutants 6
B.6. Hydraulic variants 7
C. Installation 8
C.1. Wall installation 8
C.2. Electrical connection 9
C.3. Electrical connection 10
C.4. Installing the temperature sensors 11
D. Terminal connect ion diagrams 12
E. Operation 13
E.1. Display and input 13
E.2. Menu sequence and menu structure 14
Conformity has been veried and the corresponding documentation and the EC declaration
of conformity are kept on le by the manufacturer.
A.2. - General instructions
It is essential that you read this!
These installation and operating instructions contain basic instructions and important information regarding safety, installation, commissioning, maintenance and the optimal use of the
unit. Therefore these instructions must be read completely and understood by the installation
technician/ specialist and by the system user before installation, commissioning and operation of the unit.The valid accident prevention regulations, VDE regulations, the regulations
of the local power utility, the applicable DIN-EN standards and the installation and operating
instruction of the additional system components must also be observed. The controller does
not under any circumstances replace any safety devices to be provided by the customer!
Installation, electrical connection, commissioning and maintenance of the unit may only be
carried out by specialists who possess the appropriate training.
For the user: Make sure that the specialist gives you detailed information on the function and
operation of the controller. Always keep these instructions in the vicinity of the controller.
A.3. - Explanation of symbols
Failure to observe these instructions can result in danger to life from electric
Danger
voltage.
Failure to observe these instructions can result in serious damage
Danger
to health such as scalding, or even life-threatening injuries.
Failure to observe these instructions can result in destruction of
Caution
the unit or the system, or damage to the environment.
Information which is especially important for the function and optimal use of
Caution
the unit and the system.
3
Safety instructions
A.4. - Changes to the unit
Changes to the unit can compromise the safety and function of the unit or the entire
Danger
- Changes, additions to or conversion of the unit are not permitted without the written permission from the manufacturer
- It is likewise forbidden to install additional components that have not been tested together
with the unit
- If it becomes clear that safe operation of the unit is no longer possible, for example because
of damage to the housing, then turn the controller off immediately
- Any parts of the unit or accessories that are not in perfect condition must be exchanged
immediately
- Use only original spare parts and accessories from the manufacturer.
- Markings made on the unit at the factory must not be altered, removed or made illegible
- Only the settings actually described in these instructions may be made on the controller
A.5. - Warranty and liability
The controller has been manufactured and tested with regard to high quality
and safety requirements. The unit is subject to the statutory guarantee period
of two years from the date of sale.
The warranty and liability shall not include, however, any injury to persons or
material damage that is attributable to one or more of the following causes:
- Failure to observe these installation and operating instructions
- Improper installation, commissioning, maintenance and operation
- Improperly executed repairs
- Unauthorised structural changes to the unit
- Installation of additional components that have not been tested together with the unit
- Any damage resulting from continued use of the unit despite an obvious defect
- Failure to use original spare parts and accessories
- Use of the device for other than its intended purpose
- Operation above or below the limit values listed in the specications
- Force majeure
system.
