First English printing, October 2002
Information in this document has been carefully checked for accuracy; however, no guarantee is given to the correctness
of the contents. The information in this document is subject to change without notice. We are not liable for any injury or
loss that results from the use of this equipment.
Safety Instructions
Please read all of these instructions carefully before you use the device. Save this manual for
future reference.
■ Unplug equipment before cleaning. Don’t use liquid or spray detergent; use a moist cloth.
■ Keep equipment away from excessive humidity and heat. Preferably, keep it in an air-conditioned environment with
temperatures not exceeding 40º Celsius (104º Fahrenheit).
■ When installing, place the equipment on a sturdy, level surface to prevent it from accidentally falling and causing
damage to other equipment or injury to persons nearby.
■ When the equipment is in an open position, do not cover, block or in any way obstruct the gap between it and the
power supply. Proper air convection is necessary to keep it from overheating.
■ Arrange the equipment’s power cord in such a way that others won’t trip or fall over it.
■ If you are using a power cord that didn’t ship with the equipment, ensure that it is rated for the voltage and current
labeled on the equipment’s electrical ratings label. The voltage rating on the cord should be higher than the one listed
on the equipment’s ratings label.
■ Observe all precautions and warnings attached to the equipment.
■ If you don’t intend on using the equipment for a long time, disconnect it from the power outlet to prevent being
damaged by transient over-voltage.
■ Keep all liquids away from the equipment to minimize the risk of accidental spillage. Liquid spilled on to the power
supply or on other hardware may cause damage, fi re or electrical shock.
■ Only qualifi ed service personnel should open the chassis. Opening it yourself could damage the equipment and
invalidate its warranty.
■ If any part of the equipment becomes damaged or stops functioning, have it checked by qualifi ed service personnel.
What the warranty does not cover
■ Any product, on which the serial number has been defaced, modifi ed or removed.
■ Damage, deterioration or malfunction resulting from:
□ Accident, misuse, neglect, fi re, water, lightning, or other acts of nature, unauthorized product modifi cation, or failure to follow instructions supplied with the product.
□ Repair or attempted repair by anyone not authorized by us.
□ Any damage of the product due to shipment.
□ Removal or installation of the product.
□ Causes external to the product, such as electric power fl uctuation or failure.□ Use of supplies or parts not meeting our specifi cations.□ Normal wear and tear.
□ Any other causes which does not relate to a product defect.
■ Removal, installation, and set-up service charges.
Regulatory Notices Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of
the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation.
Any changes or modifi cations made to this equipment may void the user’s authority to operate this equipment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
■ Re-position or relocate the receiving antenna.
■ Increase the separation between the equipment and receiver.
■ Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
www.austin-hughes.comUM-ICM-02-Q215V1
Unpacking
The equipment comes with the standard parts shown on the package contents. Check and make sure they are included and in good
condition. If anything is missing, or damage, contact the supplier immediately.
www.austin-hughes.comUM-ICM-02-Q215V1
Content
Part I. Installation
< 1.1 > 1U Fan Tray
< 1.2 > 33U Door Mount Fan Panel
Part II. Hardware
< 2.1 > Key Features
< 2.2 > Fan Kit Specifi cation
< 2.3 > Master IP Fan Unit Model & Specifi cation
MRF-1.3 ( 1U Fan Tray with 3 fans )
MRF-1.6 ( 1U Fan Tray with 6 fans )
MRF-1.9 ( 1U Fan Tray with 9 fans )
P. 1
P. 6
MRF-33.9 ( 33U Door Mount Fan Panel with 9 fans )
Specifi cation Table
< 2.4 > Remote Fan Unit Model & Specifi cation
RF-1.3 ( 1U Fan Tray with 3 fans )
RF-1.6 ( 1U Fan Tray with 6 fans )
RF-1.9 ( 1U Fan Tray with 9 fans )
RF-33.9 ( 33U Door Mount Fan Panel with 9 fans )
Specifi cation Table
< 2.5 > Daisy Chain Connection
< 2.6 > Audio Temperature Alarm Setting
< 2.7 > Temperature Sensor
< 2.8 > Alarm Temperature Setting
< 2.9 > Fan Unit CFM Setting
www.austin-hughes.comUM-ICM-02-Q215V1
Part III. Software
< 3.1 > Key Features
< 3.2 > Master IP Confi guration
< 3.3 > Hardware Requirements of the Management PC
< 3.4 > Supported OS Platform & Language
< 3.5 > Software Download
< 3.6 > First Time Start-up Setting
< 3.7 > Change Port no. of Web Server
P.23
Part IV. System Setup & Remote Access
< 4.1 > System Setup
< 4.2 > Remote Access
Part V. Software Usage & Operation
Part VI. Events / Log / Report
Part VII. SNMP
P.29
P.36
P.39
P.42
Part VIII. FAQ
Part IX. Troubleshooting
P.44
P.46
www.austin-hughes.comUM-ICM-02-Q215V1
< Part I > Installation
< 1.1 > 1U Fan Tray
Package Content
- 1U rackmount fan tray x 1 pc
- Temp. sensor x 1 pc
- 6 ft power cord x 1 pc
- Rear mounting bracket x 1 pair
* Bracket for MRF-1.6 / 9 & RF-1.6 / 9 only
* M6 screws for fi xing are not included
Installation
MRF-1.3 / RF-1.3
MRF-1.6 / RF-1.6
Rear mounting
brackets
M6 screws
M6 screws
MRF-1.9 / RF-1.9
Rear mounting
brackets
M6 screws
www.austin-hughes.comUM-ICM-02-Q215V1P.1
< 1.2 > 33U Door Mount Fan Panel
MRF-33.9 & RF-33.9 Door mount Fan Panel are typically installed on the outside of a cabinet’s rear perforated
door to improve extraction of heat from high density cabinet.
The unit can be attached to most 42U or taller cabinets. If aisle is relatively narrow for exterior mounting, the
unit may be installed on the inside of the perforated door. For details, please refer to the model table below :
Front Door
Cool Air In
ModelInstallationAirfl owPurpose
MRF-33.9A
RF-33.9A
MRF-33.9B
RF-33.9B
Rear door outsideExtract airfl owExhaust air out from cabinet
Front door insideIntake airfl owCool air in from aisle
Front door outsideIntake airfl owCool air in from aisle
Rear door insideExtract airfl owExhaust air out from cabinet
Rear Door
Hot Air Out
Package Content
- 33U door mount fan panel x 1 pc
- Temp. sensor x 1 pc
- 6 ft power cord x 1 pc
- User Manual x 1 pc
- Mounting screw x 6 pcs ( attached with the unit )
- Air blocking material x 1 pc
Optional mounting kit
Hanging bracket kit
Part no. : F-HBK
- Hanging bracket x 2 pcs
- M4*6mm screw with nut x 4 sets
- M4*10mm screw x 2 pcs
* For installation, please
refer to p.5
www.austin-hughes.comUM-ICM-02-Q215V1P.2
< 1.2 > 33U Door Mount Fan Panel
Caution - Power off the fans if the door is to be opened for maintenence or service of
items within the cabinet. The fans have fi nger guards but care must be excerised when working
around spinning fans. Keep hair, fi ngers and other small objects away from the spinning blades.
www.austin-hughes.comUM-ICM-02-Q215V1P.3
< 1.2 > 33U Door Mount Fan Panel
Installation steps
The weight of the unit is less than 5.5 kg, so in most cases, holes in perforated cabinet doors can be used to mount the unit.
Lift the unit to the desired position.
1
Place attached 6 screws then through the door and tighten them.
2
To eliminate bypass air to maximize heat removal from the cabinet, cut the air blocking material to the size necessary with cutter or
3
scissors then apply the material to the inside surface of the door with screws or adhesive backing. Ensure all open perforations are
covered by the material.
Connect the power cord to the PDU of the cabinet through the cable entry hole on the rear top of the cabinet.
4
If no cable entry on the top, the unit may be installed on the inside but the model need to be changed. Please refer to P.2 .
5
Use cable clip to hold the
power cord if necessary
Mounting
screws
Power
cord
Cable
clip
ON / OFF
Button
Perforated
Cabinet Door
www.austin-hughes.comUM-ICM-02-Q215V1P.4
< 1.2 > 33U Door Mount Fan Panel
Hanging bracket installation
Assemble & adjust the hanging bracket with M4*6mm screw & nut, to fi t the thickness of the door.
1
Install the hanging bracket kit on the rear side of the fan panel with M4*10mm screw.
2
Hang the unit on the door.
3
Place attached 4 screws then through the door and tighten them.
4
Follow steps - on P.4 .
5
35
Cable
clip
Power
cord
Hanging bracket with
M4*6mm screw & nut
M4*10mm
screws
ON / OFF
Button
Mounting
screws
Perforated
Cabinet Door
www.austin-hughes.comUM-ICM-02-Q215V1P.5
< Part II > Hardware
< 2.1 > Key Features
Master IP
Fan Unit
Daisy Chain Position1st Level2nd - 16th Level
IP Port
Daisy Chain Port - LINK
Daisy Chain Port - OUT
Temp. Port
Temp. Sensor
Control Panel :
- Individual Fan On / Off
- Alarm Temp. Setting
- Unit CFM ( fan speed ) Setting
- Temperature LED
- Fan Status LED
- CFM Status LED
Remote
Fan Unit
1U Fan Tray3 / 6 / 9 fans3 / 6 / 9 fans
Door Mount Fan Panel6 / 9 fans6 / 9 fans
www.austin-hughes.comUM-ICM-02-Q215V1P.6
< 2.2 > Fan Kit Specifi cation
Fan Specifi cation
Air Delivery :
Rate Speed :
Rated Voltage :
Rated Current :
Noise Level :
Dimension :
Bearing System :
108 CFM
3000 rpm, +/-10%
12V DC
350 mA
41 dB
120 x 120 x 25 mm
Dual ball bearing
www.austin-hughes.comUM-ICM-02-Q215V1P.7
< 2.3 > Master IP Fan Unit Model
Model : MRF-1.3
1U Fan Tray with 3 fans
2
1
- Individual fan status
- Individual fan On /
Off buttons
- Unit CFM Status LED
- Unit CFM Setting
3
- Buttons for Alarm
Temp. Setting
- Temp. LED display
- DIP switch for
4
daisy chain level setting
567
TEMPI POUT
- Temp. port bundled w/ a temp. sensor
5
- IP port for remote access
6
- Only master fan unit provides an IP port
- 1 x IP port allows access to 16 levels
7
- Daisy chain port for connecting to the link
port of the 2nd level fan unit
463
43.5
www.austin-hughes.comUM-ICM-02-Q215V1P.8
< 2.3 > Master IP Fan Unit Model
Model : MRF-1.6
1U Fan Tray with 6 fans
1