4
Description of controller
B.1. - Specications
Electrical specications:
Mains voltage 100 - 240VAC
Mains frequency 50 - 60Hz
Power consumption 0,5W - 2,5W
Internal fuse T2 A / 250V slow blow
Protection category IP40
Protection class II
Overvoltage Category II
Degree of Pollution Category II
mechanical relay 460VA for AC1 / 46 0W for AC33 (R1- R3)
0-10V outp ut, tolerance 10%, 10 k Ω loa d or
PWM out put freq. 1 kHz, level 10 V
PT1000 se nsor input measurin g range - 40°C to 30 0°C6
VFS / RPS in puts
0°C -100°C (-25°C /120 °C short t erm)
1 l/m in - 12 l/min (V FS1-12)
1 l/m in - 20 l/min ( VFS1- 20)
2 l/m in - 40 l/min ( VFS2- 40)
5 l/m in - 100 l/min ( VFS5 -100)
10 l/m in - 200 l/min (VFS10- 200)
Permissible cable length of sensors and appliances:
other PT1000 sensors <10m
VFS/RPS Sensoren <3m
CAN <3m
PWM / 0...10V <3m
mechanichal relay <10m
Real Tim e ClockRTC with 24 hour power reserve
Permissible ambient conditions:
Ambient temperature
for controller operation 0°C...40°C
for transport/storage 0°C...60°C
Air humidity
for controller operation max. 85% rel. humidity at 25°C
for transport/storage no moisture condensation permiddled
Other specications and dimensions
Housing design 2-part, ABS plastic
Installation methods Wall installation, optionally panel installation
Overall dimensions 163mm x 110mm x 52mm
Aperture installation
dimensions 157mm x 106mm x 31mm
Display Fully graphical display, 128 x 128 dots
Light diode Multicolor red/green
Operation 4 entry keys
0-0,6 bar
0-1 bar
0-1,6 bar
0-2,5 bar
0- 4 bar
0- 6 bar
0-10 bar
2
2
B.2. - Temperature resistance table for Pt1000 sensors
The Fresh water controller ECO SWIFT facilitates efcient use and function control through
of your fresh water system. Tap water temperature is regulated fast and precise. The device
is impressive most of all for its functionality and simple, almost self-explanatory operation.
For each step in the input process the individual entry keys are assigned to appropriate functions and explained. The controller menu contains headwords for the measured values and
settings, as well as help texts or clearly-structured graphics.
Important characteristics of the ECO SWIFT:
- Depiction of graphics and texts in a lighted display
- Simple viewing of the current measurement values
- Analysis and monitoring of the system by means of statistical graphics,etc.
- Extensive setting menus with explanations
- Menu block can be activated to prevent unintentional setting changes
- Resetting to previously selected values or factory settings
B.4. - Scope of supply:
- Fresh water controller ECO SWIFT
- replacement fuse 2A slow-blow
- Installation and operating instructions ECO SWIFT
Optionally contained depending on design/order:
- Pt1000 temperature sensor and Vortex Flow Sensor
B.5. - Disposal and pollutants
The unit conforms to the European RoHS directive 2011/65/EU for the restriction of the use
of certain hazardous substances in electrical and electronic equipment.
The unit must not under any circumstances be disposed of with ordinary
Caution
6
household refuse. Dispose of the unit only at appropriate collection points or ship it
back to the seller or manufacturer.
Description of controller
B.6. - Hydraulic variants
The following illustrations should be viewed only as schematic diagrams showing
the respective hydraulic systems, and do not claim to be complete. The controller
does not replace safety devices under any circumstances. Depending on the spe-
Caution
cic application, additional system components and safety components may be
mandatory, such as check valves, non-return valves, safety temperature limiters,
scalding protectors, etc., and must therefore be provided.
S3
S4
S5
VFS
S1
S2
S6
7
C.1. - Wall installation
Install the controller only in dry areas and under the ambient conditions
Caution
described under 2.1 “Specications”. Carry out the following steps 1-8.
Installation
Fig.C.1.2
A
Fig.C .1.1
1.Unscrew cover screw completely
2.Carefully pull upper part of housing
from lower part.
3.Set upper part of housing aside, being
sure not to touch the electronics when
doing so.
4.Hold the lower part of the housing up
to the selected position and mark the 3
mounting holes. Make sure that the wall
surface is as even as possible so that the
housing does not become distorted when
it is screwed on.
5.Using a drill and size 6 bit, drill 3 holes
at the points marked on the wall and push
in the plugs.
6.Insert the upper screw and screw it in
slightly.
7.Fit the upper part of the housing and
insert the other two screws.
8. Align the housing and tighten the three
screws.
8
C.2. - Electrical connection
Before working on the unit, switch off the power supply and secure it against being
switched on again! Check for the absence of power! Electrical connections may
Danger
only be made by a specialist and in compliance with the applicable regulations. Do
not use the controller if the housing shows visible damage.