- Individual fan status
- Individual fan On / Off buttons
- Unit CFM Status LED
2
- Unit CFM Setting
3
- Buttons for Alarm
Temp. Setting
- Temp. LED display
567
TEMPI POUT
- Temp. port bundled w/ a temp. sensor
5
- IP port for remote access
6
- Only master fan unit provides an IP port
- 1 x IP port allows access to 16 levels
7
- Daisy chain port for connecting to the link
port of the 2nd level fan unit
- DIP switch for
4
daisy chain level setting
463
43.5
www.austin-hughes.comUM-ICM-02-Q215V1P.9
< 2.3 > Master IP Fan Unit Model
Model : MRF-1.9
1U Fan Tray with 9 fans
1
- Individual fan status
- Individual fan On / Off buttons
- Unit CFM Status LED
2
- Unit CFM Setting
3
- Buttons for Alarm
Temp. Setting
- Temp. LED display
567
TEMPI POUT
- Temp. port bundled w/ a temp. sensor
5
- IP port for remote access
6
- Only master fan unit provides an IP port
- 1 x IP port allows access to 16 levels
7
- Daisy chain port for connecting to the link
port of the 2nd level fan unit
- DIP switch for
4
daisy chain level setting
463
43.5
www.austin-hughes.comUM-ICM-02-Q215V1P.10
< 2.3 > Master IP Fan Unit Model
Model : MRF-33.9 33U Door Mount Fan Panel with 9 fans
Front View
195 mm
Side View
42.9 mm
1466 mm
Top View
195 mm
4
TEMPI POUT
567
4
- DIP switch for daisy chain level setting
5
- Temp. port bundled w/ a temp. sensor
- IP port for remote access
6
- Only master fan unit provides an IP port
- 1 x IP port allows access to 16 levels
7
- Daisy chain port for connecting to the link
port of the 2nd level fan unit
- Individual fan status
1
- Individual fan On / Off buttons
- Unit CFM Status LED
2
- Unit CFM ( fan speed ) Setting
3
- Buttons for Alarm Temp. Setting
www.austin-hughes.comUM-ICM-02-Q215V1P.11
< 2.3 > Master IP Fan Unit Specifi cation Table
Master IP Fan
Temperature
Sensor
Power
Model
No. of Fan
Mounting1UDoor mount
CFM LevelNormal / High / Max.
Individual Fan ON / OFFYes
Individual Fan CFM108 CFM
Unit CFM ( Approximately )324 / 648 / 972 CFM972 CFM
■ Only Master IP fan unit built-in IP remote access module.
■ Master IP fan unit MUST be set on the 1st daisy chain level according to the table below.
■ For the 2nd - 16th levels ( remote fan unit models ), please make the level setting according to the table below.
■ For the cabling connection, please refer to the next page.
ON
OFF
Daisy chain level setting
Using the dip switch no. 1, 2, 3, 4, 5, 6 & 8 to setup each FAN unit level as below :
Cascaded FAN unitsDip switch no.
1234568
1st level
2nd level Remote Fan Unit ModelOffOnOnOnOnOnOff
3rd level Remote Fan Unit ModelOnOffOnOnOnOnOff
4th level Remote Fan Unit ModelOffOffOnOnOnOnOff
5th level Remote Fan Unit ModelOnOnOffOnOnOnOff
6th level Remote Fan Unit ModelOffOnOffOnOnOnOff
7th level Remote Fan Unit ModelOnOffOffOnOnOnOff
8th level Remote Fan Unit ModelOffOffOffOnOnOnOff
9th level Remote Fan Unit ModelOnOnOnOffOnOnOff
10th level Remote Fan Unit ModelOffOnOnOffOnOnOff
11th level Remote Fan Unit ModelOnOffOnOffOnOnOff
12th level Remote Fan Unit ModelOffOffOnOffOnOnOff
13th level Remote Fan Unit ModelOnOnOffOffOnOnOff
14th level Remote Fan Unit ModelOffOnOffOffOnOnOff
15th level Remote Fan Unit ModelOnOffOffOffOnOnOff
16th level Remote Fan Unit ModelOffOffOffOffOnOnOff
Master IP Fan Unit ModelOnOnOnOnOnOnOff
** No. 7 dip switch only for audio alarm setting
www.austin-hughes.comUM-ICM-02-Q215V1P.18
< 2.5 > Daisy Chain Connection
Remarks :
■ Each Master IP group supports 16 daisy chain levels.
■ The 1st level fan unit must be one of the Master IP fan unit models.
■ 1 x Master IP fan unit allows access to 16 levels.
■ For IP fan unit access, simply connect 1 x Master IP fan unit.
■ The 2nd - 16th level fan unit must be one of the Remote fan unit models.
2nd level
Remote fan unit model
1st level
Master IP fan unit model
IP
OUT
max. 20 meters
Cat5 / 6 cable
LINK
OUT
Cat5 / 6 cable
max. 20 meters
3rd level
Remote fan unit model
LINK
OUT
To Network Device
for IP Access via WAN
To LINK port of next
level Remote Fan Unit
(max level: 16)
www.austin-hughes.comUM-ICM-02-Q215V1P.19
< 2.6 > Audio Temperature Alarm Setting
Using the dip switch no. 7 to setup each FAN unit audio alarm as below :
Dip switch 7
EnableOn
DisableOff
If enable the audio alarm, the buzzer will sound when the outside temperature is over the preset
alarm temperature.
< 2.7 > Temperature Sensor
TEMP
Bundled Temp. Sensor
Part no. : IG - T01 - 2M
- Plug & Play
- External sensor with 2M cord
- Low profi le design with magnetic base for easy
affi xing to the rack cabinet
Optional 4M cord for Temp. Sensor
www.austin-hughes.comUM-ICM-02-Q215V1P.20
< 2.7 > Temperature Sensor
Part no.
Temp. Sensor
IG-T01
Temperature
Sensitivity
Power
Requirement
HousingChassis & Cover
Connection
Range
Accuracy
Resolution0.1°C ( 0.2°F )
Response Time5 to 30 sec
Voltage 12VDC, powered by sensor port
Current Consumption20mA
Power consumption0.24 Watt
Power on indicatorGreen
Color
InstallationMagnetic base for unrestricted installation
Cable Length
Cable Specifi cation4-wired 3.5mm to RJ11
Cable ColorBeige
0 to 80°C ( 32 to 176°F )
±1°C ( ±2°F)
Plastic
Dark gray
T sensor w/ 2m cable ( standard )
T sensor w/ 4m cable ( option )
Environmental
Dimensions
Weight
Supply includes
Compatibility
Safety Regulatory
Environmental
Operating0 to 80°C Degree
Storage-5 to 80°C Degree
Humidity0~100%, non-condensing
Product30L x 25W x 18H mm
Net66g
1Temperature Sensor
24-wired 3.5mm to RJ11 cable ( 2m, black color )
InfraPowerW / WS / Wi / WSi series PDU
InfraSolutionX-2000 series
InfraGuardEC-300M & EC-300
FCC & CE certifi ed
RoHS2 & REACH compliant
www.austin-hughes.comUM-ICM-02-Q215V1P.21
< 2.8 > Alarm Temperature Setting
How to set alarm temperature :
■ Hold for 5 seconds.
■ Press button to set the alaram temperature.
The alarm temp. can be set either by these buttons or software.
How to set temp. unit ( Celsius or Fahrenheit ) :
■ Hold for 5 seconds.
■ Press button to set the temp. unit.
The above steps are only for local LED temp. display.
Users need to set the temp. unit ( °C or °F ) in the software GUI
separately.
< 2.9 > Fan Unit CFM Setting
To save the energy, the fan unit provides a CFM setting by three levels :
- Normal ( Approx. 60% of the unit CFM )
- High ( Approx. 75% of the unit CFM )
- Max. ( Approx. 100% of the unit CFM )
Please set the CFM according to the environmental conditions.
How to set unit CFM :
■ Press button to change the fan unit CFM setting.
However, if the outside temperature is over alarm temperature, the unit CFM will be automatically
changed to Max. level. Under this condition, all fan kits will be turned on.
www.austin-hughes.comUM-ICM-02-Q215V1P.22
< Part III > Software
< 3.1 > Key Features
InfraCool Manager ICM-02 is a FREE Air Flow management software to remote & monitor up to
30 Master IP Groups ( max. 16 fan unit levels in each Master IP Group), total 480 fan units.
5 concurrent user access are bundled for achieving the demand of multi-user / multi-tasking in
nowadays’ time sharing data center operation.
InfraCool ICM-02
Features
Capacity
Features
Software Platform
Fan Unit
Models Support
Master IP Group ( Just 1 IP for remote Fan unit levels )
Remote Fan unit number
Concurrent user
Unit CFM ( fan speed ) Setting
Auto CFM Control Setting
Individual Fan ON / OFF
Fan Unit ON / OFF
Temp. Monitoring
Alarm Temp. Setting
Reporting
Graphical User Interface
Remote Access via Web Browser
Windows
Master IP Fan Unit (IP dongle built-in)
Remote Fan unit
30
480
5
www.austin-hughes.comUM-ICM-02-Q215V1P.23
< 3.2 > Master IP Confi guration
Please take the following steps to confi gure the Master IP fan unit :
1. Prepare a notebook computer to download the IP setup utilities from the link :
http://www.austin-hughes.com/support/utilities/infracool/IPSetupUtilities.msi
2. Double click the IPSetupUtilities.msi and follow the instruction to complete the installation.
3. Go to each Master IP fan unit with the notebook computer & a piece of
CAT. 5 / 6 cable to set up the confi guration
by IP setup utilities as below. Please take the procedure for all Master IP fan unit ONE BY ONE.
Master IP fan unit
CAT. 5 / 6 cable
To IP portTo notebook computer
LAN port
Reconnect the Master IP fan unit with the network device (
router or hub ), after fi nish the confi guration.
Ensure the FAN unit in
IPOUT
power ON status
Write down the new IP address & password
for < Setup > purpose, refer to P.33
4. Click Scan to search the connected Master IP fan unit.
5. Enter the device name in the name fi eld ( min. 4 char. / max. 16 char. ). The default is Name.
6. Enter the location in the location fi eld ( min. 4 char. / max. 16 char. ). The default is Rack_001.
7. Enter the password in the password fi eld for authentication ( min. 8 char. / max. 16 char. ). The default is 00000000.
8. Enter the new password in the new password fi eld ( min. 8 char. / max. 16 char. ).
9. Re-enter the new password in the Confi rm new password fi eld.
10. Change the desired IP address / Subnet mask / Gateway, then click Save to confi rm the setting to Master IP fan unit.