Low-voltage cables such as temperature sensor cables must be routed separately
from mains voltage cables. Feed temperature sensor cables only into the left-hand
Caution
side of the unit, and mains voltage cables only into the right-hand side.
The customer must provide an all-pole disconnecting device, e.g. a heating emer-
Caution
gency switch.
The cables being connected to the unit must not be stripped by more than 55mm,
Caution
and the cable jacket must reach into the housing just to the other side of the strain
relief.
Controller and VFS sensor have to have the same ground potential. The VFS
Caution
sensor uses a functional earth connector (PELV). The PE-connector of the
controller has to be connected to the pipe system near the sensor.
Installation
9
C.3. - Electrical connection
C.3.1.
C.3.2.
Installation
1. Select necessary program/ hydraulics
2. Open controller
3. Strip cables by 55mm max., insert, t the
strain relief devices, strip the last 8-9mm
of the wires. (Fig. C.3.1)
4. Open the terminals using a suitable
screwdriver (Fig. C.3.2) and make electrical
connections on the controller
5. Connect the ow sensor to the socket
on the board (Fig. C.2.3.).
6. Ret upper part of housing and fasten
with screw.
7. Switch on mains voltage and place controller in operation.
C.3.3.
10
Installation
C.4. - Installing the temperature sensors
The controller operates with Pt1000 temperature sensors which are accurate to the
degree, thus ensuring optimal control of system functions.
Position the sensor precisely in the area to be measured!
It is recommended that at least 20 cm of the sensor cable at the sensor are installed inside the
pipe insulation.
Connect the VFS sensors with the matching jacks.
Sensor cables for PT1000 can be extended to a maximum of 10m using a
cable with a cross-section of at least 0.75mm².
Caution
Caution
Caution
Sensor cables for the VFS sensor can be extended to 3m.
Make sure that there is no contact resistance!
The temperature sensor cables must be routed separately from mains voltage
cables, and must not, for example, be routed in the same cable duct!
Controller and VFS sensor have to have the same ground potential. The VFS
sensor uses a functional earth connector (PELV). The PE-connector of the
controller has to be connected to the pipe system near the sensor.
Example:
Connections and dimensions of the Vortex Flow Sensors VFS2-40
3/4 “
10,7 cm
1 “
11
Installation
S6V1V2
+
S5
S4 S3 S2S1
-
PELV
R3I
R3R2 R1LN
VFS2VFS1CAN CAN
D. - Terminal connection diagrams
D.1. - „With circulation pump“
Sensor side
max. 12V
Caution
Low voltage max. 12VAC/DC connection in
the left-hand terminal compartment!
Terminal: Connection for:
S1 Circulation (opt.)
S2 Cold water (optional, see box below)
S3 Primary ow (opt.)
S4 Storage top (opt.)
S5 storage middle (opt.)
V1 0-10V/PWM signal primary pump
V2 0-10V/PWM signal (opt.)
S6 Primary return ow (opt.)
- Terminal connection sensor VFS1 Warm water tap
Mains voltages 230VAC 50-60Hz
Connection in the right-hand terminal
compartment!
Terminal: Connection for:
L Mains phase conductor L
N Mains neutral conductor N
R1 Primary pump (opt.)
R2 Relay 2
R3 Relay 3 (normally open)
R3I Relay 3 (normally closed)
The PE protective conductor must be
connected to the PE metal terminal block!
Mains side
230VAC
Danger
VFS2 optional
The polarity of the sensors is freely selectable.
Relay connection changes depending on the additional functions selected.
Connection of sensor earths (1-6) via terminal block sensor(-)
VFS sensor has to be connected to the socket on the circuit board.
Sensor 2 / Cold water: If no sensor is connected, a temperature of 10° C is set. See also „6.2
Sensor calibration“
12
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.