11. The default IP address is as below:
IP address : 192.168.0.1
Subnet mask : 255.255.255.0
Gateway : 192.168.0.254
www.austin-hughes.comUM-ICM-02-Q215V1P.24
< 3.3 > Hardware Requirement of the Management PC
Please prepare a management PC with the hardware requirements as below for
InfraCool Manager - ICM-02
Recommended hardware requirements :
- Processor: Dual Core 2GHz or above
- Memory: 2GB RAM
- Available Disk Space: 500GB
- Drive: DVD ROM drive
- Display: 1440 x 900 or higher resolution monitor
- The default service port of web server is 80.
- A dedicated PC to run InfraCool Manager - ICM-02 is recommended.
- Make sure the management PC is POWER ON & ICM-02 is under operation.
Otherwise, daily data backup will NOT be proceeded.
< 3.4 > Supported OS Platform & Language
InfraCool Manager - ICM-02 supports the OS platforms & languages as below:
- MS Windows XP Professional with SP3 (32bit only)
- MS Windows 7 Professional with SP1
- MS Windows 7 Ultimate with SP1
- MS Windows Server 2003 R2 Standard Edition with SP2
- MS Windows Server 2008 Standard Edition SP2
- MS Windows Server 2008 R2 Standard Edition SP1
Ensure the user logins in the management PC as a member of “Administrators” Group
before ICM-02 Installation and execution.
User can select the following languages under Control Panel > Region and Language in English Edition OS:
1) Arabic (Saudi Arabia)
2) Chinese (Traditional, Hong Kong S.A.R.)
3) Dutch (Netherlands)
4) English (Australia)
5) English (United Kingdom)
6) English (United States)
7) French (France)
8) German (Germany)
9) German (Switzerland)
10) Italian (Italy)
11) Japanese (Japan)
12) Korean (Korea)
13) Norwegian (Norway)
14) Portuguese (Portugal)
15) Russian (Russia)
16) Spanish (Spain)
17) Turkish (Turkey)
www.austin-hughes.comUM-ICM-02-Q215V1P.25
< 3.5 > Software Download
InfraCool Manager, ICM-02, is a AIR FLOW management software to monitor the temperature change
by providing a centralized and remote management platform, and total reporting with detailed logs &
event occurrences.
InfraCool Manager ICM-02 can support max. 5 concurrent login users and manage multi- Master IP
group max. 30, hence the concurrent login users can access & remote FAN units max. 480 ( 30 Master
IP groups x 16 level fan units ).
Software download
Please download the InfraCool Manager - ICM-02 to the management PC
from the link http://www.austin-hughes.com/support/software/infracool/ICM-02.msi
Double click the ICM-02.msi and follow the instruction to complete the installation.
click “ Next ”
click “ Install ”
click “ Finish ”
ICM-02.msi
Complete
www.austin-hughes.comUM-ICM-02-Q215V1P.26
< 3.6 > First Time Start-up Setting
Step 1.
Double click the InfraCool Manager - ICM-02
and follow the instruction to complete start-up setting.
Step 2. Click “ Next “ in “ InfraCool Manager start-up setting “ box
Step 3. Input the fi elds of the following window & Click “ Install “
ICM-02
InfraCool Manager
PostgreSQL password can be changed by user.
The password
MUST contain at least three of the following four character groups:
- English uppercase characters ( A through Z )
- English lowercase characters ( a through z )
- Numerals ( 0 through 9 )
- Non-alphabetic characters ( such as !, $, #, % )
If the port of web server
is not 80, please input the
appropriate no. here and
follow the instruction in “
Change port no. of web
server“ on next page to
make the change effective.
www.austin-hughes.comUM-ICM-02-Q215V1P.27
< 3.7 > Change Port no. of Web Server
Change port no. of web server.
If users want to use another port no. instead of 80, please take the following steps after
InfraCool Manager ICM-02 “ First time start-up setting “ is completed.
Step 1. Go to the path of web server being installed. ( Default: C:\AppServ\Apache2.2\conf\ )
Step 2. Open “ httpd.conf “ & change “ Listen 80 “ to “ Listen xx “ where xx means the port
users want to use save the change
Step 3. Restart Apache services.
Go to Control Panel > Administrative Tools > Services > Apache2.2 & Click “ Restart “
Complete
www.austin-hughes.comUM-ICM-02-Q215V1P.28
Part IV. System Setup & Remote Access
< 4.1 > System setup
Users can follow below step 1 - 3 to access the management PC and InfraCool Manager ICM-02
Step 1. Open Internet Explorer ( I.E. ), version 8.0 or above
Step 2. Enter the URL of management PC into the address bar
( If fail to access, please ask MIS to check if the port for web server is enable.
Default port : 80 )
e.g. http://192.168.0.1/ICM-02/
Step 3. Enter “ User name “ . Default is “ admin “
Enter “ Password “ . Default is “ 00000000 “
12345
Login user
Then users should go to
system setup
Login userLogin userLogin userLogin user
Router or hub
Management PC
InfraPower Manager IPM-03
< User >, < Setup >, < Alarm >, < General > & < Backup > for initial
Only Administrator is authorised to access < User >, < Setup >, < Alarm >, < General > &
< Backup >
www.austin-hughes.comUM-ICM-02-Q215V1P.29
< 4.1 > System setup
In < User > page, administrator can create 4 more operators.
Step 1. Tick “ Operator 1: “
Step 2. Input “ User name “ & “ User login password “
Step 3. Input user login password in “ Confi rm password “ again
Step 4. Repeat Step 1 to 3 for other operators if necessary
Step 5. Click “ Apply “ to fi nish the user setup
www.austin-hughes.comUM-ICM-02-Q215V1P.30
< 4.1 > System setup
In < Setup > page, administrator can activate max. 30 Master IP groups & set the group command
password
Step 1. “ Activate “ Master IP group 01
Step 2. Input “ IP address “ & “ password “ of the Master IP group 01
Step 3. “ Enable “ Command password
Step 4. Input “ New command password ”. Default is “ 00000000 “
Step 5. Input new command password in “ Confi rm new password “ again.
Step 6. Click “ Apply “ to fi nish the Master IP group setup
Step 7. Repeat step 1 to 6 for other Master IP groups if necessary
www.austin-hughes.comUM-ICM-02-Q215V1P.31
< 4.1 > System setup
In < Alarm > , administrator can confi gure the alarm email server & max. 5 email recipients to receive
alarm notifi cations from the software
Step 1. “ Enable “ alarm email
Step 2. Input “ SMTP server “ , “ SMTP port “
Step 3. Input sender email account in “ User email “
Step 4. “ Enable “ or “ Disable “ the “ SMTP authentication “
Step 5. Input “ User name “ and “ Password “
Step 6. Select the “ SMTP secure “ ( None / SSL / TLS )
Step 7. Input the “ Alarm interval “
Step 8. Input the alarm recipient email account in “ Alarm mail recipient 01 “
Step 9. Repeat step 8 for other alarm recipients
Step 10. Click “ Apply “ to fi nish the alarm email server setting
www.austin-hughes.comUM-ICM-02-Q215V1P.32
< 4.1 > System setup
In < General > , administrator can change the “ Refresh rate “ , “ Scan rate “ & “ Temperature unit “
across all Master IP groups
In < Backup > , administrator can “ Enable “ or “ Disable “ the daily data backup. When “ Enable “,
the backup path can be changed
www.austin-hughes.comUM-ICM-02-Q215V1P.33
< 4.1 > System setup
< Sys log > provides last 2000 events in < User >, < Setup >, < Alarm >, < General > & < Backup > .
www.austin-hughes.comUM-ICM-02-Q215V1P.34
< 4.2 > Remote Access
After administrator completes < System Setup >, up to 4 additional users can access the
management PC remotely. User can follow the steps below to access management PC &
InfraCool Manager ICM-02
Step 1. Add the port of web server in the fi rewall settings of the management PC.
- Open “ Control Panel ”
- Select “ Windows Firewall “
- Select “ Advanced settings ”
- Right Click “ Inbound Rules ” & select “ New Rule… “
- Select “ Port ” & Click “ Next> ”
- Select ” TCP ” then “ All local ports ” & Click “ Next> ”
- Input the “ Name “ & “ Description “ of the port & Click “ Finish “
Step 2. Open the web browser of remote client PC
Step 3. Input the URL of InfraCool Manager ICM-02 in the address bar
e.g. http://192.168.0.1/ICM-02/
If the port no. of web server is not 80, please enter the appropriate port no. follow
the IP address e.g. http://192.168.0.1:81/ICM-02/
Step 4. System authentication page pops up automatically.
Input “ User name “, “ Password “ & Click “ Login “
www.austin-hughes.comUM-ICM-02-Q215V1P.35
Part V. Software Usage & Operation
< Status > provides
- < Search > function to search new installed fan units in each Master IP group.
- Scan function to monitor the fan units’ status of each Master IP group ONE by ONE
www.austin-hughes.comUM-ICM-02-Q215V1P.36
Part V. Software Usage & Operation
In < Details >,
- Change “ Rack “ and “ Position ” of Fan unit
- Switch ON / OFF fan unit
- Change fan unit CFM
- Switch ON / OFF individual fan
- Click “ Apply ” to fi nish the above settings
www.austin-hughes.comUM-ICM-02-Q215V1P.37
Part V. Software Usage & Operation
In < Temp setting >,
- “ Activate ” or “ Deactivate ” Temp sensor
- Change “ Location ”, “Alarm Setting ” & “ R. alert setting “ of Temp sensor
- “ Enable “ or “ Disable “ auto CFM control
- Click “ Apply ” to fi nish the above settings
The default Temp setting is Deactivate .
- When install Temp sensor, please tick Activate . Otherwise, no readings display.
- DON’T activate Temp sensor if no sensor installed.
www.austin-hughes.comUM-ICM-02-Q215V1P.38
Part VI. Events / Log / Report
< Event > provides past 2000 events about FAN unit’s confi guration & connection in a
certain Master IP Group.
< FAN unit log > provides past 2000 FAN unit log records about a certain FAN unit by the user’s
selection. The software will generate a FAN unit log record in every 10 mins.
www.austin-hughes.comUM-ICM-02-Q215V1P.39
Part VI. Events / Log / Report
< FAN log > provides past 2000 FAN log records about an individual fan of specifi c fan unit by the
user’s selection.
The software will generate a FAN log record in every 10 mins.
www.austin-hughes.comUM-ICM-02-Q215V1P.40
Part VI. Events / Log / Report
< Report > provides monthly report for Fan unit log , Fan log & Event log which can be
export to csv format.
Please follow the steps below to export the log category you want :
Step 1. Select the category, period & target.
Step 2. Click “ Apply ” & Click “ OK “ from the pop up window
Step 3. Right click the fi le name below & select Save target as to download the log fi le.
Step 4. Click “ Close “ to complete or “ Open “ to view the content of log fi le
Complete
www.austin-hughes.comUM-ICM-02-Q215V1P.41
Part VII. SNMP
SNMP Management
The Master IP fan unit can manage the connected remote fans ( up to 16 remote fans), using tools that
support SNMP v2c ( Simple Network Management Protocol).
Only for Master IP fan unit with built-in IPD-02-S
( I ). Accessing MIB Files
Use the World Wide Web (WWW) to download the SNMP MIB fi le at this URL:
The following procedure summarizes how to enable the Master IP fan unit for SNMP support.
Step 1. Connect the Master IP fan unit to a computer. ( Please refer to P.26 )
Step 2. Open the Internet Explorer ( I.E. ) version 7.0 or above
Step 3. Enter the confi gured IP dongle address into the I.E. address bar. Default IP address is “ 192.168.0.1 “
Step 4. Enter “ Login name “ & “ Password “. Default login name & password are “ 00000000 “
www.austin-hughes.comUM-ICM-02-Q215V1P.42
Part VII. SNMP
Step 5. Select the SNMP from the left navigation
Step 6. The SNMP Settings window appears as below:
Step 7. Click “ Enable “ in “ SNMP Agent “ to start the SNMP agent service
Step 8. Input “ Read Community “. Default is “ public ”
Step 9. Input “ Write Community “. Default is “ private ”
Step 10. Select “ disabled “ or “ V2Trap “ in “ SNMP Traps “
If select “ V2Trap “ , please input IP address of the SNMP management station in “ Station IP: “
Step 11. Click “ Apply “ to fi nish the SNMP settings
www.austin-hughes.comUM-ICM-02-Q215V1P.43
< Part VIII > FAQ
InfraCool Manager - ICM-02
1. What is InfraCool Manager?
The InfraCool Manager is a Windows based system to consolidate management of max. 480 FAN units
via 30 Master IP groups, using a simple web interface which monitors temp. status of cabinets in the
data center. It also provides the detailed FAN unit and event logged records, and sends alarm email
once temp. over alarm level.
Please fi nd the link below:
2. Which OS platform does ICM-02 support?
- MS Windows XP Professional with SP3 (32bit only)
- MS Windows 7 Professional with SP1
- MS Windows 7 Ultimate with SP1
- MS Windows Server 2003 R2 Standard Edition with SP2
Ensure the user logins in the management PC as a member of “Administrators” Group
before ICM-02 Installation and execution.
3. Which database does the ICM-02 support?
PostgreSQL
4. What is the PostgreSQL default password for ICM-02?
1qaz2WSX
5. How can I receive alarm email and get full log report?
Ensure that ICM-02 is executed and the alarm server is confi gured properly and being enabled.
6. What is the default login name & password of ICM-02?
Default login name “admin” & password “00000000”
7. What is the command password of ICM-02?
Each Master IP Group has its command password. It will be requested for any FAN unit confi guration
and control. The administrator can set different command password for different Master IP Group or all
Master IP Groups use the same password.
8. The FAN units can’t be found by ICM-02?
Please double check the cable connection and the level setting of each FAN unit. If a cascade chain has
duplicate the level FAN units, it will cause this problem.
9. Is it possible to manage the FAN units from different workstations?
Yes, the InfraCool manager supports 5 concurrent login users from different workstations.
www.austin-hughes.comUM-ICM-02-Q215V1P.44
< Part VIII > FAQ
Master IP fan unit
1. What is the Master IP fan unit?
The Master IP fan unit has a built-in IP dongle which provides a simple and economical way to consolidate management of max. 16 remote FAN units, by a single IP connection to the network.
2. What is the IP setup utilities?
This is a windows application used to assign the IP address of Master IP fan unit. You can download
the IP setup utilities from the link below:
3. Does the Master IP fan unit support DHCP (Dynamic Host Confi guration Protocol)?
No, the Master IP fan unit only works with static IP-address.
Temp. sensor
1. How accurate is the Temp. sensor?
It is accurate to ± 1.5°C ( typical ).
2. How to install the Temp. sensor ?
Plug in the Temp. sensor to the temp. port of the FAN unit at any time.
Others
1. Where can I fi nd the Catalogue / User manual /Model list / Wire diagram of InfraCool FAN
units?
Please visit the
2. How can we get a further support?
Please send the email to
www.austin-hughes.com
support@austin-hughes.com or sales@austin-hughes.com
www.austin-hughes.comUM-ICM-02-Q215V1P.45
< Part IX > Troubleshooting
FAN unit disconnection
1. GUI shows a certain level remote fan unit disconnected (Except Master IP fan unit)
Step 1 - Remote fan unit power off ?
Check the remote fan unit is power ON or not.
Step 2 - Fan unit level setting duplicated in the same Master IP group?
Check and make sure fan unit level is unique and not duplicated in the same
Master IP group.
( Please refer to user manual < 2.5 > for the fan unit level setting )
2. GUI shows from a certain level remote fan unit to the last one disconnected
(Except Master IP fan unit)
Step 1 - Cable disconnected, loose or defective ?
Check the Cat. 5 / 6 cable connection between remote fan units. Make sure the
connectors are fi rmly attached. And check if any defects on your cables or not. If yes, replace a new one.
Step 2 - The fi rst disconnected remote fan unit failed ?
Unplug the Cat. 5 / 6 cable on the fi rst disconnected remote fan unit, then plug it to the second disconnected remote fan unit to check if the problem caused by
the fi rst disconnected remote fan unit.
3. GUI shows the whole group of remote fan unit(s) disconnected
Step 1 - Cable disconnected, loose or defective ?
Check the Cat. 5 / 6 cable connection to remote fan units and network devices.
Make sure the connectors are fi rmly attached. And check if any defects on your cable or not. If yes, replace a new one.
Step 2 - Master IP fan unit failed ?
i. Check if the network setting of the Master IP fan unit is correct or not.
If duplicate IP address is in the network, it may cause such problem.
ii. Disconnect the Master IP fan unit from the network and try to direct connect
the Cat. 5 / 6 cable from the <IP> port to a computer network port and use
IP Setup utilities to check if the Master IP fan unit can be found or not.
If it cannot be found, the Master IP fan unit may be failed.
www.austin-hughes.comUM-ICM-02-Q215V1P.46
< Part IX > Troubleshooting
Replacement, removal or addition for remote FAN unit
1. How to replace the failed Master IP fan unit with a new one ?
Step 1 - Prepare a new Master IP fan unit and set it to 1st level.
( Please refer to user manual < 2.5 > for the fan unit level setting )
Step 2 - Disable alarm email in <Alarm> page.
Step 3 - Power off & remove the failed Master IP fan unit from connection.
Step 4 - Install the new Master IP fan unit to the connection & power it on.
Step 5 - Click Start Connection in <Status> page for the relevant Master IP Group.
Step 6 - Confi gure the new Master IP fan unit in <Details> & <Temp. sensor> page such as Rack, Position, AlarmTemp...
Step 7 - Enable alarm email in <Alarm> page.
2. How to replace a failed certain level remote fan unit with a new one ?
Step 1 - Prepare a new remote fan unit and set the remote fan unit level accordingly.
( Please refer to user manual < 2.5 > for the fan unit level setting )
Step 2 - Prepare an appropriate length Cat. 5 / 6 cable.
Step 3 - Click Set maintenance in <Details> page for the failed remote fan unit.
Step 4 - Use a Cat. 5 / 6 cable to bridge over the failed remote fan unit which will be replaced
to minimize log / data loss.
Step 5 - Power off & remove the failed remote fan unit from connection.
Step 6 - Install the new remote fan unit, cancel the cable-bridging and reconnect the remote fan
unit to the last and next one.
Step 7 - Power on the new remote fan unit.
Step 8 - Click Remove maintenance in <Details> page for the new remote fan unit.
Step 9 - Confi gure the new remote fan unit in <Details> & <Temp. sensor> page such as Rack, Position, AlarmTemp...
Ignore step 2 & 4 if the failed remote fan unit is in the last level.
www.austin-hughes.comUM-ICM-02-Q215V1P.47
< Part IX > Troubleshooting
Replacement, removal or addition for remote FAN unit
3. How to move out a remote fan unit ( without a replacement ) ?
Step 1 - Prepare an appropriate length Cat. 5 / 6 cable.
Step 2 - Click Disable monitoring in <Details> page to stop monitoring the removed remote
fan unit.
Step 3 - Use the Cat. 5 / 6 cable to bridge over the removed remote fan unit to minimize
log / data loss.
Step 4 - Power off & remove the fan unit from connection.
If the removed remote fan unit NOT in the last level, you MUST reconfi gure and reset the
level for the affected remote fan unit(s) which next to the removed remote fan unit.
Ignore step 1 & 3 if the removed fan unit is in the last level.
4. How to add an extra remote fan unit to an existing fan unit group ?
Step 1 - Prepare a new remote fan unit and set the remote fan unit level accordingly.
( Please refer to user manual < 2.5 > for the fan unit level setting )
Step 2 - Prepare an appropriate length Cat. 5 / 6 cable.
Step 3 - Click Set maintenance in <Details> page for the affected remote fan unit(s) which
next to the added remote fan unit.
Step 4 - Install, connect and power on the new remote fan unit.
Step 5 - Reconfi gure & reset the level for the affected remote fan unit(s) which next to the
added remote fan unit.
Step 6 - Click Remove maintenance in <Details> page for the affected remote fan unit(s).
Step 7 - Click Search in <Status> page to search the new installed remote fan unit.
Step 8 - Confi gure the new remote fan unit in <Details> & <Temp. sensor> page such as Rack, Position, AlarmTemp...
Ignore step 3, 5 & 6 if the added remote fan unit is in the last level.
www.austin-hughes.comUM-ICM-02-Q215V1P.48
< Part IX > Troubleshooting
InfraCool Manager ICM-02
1. Try to login InfraCool Manager ICM-02 but the web browser only shows “ HTTP 404 Not Found ”
Step 1 - Services for Web server in management PC started ?
Make sure the services is started. Go to Control Panel -> Administrative Tools ->
Services -> Apache2.2 and make sure the status is “ Started ”.
Step 2 - Port for web server in management PC is occupied by other service ?
Check if the port for web server is used by other service. If yes, please release
the port of that particular service and assign another port for it.
Step 3 - Port for web server is added in the fi rewall of management PC ?
Check if the port is added in the fi rewall. If not, please add and enable the connection in
the fi rewall. Please refer to user manual < 4.2 > for details.
www.austin-hughes.comUM-ICM-02-Q215V1P.49
The company reserves the right to modify product specifi cations without prior notice and assumes no responsibility
for any error which may appear in this publication.
All brand names, logo and registered trademarks are properties of their respective owners.
Copyright 2015 Austin Hughes Electronics Ltd. All rights reserved.
www.austin-hughes.comUM-ICM-02-Q215V1